KALVIS K-5 Central Heating Solid Fuel Boiler Instruction Manual

June 4, 2024
KALVIS

K-5 Central Heating Solid Fuel Boiler
Instruction Manual

Dear Customer,
Thank you for selecting the KALVIS product.
Please read this manual carefully, taking particular attention to the safety clauses given on the starting pages.
Be sure to save this manual to use in the future or to pass on the further users.
Transport damages
After unpacking, check the item for transport damages. If in doubt, don’t start using it, contact the seller.
Legend:

| Important information or useful advice on the installation or use of this product.
---|---
| Warnings for your health or property safety and correct operation of the product.
| Warnings on fire hazards.
| Warnings on potential explosion hazards.
****| Warnings on hot surfaces.
| Advises and information on economical and environment-friendly use of the product.

** This user manual was compiled observing the requirements provided for in LST EN 12171 Heating systems in buildings – Procedure for the preparation of documents for operation, maintenance, and use – Heating systems not requiring a trained operator. 
**

Purpose

Solid fuel water heating boiler Kalvis-5-8(6); Kalvis-5-12(10) (the boiler) is used to heat various premises having a central heating system with forced circulation installed.

Safety precautions

** a boile r  can be operated by adults well familiar with its construction and this technical manual.
**
In the case of fire or if the chimney is on fire, close the air supply to the boiler and call the fire fighting service (tel. 112). If possible, remove burning fuel and ember from the hearth into a tight or water-filled container (beware of water steam, use protective gloves).
It is prohibited:

  • To modify boiler construction without permission;
  • To dry fuel and other flammable objects near or on the boiler;
  • To leave unattended children or entrust boiler maintenance to children, disabled, untrained persons;
  • During stoking, open or keep open boiler door;
  • To fire the boiler without filling the heating system with water. Water should not freeze in the heating system and boiler;
  • To connect the boiler into a closed system without a protective valve, which prevents overpressure in the system of more than 2,5 bar (0,25 MPa);
  • When a boiler is in operation, close the inlet and return line valves;
  • To dispose of glowing ash near residential and auxiliary buildings.

It is prohibited to stoke the boiler with:

  • Fine wood waste (dust), because of explosion risk or spark discharge from the chimney;
  • Waste (household waste);
  • Furniture waste.

**** It is prohibited to overheat (boil) water in the boiler!

General remarks

Since the boiler construction is constantly being improved, minor deviations from this manual are possible.
When installing the boiler, the country’s building standards and fire protection requirements must be respected.
Only the attested firm, the installation work specialists, or duly authorized manufacturer’s agent are allowed to carry out the boiler installation, adjustment, and training of boiler operators. It is mandatory to make an installation mark in this passport “the installation report”. The installed and connected boiler must be checked by fire safety personnel. The boiler shall be installed in the heating system that maintains at least
60 °C return water temperature. In the case of failure to comply with this requirement, corrosion from condensate significantly shortens the life of the casing.
It is strictly forbidden to fire the boiler, without having filled it with heating system water.
When firing the boiler for the first time, while its body is heating and paint is finally curing, unpleasant-smelling volatile substances emit, so the premises should be well ventilated.
Use fuel no wetter than 25 % of moisture content. At higher moisture content, boiler power decreases fuel consumption increases.
In case of an excessive chimney draught, when sawdust, wood chips, chaff or other bulk materials are used as fuel, during its loading or after burning off fuel and shaking the residues, sparks may fly from the chimney.
If the roof or the building itself were built using easily flammable materials or other similar construction works, building materials, fuel, and so on is less than 20 meters away from the chimney, the use of referred fuels is strictly prohibited!
The boiler is working optimally when it reaches power close to nominal. If the boiler output is too high and significantly lower than the nominal is needed, we recommend installing the boiler with an accumulation tank.
With lower heat demand than the boiler’s nominal power, in order, there was no constant loaded fuel smoldering (resins may start to accumulate in the boiler), do not fill the fuel combustion chamber at full. It is recommended to remove the heat exchanger nebulizer and reduce chimney draught by tightening the smoke damper.
**** It is categorically forbidden to pour water on the burning fuel in the combustion chamber. This can cause permanent damage to the boiler.

