state WATER HEATERS SCESS00106 Commercial Light Duty Electric Water Heaters Instructions

June 4, 2024
state WATER HEATERS

state WATER HEATERS SCESS00106 Commercial Light Duty Electric Water

Heaters

state-WATER-HEATERS-SCESS00106-Commercial-Light-Duty-Electric-Water-
Heaters-product

PATRIOT™

Designed for use as a recovery heater having its own storage tank. Available in upright, standard, and lowboy models.

GLASSLINED TANK

Thirteen sizes; 6 thru 119 gallon capacity. Tank interior is coated with glass specially designed by State Water Heaters for water heater use.

ELEMENTS

Zinc plated copper sheaths for longer life. Medium watt density means lower surface temperature to minimize scale build-up and more surface to heat water. Element sizes from 1.5 to 6.1 KW. Maximum input 12 KW (see chart).

STANDARD VOLTAGES

120, 277 single phase and 208, 240 and 480V unbalanced three-phase delta; easily converted to single-phase at terminal block (except 208V with 5500 watt elements). Single element heaters, single-phase only.

TERMINAL BLOCK

Factory-installed. Just bring the service to heater and connect to block. Terminal block not supplied on 120V & 277 volt models. (No junction box on PCE 6-20)

CONTROLS

Temperature control (adjustable through arange of 130° to 170°F on single element and 120° to 181°F on dual element) and manual reset high temperature cutoff per element (dual element models). Factorywired for non-simultaneous operation; easily converted to simultaneous element operation (three phase models only).

  • CSA CERTIFIED AND ASME RATED T&P RELIEF VALVE
  • SIMPLIFIED CIRCUITRY, COLOR CODED FOR EASE OF SERVICE
  • ANODE ROD FOR MAXIMUM CORROSION PROTECTION
  • CABINET HAS BONDERIZED UNDERCOAT WITH BAKED ENAMEL FINISH
  • TOP INLET AND OUTLET OPENINGS
  • DRAIN VALVE (EXCLUDES PCE 6-20)
  • UL APPROVED FIELD CONVERSION PROGRAM

COMPLIANCE

Meets the standby loss Requirements of the U.S. Department of Energy and current edition of ASHRAE/IESNA 90.1.

LIMITED WARRANTY OUTLINE

If the tank should leak any time during the first three years, under the terms of the warranty, State Water Heaters will furnish a replacement heater; installation, labor, handling and local delivery extra. THIS OUTLINE IS NOT A WARRANTY. For complete information consult the written warranty or statewaterheaters.com 

PRODUCT OVERVIEW

state-WATER-HEATERS-SCESS00106-Commercial-Light-Duty-Electric-Water-Heaters-
fig1

ROUGH-IN DIMENSIONS


Models

| ****

UEF

| No. of Elements| Nominal Capacity| Rated Storage Volume| A| B| C| D| Shipping Weight
---|---|---|---|---|---|---|---|---|---
Inches| mm| Inches| mm| Inches| mm| Inches| mm| lbs.| Kg.
PCE- 6| N/A| 1| 6| 6| 15-1/2| 394| 14-1/4| 362| 11| 279| N/A| N/A| 35| 15.9
PCE- 10| N/A| 1| 10| 10| 18-1/4| 464| 18| 457| 12-1/2| 318| N/A| N/A| 54| 24.5
PCE- 15| N/A| 1| 15| 15| 26| 660| 18| 457| 20-1/2| 521| N/A| N/A| 58| 26.3
PCE- 20| N/A| 1| 20| 19| 22-1/4| 565| 21-3/4| 552| 15-3/8| 391| N/A| N/A| 73| 33.1
PCE-30-20LS| 0.92| 2| 30| 33| 33-1/2| 851| 26| 660| 24| 610| 8| 203| 118| 53.5
PCE-40-20LS**| 0.92| 2| 40| 35| 32| 813| 23| 584| 24| 610| 8| 203| 118| 53.5
PCE-50-20LS| 0.92| 2| 50| 48| 36| 914| 26-1/2| 673| 25| 635| 8| 203| 172| 78
PCE-30-20RT| 0.92| 2| 30| 37| 49-3/4| 1264| 20-1/2| 521| 53-1/4| 1353| 8| 203| 118| 53.5
PCE-40-20RT| 0.92| 2| 40| 45| 59| 1499| 20-1/2| 521| 51-1/4| 1302| 8| 203| 125| 56.7
PCE-52-20RT| 0.92| 2| 52| 55| 56-1/2| 1435| 24| 610| 48-1/2| 1232| 8| 203| 145| 65.8
PCE-66-20RTA| N/A| 2| 66| 60| 60-3/4| 1543| 21-3/4| 552| N/A| N/A| 8| 203| 176| 79.8
PCE-82-20RTA| N/A| 2| 80| 76| 59-3/8| 1508| 24| 610| N/A| N/A| 8| 203| 211| 95.7
PCE-120-20RTA| N/A| 2| 120| 108| 62-7/16| 1586| 29-3/8| 746| N/A| N/A| 8| 203| 326| 147.9

