CRISTEC YPO-1M-2M-I YPOWER Battery Chargers User Manual
- June 5, 2024
- CRISTEC
Table of Contents
CRISTEC YPO-1M-2M-I YPOWER Battery Chargers
PRECAUTIONS – WARRANTY
The CRISTEC equipment includes the following :
- A box containing the battery charger’s electronic function.
- AC input connector
- DC output connector
- This user manual
- Specific packing
This document applies to battery chargers from the YPOWER range as listed on the cover (available in colour on our website www.cristec.fr).
The manual is intended for users, installers and equipment maintenance staff. Please read this manual carefully before working on the charger.
This manual should be kept safely and consulted before attempting any repairs because it contains all the information required to use the appliance.
This document is the property of CRISTEC; all the information it contains applies to the accompanying product. CRISTEC reserves the right to modify the specifications without notice
PRECAUTIONS (WARNING) – PROVISIONS RELATING TO SAFETY
Material class I according to NF EN 60335-2-29 standards.
The requirements for installation are contained in the NFC 15-100 standards and in the specific standard “for pleasure boats – electrical systems – alternating current installations” ISO13297reference.
The installation must be carried out by an electrician or a professional installer.
The AC network must be disconnected before starting any maintenance work on the equipment. This equipment is not intended to be used by children.
Main precaution
Before handling the charger, please read carefully this manual.
Precautions regarding electric shocks
Risk of electric shock and danger of death: it’s strictly forbidden to
interfere with the charger when under voltage.
Precautions regarding accidental earth leaks
The charger’s PE terminal must be earthed and connected before any other
terminal. The charger must be closed before it is turned on with the screw
provided for this purpose.
Accidental leakage current between phase and earth :
standard NFC15-100 should be followed when installing. Use the services of an electrician or professional installer to make the necessary connections. The charger should be connected to a system having a 30mA differential bipolar differential circuit-breaker. Accidental leakage current between the charge circuitand the earth : accidental current leakage at the earth must be detected by means of an independent protective device outside the charger (a residual current device or an insulation detector). The installer should decide on the rating and nature of the protection according to the risks. Special precautions should be taken on any installation prone to electrolyse phenomena.Regulations require the presence of a battery switch on the outputs of the + and the – poles.
Precautions regarding lightning
In areas highly exposed to lightning, it may be advisable to install a
lightning arrestor upstream ofthe charger to safeguard it against irreversible
damage.
Precautions regarding overheating of the appliance
This appliance is designed to be munted on a vertical wall or partition as indicated herein.
It is imperative that there be a gap of 150mm around the charger. The
installer must ensure that the temperature of the air at the input is lower
than 65°C in extreme operating conditions.
Measures should also be taken to allow for the evacuation of hot air on
either side of the charger.
It’s strictly forbidden to put any device on or against the charger.
The charger must not be installed near a heat source ; it should be installed
in a well-ventilated area. The charger’s air inlets and outlets must not be
obstructed.
**** Attention hot surface : do not touch the charger during and after its
operation (burn hasard).
Precautions regarding dust, seepage and falling water
The charger should be located so as to prevent penetration of damp, liquid, salt and dust, any of which could cause irreparable damage to the equipment and be potentially hazardous for the user.
The appliance should be installed in a dry and wellventilated place.
Precautions regarding inflammable materials
The charger should not be used near inflammable materials, liquids or gases.
The batteries can emit explosive gases : please follow the manufacturer’s
instructions carefully when installing them.
Nearby the batteries : ventilate the area, do not smoke, do not use any open
flame.
Use fuses as defined in this manual.
Ignition protection (Protection against ignition of surrounding flammable
gases) YPOWER 12V/40A without option is protected against ignition of
flammable gases following the ISO 8846 standard.
The DC output fuses F500 and F501 should only be replaced by the following
blade fuse Label : F500, F501, Quantity : 2
Manufacturer : BUSSMAN
Reference : BK-ATC-25M
Rating : 32V-25A
Other precautions
Never attempt to drill or to machine the charger’s case : this may damage components or cause metal chips or filings to fall on the charger’s board.
