echoflex FLS-41 Open Loop CCT Sensor Installation Guide
- June 5, 2024
- echoflex
Table of Contents
echoflex FLS-41 Open Loop CCT Sensor Installation Guide
Overview
The Open Loop CCT Sensor (FLS-41) is a solar-powered sensor that monitors exterior natural light and Correlated Color Temperature (CCT) levels.
It uses wireless messaging to provide controllers sensor data to automatically adjust the tunable white color output and dimming capability of an LED fixture throughout the day.
The sensor can monitor exterior light levels up to 100,000 lux (9,290 fc) and a color temperature range of 2,000 to 7,500 kelvin with a resolution of ±10 and an accuracy of ±100 kelvin.
This document covers installation, testing, and setup of all FLS-41 models.
The product package includes the sensor and incorporated adhesive pads for
mounting.
Prepare for Installation
To ensure optimal function, consider the installation environment and the following guidelines:
- For indoor use only. Operating temperature -25°C to 65°C (-13°F to 149°F), 5%–92% relative humidity (non-condensing).
- High density construction materials and large metal appliances or fixtures in the space may disrupt wireless transmissions.
- Install the sensor within range of linked receivers or controllers, 24 m (80 ft). Consider adding a repeater to extend reception range.
- Before linking the sensor, expose it to a good light source for at least five minutes at 200 lux (19 fc). Install the FLS-41 with the solar cell facing outdoors.
Installation
The FLS-41 sensor should be installed on the inside window casing facing out through clean glass. To maximize the sensor’s 60° field of view, ensure there are no mullions or overhangs outside the window that block or shadow the sensor.
Position the sensor right up against the window to ensure reflections from interior lights do not affect the sensor readings.
The location and position of the sensor directly affects the quality of messages received by the linked controller.
Note: Consider linking the FLS-41 while you have access and before replacing the cover. See Link to a Controller on the facing.
Obstructed View
Unobstructed View
Mount the Sensor
Use the adhesive pads on the bottom of the sensor to mount it to any suitable surface.
- Clean the mounting surface with an alcohol wipe and wait for the surface to dry.
- Remove the protective backing from the adhesive pads on the sensor.
- Press the sensor in place and hold for 30 seconds.
Rear View
Link to a Controller
The compatible target controller must be installed, powered, and within range of the FLS-41.
Note: The linking process can be used both to link a device to a controller and to unlink a linked device from a controller.
-
Press the [Learn] button on the controller to activate Link mode. If necessary, refer to the controller product documentation.
-
Press the [Teach] button on the sensor once to send a link message.
An LED blinks to confirm a successful transmission. -
Deactivate Link mode on the controller before attempting to link to any other controllers.
Sensor Operation
The sensor records sample values at a rate based on the current ambient light level and the stored energy in the sensor. The sensor is configured to transmit messages at a heartbeat rate and immediately when daylight levels change more than 12%. During normal operation, the heartbeat rate is 10 times longer than the sample rate.
The table below shows the range of ambient light values that determine the sample rate compared to the heartbeat rate. The sample rate marks the recording of daylight level values used to calculate the percent of change, while the heartbeat rate marks the transmission of a message.
Ambient Light Value Lux (Footcandles)| Sample Rate|
Heartbeat Message Rate
---|---|---
< 50 (< 4.6)| 128 seconds| > 21 minutes
< 100 (< 9.3)| 64 seconds| 10 minutes
< 100–200 (< 9.3–18.6)| 32 seconds| 320 seconds
200 (>18.6)| 16 seconds| 160 seconds
For the sensor to send an on-change message, it needs sufficient power:
- Stored energy above 3.5 V, or
- Ambient light level above 300 lux (27.9 fc)
On-Change Formula
The sensor compares the current sample value to an average of the last three readings. If the difference is more than 12%, the sensor transmits the value immediately.
The averaged reading ensures that the sensor sends multiple messages if a large change occurs before it returns to sending messages at the default heartbeat transmission rate.
If both the average lux value and the current lux value are less than 50 lux, the on-change transmission behavior is disabled.
Note: On-change behavior for the CCT value is determined in a similar way as the lux level. If a large step change occurs, the CCT in kelvin can be smoothed out using a calculated average reading.
Tests and Settings
Use the [Teach] button and color LEDs to navigate the Tests and Settings menu. The [Teach] button and LED display are on the back of the sensor.
Note: The FLS-41 must be fully charged before running any test.
Expose the sensor to a strong light source, 200 lux (19 fc), for 15 minutes.
- Light Level Test (green LED)
- Range Confirmation (blue LED)
- Rapid Response Test (red LED)
- EEP Select (blue and red LEDs)
The menu times out after two minutes of inactivity.
Light Level Test
The Light Level Test quantifies the amount of energy produced by the solar cells and confirms a good installation location.