Product Description

4.1. Technical Data

Boiler model Kalvis-5-8 6 Kalvis-5-12 10
Inserted heat exchanger turbulizer *1 +
Nominal power *2 kW 8 6
Release to the heating system kW 7,5 5,6
Release to premises *3 kW 0,5 0,4
Chimney draught no less than Pa 8
no more than 13 11 18
Heated area *4 for B class buildings ma 69…168
for C class buildings 37…88 28…66 55…132
Fuel used firewood *5
Firewood size L x 0, up to cm 30 x 10 30 x 10
Firewood position in the combustion chamber longitudinal longitudinal
Loading hole dimensions mm 215 x 130 320 x 145
The volume of the combustion chamber dm3 (I) 25 32
Foe charge combustion duration, at nominal power. hour 2 I 2,2 2,2 I 3
Efficiency factor at nominal power, no less than % 76
Boiler class according to LST EN 303-5 3
Boiler water volume I 1824
Recommended minimum accumulation tank volume I 280410
Water operation pressure in the boiler no less than bar (MPa) 0,3 (0,03)
no more than 2,5 (0,25)
Max allowed water temperature in closed heating system °C 90
in the open heating system *7 °C 80
Lowest boiler retum water temperature during operation °C 60
Hydraulic resistance bar 2,5
Working environment temperature °C 3 … 40
Temperature regulator adjustment range °C 70 … 90
Discharged flue temperature at nominal power, up to °C 210 200
Discharge flue gas volume at nominal power kg/s 0,013 I 0,011 0,020 I 0,018
Connection pipe dimensions: flue pipe

heating system
water discharge| mm
col
col| 0120
G1-B
G’/2-B| 0130
G1-B
G1/2-B
Overall dimensions (net/gross), no more than:| height (H) breadth (B) length (L)| mm
mm
mm| 790 / 830
410 / 550
620 / 850| 1010 / 1170
455 / 550
620 / 850
Mass (net/gross), no more than (±10%)| kg| 112 / 118| 160 / 166

  1. With inserted heat exchanger nebulizer (extended flue path) and having set flue draught valve at 8…10 Pa draught, 8 kW boiler power is reached. After reducing the draught  closing the flue draught valve) to 6…8 Pa and removing heat exchanger nebulizer (shortened flue path), boiler power is reduced to 6 kW.
  2. When stoking with 18-20 % moisture birch firewood. It is not recommended to stoke with firewood with moisture over 25 %.
  3. It is recommended to avoid radiator installation in the boiler room because heat from the boiler is transmitted by air. If there is a possibility, additional heat (from the boiler room) should be transferred into rooms next to it, by the natural convection method.
  4. Energy quantity calculated in accordance with the requirements of STR 2.01.02:2016 „Energy Performance of Buildings Design and Certification“, expressed for B and C  lass Energy Performance of Buildings.
  5. As a backup fuel, piece wood waste, and sawdust briquettes can be used.
  6. Fuel charge burning duration depends on the fuel type, moisture, outdoor temperature, and other factors.
  7. It is not recommended to install a boiler with an accumulator tank in an open heating system. An intensive boiler firing at an ambient temperature close to 80 °C will cause water o boil in the boiler, resulting in extraneous sounds.

4.2. Construction
The boiler body is welded from steel sheets and has water compartments where water is heated. The body is covered with thermal insulation decorative panels.
In front of the boiler, there is the combustion chamber and the fuel loading door. Behind the combustion chamber, there is an iron door. Inside the housing, there is a fire grate and ash drawer underneath. Air draught control manages the air supply valve located in the combustion chamber door. The air required for combustion is supplied through the grate.
In the upper part of the housing, there is a heat exchanger with the removable nebulizer, which represents a long way for the flue to give up the heat, before reaching the flue pipe.
The hot water flows into the heating system through the upper pipe installed at the back of the boiler and the cooled water returns via the bottom branch pipe. The pipe of the discharge of water from the boiler and the whole heating system is also welded in the bottom.

Fig. 1. Boiler construction.