Do not do anything that is not explicitly stated in this manual.
WARRANTY
CRISTEC waives all liability if the installation rules and instructions for use are not observed.
The warranty applies if the origin of the failure is a fault internal to the charger due to CRISTEC.
The warranty applies for equipment returned to the Quimper plant (France).
-
The warranty, if confirmed by the expert’s report, covers only:
The repair (part(s) and labour)of faulty equipment returned to the Quimper plant (France). Only original parts recognized as being defective will be replaced under the warranty. -
Return shipping costs after repair (courier, by a carrier of our choice).
The warranty, if confirmed by the expert’s report, gives rise only to a repair of the equipment and not to a replacement of the equipment.
The warranty does not cover any other costs that may have been caused by the malfunction of the equipment, such as: shipping and packaging, disassembly, reassembly and testing costs, as well as all other costs not mentioned.
Our warranty on no account provides for any form of compensation. CRISTEC shall not be held liable for damage incurred as a result of using the battery charger.
The warranty does not apply if the origin of the failure is due to an external default (see below). In this case, a repair estimate will be issued.
Our warranty does not cover :
- Failure to abide by this manual
- Any mechanical, electrical or electronic alterations to the appliance
- Improper use
- Presence of moisture
- Failure to comply with AC power-supply tolerances (i.e. overvoltage)
- Incorrect connections
- Falls or impacts during transportation, installation or use
- Repairs carried out by anyone unauthorized by CRISTEC
- The maintenance in the energy conversion area made by a non-authorized person by CRISTEC
- Connection of any interface not supplied by CRISTEC
- The cost of packaging and carriage
- Apparent or latent damage sustained during shipment and/or handling (any such claims should be sent to the haulier)
- Any unjustified return of equipment (no failure on the equipment)
- Any other causes not listed above
OPERATING-PRESENTATION-INTERFACES
OPERATING PRINCIPLE
The design of the battery chargers in the YPOWER range is based on a high- frequency split converter that transforms the AC signal into regulated and filtered DC current. They can operate as a DC power supply.
Once the type of battery and type of charge has been selected, operation of the battery charger is entirely automatic (unless otherwise specified by the supplier or the manufacturer of the batteries). It can remain connected to the batteries and does not need to be disconnected when starting up an engine (marine application), because it is equipped with an integrated separator.
The appliance’s output voltage is sufficient to recharge 1, 2 or separate 3 batteries (integrated charge distributor, separation of batteries). The charger’s maximum output is the rated current distributed to each output according to the connected batteries banks.
Each output can deliver the rated current.
Not all the outputs have to be connected. However, if only one output is used,
we recommend interconnecting outputs +BAT 1, +BAT 2 and +BAT E to one another
(optional).
OVERVIEW PRESENTATION
The chargers are divided into 2 zones :
- The user interface zone
- The energy conversion zone (all maintenance in this area is forbidden except with CRISTEC authorization, under penalty of warranty termination)
Fixing of the charger is made by 4 x M5 round head screws (screw head diameter
less than 10 mm).
Center distance : see corresponding drawing in the appendices 3 to 5 depending
on model.
CONNECTIONS :
USER INTERFACE AREA
Chargers YPO 12-16, 12-25 and 24-12 – See appendix 1
Chargers YPO 12-40, 12-60, 24-20 and 24-30 – See appendix 2
INSTALLATION
This paragraph deals with installation of the equipment.
Installation and initial commissioning should be carried out by an electrician or professional installer in accordance with the standards currently in force (for pleasure boats the applicable internationa standard is ISO13297).
The installer should familiarize himself with this operating manual and inform
users of the instructions for use and the
safety warnings set out in the manual.
CHARGER OVERALL DIMENSIONS
Chargers YPO 12-16, 12-25 and 24-12 – See appendix 3
Chargers YPO 12-40 and 24-20 – See appendix 4
Chargers YPO 12-60 and 24-30 – See appendix 5
WIRING
When connecting or disconnecting a cable, the charger’s power supply must be
turned off and the batteries electrically insulated from the charger.
