KEYSTONE KTSL-FC2-12V-SM-PIR Integrated Fixture Controller Owner’s Manual
- June 3, 2024
- Keystone
Table of Contents
KEYSTONE KTSL-FC2-12V-SM-PIR Integrated Fixture Controller
DESCRIPTION
Bluetooth mesh wireless low voltage individual fixture controller for
SmartLoop system with integrated daylight and PIR motion sensors.
APPLICATION
Ideal for small- to medium-size systems, such as schools and offices. Installs
directly into 0-10V fixtures with available 12V auxiliary power.
PRODUCT FEATURES
- Small form factor for unobtrusive installation
- 0-10V control wires for integration with most commercially available fixtures
- 12VDC input (use driver with 12V aux power)
- Installs via 3/8” drilled hole on fixture sheetmetal. Simply drill, route the wires and threaded collar through, and tighten nut to lock into place.
- Driver should be dim-to-off, no relay control on sensor
- Commissioned via SmartLoop mobile app for iPhone and Android
- Controlled via SmartLoop mobile app, keypad, and sensors
- Utilizes Bluetooth mesh technology for reliable and secure wireless communication
- Power outage recovery defaults to automatic on state
- Indicator LED communicates device status
- UL2043 certified for plenum installations
- Suitable for dry and damp locations
ELECTRICAL SPECIFICATIONS
Input Voltage | 10-15VDC |
---|---|
Power Consumption | 0.2W |
RF Transmit Power | 8dBm |
Max 0 –10V Sinking Current | 10mA |
Wireless Frequency | 2.4GHz |
Wireless Range (Open Air) | 100m |
Wireless Protocol | Bluetooth 4.2 |
Sensor Detection Height | 16’ max |
Sensor Detection Angle | 120º |
Daylight Harvesting Range | 100-1000 lux |
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature | − 20ºC/–4ºF to 60°C/140ºF |
---|---|
Storage Temperature | − 40ºC/− 40ºF to 85°C/185ºF |
Humidity | 5–95% |
Lifetime Rating | >100,000 hrs |
Moisture and Dust Rating | Suitable for dry and damp locations |
FACTORY SETTINGS
Photo Sensor | Enabled |
---|---|
Motion Sensitivity | 100% |
Motion Sensor | Enabled |
Motion Mode | Occupancy |
Hold Time | 20m |
Standby Time | 1m |
Standby Percentage | 50% |
SAFETY AND EMC COMPLIANCE
UL/cUL | UL8750, UL2043 |
---|---|
FCC | Part 15.247 |
PHYSICAL SPECIFICATIONS
WIRING DIAGRAM
WIRE SPECIFICATIONS
Name| Function| Color| Gauge| Type| Length|
Strip Length
---|---|---|---|---|---|---
+12V| Aux Power| Yellow| ****
22AWG
| ****
Stranded
| ****
15.35”
| ****
0.39”
10V+| Dimming Level| Purple
10V−| Low Voltage Common| Pink
LENS COVERAGE
FACTORY RESET
If a controller is assigned to another region, it will not appear when
searching for new fixtures. Perform the following power cycle sequence to
factory reset the controller:
- Power on for 1 second, then off for 10 seconds.
- Power on for 1 second, then off for 10 seconds.
- Power on for 1 second, then off for 10 seconds.
- Power on for 10 seconds, then off for 10 seconds.
- Power on for 10 seconds, then off for 10 seconds.
- Turn the fixture back on. The device should now be decommissioned and ready to add to a region.
ORDERING INFORMATION
ORDER CODE | PACK QTY. | EASY CODE | UPC |
---|---|---|---|
KTSL-FC2-12V-SM-PIR | 54 | TCM-01 | 843654135236 |
CATALOG NUMBER BREAKDOWN
- Keystone Technologies SmartLoop
- Fixture Controller
- Design Style 2
- Low Voltage
- Surface Mount
- PIR Sensor Type
Keystone Technologies
- Philadelphia, PA
- Phone 800-464-2680
- www.keystonetech.com
Specifications subject to change. Last revised on 09.23.22