*No side outlet available on PCE-6 Model
**Blanket model
Note: All 66, 80 and 120 models will be manufactured with two 6.1kW elements – 12.2kW

U.S Gallons/HR and Litres/HR at Temperature Rise Indicated

Element Wattage (Upper/Lower)|

Input KW

| | 36 | 40 | 54 | 60 | 72 | 80 | 90 | 100 | 108 | 120 | 126
| 20 | 22.2 | 30 | 33.3 | 40 | 44.4 | 50 | 55.5 | 60 | 66.6 | 70

6100/6100

|

12.2

| GPH| 138| 124| 92| 82| 69| 62| 55| 49| 46| 41| 39
LPH| 522| 469| 348| 310| 261| 235| 208| 184| 174| 153| 146

Recovery capacities at 100° F equal: for simultaneous element operation – 4.1 gal. x 2/3 KW of both elements. For other rises multiply element KW as previously explained by 4.1 and divide by temperature rise.
Full load current for single phase = total watts.

ELEMENT AVAILABILITY CHART (LIGHT-DUTY COMMERCIAL ELECTRIC)

Models & Elements| Voltage| Wiring| kW Input Available
---|---|---|---



6-Gallon Models Single-Element

| 120V| –| 1.5| 2| 2.5| 3|  |  |  |  |  |
208V| –| 1.5| 2| 2.5| 3|  |  |  |  |  |
240V| –| 1.5| 2| 2.5| 3|  |  |  |  |  |
277V| –| 1.5| 2| 2.5| 3|  |  |  |  |  |
480V| –|  | 2| 2.5| 3|  |  |  |  |  |



10-Gallon through 20-Gallon Models Single-Element

| 120V| –| 1.5| 2| 2.5| 3|  |  |  |  |  |
208V| –| 1.5| 2| 2.5| 3| 3.5| 4| 4.5| 5| 5.5| 6
240V| –| 1.5| 2| 2.5| 3| 3.5| 4| 4.5| 5| 5.5| 6
277V| –| 1.5| 2| 2.5| 3|  | 4| 4.5| 5|  | 6
480V| –|  | 2| 2.5| 3|  | 4| 4.5| 5| 5.5| 6

6 gallon model not available above 3kW
6/10/15/20 gallon models all A6 circuit (2 wire) only † Exceeds maximum amp draw.
** Simultaneous only in 3ph

Model

| Element Wattage
---|---
 | 120V| 208V| 240V| 277V| 480V

PCE-20-20LS

| Min Watts| N/A| 4500| 4500| 4500| 4500
Max Watts| N/A| 6000 ()| 6000 ()| 6000| 6000

PCE-40-20LS

| Min Watts| N/A| 4500| 4500| 4500| 4500
Max Watts| N/A| 6000 ()| 6000 ()| 6000| 6000

PCE-50-20LS

| Min Watts| N/A| 4000| 4000| 4000| 4000
Max Watts| N/A| 6000 ()| 6000 ()| 6000| 6000

PCE-30-20RT

| Min Watts| N/A| 4500| 4500| 4500| 4500
Max Watts| N/A| 6000 ()| 6000 ()| 6000| 6000

PCE-40-20RT

| Min Watts| 3000 ()| 3000| 3000| 3000| 3000
Max Watts| 3000 (
)| 6000 ()| 6000 ()| 6000| 6000

PCE-52-20RT

| Min Watts| 2500| 2500| 2500| 2500| 2500
Max Watts| 3000 ()| 6000 ()| 6000 (*)| 6000| 6000

Additional limitations apply to 120V, 208V, and 240V – Simultaneous Operation are not available (*) for these voltages.