The references for additional cables and connectors required for the appliance
to operate efficiently are provided in the following paragraphs : failure to
comply with these provisions renders the warranty null and void.
Cable from the public AC power supply network or generator
Disconnect AC network before any wiring and connecting of the connector.
All YPOWER battery chargers can operate automatically and equally on single phase networks from 90 to 265VAC and from 47 to 65Hz.
Generators
The CRISTEC battery chargers are designed to operate from a generator.
Be careful : In some cases, the generators can produce high over voltages,
in particular during start-up phase. Before connecting the charger, please
check its compatibility with the characteristics of the generator : power,
voltage, overvoltage, frequency, current, etc.
It’s highly advised to disconnect the charger from the AC network during the
generator starting phase.
Any damage to the charger due to a voltage surge will be excluded from the
warranty.
Depending on cable lengths, the cross-section of AC power cables must be at least equal to or greater than the values provided in the table below :
Model| Minimum cross-section for 115VAC| Minimum cross-section
for 230VAC
---|---|---
YPO 12-16, 12-25 and 24-12| 3 x 1.5 mm²
YPO 12-40 and 24-20| 3 x 1.5 mm²
YPO 12-60 and 24-30| 3 x 2.5 mm²| 3 x 1.5 mm²
The type of cable (H07-VK, MX, etc.) should be defined by the installer according to the application type and applicable standards.
For applications where the electricity network may be either 115VAC or 230VAC, always choose the cross section recommended for 115VAC.
Always use cable markers without insulating collars in accordance with
installation standards governing AC network input connections.
The rating of the upstream circuit-breakers should match the equipment’s
requirements.
Mounting of AC supply connector
The AC input must be made using a WAGO connector type WINSTA reference770-103
| Strip the cable
about 3cm
---|---
| Strip 3
wires about 8mm.
Tin the end of bare copper or crimp a wire tip without collar.
| Open the
housing.
Remove the cable seal from the housing.
| Pass a flat
screwdriver into the square hole to open the contact and insert the wire.
| Carry out this
operation on the 3 wires, respecting polarity.
:Earth
N :Neutral
L:Phase
| Position the
connector in the housing, making sure that the cable enters by 1 cm approx.
Close the sides of the housing and screw.
Remarks :
The YPOWER chargers work as soon as they are powered on. (Input cable
connected and powered)
The YPOWER chargers stop as soon as they are not under voltage (disconnected
from AC network or installation circuit breaker in OFF position).
Battery cable
Disconnect batteries before any wiring and junction of the connector.
Please check the compatibility of voltage, current and setting according to the battery type before switching ON the charger.
Checking of the charge voltage
Before connecting the batteries to the charger, first check their polarity.
Equally check the battery voltage with a calibrated voltmeter. A too low
voltage value on some types of batteries show irreversible damage and
impossibility to recharge. Any damage due to incorrect connections will be
excluded from the warranty.
For battery cables up to 3 metres, the cross-section of the battery cables should be at least equal to or greater than the values provided in the table below:
Model | Battery cable cross-section |
---|---|
YPO 12-16, 12-25 and 24-12 | 10mm² |
YPO 12-40, 24-20 and 24-30 | 16mm² |
YPO 12-60 | 35mm² |
The installer should choose the type of cable (H07-VK, MX, etc.) according to the type of application and the applicable standards.
The DC outputs must use a PHOENIX CONTACT connector type. If you do not have 3 batteries, the terminals non-used bank will remain unconnected.
Model | PHOENIX CONTACT connector reference |
---|---|
YPO 12-16, 12-25, 12-40, 24-12, 24-20 and 24-30 | PC 16/4-STF-10,16 BK |
YPO 12-60 | PC35 HC/4-STF-15,00 BK |
PHOENIX CONTACT connector junction
- Connect from left to right : -BAT, +BAT E, + BAT 1 and BAT 2.
- – BAT (minus set of batteries)
- +BAT E (plus engine battery)
- +BAT 1 (plus battery set 1)
- +BAT 2 (plus battery set 2
Precautions regarding electromagnetic disturbance generated by the appliance
We recommend a minimum distance of 2m between the charger and any potentially sensitive equipment.