1. Boiler body. 2. Heat exchanger turbulizer. 3. Flue pipe. 4. Flue draught damper. 5. Outgoing
(hot) water branch pipe. 6. Decorative thermal insulation panels. 7. Combustion chamber.
8. Returning (cooled) water branch pipe. 9. Water from the boiler discharge branch pipe.

  • dimensions:

1. Boiler body.
2. Heat exchanger turbulizer.
3. Flue pipe.
4. Flue draught damper.
5. Outgoing (hot) water branch pipe.
6. Decorative thermal insulation panels.
7. Combustion chamber.
8. Returning (cooled) water branch pipe.
9. Water from the boiler discharge branch pipe.
10. Firegrate.| 11. Ash drawer.
12. Air supply valve.
13. Combustion chamber door.
14. Cast iron door.
15. Fuel loading door.
16. Smoke damper.
17. Air draught regulator.
18. Air supply valve adjustment screw.
19. Welded nuts for boiler fastening onto the pallet and height adjustment at installation.
---|---

* dimensions:

Model| H| B| L| A| C| D| E| F| G| J| K| M
---|---|---|---|---|---|---|---|---|---|---|---|---
Kalvis-5-8(6)| 790| 410| 620| 235| 415| 705| 635| 145| 190| Ø120| 110| 95
Kalvis-5-12(10)| 1010| 470| 620| 310| 415| 930| 880| 145| 230| Ø130| 150| 135

Boiler Installation

The boiler shall be installed observing the requirements set for the relevant premises in the relevant country.
Boiler stoking needs a lot of air, so it is necessary to ensure sufficient air supply into the premises where the boiler is to be installed.
Set the boiler vertically or inclined forward by no more than 1°. The floor in the premises shall be even, inflammable, and able to withstand up to 0.2 t/m load.
Boiler installation height (leveling) can be adjusted with the means of the 2 screws used for boiler fastening onto the transportation pallet. Before connecting the boiler to the eating system and chimney, take into account that during operation it has to be maintained (cleaning, adjustment, worn part changing, etc). The least distances from the boiler to the walls and ceiling required for correct maintenance and fire safety are given in Fig. 2.

5.1. Fire Safety Precautions

  • ****Set the boiler on an inflammable base.
  • If metal tubes are used to connect the boiler to the chimney, such tubes must be mechanically strong enough and covered with heat insulation material.

5.2. Requirements for Chimney
Chimney construction and boiler connection options are shown in Fig. 3.
Requirements:

  • Chimney draught has to be in line with the data in the main technical data table (see page 6);
  • The chimney hole has to have no less cross-section than the cross-section of the flue pipe outgoing from the boiler;
  • The boiler needs a separate chimney hole. No other connections are allowed into the same hole;
  • If the chimney is connected through an extra elbow, it must have no less cross-section than the flue exit from the boiler hole, with bending radii no less than 100 mm;
  • Pipe from boiler flue pipe to chimney has to be no longer than 1.5 m and rise in the direction of the chimney, providing the option for its cleaning;
  • Seal well the gaps in the joining and chimney entering places.

It is necessary to know that:

  • Flue out of the boiler goes through a flue pipe, enters the chimney further cooling, vapor contained in the flue condenses and settles on the chimney walls, in particular in an unheated attic and external part of the chimney;
  • Condensate acids and heat-frost erosion over several years can destroy the chimney;
  • Not cleaning soot in the chimney over time can cause a fire if the chimney is in the improper state or if the roof covering is easily flammable.

It is recommended:

  • To install stainless steel liner in the chimney. Wall mounted chimney insert prevents condensation and improves draught;
  • Insert shall not significantly decrease the cross-section of the chimney;
  • Insert parts should be sealed together (not by soldering);
  • A condensate drain must be installed at the bottom;
  • Fill in the gap between the liner and the chimney walls, at least in the outer part of the chimney, with non-combustible heat insulating material. Plaster hermetically the gap  n the top and tin-coat with a slope (from the opening to the edge of the chimney);
  • In the cold attic, winterize the chimney with inflammable heat insulation material;
  • If a fire starts in the chimney, close the air supply to the boiler and call fire service;
  • Install vents in the chimney connection, in a convenient location, for periodic (once a month) soot cleaning;
  • It is recommended to have the chimney once a year examined by qualified chimney maintenance professional.