RECOVERY CAPACITIES


Element Wattage (Upper/Lower)

| ****

Input

| U. S. Gallons/Hr and Litres/Hr at Temperature Rise Indicated
---|---|---
| 36| 40| 54| 60| 72| 80| 90| 100| 108| 120| 126
kW| | 20| 22.2| 30| 33.3| 40| 44.4| 50| 55.5| 60| 66.6| 70
Non-Simulataneous Operation
/1500| 1.5| GPH| 17| 15| 11| 10| 8| 8| 7| 6| 6| 5| 5
LPH| 64| 58| 43| 38| 32| 29| 26| 23| 21| 19| 18
/2000| 2| GPH| 23| 20| 15| 14| 11| 10| 9| 8| 8| 7| 6
LPH| 85| 77| 57| 51| 43| 38| 34| 31| 28| 26| 24
/2500| 2.5| GPH| 28| 25| 19| 17| 14| 13| 11| 10| 9| 8| 8
LPH| 107| 96| 71| 64| 53| 48| 43| 38| 36| 32| 30
3000/3000| 3| GPH| 34| 30| 23| 20| 17| 15| 14| 12| 11| 10| 10
LPH| 128| 115| 85| 77| 64| 58| 51| 46| 43| 38| 37
4000/4000| 4| GPH| 45| 41| 30| 27| 23| 20| 18| 16| 15| 14| 13
LPH| 170| 153| 114| 102| 85| 77| 68| 61| 57| 51| 49
4500/4500| 4.5| GPH| 51| 46| 34| 30| 25| 23| 20| 18| 17| 15| 14
LPH| 192| 173| 128| 115| 96| 86| 77| 69| 64| 58| 55
5000/5000| 5| GPH| 56| 51| 38| 34| 28| 25| 23| 20| 19| 17| 16
LPH| 213| 192| 142| 128| 107| 96| 85| 77| 71| 64| 61
6000/6000| 6| GPH| 68| 61| 45| 41| 34| 30| 27| 24| 23| 20| 19
LPH| 256| 230| 170| 153| 128| 115| 102| 92| 85| 77| 73
Simulataneous Operation
3000/3000| 6| GPH| 68| 61| 45| 41| 34| 30| 27| 24| 23| 20| 19
LPH| 256| 230| 170| 153| 128| 115| 102| 92| 85| 77| 73
4000/4000| 8| GPH| 90| 81| 60| 54| 45| 41| 36| 32| 30| 27| 26
LPH| 341| 307| 227| 205| 170| 153| 136| 123| 114| 102| 97
4500/4500| 9| GPH| 101| 91| 68| 61| 51| 46| 41| 36| 34| 30| 29
LPH| 384| 345| 256| 230| 192| 173| 153| 138| 128| 115| 110
5000/5000| 10| GPH| 113| 101| 75| 68| 56| 51| 45| 41| 38| 34| 32
LPH| 426| 384| 284| 256| 213| 192| 170| 153| 142| 128| 122
6000/6000| 12| GPH| 135| 122| 90| 81| 68| 61| 54| 49| 45| 41| 39
LPH| 511| 460| 341| 307| 256| 230| 205| 184| 170| 153| 146

Recovery capacities at 100° F rise equal: for non-simultaneous element operation = 4.1 gal. x kW of one element; for simultaneous element operation = 4.1 gal. x 2/3 kW of both elements.
For other rises multiply element kW as previously explained by 410 and divide by temperature rise. Full load current for single phase = total watts/voltage.

SPECIFICATION

The water heaters(s) shall be Patriot™ Model(s) No. __ as manufactured by State Water Heaters or an approved equal. Heater(s) shall be rated at kW, volts, -phase, 60 cycle AC, and listed by Underwriters’ Laboratories. Models shall meet the standby loss requirements of the U.S. Department of energy and current edition of ASHRAE/IESNA 90.1. Tank(s) shall be gallon capacity. Heater(s) shall have 150 psi working pressure and be equipped with extruded high density anode rod. All internal surfaces of the heater(s) exposed to water shall be glasslined with an alkaline borosilicate composition that has been fused-to-steel by firing at a temperature range of 1400°F to 1600°F. Electric heating elements shall be medium watt density with zinc plated copper sheath. Each element shall be controlled by an individually mounted thermostat and high temperature cutoff switch. The outer jacket shall be of backed enamel finish and shall enclose the tank with foam insulation. Electrical junction box with heavy duty terminal block shall be provided (except on 120V & 277V {no junction box on PCE 6 thru 20}). The drain valve shall be located in the front for ease of servicing. Heater tank shall have a three year limited warranty as outlined in the written warranty. Fully illustrated instruction manual to be included.

FOR MORE INFORMATION, CONTACT: STATE WATER HEATERS 500 TENNESSEE WALTZ PARKWAY, ASHLAND CITY, TN 37015 800-365-0024 TOLL-FREE USA STATEWATERHEATERS.COM

© January 2022 State Water Heaters. All Rights Reserved
www.statewaterheaters.com | 800-365-0024 Toll-Free USA | State Water Heaters | 500 Tennessee Waltz Parkway | Ashland City, TN 37015

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

state WATER HEATERS User Manuals

Related Manuals