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and the receiving ends.
Keep cable length and shielding connections to a minimum.
Route cables as close as possible to conductive parts (“loose” cables or loops should be avoided – cables should be placed against the hull or walls).
Keep power cables separate from battery cables.
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any deviation to power
another appliance is prohibited.
(*) This is a recommendation for installation rather than an obligation. The
installing electrician should decidewhether or not to use shielded cable
depending on the EMC environment.
Cabling principle
Typical installation
This installation requires a GFCI (Ground Fault Circuit Interrupter), appropriate fuses on batteries and a battery compartment temperature probe.
Other types of cabling – see appendix 6.
SWITCHES SETTING-ADJUSTMENT-INDICATORS
Description
The YPOWER chargers are equipped with switches to configure the charger according the battery type and the application.
2 charging modes are available :
-
The BOOST function enables a faster charge of the batteries. This function is timed controlled (see table here after)
and is automatically switched off when the battery is fully charged : BOOST stops when batteries current < 20% of charger rated current. The BOOST function can also be disabled by means of a switch (E). -
The REFRESH function enables to apply periodically a voltage step to maintain the battery, to promote its equalization and prevent from any sulphation. This function is activated by means of a switch (F).
Setting according to the batteries type
Switches setting| Description of the battery type| Voltage with BOOST OFF|
Voltage with BOOST ON| Maximum duration of BOOST at +/- 5% T BOOST|
Maximum duration of ABSOPTION at +/- 5% T ABS
---|---|---|---|---|---
A| B| C| D|
0
| ****
0
| ****
0
| ****
0
| Opened type bat free electrolyte (wet)| ****
13.4V
| ****
14.1V
| ****
2H
| ****
4H
1
| ****
0
| ****
0
| ****
0
| Classic sealed type
bat (Sealed lead)
| ****
13.8V
| ****
14.4V
| ****
2H
| ****
4H
FACTORY SETTING
0
| ****
1
| ****
0
| ****
0
| GEL type bat| ****
13.8V
| ****
14.4V
| ****
2H
| ****
4H
1
| ****
1
| ****
0
| ****
0
| AGM type bat**| ****
13.6V
| ****
14.4V
| ****
2H
| ****
4H
0
| ****
0
| ****
1
| ****
0
| Spiral type bat| ****
13.6V
| ****
14.4V
| ****
2H
| ****
4H
1
| ****
0
| ****
1
| ****
0
| Tin calcium lead bat| ****
14.4V
| ****
15.1V
| ****
2H
| ****
4H
0
| 1| 1| 0| Wintering or standby sealed bat| ****
13.4V
| ****
13.4V
| ****
0H
| ****
0H
1
| 1| 1| 0| Stabilized DC power supply| ****
12.0V
| ****
12.0V
| ****
0H
| ****
0H
0
| ****
0
| ****
0
| 1| **SPE1 open type bat| **
13.2V
| ****
14.8V
| ****
2H
| ****
4H
1| 0| 0| 1| lithium iron phosphate (LiFePO4) with BMS **(*)| 13.8V| 14.4V| ****
6H
| ****
1H
0| 1| 0| 1| STORMLINE Bat| ****
13.7V
| ****
14.5V
| ****
2H
| ****
6H
0| 1| 1| 1| Booked
1| 1| 1| 1| Booked
(*) Voltage on + BAT 1, + BAT 2 and + BAT E with 10% of the rated current and a tolerance of +/- 1%.
The voltages values must be doubled for 24V batteries. ( ** ) REFRESH is not advised for certain types of AGM batteries (***) Battery Management System
Some specific settings are possible – please consult us.
Temperature compensation
The STP-NEW-2.8 probe enables the compensation of Absorption voltage and
Floating Voltage depending on the ambient temperature of the battery room. The
coefficient used is -3mV/°C/element. Temperature is not compensated when
Wintering (or standby sealed bat),
Stabilized DC power supply and lithium iron phosphate (LiFePO4) with BMS
settings are selected.