5.3. Connection to the heating system
Many heat consumers’ boiler house connection schemes are becoming increasingly complex. Several alternative heat generators: solid fuel or gas boiler, additional pellet burner, electric heating, heat pumps, solar collectors, etc. are combined. For indoor, various heating radiators, underfloor or air heating, accumulation tanks, and various water heating equipment are used. Therefore, under specific conditions and user preferences, the selection of a suitable boiler and preparation of a connection scheme, can be entrusted only to skilled designers and experienced installers.

A part of recommended boiler connection circuit, execution of which ensures long-term boiler operation, prevents condensate formation inside the boiler. The circuit shows no auxiliary technology equipment (valves, expansion vessel, etc.)
** Fig. 5 shows only recommended part of the circuit for boiler connection into the heating system, ensuring no less than 60 ºC return water temperature to the boiler. The circuit has no auxiliary technology equipment (valves, expansion vessels, etc.).
Requirements for connection:**

  • In order to avoid condensation in the boiler, which could reduce the operation time of the boiler, the heating system has to maintain no less than 60 ºC return water temperature.

  • A safety valve (G½B) has to be installed in the system as close to the boiler as possible, in order to protect boiler housing from a pressure exceeding 2.5 bar (0.25 MPa). No losing fittings are allowed between the boiler and the safety valve.
    **** If valves disconnecting the boiler from the heating system are installed in the system pipes, they must be fully open. To avoid accidents due to inadvertence, after opening the valves, it is appropriate to remove their handles.

  • In the case boiler is connected to a closed heating system with a membrane expansion vessel, its permissible pressure can be up to 10 bar, and air pressure must be equal to the system pressure, e.g. 0.6 bar. In the case of preparing an open-type heating system, instead of a membrane expansion vessel, an open-type expansion tank can be installed.
    **** During installation, a sleeve with G½B thread shall be welded in a clearly visible place on the outgoing water pipe to be used to screw in the supplied thermal-pressure gauge.

  • If the boiler operates at much lower nominal power than it is given in the technical data sheet, boiler efficiency is drastically reduced, and ecological indicators get worse. In this case, a boiler with an accumulation tank is recommended.
    If there is a system freezing risk or during boiler repairs, drain water from the system and boiler through a discharge branch pipe.
    5.4. Air draught regulator installation
    Screw in the air draught regulator (the regulator) using hemp or sealing tape.
    Connect the chain to the air supply valve (also see par. 6.3).

Boiler Maintenance

Flue pipe and other boiler surfaces not covered with thermal insulation panels during operation become extremely hot, don’t touch them. Recommended moisture for the fuel to be used is no more than 25 %.
If using damp fuel (firewood or sawdust) for stoking, condensate combines with flue gas products forming acids, reducing boiler service life by a number of times.
If damp fuel is used for stoking, the specified efficiency factor cannot be reached, so much more firewood is needed.
Users at/her option can use a different solid fuel, without making claims towards the boiler manufacturers regarding the operation results and boiler service life.
In order to prevent smoke from getting into the premises, close tightly the combustion chamber and fuel loading doors, except in the cases when the boiler is fired or fuel is loaded.
** If more air-consuming equipment is installed in the boiler operation premises, the air supply to the premises must be sufficient for all equipment.
6.1. System preparation for heating
**
Before firing the boiler, check whether the system is filled with heating water and deaerated.
It is advisable to fill the system with desalted soft or at least rainwater. If prepared soft water is used in the system, boiler housing will serve longer.
Valves disconnecting the boiler from the system have to be open.
6.2. Boiler ignition
Before firing the boiler, fully open the flue draught valve. Load chopped dry wood or chips through the combustion chamber door and internal cast iron doors onto the fire grate and get on fire.
After fuel burns well, load the combustion chamber (hearth) with fuel (on how to load, see below: Filing combustion chamber with fuel). Adjust flue draught valve for a proper draught from the boiler.
Finely chopped firewood burns more efficiently and increases boiler power. Put firewood into the combustion chamber (hearth) freely, for while burning they could fall down to the bottom of the chamber.
6.3. Air draught regulator adjustment
After the boiler reaches the desirable temperature (70 ÷ 90 °C), compared with the readings of the thermal-pressure gauge installed on the outgoing (hot) water pipe, set air draught regulator for the same temperature.
** Regulator graduation can differ from thermal-pressure gauge readings.
Shorten the chain so that the air supply valve was closed or there was a gap of no more than 2 mm. Set the desired temperature by turning the regulator hand to the relevant position. A boiler can be supplied with the regulator having temperature limits marked not in degrees.
6.4. Boiler stoking**
Refilling combustion chamber with fuel