- Press and hold the [Teach] button until the green LED is displayed. Release the button to enter the menu and display the first item, the blinking green LED.
- Press and hold the [Teach] button again until the green LED stops blinking. The green LED then repeats a number of blinks according to the detected light level. The sensor reevaluates the light level every two seconds.
Blinks| Ambient Light Lux (Footcandles)| Time to Fully Charge| To Maintain Charge
---|---|---|---
0| < 80 (< 7.4)| Non-operational| N/A
1| 80–200 (7.4–18.6)| Operational| N/A
2| 200–400 (18.6–37.2)| 30–60 hours| 8 hours per day
3| 400–800 (37.2–74.3)| 15–30 hours| 4 hours per day
4| 800–2000 (74.3–185.8)| 7–15 hours| 2 hours per day
5| > 2000 (> 185.8)| 3–7 hours| 1 hour per day
The test repeats every two seconds and runs for 100 seconds. To exit before the time-out, press and hold the [Teach] button for 10 seconds.
Range Confirmation
The Range Confirmation test quantifies the strength of the wireless signal to a linked controller that has range confirmation capability.
Note: Only one controller can be linked to the FLS-41 to run the test properly. Disable repeaters that are in range.
- Press and hold the [Teach] button until the green LED is displayed. Release the button to enter the menu and display the first item, the blinking green LED.
- Press and release the [Teach] button to cycle through the menu of color LEDs and stop when the blue LED is blinking.
- Press and hold the [Teach] button until the LED stops blinking to initiate the Range Confirmation test.
After the FLS-41 transmits and receives a Range Confirmation message, the signal strength status is displayed as an LED blink color. LED Blink| Signal Strength
---|---
Green| -41 to -70 dBm (best)
Blue| -70 to -80 dBm (good)
Red| -80 to -95 dBm (poor, move closer)
No LED| No linked controllers detected
The test repeats every five seconds and runs for 50 seconds. To exit before the time-out, press and hold the [Teach] button.
Rapid Response Test
The Rapid Response Test confirms the settings on powered controllers to which the FLS-41 is linked. The test accelerates the sensor’s message rate, making the controller respond to light level changes faster. The transmission rate is increased to every 16 seconds for 100 seconds and then returns to normal operation.
-
Press and hold the [Teach] button until the green LED is displayed.
Release the button to enter the menu and display the first item, the blinking green LED. -
Press and release the [Teach] button to cycle through the menu of color LEDs and stop when the red LED is blinking.
-
Press and hold the [Teach] button to initiate the Rapid Response Test.
-
Vary the light level on the sensor to test the dimming and recovery response of the connected light fixture.
-
To exit before time-out, press and hold the [Teach] button.
EEP Select
The default EEP setting is configured to work with Echoflex controllers.
You can configure the sensor to be compatible with controllers that use an
alternate profile.
-
Press and hold the [Teach] button until the green LED is displayed.
Release the button to enter the menu and display the first item, the blinking green LED. -
Press and release the [Teach] button to cycle through the menu of color LEDs and stop when the blue and red LEDs are both blinking.
-
Press and hold the [Teach] button until the LEDs stop blinking to select EEP Select. The blue LED blink code displays the current setting.
-
Press and release the [Teach] button to navigate the options.
Indication| Setting
---|---
1 blue blink| EEP A5-06-04 Curtain Wall Brightness Sensor
2 blue blinks| EEP D2-14-25 Light Sensor and CCT (default)
3 blue blinks| General Profile -
Press and hold the [Teach] button to make a selection.
Compliance
For complete regulatory compliance information, see the Open Loop CCT Sensor datasheet at echoflexsolutions.com.
FCC Compliance
Echoflex Open Loop CCT Sensor
(For any FCC matters):
Echoflex Solutions, Inc.
3031 Pleasant View Road
Middleton, WI 53562
+1608-831-4116
echoflexsolutions.com
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received; including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to Part 15 of the FCC rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference
to radio communications. Any modifications or changes to this product not
expressly approved by Electronic Theatre Controls, Inc. could void the user’s
authority to operate the product.
Operation of this equipment in a residential area is likely to cause harmful
interference, in which case the user will be required to correct the
interference at their own expense.
Contains FCC ID: TCM300U
ISED Compliance
This device contains a license-exempt transmitter/receiver that complies with Innovation, Science, and Economic Development Canada’s license-exempt RSSs. Operation is subject to the following two conditions:
- This device may not cause interference.
- This device must accept any interference, including interference that may cause undesired operation of the device.
Contains IC ID: 5713A-STM300U
References
- The future of intelligent spaces | Echoflex
- The future of intelligent spaces | IP | Echoflex
- The future of intelligent spaces | Echoflex
- The future of intelligent spaces | IP | Echoflex
- The future of intelligent spaces | Echoflex