Factory setting
The charger’s factory settings are:
Sealed type battery (lead sealed) BOOST in ON position REFRESH in OFF
position|
---|---
This setting is a compromise for satisfactory recharging of different technologies of batteries :
- Opened classic lead
- Sealed, Gel or AGM
- Spiral sealed
- Lithium iron phosphate (LiFePO4) with BMS
To define the charge in function of your battery, please refer to the chart, paragraph : 3.3.2.The installer should set the switches (excluding input and output voltage) and possibly adjust the output voltage with no load using potentiometer R432 (use the appropriate tool to turn the screw of the potentiometer), depending on :
- the type of battery (contact the battery manufacturer if necessary)
- the intended usage
- the cross-section and length of the output cables
- whether or not the boost function is required
For special batteries, call in a professional installer, who will make the specific settings in accordance with the battery manufacturer’s specifications and according to the specifics of the installation.
CRISTEC is not liable for any damage caused to the batteries or for inefficient recharging.
Charging curve
BOOST in ON position
V BOOST : | BOOST voltage (see table above) |
---|---|
V FLOAT : | FLOATING voltage (see table above : voltage with no BOOST) |
T BOOST : | BOOST maximum duration (see table above – paragraph 3.3.2) |
TABS : | ABSORPTION maximum duration (see table above – paragraph 3.3.2 ) |
BOOST phase :
Starts up automatically when the charger is turned on if the battery is flat.
The current is then at maximum output.
ABSORPTION phase :
Begins when the voltage has reached the maximum BOOST level. The current level
starts falling.
These two phases combined last a maximum of TBOOST+TABS (depending on
setting). If the current falls below 20% of rated current, the FLOATING phase
automatically kicks in. Duration and current intensity depend on how charged
the battery is.
FLOATING phase :
Starts after TBOOST or if output current has reached 20% of the charger’s
rated current. The voltage switches to the FLOATING value and the rated
current continues to drop.
REFRESH phase :
It is an automatic weekly cycle (Inhibited or not by means of switch F) in
order to optimize the battery life duration. It will occur only after a
complete recharge cycle (BOOST, ABSORPTION and FLOATING).The charger will
generate automatically a safe timed voltage step every 7 days whatever the
position of BOOST switch.
Phase REBOOST :
Automatic phase consisting in coming back to a BOOST voltage if the DC
utilizations require it (i.e. after a complete recharge cycle BOOST,
ABSORPTION and FLOATING if a some DC constant consumptions are detected the
charger will restart a new complete charge cycle including a BOOST phase).
This REBOOST phase will be authorized after measuring certain battery voltage
during a determined time.
BOOST in OFF position
With this setting, the YPOWER charger produces a single-stage UI type charge
curve. It generates a constant voltage, supplying the current required by the
battery(ies). Recharging time depends on the state of the battery, being
longer than when the BOOST is in the ON position.
Indicators
The following led indicators are visible on the front of the appliance for monitoring
INDICATORS | STATE | MEANING |
---|---|---|
Green LED 1 “ON” | On | |
Off | No or poor quality AC current |
Input fuse is blown
Internal charger malfunction
Orange LED 2 “BOOST/ABSORPTION”| | Flashing (1 sec. ON, 1 sec. OFF)| Charger
in BOOST phase (switch E = ‘1’)
On fixed| Charger in ABSORPTION phase (switch E = ‘1’)
Green LED 2 “FLOATING/REFRESH”|
| On fixed| Charger in FLOATING phase
Flashing (1 sec. ON, 1 sec. OFF)| Charger in REFRESH phase (switch F = ‘1’)
Off| Internal charger malfunction or output fuse blown
EQUIPMENT MAINTENANCE AND REPAIRS
OVERVIEW
This paragraph deals with equipment maintenance and repairs. Proper operation of the product and its service life are dependent on strict compliance with the following recommendations.
EQUIPMENT MAINTENANCE
Disconnect the battery charger from the AC network and the batteries before
starting any maintenance work.