  • Fully open flue draught valve;
  • Turn the air draught regulator handle to close the air supply valve in the door;
  • Open a little fuel loading door and wait for 15…20 seconds (after opening, look when there is no smoke in the chamber);
  • Open the door fully and refuel the chamber;
  • Close tightly the fuel loading door;
  • Return the flue draught valve to the previous position for a proper draught from the boiler;
  • According to the selected temperature, an open-air supply valve with an air draught regulator.

** Refueling is recommended only after the previous charge has fully burned out; earlier refueling should be applied only in cases when there is no other option.
Stoking efficiency
**
Set the necessary draught from the boiler by closing the flue draught valve so that no smoke got into the premises at proper stoking.
Draught exceeding the value given in the technical data table (see page 6) reduces the boiler efficiency factor, also there is a risk of boiler overheating.
During fuel combustion,  sh covers the fire grate; burning intensity, as well as boiler power, drops down. Due to this fact, poke the fuel. The large volume of ash prevents air from entering, therefore remove ash timely. Don’t open the fuel loading door during intense burning. Boiler stoking needs much air, so ensure sufficient air volume in the premises with the boiler.
If less heat is needed than the boiler’s nominal power, don’t fill the combustion chamber in full for there was no constant loaded fuel smoldering (resins can start accumulating in the boiler).
In the beginning of boiler operation, at ignition, during wood burning, condensate forms on the inner walls of the boiler while there is no layer of smoothness, giving the impression that the boiler is not watertight and leaks. Water steam condensate disappears after reaching water temperature in the boiler of 70 – 80 °C with the means of a three-way mixing valve. We recommend maintaining as high a temperature in the boiler as possible. If the return water temperature is lower than 60 °C, water condensates on the inner surfaces of the boiler, condensate combines with combustion products forming chemically aggressive acids, which can drastically reduce boiler service life. In order to check the oiler for tightness, stoke it for several hours with dry wood, then stop stoking and watch if condensate volume is growing. If not, the boiler is tight.
If improperly operating the boiler, using improper fuel, or insufficient chimney draught, the flue draught valve can get stuck, so during the heating season, the valve has to be moved by opening-closing it several times.
6.5. Boiler Extinguishing
At normal use, the boiler goes off by itself after the fuel charge burns out. In the case of forced extinguishing, first of all, remove fuel from the combustion chamber.
** Put burning fuel into a vessel with waterless smoke that will form in the room.
In the case of forced extinguishing, open doors or windows to ventilate the room.
6.6. Boiler Cleaning
Ash, accumulating under the fire grate, prevents air from entering the combustion chamber. Therefore, no rarely than before every second ignition, remove ash from the ash ox and scoop it from the ashtray.
Clean the boiler, remove the ash drawer and scoop the remaining ash only after the boiler has fully stopped and cooled down.
In order to ensure more efficient and safer boiler operation, periodically remove sooth from its internal surfaces. Intervals between cleaning depend on fuel quality (especially moisture), stoking intensity, chimney draught, and other circumstances. We recommend cleaning the heat exchanger and combustion chamber when the smooth layer reaches 3 mm, but no early than 2 – 3 times a month. When cleaning, remove the heat exchanger nebulizer; thoroughly clean the internal surfaces of the boiler with a scraper and brush.
Use chemical agents to remove hardened deposits.
Clean boiler chimney at least once a year, necessarily before the start of the heating season.
**
We recommend having the boiler inspected by a qualified boiler inspector once a year.
6.7. Frequently Asked Questions
I. What can happen if after full combustion there is an electric power interruption?
When there is no forced water circulation, water can boil up; the boiler can overheat; if the safety valve is not in proper condition, there is a risk of boiler or pipeline explosion, scalding with boiling water.
a) Reduce combustion intensity: close air supply valve; close flue draught valve as far as possible not letting smoke get into the room.
b) In the case of an emergency situation, extinguish the boiler by removing fuel from the combustion chamber (for there was less smoke in the room, put burning fuel into a  vessel with water, open windows, and doors). Don’t pour water into the combustion chamber as this may cause permanent damage to the boiler.
c) In winter if there is a long power interruption and risk or freezing, drain water from the system.
II. Why, while stoking, a strange sound (boiling) is heard, finishing and flue pipe color changes?
The boiler operates at a power exceeding its nominal power, a circulation pump is disrupted, too low pressure in the heating system.
a) Check the smoke valve for tightness.
b) Check the air draught regulator for correct adjustment, whether it is set for too high a temperature.
c) Check for too strong chimney draught; close flue draught valve.
d) Possible failure or water circulation: check circulation pump for operation; whether water level (pressure) is sufficient in the system; is the system properly deaerated; maybe one valve is closed in the system or water filters clogged.
e) Check for worn door and lid sealing parts from glass fiber, replace if needed.
f) Increase water pressure in the system.
III. Why boiler “weeps”, extinguish, and smoke gets out from the boiler?
Boiler works at too low power or chimney draught is insufficient so condensate accumulates.
a) If less heat is needed, load less fuel for there was combustion instead of smoldering.
b) Try taking out the heat exchanger nebulizer, this should improve chimney draught reducing boiler power.
c) Use the proper fuel and dryer wood.
d) Check the return water for too low temperature, and adjust the mixing valve so that the returning to the boiler water temperature was no less than 60C.
e) Check chimney draught, clean the chimney, flue pipe, and boiler; check for too much ash accumulated under the fire grate.
f) Check for worn door and lid sealing parts from glass fiber, replace if needed.
IV. Why after firing the boiler water pressure increase?
After the boiler heats up to its nominal power, water pressure exceeds the permissible pressure.
a) Possibly inoperable or too small expansion vessel is installed.
b) Possibly there is no water circulation: check circulation pump for operation; whether water level (pressure) is sufficient in the system; is the system properly deaerated; maybe one valve is closed in the system or water filters clogged.
c) Possibly, at filling the system, the pressure was exceeded, reduce it.

