Tempco TPC40034 Power Control Console User Manual

June 5, 2024
TEMPCO

Tempco TPC40034 Power Control Console User Manual
Tempco TPC40034 Power Control Console

SPECIFICATIONS

Temperature Controllers: Model TEC-9400, 1/16 DIN Dual Display with PID Auto-tuning
Sensor Inputs: Type “J” thermocouples
Connector Bodys: Black
Power Cord/voltage Input: 240VAC, 50/60 HZ, 15A
Heater Outputs: 3A Max, 720 watts max per zone.
Output Devices: Solid State Relays
Main Power Switch: Located on front panel
Main Power Fuse: See replacement parts list on next page (located on back panel)
Control Fuses: See replacement parts list on next page (located on back panel)

WARNINGS

  1. Air vents located on top and bottom of console must not be blocked! To prevent an overheating condition the internal components must remain as close to room temperature (75ºF / 24ºC) as possible.
  2. Dangerous voltage capable of causing injury or death is present within this console. Power to all equipment must be disconnected before installation or beginning any troubleshooting procedures. Heater output wiring and component replacement must be made by qualified personnel only.
  3. To minimize the possibility of fire or shock, do not expose this console to rain or excessive moisture.
  4. Do not use this console in areas where hazardous conditions exist such as excessive shock, vibration, dirt, corrosive gases, oil or where explosive gases or vapors are present.
  5. It is strongly recommended that a process should incorporate a Limit Control like a Tempco TEC-910 which will shut down the equipment at a preset process condition in order to avoid possible damage to products or systems.

WIRING (For safety, disconnect all power sources prior to wiring)

  1. Attach the leads from your type “J” thermocouples to the mini-plugs provided. Take care to note the correct polarity. The red lead is (-) negative.
  2. The heater output current is sourced directly through the line cord. The rear console output receptacles and mating Hubbell plugs provide live controlled power for direct connection to your heater(s). Connect one lead from your heater to one prong of the Hubbell plug (not ground). Connect the other lead from your heater to the other prong. Connect heater ground (if applicable) to the ground connection (G) on the plug.

OPERATION

  1. Verify the power switch is in the off position. Plug your heaters & thermocouples into the rear connectors. Plug the provided line cord from the console into a standard 240V, 15A outlet. Switch on the console.
  2. Set your desired temperature setpoint by using the up and down arrow buttons on the TEC-9400 temperature controllers.
  3. Refer to the following pages for complete operation and pages 4 & 7 for auto-tuning of the TEC-9400 temperature controllers.

SPARE/REPLACEMENT PARTS

Tempco Part Number Description
EHD-124-148 Fuse (1), rated 15 Amp/250V, ¼ x 1 ¼”, fast acting BUSS ABC-15-R.

Used for main control console power.
EHD-124-297| Fuse (1), rated 1½ Amp/ 250V, ¼” x 1¼”, time delay, BUSS MDA-1½ -1-R. Used for TEC-9400 Controllers.
EHD-124-282| Fuses (4), rated 4 Amp/ 250V, ¼” x 1¼”, fast acting, BUSS ABC-4-R. Used for individual heater outputs.
EHD-102-121| Power output plugs (1 per zone), Hubbell HBL4570C, 15A 250V Twist-Lock.
TCA-101-105| Type “J” thermocouple mini plug (1 per zone), Black

NOTE: For all fuses, use listed BUSS part numbers or equivaliant.

SPARE/REPLACEMENT PARTS

KEYPAD OPERATION

SCROLL KEY:
This key is used to scroll through a menu to select a parameter to be viewed or adjusted.

UP KEY:
This key is used to increase the value of the selected parameter.

DOWN KEY:
This key is used to decrease the value of the selected parameter.

RESET KEY:
This key is used to:

  1. Revert the display to the home screen.
  2. Reset a latching alarm once the alarm condition is removed.
  3. Stop manual control mode, Auto-Tuning mode or calibration mode.
  4. Clear an Auto-Tuning or communication error message.
  5. Restart the dwell timer when the dwell timer has timed out.
  6. Enter the manual control menu if failure mode occurs.

ENTER KEY: Press and hold for 5 seconds or longer to:

  1. Enter the setup menu. The display will show
  2. Enter manual control mode. Press and hold mode. The display will show .
  3. Enter Auto-Tuning mode. Press and hold   for 7.4 seconds, then let go to select Auto-Tuning  mode. The display will show .
  4. Perform calibration of a selected parameter during the calibration procedure. Press and hold for 8.6 seconds, then let go to select calibration mode. During power-up, the upper display will show PROG and the lower display will show the Firmware version for 6 seconds.

Menu Flowchart

The Menu has been divided in to 5 groups. They are as follows:

  1. User Menu – Below
  2. Setup Menu – Page 5
  3. Manual Mode Menu – Page 7
  4. Auto-Tuning Mode Menu – Page 7
  5. Calibration Mode Menu (not recommended, calibration section has been removed)

Menu Flowchart

Press for the next parameter
Press and key to return to the previous parameter.

User Menu

The below user menu parameters are available depending on user selection.

Setup Menu

The setup menu has been categorized in to eight categories. They are listed below.

  1. Basic Menu – Below
  2. Output Menu)
  3. Alarm Menu
  4. Event Input Menu *8. Profile Menu (Ramp and Soak)
  5. User Select Menu
  6. Communication Menu
  7. Current Transformer Menu

Basic Menu (bASE)

In the setup menu, when the upper display says “SET”, Use the or keys to get “bASE” in the lower display.
Then, use the key to cycle through the “bASE” menu parameters./

Basic Menu

Does not apply to the controller used in this console.

Output Menu (oUT)

In the setup menu, when the upper display says “SET”, use the or key to get “oUT” in the lower display. Then, use the key to cycle through the “oUT” menu parameters.

Output Menu

Manual Mode Menu – (Use for Temporary Operation if Sensor Fails)

Press and hold the “ ” key for approx. 6sec until the “HAND” parameter is shown in the upper display.
Then, press and hold the “ ” key for an additional 5 sec. until an “MANU” led starts to flash in the lower left of the display. Then, use the “ ” key to cycle through the available options.
User is able to manually set the out output to be energized from 0-100% of the cycle time.
“Hx.xx” is used to adjust output 1.
“Cx.xx” is used to adjust output 2.

You are able to exit manual mode by pressing and holding the key

Auto-Tuning Mode – (Tunes PID Parameters to Your Application)

Press and hold the “ ” key for approx. 7sec until the “A-T” parameter is shown in the upper display.
Press and hold the “ ” key for 5 seconds to activate Auto-Tuning Mode. Continue to hold the “ ” key for an additional 3 seconds, else the display will revert to a “User Menu” parameter.

Auto-tuning allows the controller to find its own optimal control parameters (PID) by measuring the speed of your thermal process.

Parameter Description

(*Parameters that are not applicable are not shown)

Register Address| Parameter Notation| Parameter Description| Range| Default Value
---|---|---|---|---
0| SP1| Set Point 1 (Used for Output 1)| Low: SP1L

High: SP1H

| 77.0° F
__

__

__

__

__

__

__

__

__

8

| __

__

__

INPT

(Do Not Change)

| __

__

__

__

Input sensor selection

| 0 _JtC : J type Thermocouple 1 _KtC : K type Thermocouple 2 _TtC : T type Thermocouple

3 _EtC : E type Thermocouple

4 _BtC : B type Thermocouple 5 _RtC : R type Thermocouple 6 _StC : S type Thermocouple 7 _NtC : N type Thermocouple 8 _LtC : L type Thermocouple 9 _UtC : U type Thermocouple 10 _PtC : P type Thermocouple 11 _CtC : C type Thermocouple 12 _DtC : D type Thermocouple 13 Pt.dN : PT100           DIN curve 14 Pt.JS : PT100       JIS curve

15 4-20 : 4-20mA linear current input

16 0-20 : 0-20mA linear current input 17 0-5V : 0-5VDC linear voltage input 18 1-5V : 1-5VDC linear voltage input 19 0-10 : 0-10VDC linear voltage input

| __

__

__

__

__

__

__

0

__

9

| UNIT| Input unit selection| 0 oC :°C unit

1 oF :°F unit

2 Pu :Process unit

| 1
10| DP| Decimal point selection| 0 No.dP : No decimal point

1 1-dP : 1 decimal digit

2 2-dP : 2 decimal digit

3 3-dP : 3 decimal digit

| __

0

__

13

| __

SP1L

| Low limit of set point 1 (Span Value)| Low: -19999

High :SP1H

| __

0.0° F

(-18.0° C)

__

14

| SP1H| High limit of set point 1 (Span Value)| Low: SP1L High: 45536| 1000.0° F

(538° C)

15| FILT| Filter damping time constant of PV Sensor

(See Pg. 14)

| 0 0 : 0 second time constant

1 0.2 : 0.2 second time constant

2 0.5 : 0.5 second time constant

3 1 : 1 second time constant

4 2 : 2 second time constant

5 5 : 5 second time constant

6 10 : 10 second time constant

7 20 : 20 second time constant

8 30 : 30 second time constant

9 60 : 60 second time constant

| __

__

__

2

(*Parameters that are not applicable are not shown)

Register Address| Parameter Notation| Parameter Description| Range| Default Value
---|---|---|---|---
16| DISP| Secondary display selection| 0 None : No Display 1 MV1 : Display MV1 2 MV2 : Display MV2

3 tIMR : Display Dwell Time

4 PRoF: display Profile Status

|

0

17| PB| Proportional band value

(See Pg. 17)

| Low: 0.0

High: 500.0°C (900.0°F)

| 18.0° F

(10.0° C)

18

|

TI

| Integral time value

(See Pg. 17)

|

Low: 0

High: 3600 sec

|

100

19| TD| Derivative time value (See Pg. 17)|

Low: 0.0
High: 360.0 sec

|

25

20| OUT1| Output 1 function|

0 REVR : Reverse (heating) control action

1 dIRt : Direct (cooling) control action

|

0

21| O1TY FACTORY SET, DO NOT CHANGE|

Output 1 signal type

| 0 RELY : Relay output

1 SSrd : Solid state relay drive output

2 4-20 : 4-20mA linear current

3 0-20 : 0-20mA linear current

4 0-5V : 0-5VDC linear voltage

5 1-5V : 1-5VDC linear voltage

6 0-10 : 0-10VDC linear voltage

|

1

22

| O1FT| Output 1 failure transfer mode

(See Pg. 15)

|

Select BPLS (Bumpless transfer), or

0.0 ~ 100.0 % to continue output 1 control function if the sensor fails, or select OFF (0) or ON (1) for ON-OFF control

|

0

23| O1HY| Output 1 ON-OFF control hysteresis. PB=0|

Low: 0.1°C (0.2°F) High: 50.0°C (90.0°F)

|

0.2° F

(0.1° C)

24| CYC1| Output 1 cycle time| Low: 0.1

High: 90.0 sec.

| 1.0
26| RAMP| Ramp function selection

(See Pg. 13)

| 0 NoNE : No Ramp Function

1 MINR : Use °/minute as Ramp Rate

2 HRR : Use °/hour as Ramp Rate

| 0

(*Parameters that are not applicable are not shown)

Register Address| Parameter Notation| Parameter Description| Range| Default Value
---|---|---|---|---
27| RR| Ramp rate

(See Pg. 13)

| Low: 0.0 High: 900.0°F| 0

61

| PL1L| Output 1 Low Power limit| Low: 0

High:PL1H or 50%

| 0
62| PL1H| Output 1 High Power limit| Low: PL1L

High: 100 %

| 100
94| PASS| Password entry

(See Next Page)

| Low: 0

High: 9999

| 0

Programming

Press and hold for 5 seconds, then release to enter the setup menu. Press and release to cycle  through the list of parameters. The upper display indicates the parameter symbol, and the lower display indicates the value of the selected parameter.

User Security

There are two parameters, PASS (password) and CODE (security code), which will control the lockout program.

CODE Value PASS Value Access Rights
0 Any Value All parameters are changeable
1000 =1000 All parameters are changeable
≠1000 Only user menu parameters changeable
9999 =9999 All parameters are changeable
≠9999 Only SP1 to SP7 are changeable
Others =CODE All parameters are changeable
≠CODE No parameters can be changed

Signal Input

INPT: Factory set to type “J” thermocouple.
DO NOT CHANGE

UNIT: Select the desired process unit
Options: °C, °F.

DP: Select the desired resolution (decimal points) for the process value.

Control Output

There are 4 kinds of control modes can be configured as shown below.

Heat Only ON-OFF Control – (Used for Solonoids and Valves)

Select REVR for OUT1, Set PB to 0. O1HY is used to adjust the hysteresis for ON-OFF control. The output 1 hysteresis (O1HY) setting is only available when PB = 0. The heat only ON-OFF control function is shown below.

Control Output

ON-OFF control may cause excessive process oscillations even if the hysteresis is set to the smallest value.
If ON-OFF control is used (i.e. PB = 0), TI, TD, CYC1, OFST, CYC2, CPB, DB will no longer be applicable and will be hidden. Auto-Tuning mode and Bumpless transfer are not possible in on/off mode.

Heat only P or PD Control – (Used for Electric Heater

Select REVR for OUT1, set TI = 0, OFST is used to adjust the control offset (manual reset). If PB ≠0 then O1HY will be hidden.
OFST Function: OFST is measured in % with a range of 0 – 100.0 %. When the process is stable, let’s say the process value is lower than the set point by 5°F. Let’s also say that 20.0 is used for the PB setting. In this example, 5°F is 25% of the proportional band (PB).
By increasing the OFST value by 25%, the control output will adjust itself, and the process value will eventually coincide with the set point.
When using Proportional (P) control (TI = 0), Auto-Tuning will be unavailable. Refer to the “manual tuning” section for the adjustment of PB and TD. Manual reset (OFST) is usually not practical because the load may change from time to time; meaning the OFST setting would need to be constantly adjusted. PID control can avoid this problem.

Heat only PID Control – (Default for Electric Heaters)

Select REVR for OUT1. PB and TI should not be zero. Perform Auto-Tuning for initial startup. If the control result is not satisfactory, use manual tuning or try Auto-Tuning a second time to improve the control performance.

Cool only Control

ON-OFF control, Proportional control, and PID control can be used for cooling control. Set “OUT1” to DIRT (direct action).

NOTE: ON-OFF control may result in excessive overshoot and undershoot in the process. Proportional control could result in a deviation of the process value from the set point. It is recommended to use PID control for Heating or Cooling control to produce a stable process value.

When selecting parameters, all of the above parameters may not be available. The number of visible parameters depends on the configuration of the controller.

Ramp

The ramping function is performed during power up or any time the set point is changed. Choose “MINR” (ramp in minutes) or “HRR” (ramp in hours) for the “RAMP” setting, and the controller will perform the ramping function. The ramp rate is programmed by adjusting the “RR” setting. The ramping function is disabled whenever the controller enters Failure mode, Manual control mode, Auto-Tuning mode or Calibration mode.

Ramping Example without Dwell Timer

Set the “RAMP” setting to “MINR” to ramp in minutes.
Set the ramp rate (RR) to 10.
The starting temperature is 30°C.
The setpoint is initially set to 200°C.
After the process warms up, the user changed the setpoint to 100°C after 30 minutes.
After power up, the process will behave as shown below.

Note: When the ramp function is used, the lower display will show the current ramping value. However, it will revert toshow the set point value as soon as the up or down key is touched for adjustment. The ramp rate is initiated at power on and/or whenever the Set point is changed. Setting the “RR” setting to zero means no ramping function is used.

User Calibration – Display Offset

Each unit is calibrated in the factory before shipment. The user can still modify the calibration in the field.
The basic calibration of the controller is highly stable and set for life. User calibration allows the user to offset the permanent factory calibration in order to:

  • Calibrate the controller to meet a user reference standard.
  • Match the calibration of the controller to that of a particular transducer or sensor input.
  • Calibrate the controller to suit the characteristics of a particular installation.
  • Remove long term drift in the factory set calibration.

There are two parameters: Offset Low (OFTL) and Offset High (OFTH) for adjustment to correct an error in the process value.
There are two parameters for the sensor input. These two signal values are CALO and CAHI. The input signal low and high values are to be entered in the CALO and CAHI parameters respectively.
Refer to section 1.6 for key operation and section 1.7 for the operation flowchart. Press and hold the key until the setup Menu page is obtained. Then, press and release the key to navigate to the calibration low parameter OFTL. Send your low signal to the sensor input of the controller, then press and release the key. If the process value (the upper display) is different from the input signal, the user can use and keys to change the OFTL value (the lower display) until the process value is equal to the value the user needs. Press and hold the key for 5 seconds to complete the low point calibration (the display should blink once). The same procedure is applied for high scale calibration.
As shown below, the two points OFTL and OFTH construct a straight line. For the purpose of accuracy, it is best to calibrate with the two points as far apart as possible. After the user calibration is complete, the input type will be stored in the memory. If the input type is changed, a calibration error will occur and an error code is displayed.

Digital Filter

In certain applications the process value is too unstable to be read. To improve this, a programmable low pass filter incorporated in the controller can be used. This is a first order filter with a time constant specified by the FILT parameter. A value of 0.5 seconds is used as a factory default. Adjust FILT to change the time constant from 0 to 60 seconds. 0 seconds represents no filter applied to the input signal.
The filter is characterized by the following diagram.

Note: The Filter is available only for the process value (PV), and is performed for the displayed value only.
The controller is designed to use an unfiltered signal for control even when a filter is applied. If a lagged (filtered) signal is used for control; it may produce an unstable process.

Failure Transfer

The controller will enter failure mode if one of the following conditions occurs:

  1. An SBER error occurs due to an input sensor break, an input current below 1mA for 4-20mA, or an input voltage below 0.25V for 1-5 V.
  2. An ADER error occurs due to the A-D converter failing.
    Output 1 and Output 2 will perform the failure transfer (O1.ft & O2.ft) function as the controller enters failure mode.

Output 1 Failure Transfer

If Output 1 Failure Transfer is activated, it will perform as follows:

  1. If output 1 is configured as proportional control (PB≠0), and BPLS is selected for O1FT, then output 1 will perform a Bumpless transfer. After that, the previous average value of of the output will be used for controlling output 1.
  2. If output 1 is configured as proportional control (PB≠0), and a value of 0 to 100.0 % is set for O1FT, then output 1 will perform failure transfer. After that the value of O1FT will be used for controlling output 1.
  3. If output 1 is configured as ON-OFF control (PB=0), then output 1 will transfer to an off state if OFF is set for O1FT, or it will transfer to an on state if ON is set for O1FT.

Auto-Tuning

 The Auto-Tuning process will be performed at the set point (SP1). The process will oscillate around the set point during the tuning process. Set a set point to a lower value if overshooting beyond the normal process value will cause damage. It is usually best to perform Auto-Tuning at the Set point the machine is expected to be operated at, with the process running normally (i.e. material in the oven, etc.)

Auto-Tuning is generally applied in the following cases:

  • Initial setup for a new process
  • The set point is changed substantially from the previous Set point when Auto-Tuning was performed.
  • The control result is unsatisfactory

Auto-Tuning Operation Steps

  1. The system is set up to run under real-world conditions.
  2. “PB and “TI” settings should not be set to zero.
  3. The LOCK parameter should be set to NONE.
  4. Set the set point to a normal operating value, or a lower value if overshooting beyond the normal process value will cause damage.
  5. Press and hold the key until appears on the upper display. Continue to hold the “ ” key for an additional 3 seconds, else the display will revert to a “User Menu” parameter.
  6. Press and hold the key until the TUNE indicator begins to flash.
  7. The Auto-Tuning process has begun.

NOTE:
During Auto-Tuning, the output will stay on until the Process Value reaches the setpoint. This is likely to cause the temperature to exceed the setpoint.
Then, the output will remain off until the process value falls below the setpoint.
This will occur at least two times while the controller “learns” how to control your process.

Procedures

Auto-Tuning can be applied either as the process is warming up (Cold Start) or as the process has been in steady state (Warm Start). After the Auto-Tuning process is completed, the TUNE indicator will stop flashing and the unit will revert to PID control by using its new PID values. The PID values obtained are stored in nonvolatile memory.

Auto-Tuning Error

If Auto-Tuning fails, an ATER message will appear on the upper display in any of the following cases.

  • If PB exceeds 9000 (9000 PU, 900.0°F or 500.0°C)
  • If TI exceeds 1000 seconds
  • If the set point is changed during the Auto-Tuning process

Solution for an Auto-Tuning Error

  1. Try Auto-Tuning once again.
  2. Avoid changing the set point value during the Auto-Tuning process.
  3. Ensure PB and TI are not set to zero.
  4. Use manual tuning.
  5. Touch RESET key to reset the message.

Manual Tuning

In certain applications, using Auto-Tuning may be inadequate for the control requirement, or, the process moves too slowly to Auto-tune accurately.
If this is the case, the user can try manual tuning.
If the control performance by using Auto-Tuning is still unsatisfactory, the following guidelines can be applied for further adjustment of PID values.

ADJUSTMENT SEQUENCE SYMPTOM SOLUTION
Proportional Band ( PB ) Slow Response Decrease PB
High overshoot or Oscillations Increase PB
Integral Time ( TI ) Slow Response Decrease TI
Instability or Oscillations Increase TI
Derivative Time ( TD ) Slow Response or Oscillations Decrease TD
High Overshoot Increase TD

2-2.PID Parameter Adjustment Guide

Effects of PID Adjustment

Manual Control

To enable manual control, ensure the LOCK parameter is set to NONE.
Press and hold until (Hand Control) appears on the display. Press and hold until the “MANU”  indicator begins to flash. The lower display will show .
Indicates the output control variable for output 1, and indicates the control variable for output 2. The user can use the up-down keys to adjust the percentage values for the heating or cooling output. This % value is based on the CYC1 and CYC2 settings, where the associated output will stay on for the % of time the CYC1 & CYC2 values are set for.

Example: If CYC1 is set to 20seconds, and the controller is set to “H50.0”, the output will be on for 10seconds, then turn off for 10 seconds.

The controller performs open loop control and ignores the input sensor as long as it stays in manual control mode

Exit Manual Control

Pressing the  key will revert the controller to its normal display mode.

Setting Controller to Factory Default

The controller’s parameters can be loaded with default values listed in the parameter description table . In certain situation it is desirable to retain these values after the parameters values has been changed. The below procedure to be followed to reload the default values.

  1. Ensure the LOCK parameter is set to NONE.
  2. Press and hold until (Hand Control) appears on the display.
  3. Press and release the key to cycle through the manual mode menu to reach “FILE”.
  4. Press and hold for 5 seconds or until the upper display FILE flash for a moment.

The description of the Error code is explained below

Error Code| Display Symbol| Description & Reason| Corrective Action
---|---|---|---

4

|

ER04

|

Illegal setup values used: COOL is used for OUT2 when DIRT (cooling action) is used for OUT1,

or when PID mode is not used for OUT1 (PB =0 and/or TI=0)

| Check and correct setup values of OUT2, PB1, PB2, TI1, TI2 and OUT1. IF OUT2 is needed for cooling control, the controller should use PID mode (PB≠ 0 and TI≠ 0) and OUT1 should use reverse mode (heating action), otherwise, OUT2 cannot be used for cooling control

10

|

ER10

| Communication error: bad function code| Correct the communication software to meet the protocol requirements.
11| ER11| Communication error: register address out of range| Do not issue an over-range address of the register to the secondary
14| ER14| Communication error: attempt to write a read-only data| Do not write read-only data or protected data to the secondary.

15

|

ER15

| Communication error: write a value which is

out of range to a register

| Do not write an over-range data to the secondary register
16| EIER| Event Input Error: Two or more event inputs are set to the same function| Do not set the same function in two or more Event Input Function parameters (E1FN through E6FN)
26| ATER| Auto-Tuning Error: Failed to perform Auto-Tuning function|

1.   The PID values obtained after Auto-Tuning process are out of range. Retry Auto-Tuning.

2.   Do not change the setpoint value during Auto- Tuning process.

3.   Use manual tuning instead of Auto-Tuning process.

4.   Do not set a zero value for TI.

5.   Do not set a zero value for PB.

6.   Touch RESET key

29| EEPR| EEPROM can’t be written correctly| Return to factory for repair.
30| CJER| Cold junction compensation for Thermocouple malfunction| Return to factory for repair.
39| SBER| Input sensor break, or input current below 1 mA if 4-20 mA is used, or input voltage below

0.25V if 1 – 5V is used

| Replace the input sensor.
40| ADER| A to D converter or related component(s) malfunction| Return to factory for repair.

6.5 Mode

The Value of the Mode Register is as below.

Value Mode
H’000X Normal mode
H’010X Calibration mode
H’020X Auto-Tuning mode
H’030X Manual control mode
H’040X Failure mode
H’0X00 Alarm status is off
H’0x01 Alarm status is on
6-6.Operation Mode

RETURNS
No product returns can be accepted without a completed Return
Material Authorization (RMA) form.

TECHNICAL SUPPORT
Technical questions and troubleshooting help is available from
Tempco. When calling or writing please give as much background
information on the application or process as possible.
E-mail: techsupport@tempco.com
Phone: 630-350-2252
800-323-6859

Note: Information in this manual was deemed correct at the time of printing.
The policy of Tempco is one of continuous development and product improvement, and we reserve the right to modify specifications and designs without prior notice. Not responsible for typographical errors.

Custom Manufacturer Since 1972

ELECTRIC HEATING ELEMENTS • TEMPERATURE CONTROLS • SENSORS • PROCESS HEATING SYSTEMS

HEAT THINGS UP!

With Thousands of Design Variations We Make Everything You Need.

Band Heaters
Cast-In Heaters
Radiant Heaters
Flexible Heaters
Process Heaters
Temperature Control

Cartridge Heaters
Coil & Cable Heaters
Strip Heaters
Tubular Heaters
Instrumentation
Temperature Sensors

607 N. Central Avenue Wood Dale, IL 60191-1452 USA
P: 630-350-2252 Toll Free: 800-323-6859
F: 630-350-0232 E: info@tempco.com
www.tempco.com

© Copyright 2022 TEHC. All Rights Reserved