If appliances are in a dusty atmosphere, vacuum-clean them regularly, since
dust deposits may adversely affect heat dissipation.
Check the state of battery charge every 3 months.
Nuts and screws should be tightened annually to ensure efficient operation of
the appliance (particularly in rugged conditions: vibrations, shocks, high
variations in temperature etc.).
EQUIPMENT REPAIRS
Disconnect the battery charger from the AC power network and disconnect the
batteries before undertaking any repairs.
When fuses have blown, only use fuses of the type and size recommended in this
manual. Please contact CRISTEC or their distributor for any other repairs. Any
repair without CRISTEC prior agreement entails an exclusion of warranty.
TECHNICAL SPECIFICATIONS
YPO 12V-16A, 12V-25A, 24V12A
Part Number | YPO12-16 | YPO12-25 | YPO24-12 |
---|---|---|---|
Model | 12V/16A | 12V/25A | 24V/12A |
recommended battery bank (Ah) | 100-200Ah | 200-300Ah | 100-200Ah |
Input | |||
Voltage | from 90 to 265VAC single-phase automatic | ||
Frequency | from 47 to 65Hz automatic |
Input current consumption
230/115VAC
| 1.1/2.2A| 1.7/3.4A| 1.7/3.4A
Recommended power for a generator| 280W| 435W| 420W
Power factor| 1
Efficiency| 90% typical
Input fuses| T6,3A/250V – SCHURTER MST 250 Ref. 0034.6623 (F101)
Output|
Number of battery bank
| 3 : +BAT E, +BAT 1 et +BAT 2 (integrated Mosfet splitter )
1 -BAT
Each bank can be used individually and deliver the rated current
Total rated current (+/-7%) /
Rated power
| 16A/228W| 25A/356W| 12A/342W
Charging curve| IU or IUoU through internal dip switches (Boost, Absorption,
Floating and Refresh – factory setting)
Battery type| Lead sealed as factory setting – Gel, AGM, calcium lead,
LiFePO4, DC power-supply mode, etc.
Specific request on demand
Boost voltage| 14.4VDC for lead sealed battery (factory setting)| 28.8VDC for lead sealed battery (factory
setting)
Floating voltage| 13.8VDC for lead sealed battery (factory setting)| 28.8VDC for lead sealed battery (factory
setting)
Regulation tolerance before output
Mosfet splitter and fuse
| < 2% (at rated conditions)
Peak to peak ripple and noise| < 2% (at rated conditions)
Automotive output fuse mounted in
series in minus pole -BAT
| 1 x 20A/32V (F500)| 1 x 30A/32V (F500)| 1 x 15A/32V (F500)
Environment|
Cooling| Natural (fanless)
Sound level| 0| 0
Operating temperature at 230VAC| From -20°C to +60°C, derating from 60°C.
Above 65°C, automatic charger switch off, automatic restart when temperature
decreases
Storage temperature| From -20°C to +70°C
Relative humidity| up to 70% (95% without condensation)
Casing|
Material| Casing comprises 3 parts :
- Aluminium sink frame
- Thermoplastic body
- Aluminium clasp
Dimensions (length, height, depth) / Weight| 236 x 180 x 96 mm / 2.1kg| 236 x
180 x 96 mm / 2.1kg
Fixing center distance| 219 x 155 mm
Fixing screw (wall)| 4 x M5 round head screws
Protection factor| IP22
PCB protection| Water-repellent varnish (marine environment)
Standards|
CE declaration of conformity| Available on request
CE / EMC| EN61204-3
CE / Security – Others| EN60335-2-29. Pending UL and CSA.