Fuel types and properties

Combustion heat of absolutely dry wood actually doesn’t depend on wood spice and is equal to about 4500 kcal/kg. So, as to assess different wood species, one should take into consideration their comparative weight. The weight per cubic meter of various firewood species is as follows:
– oak firewood – 500 kg;
– birch firewood – 450 kg;
– for firewood – 330 kg;
– aspen firewood – 330 kg.
The damper is firewood the less is its caloric content. Wet firewood caloricity reduction, compared with dry firewood (dampness ~20 %) is as follows:
– 30 % moisture – 10 ÷ 15 %;
– 50 % moisture – 35 ÷ 40 %.
Just cut tree contains 35÷ 60 % water. Tree cut at the beginning of winter contains the least quantity of water. Hardwood contains less water.
Wood has to be cut and split to make firewood. Firewood, after one year spent in a garret, is 20 ÷25 % moisture.
After two years it is 13÷17 %, and this means that after drying half of the fuel is needed than combustion with damp firewood.

Transportation and Storing

Boilers are stored and transported fastened onto a wooden pallet and wrapped into polythene film if nothing else is agreed to in the supply agreement.
Boilers are allowed to transport exclusively in a vertical position by any type of covered vehicle. If the weather is dry, the open vehicle can be used. In order to protect boilers from turning over, and scratching each other, extra protective measures are to be used. During loading/unloading, it is prohibited to beat, turn, and throw boilers.
Boilers are stored in dry premises without the presence of fumes of chemically active substances.
Product packing (wooden pallet and polythene film) disposal actions shall be in line with environmental requirements and rules in the user’s country. In extreme case, the wooden pallets can be used as fuel for the boiler. Boiler fastening to pallet screws can be used for boiler height adjustment at mounting.

Quick Wear Parts

Door and other sealing parts from sealing rope and glass fiber; cast iron fire grate and doors, and heat-proof concrete parts can become worn, burn out, and disintegrate while in use.
These parts are available for purchase at the boiler manufacturer or its representatives.