Protections|
|
- Against leaking input surges by VDR rupture (voltage dependent resistor) – Not covered by warranty
- Against output polarity reversal by fuse rupture (removable automotive type)
- Against short-cuircuit and surge
- Against abnormal overheating by cutting off the charger (internal temperature probe – automatic restart)
Options|
Temperature probe| Output voltage compensation : -18mV/°C| Output voltage
compensation : -36mV/°C
Communication| CAN BUS interface
YPO 12V-40A, 12V-60A, 24V20A, 24V 30A
Part Number | YPO12-40 | YPO12-60 | YPO24-20 | YPO24-30 |
---|---|---|---|---|
Model | 12V/40A | 12V/60A | 24V/20A | 24V/30A |
recommended battery bank (Ah) | 300-500Ah | 500-700Ah | 200-300h | 300-500Ah |
Input | ||||
Voltage | from 90 to 265VAC single-phase automatic | |||
Frequency | from 47 to 65Hz automatic |
Input current consumption
230/115VAC
| 2.7/5.6A| 4.4/8.7A| 2.9/5.9A| 4.5/8.8A
Recommended power for a generator| 700W| 1050W| 700W| 1050W
Power factor| 1
Efficiency| 90% typical
Input fuses| T15A/250V – 6,3×32 (F101)| T15A/250V – 6,3×32 (F101)
Output|
Number of battery bank| 3 : +BAT E, +BAT 1 et +BAT 2 (integrated Mosfet
splitter ) 1 -BAT
Each bank can be used individually and deliver the rated current
Total rated current (+/-7%) / Rated power| 40A/570W| 60A/855W| 20A/570W|
30A/855W
Charging curve| IU or IUoU through internal dip switches (Boost, Absorption,
Floating and Refresh – factory setting)
Battery type| Lead sealed as factory setting – Gel, AGM, calcium lead,
LiFePO4, DC power-supply mode, etc.
Specific request on demand
Boost voltage| 14.4VDC for lead sealed battery (factory setting)| 28.8VDC for
lead sealed battery (factory setting)
Floating voltage| 13.8VDC for lead sealed battery (factory setting)| 28.8VDC
for lead sealed battery (factory setting)
Regulation tolerance before output
Mosfet splitter and fuse
| < 2% (at rated conditions)
Peak to peak ripple and noise| < 2% (at rated conditions)
Automotive output fuse mounted in series in minus pole -BAT| 2 x 25A/32V
(F500, F501)| 3 x 25A/32V (F500, F501, F502)| 1 x 25A/32V (F500)| 2 x 20A/32V
(F500, F501)
Environment|
Cooling| Natural (fanless) – Electric fan controlled in temperature and
current for 12V/60A and 24V/30A models
Sound level| 0| < 50dBa at 1m| 0| < 50dBa at 1m
Operating temperature at 230VAC| From -20°C to +60°C, derating from 60°C.
Above 65°C, automatic charger switch off, automatic restart when
temperature decreases
Storage temperature| From -20°C to +70°C
Relative humidity| up to 70% (95% without condensation)
Casing|
Material| Casing comprises 3 parts :
- Aluminium sink frame
- Thermoplastic body
- Aluminium clasp
Dimensions (length, height, depth) /
Weight
| 289 x 195 x 106 mm / 3.5kg| 289 x 195 x 106 mm / 3.5 kg
Fixing center distance| 272 x 170 mm
Fixing screw (wall)| 4 x M5 round head screws
Protection factor| IP22
PCB protection| Water-repellent varnish (marine environment)
Standards|
CE declaration of conformity| Available on request
CE / EMC| EN61204-3
CE / Security – Others| EN60335-2-29. Pending UL and CSA.
Protections|
|
- Against leaking input surges by VDR rupture (voltage dependent resistor) – Not covered by warranty
- Against output polarity reversal by fuse rupture (removable automotive type)
- Against short-cuircuit and surge
- Against abnormal overheating by cutting off the charger – automatic restart
Options|
Temperature probe| Output voltage compensation : -18mV/°C| Output voltage
compensation : -36mV/°C
Communication| CAN BUS interface
APPENDIX 6
-
Mounting 1 Engine Battery
-
Mounting 1 Engine Battery + 1 Auxiliary Battery
-
Mounting 1 Engine Battery + 2 Auxiliary Batteries
-
Mounting 2 Engine Batteries
-
Mounting 2 Auxiliary Batteries
-
Mounting 3 Auxiliary Batteries
Read User Manual Online (PDF format)