Boiler Disposal

Since the boiler is made from different materials, after the expiration of its service life it has to be disintegrated and disposed of:

  • Dispose of electric parts to electrical appliances recycling company;
  • Remove metal parts to metal scrap collector;
  • Remove remaining parts to dump or waste storage sites.

**** Disposal actions shall be in line with the laws and regulations applicable in the user’s country.

Acceptance Certificate

Solid fuel central heating boiler “Kalvis-5-()” meets the drawings, standard EN 303-5, ГОСТ 20548-87, ГОСТ 20548-93 requirements and is fit for operation.
The boiler was tested with 4.0 bar (0.4 MPa) pressure.
Manufacturer No
Manufacturing date

Inspector ___

Product Completeness
  1. Boiler “Kalvis-5- () ” – 1 pc

  2. Air draught regulator – 1 pc

  3. Thermo-pressure gauge – 1 pc

  4. Scrapper – poker – 1 pc

  5. Ash cleaning scoop – 1 pc

  6. Technical passport of the boiler – 1 pc

  7. Wooden transportation pallet (with fastening screws) – 1 pc

Product Warranty

Manufacturer guarantees that the product is in line with the technical document specifications.
If you correctly install and operate the boiler in accordance with these instructions, the following guarantee service period will be applied calculated
from the purchase date:
– for boiler case – 48 months.
– for completing parts – 12 months.
– for wearing parts (see p. 8) – 6 months.
Manufacturer obliges to eliminate failures occurring due to their fault during the mentioned period for free.
For warranty, repairs apply, In the case of boiler failure, to this service providing company, specified by the seller.
We ask user to take care of after-warrant repairs service employee made a relevant record in this certificate “Notes about the warrant and non-warrant repairs” and filled out the warrant repairs report.
The manufacturer’s guarantee does not apply if:

  • No purchase documents are submitted (VAT invoice, cashier’s check or cash receipt voucher);
  • Having lost this technical passport with the manufacturer’s and seller’s notes, or if the notes are not filled, or if the manufacturer’s number is different from the number on the boiler;
  • There are visible mechanical damages that could cause boiler failure;
  • The boiler failed due to incorrect connection or maintenance;
  • There are unauthorized construction changes;
  • It is found that the boiler was repaired by an unauthorized person;
  • The boiler was used not in line with the user manual (wrong fuel);
  • There is deformation or burnt metal (caused by using incorrect fuel or loading too large fuel charges);
  • The boiler failed due to natural calamities.

I have familiarized myself with warrant repair conditions. I am informed that in the case boiler is installed and operated without observing the requirements given in this manual, I lose the right to warrant repairs.
Buyer:  ……………….(name, surname, signature)

**SALES MARK

**

The boiler was sold by:
Company:………………….
Sales date:……………………
Address:………………………
Telephone:…………………..
In the case of failure please call:
Company:………………………
Address:………………………
Telephone:……………………..
Manufacturer
UAB “Kalvis”
Pramonės 15, LT-78137 Šiauliai, Lietuva (Lithuania)
Telephone: +370-671-88891
E-mail: [email protected]
Warranty service
Provided by a partner you bought a product

**NOTES ON WARRANT AND NON-WARRANT REPAIRS PERFORMED

**

Company:……………..
Expert:……………………
Failure works carried out:………………
Address:…………………….
Telephone:……………………..
Repairs date:………………..
Expert’s signature:…………………….| Company:………………
Expert:…………………..
Failure works carried out:……………
Address:……………………
Telephone:……………………….
Repairs date:……………………..
Expert’s signature:………………..| Company:……………….
Expert:…………………..
Failure works carried out:…………
Address:……………………….
Telephone:………………
Repairs date:……………………..
Expert’s signature:……………….
---|---|---

Product barcode sticking place.

Documents / Resources

| KALVIS K-5 Central Heating Solid Fuel Boiler [pdf] Instruction Manual
K-5, Central Heating Solid Fuel Boiler, K-5 Central Heating Solid Fuel Boiler, Heating Solid Fuel Boiler, Solid Fuel Boiler, Fuel Boiler, K-8
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals