eskon EPA-300 Process Control Device User Manual
- June 4, 2024
- eskon
Table of Contents
EPA-300 Process Control Device
EPA300
PROCESS CONTROL DEVICE
USER MANUAL
INDEX
1. TECHNICAL SPECIFICATIONS —————————————————— 3 2. MECHANICAL DIMENSIONS
——————————————————– 4 3. CONNECTIONS ————————————————————————- 5 4. MENU
TREE—————————————————————————– 6 5. FRONT PANEL DEFINITIONS
——————————————————- 7 6. SETUP———————————————————————————— 8 6.1 Connecting
the Sensor to the Device————————————————————– 8 6.2 Device Calibration
————————————————————————————– 9 6.3 Setting the Relay Set Value
———————————————————————— 10
7. OPERATING MODE: FUNCTIONS ————————————————-12 7.1 Tare
Function—————————————————————————————— 12 7.2 Viewing the Maximum and Minimum
Values that are read ——————————- 12 7.3 Changing Quick Set Values
————————————————————————- 13 7.4 Switching the Programming
Mode————————————————————— 13
8. PROGRAMMING MODE: PROGRAMMING OF THE DEVICE —————–14 8.1 Output Menu [OUT]
——————————————————————————— 14
8.1.1 1. Relay Output Settings (OUT-1) ————————————————————- 16 8.1.2 2., 3.,
4. Relay Output Settings(OUT-2-3-4)————————————————- 16 8.1.3 Current and
Voltage analog Output Settings (ANLOG) ———————————- 16 8.1.4 UART and CANopen
Digital Output Settings (DGTAL)———————————— 17 8.1.5 Key Tone Setting (SOUND)
———————————————————————- 17 8.2 Calibration Menu[CALIB]
————————————————————————— 18 8.2.1 Specifying Scale Values (SCALE)
————————————————————— 18 8.2.2 Manual Calibration Method Determination (CALOP)
———————————— 18 8.2.3 Number of Calibration (CL.CNT) ————————————————————— 19
8.2.4 Automatic Calibration(START) —————————————————————– 19 8.3 Display Menu
[DISP] ——————————————————————————— 19 8.3.1 Choice of decimal point location
(POINT) ————————————————— 19 8.3.2 Tare Function Settings (TARE)
—————————————————————– 19 8.3.3 Screen Refresh Rate (REFRS)
——————————————————————- 20 8.3.4 Blocking the Vibration on the Screen
(FILTR)———————————————– 20 8.3.5 Setting the LED Bar
——————————————————————————- 21 8.4 Secure Menu [SECUR]
——————————————————————————- 21 8.4.1 Hide Menu
(HIDE)——————————————————————————— 21 8.4.2 Lock Menu (LOCK)
——————————————————————————– 22 8.4.3 Setting the Password (PASS)
——————————————————————- 22 8.4.4 Return to Factory Settings
(FTRY)————————————————————- 22 8.4.5 Restart the Device
(RESET)———————————————————————- 22
9. WARRANTY DOCUMENT ———————————————————–23
2
1. TECHNICAL SPECIFICATIONS
Supply Voltage Power Consumption
Sensor Supply Voltage
Max Sensor Supply Current Sampling Rate Resolution Analog Inputs
Relay Outputs Serial Communucations (Optional)
Analog Outputs (Optional) Connection
Operating Temperature Storage Temperature Protection Class Weight Mounting
24 VAC/DC 50/60 Hz 85-265 VAC 50/60 Hz
Pot: mV/V: 0-10V: 0-5V: 0,5-4,5V: 4-20 mA: CANopen:
9 VA / 2,7 Watt Max.
100 mA 3.5 kHz 16 bit
5 VDC 10 VDC 24 VDC 5 VDC 5 VDC 24 VDC 24 VDC
Potentiometer, 0.5-4.5 V, 0-5 V, 0-10 V, 4-20 mA, 0-20 mA, 3,33 mV/V, 2mV/V, 2,5mV/V Ratiometric
2 pcs. 250 VAC 3A (for resistive load) Relay (optional 4 pcs.)
RS-232, RS-485, USB, CANopen 0-10 V, 0-5 V, 0.5- 4.5 V, 4-20 mA, 0-20 mA
2,5 mm2 terminal with socket 0 °C … 50 °C -10 °C … 60 °C
IP60 front panel, IP20 back panel ~220 gr
It is fixed to the clipboard with the feet on the upper and lower side.
3
2. MECHANICAL DIMENSIONS
SECTION A-A
SAFETY WARNINGS
1. Follow the instructions and warnings in the user guide. 2. Please check
the power supply type before connects energy to the device. 3. Please the
device mounted on panel against dangers of fall, snap, shake during working.
4. Make Sensor connections without energy on the device; do not connect in any
way during operation. 5. Make sure that is shielded cables between device and
sensor. 6. Do not leave the device exposed to a heat source (solar, heater
etc.) 7. EPA300 industrial control device is not suitable for use in the
external environment, Use only room conditions. 8. Wipe with a damp cloth to
clean the device, do not use water, thinner etc. 9. Comply with the limit
values specified in the technical specifications for relay outputs. 10. The
device cannot be changed by the user in the event of a fault, Please contact
our technical service in case of failure.
4
3. CONNECTIONS
1. Relay Output OUT-1
2. Relay Output OUT-2
3. Relay Output OUT-3
(optional)
4. Relay Output OUT-4
(optional) Supply Voltage 24 VAC / DC or 85 / 265 VAC
Digital Comm. RS485 RS232 USB HID
USB VIRTUAL CANopen
COM + NO –
NC COM
NO NC COM
NO NC COM
NO
NC + L –
N
1
15
2
16
3
17
18 4
19
5
20
6
21
7
22
8
23
9
24
10 25 11 26
27 12 28 13 29
14 30
28
29
30
A
B
GND
Rx
Tx
GND
USB CONNECTOR
USB CONNECTOR
CAN HIGH CAN LOW GND
Shown in tables below with pin numbers assigned.
ANALOG OUTPUTS 20
21
22
23
24 25 26 27
4-20 mA Output
0-10 V Output 0-5 V Output
Signal Output
GND
X
0.5-4.5 V Output
X
Signal Output
GND
Signal Output
GND
Tare Input
X
X
Tare GND
X
X
X
X
(*)Connection terminals 24, 25, 26 and 27 are used when the redundant output is desired. There is no signal in these terminals when a single analog output is desired.
SENSOR INPUT
Potentiometer 4-20 mA Input 0-20 mA Input 0-10 V Input
0-5 V Input 0.5-4.5 V Input
mV/V Input
15 1. tip
16 2. tip
17 3. tip
Supply Sensor Signal GND
Supply
X
GND
18
19
X
X
X
X
Signal(+) Signal(-)
5
4. MENU TREE
out
Top Menu Sub Menu
Out-1 Out-2 Out-3 Out-4 ANLOG DGTAL SOUND
calIB
SCALE
CALOP
DISP
POINT FILTR REFRS Bar.gr. Peah. tare
SECUR
HIDE
reset
FTRY
6
Pass.
loch
5. FRONT PANEL DEFINITIONS
56 7 8
1 2 3 4
13
9 10 11
12
- PRG (
): Programming and Enter key. It is used to enter the menus or
confirm the entered values.
- ESC (
): Escape, exit and back key. It is used to return to the upper
menu or to exit from the menus.
-
UP ( ): Up key. Used for navigating between menus, incrementing the value when entering a value or moving to upper step.
-
DOWN ( ): Down key. Used for navigating between menus, decreasing the value when entering a value or moving to lower step.
5)Set1 Status LED: Lights up when the relay 1 output is active. 6)Set2 Status LED: Lights up when the relay 2 output is active. 7)Set3 Status LED: Lights up when the relay 3 output is active. 8)Set4 Status LED: Lights up when the relay 4 output is active. 9)Min Status LED: Lights up when the lowest (minimum) value read from the moment the device starts to operate. 10)Max Status LED: Lights up when the maximum read value is displayed when the device starts operating. 11)Tare Status LED: Indicator that is lit when the key function is active. 12) Display Screen: Display screen consisting of 5 lines from a single line. 13) LED bar: The entered scale values increase and decrease in range.
7
Linear potentiometer
6. SETUP
6.1 Connecting the Sensor to the Device
Potentiometer connections:
+ –
4-20 mA, 0-20 mA or 0.5-4.5 V, 0-5 V, 0-10 V Sensor connections:
- 8
Pressure sensor with 4-20 mA or 0-10 V output
mV/V Ratiometric Sensor connections:
6.2 Device Calibration
Your device is calibrated automatically according to factory settings and
operates in the 0-100 value range. That is, on the minimum value read from the
sensor is displayed as 0 and the maximum value read from the sensor is
displayed as 100, on the display. You can change this scale from the
calibration menu. Use S-LO for the minimum value and use S-HI for the maximum
value, that will be shown on the display.
(Keep it pressed)
2X7
&D/,E
V&$/(
.
6B/2.
.
The decimal point starts flashing. Use the UP and DOWN keys to select the decimal point.
6/2.
Press and hold the UP and DOWN keys to move to the next step. To enter a negative (-) value, press the DOWN key to come to one of the non-digitized steps.
When PRG key is pressed and entered, the value input screen opens. Enter the desired value using the UP and DOWN keys.
The new S-LO value you confirmed with the PRG key has been set. Press UP to move to S-HI.
9
After specifying the S-LO value, you can do the same for the S-HI value.
6.3 Setting the Relay Set Value Set the SET values for the relay outputs of
your device to be activated. 1.Specify SET-1 for relay output:
(Keep it pressed)
2XW
2XWB
6HWB
.
.
The decimal point starts flashing. Use the UP and DOWN keys to select the
decimal point.
6HWB
Press and hold the UP and DOWN keys to move to the next step. To enter a negative (-) value, press the DOWN key to come to one of the non-digitized steps.
When PRG key is pressed and entered, the value input screen opens. Enter the desired value using the UP and DOWN keys.
The new SET1 value you confirmed with the PRG key has been set. Press the ESC key to return to the operating mode.
2.Specify SET-2 for relay output:
2XW
(Keep it pressed)
2XWB
6HWB
.
.
The decimal point starts flashing. Use the UP and DOWN keys to select the
decimal point.
6HWB
Press and hold the UP and DOWN keys to move to the next step. To enter a negative (-) value, press the DOWN key to come to one of the non-digitized steps.
When PRG key is pressed and entered, the value input screen opens. Enter the desired value using the UP and DOWN keys.
The new SET2 value you confirmed with the PRG key has been set. Press the ESC key to return to the operating mode.
10
3. Specify SET-3 for relay output:
2XW
(Keep it pressed)
2XWB
6HWB
.
.
The decimal point starts flashing. Use the UP and DOWN keys to select the
decimal point.
6HWB
Press and hold the UP and DOWN keys to move to the next step. To enter a negative (-) value, press the DOWN key to come to one of the non-digitized steps.
When PRG key is pressed and entered, the value input screen opens. Enter the desired value using the UP and DOWN keys.
The new SET3 value you confirmed with the PRG key has been set. Press the ESC key to return to the operating mode.
4. Specify SET-4 for relay output:
2XW
(Keep it pressed)
2XWB
6HWB
.
.
The decimal point starts flashing. Use the UP and DOWN keys to select the
decimal point
6HWB
Press and hold the UP and DOWN keys to move to the next step. To enter a negative (-) value, press the DOWN key to come to one of the non-digitized steps.
When PRG key is pressed and entered, the value input screen opens. Enter the desired value using the UP and DOWN keys.
The new SET4 value you confirmed with the PRG key has been set. Press the ESC key to return to the operating mode.
11
7. OPERATING MODE: FUNCTIONS
Your EPA300 process controller operates in two different modes. Your device is
in ‘operating mode’ while the initial value of the sensor readout is
displayed; In the ‘programming mode’ on the screen where the settings are
changed and the parameters are changed. In this section, the functions in
operating mode are explained.
7.1 Tare Function
***Only works when the Tare function is active. For activating or explaining
the types of functions, 8.3.2 Setting the Tare Function
Each time the UP key is pressed while the unit is in the operating mode, the
Tare function is activated according to the type of the selected function and
the Tare status lights up.
7.2 Viewing the Maximum and Minimum Values That Are Read
If you press the DOWN key while the unit is in operating mode, you can see the
lowest (minimum) value read from the moment the unit starts to operate. At the
same time, Min status will flash on the screen.
When you press the DOWN key again, you can see the highest (maximum) value
read from the moment the device starts to operate. At the same time Max will
be on the screen.
Min.
Max.
Actual Value
.
.
.
- You can see Min – Max on the screen for as long as you want and make it active for as long as you want. To make settings for Min Max menu;
2XW
‘,63
3($..
W./R.
A value in seconds is entered and the last minimum value is kept on the display for this time. If no value is entered in this menu, the minimum value in memory is valid.
W.+L.
A value in seconds is entered and the last maximum value is kept on the display for this time. If no value is entered in this menu, the maximum value in memory is valid.
W.(6&.
A value in seconds is entered, min. or max. values are kept on the display for the time entered. then the screen returns to the current value. If no value is entered in this menu, min. or max. value remains visible on the screen.
Note: You can use the ESC key to delete the (minimum) or (maximum) values in the memory.
12
7.3 Changing Quick Set Values
Press and hold the ESC key to quickly change all adjustable setpoints while
the unit is in run mode. You can then change the desired SET value by pressing
the PRG key. When entering a value, press and hold the UP and DOWN keys to
move to the next step. To enter a negative (-) value, press the DOWN key to
come to one of the non-digitized steps
1
6HWB 4
(Keep it pressed)
2
5
. .
3
6
6HWB
7.4 Switching The Programming Mode
To switch your device from working mode to programming mode Press and hold PRG
until OUT appears in the display. To return to the operating mode, press the
ESC key repeatedly until you return to the operating mode.
13
8. PROGRAMMING MODE: PROGRAMMING DEVICE
Your EPA300 process controller operates in two different modes. Your device is
in ‘operating mode’ while the initial value of the sensor readout is
displayed; In the ‘programming mode’ on the screen where the settings are
changed and the parameters are changed. In this section, the functions in
Programming Mode are explained.
To switch your device from working mode to programming mode Press and hold PRG
until OUT appears in the display. To return to the operating mode, press the
ESC key repeatedly until you return to the operating mode. While your device
is in Programming
Mode;
– To scroll between menus, press the DOWN and UP keys – Press enter (PRG) to
enter any menu. – Use the ESC key to exit from any menu and return to the
upper menu. – When entering any parameter value, press the DOWN key to
dicrease, press the UP
to increase the value. Press and hold the keys to move to the next or previous
digit.
The EPA300 consists of 4 main menu items: Output, Secure, Display and Calibration.
8.1 Output Menu [OUT]
8.1.1 1. Relay Output Settings (OUT-1) 8.1.1.1 Entering the Set Value
2XW
The first relay output activates and sets the value of the lit LED of the status SET1.
(Keep it pressed)
2XW
2XWB
6HWB
.
.
The decimal point starts flashing. Use the UP and DOWN keys to select the decimal point.
6HWB
Press and hold the UP and DOWN keys to move to the next step. To enter a negative (-) value, press the DOWN key to come to one of the non-digitized steps.
When PRG key is pressed and entered, the value input screen opens. Enter the desired value using the UP and DOWN keys.
The new SET1 value you confirmed with the PRG key has been set. Press the ESC key to return to the operating mode.
14
8.1.1.2
Relay Output Function Selection
IXQFW.
This function selection determines when the relay output will be activated and
deactivated according to the set values.
VWDQG.
The relay is activated when the value read in the device increases by
increasing Set-1 value.
EDQG
The relay is activated when the read value in the device is between Set-1A and
Set-1B.
&DWFK
The value read in the device is activated whenever the Set-1 value increases
or decreases.
GXD/
The value read in the device activates the relay whenever the Set-1A or Set-1B
value increases or decreases. aktifleir.
3H5G&
The value read in the device is activated when the value of Set-1 or the value
of Set-1 is increased or decreased by every level such as 2,3,4,5 …
15
8.1.1.3 Delay
GH/D
It specifies in seconds how long the relay output will remain active after it is
activated. If ‘0’ is entered as a zero value, the relay output will remain active until it
changes conditionally.
8.1.1.4 Hysteresis
+V8S
+VGQ
Due to the unstability in decimal value read on the connected sensor, you can enter
the hysteresis value to prevent the relay from being turned on and off at any time,
so that the set value you set for the relay will be activated and deactivated as low as
Hysdn and above Hysup.
8.1.1.5 Offset Value 2IVHW If you want to add offset to the entered set value, this menu is used. If all set values are selected forward or negative by the specified offset value, they are shifted back.
8.1.1.6 The Default State of the Relay &RQG
Depending on the factory settings of your device, the relay is normally closed
and
activated with the specified setpoint and functions. Use the Cond option on
the Out1 menu to activate the default in the default position and turn off
with the specified setpoint and functions. The factory setting NC
(NormallyClosed) is the option that
the relay is normally closed, NO. (Normally Open) indicates that the relay is
normally open.
8.1.2 2., 3., 4.Relay Output Settings (OUT-2-3-4)
2XWB
In this menu you can set the relay outputs 2, 3 and 4 of your EPA300. Complete settings 8.1.1. The 1 st relay output described in chapter is the same as the OUT-1 settings.
8.1.3 Current and Voltage Analog Output Settings (ANLOG)
D1/2J
If your EPA300, which is manufactured specifically for your order, has an analog output module, you can make the necessary settings from this menu.
Select the analogue output from the TYPE menu:
8 Q. 8
0 – 10 Volt 4 – 20 mA 0 – 5 Volt
.. Q
0.5 – 4.5 Volt 0 20 mA
From the COND menu, select whether the analogue output module is active or not. Use ON to activate or OFF to activate. From InvrS menu, you can choose which value to increase or decrease according to the sensor reading on the analogue output. This option, which is OFF by default, provides an analog output that increases or decreases in proportion to the value read at the sensor. If you turn this ON, the value read out at the sensor will increase
16
while the value at the analog output will decrease, ie an inversely proportional output will be provided.
Wave Form (VAVE.F.)
8$8(.).
The waveform of the output signal can be selected from the Vave.f menu. There are 4 options in the menu: Liner, Sin, Cos, Trian. When the liner option is confirmed with the PRG key, a linearly increasing waveform is obtained in the specified scale range. When the Cos option is confirmed with the PRG key, a waveform in the form of a waveform that starts from zero and completes a complete cosine wave is obtained at the scale interval specified. When the Sin option is confirmed, a waveform in the form of a waveform that starts at the peak value of the sine wave and completes a complete sinusoidal wave in the determined scale range is obtained. When the triangle option is selected in the same way, a triangle wave is obtained in the scale interval determined at the exact middle value corresponding to the top.
Analog Output Scale Setting (Scale)
VFDOH
In the device with the analogue output feature, SCALE mode in this menu must be ON to set the output signal to the desired scale range. S-LO started appearing on the analogue menu afterwards. And S-HI. Options and scale values can be entered.
8.1.4 UART and CANopen Digital Output Settings (DGTAL)
GJWD/
WARNING: After changing the UART or CANopen settings, you need to restart the device for the changes to take effect. If your device has a USB port, use MyPanelMeter, which you can download from our website to check your device. Check the user manual of the program.
8.1.4.1 UART Settings If you are communicating with your device via RS-485 or RS-232; You can make the necessary settings here. You can select the communication protocol, baudrate, parity, address and period information. For the MODBUS Protocol address information, see the relevant booklet.
8.1.4.2 CANopen Settings Here you can configure the baud rate, Node ID, Heartbeat, PDO etc. of your device related to the CANopen protocol. For more information on CANopen, see the EPA300-CANopen booklet.
8.1.5 Keypad Setting (SOUND)
VR8QG
When you press any key on your device, you can turn the beep sound on and off from this menu. Use ON to turn the sound on, OFF to turn it off.
17
8.2 Calibration Menu [CALIB]
8.2.1 Specify Scale Values (SCALE)
V&D/H
When your device is calibrated to its factory settings, it operates at a value
range of 0-100. That is, the smallest reading on the sensor shows 0 on the
screen and 100 on the screen. You can change this scale from this menu.
Use the S-LO for the minimum value of the scale, and the S-HI menus for the
maximum value. To change the value, press the PRG key. After specifying the
value with the UP and DOWN keys, press the PRG key again to locate the decimal
point. Then press the PRG key to confirm the value.
You can use the Fctor menu to expand this scale by multiplying it by a fixed
factor. The number of this factor, which is the default value of 1, is
multiplied by the values of S-LO and S-HI to determine the scale value.
For example; When you set the S-LO value to 1, the S-HI value to 20 and make
the factor 4, your device will run in the 4-80 value range.
OFFSET menu is designed for Loadcell applications. Zero and span points are
entered manually and calibrated.
With the Catch menu, zero calibration is performed and the current value is
automatically drawn to zero. After Catch is selected and confirmed with the
PRG key, the value on the display is set to 0.
Value menu; It is designed to perform zero calibration manually and to reverse
this value if desired. For example, if you see a value of +0,75 on the device
display, you need to enter the value of -0.75 manually to perform zero
calibration. After selecting the desired value with UP and DOWN buttons,
confirm with PRG button.
Factor menu is used in calibration of span. For example; In loadcell
application, you have a weight of 50 kg, but this value is shown as 49 kg on
the device display. In this case, 50/49 is entered into the factor section and
the span calibration is performed. WARNING: Changing the scale value does not
change the calibration of your device, it only indicates the displayed value
range on the screen. For the calibration of the instrument, 8.2.2.
8.2.2 Manual Calibration Method Determination (CALOP)
&D/2S.
Your device has been automatically calibrated during production. If you do not, you can do this calibration according to the sensor. You need to select the calibration method from this menu.
)&D/
BSQW.
VHJQW.
Factory calibration (Default) 2 point calibration Segmented calibration
In the 2-point calibration option, only the maximum and minimum points are selected. With the multiple calibration option, you can calibrate your device at up to 10 different points. For example; If the length of the sensor is 40 cm and you want to
18
calibrate at 5 different points, these points are; There must be 0 cm, 10 cm, 20 cm, 30 cm, and 40 cm points at which the sensor starts. Select the FCAL option if you want to calibrate your device to factory calibration again.
8.2.3 Number o Calibration (CL.CNT)
&/.&QW.
In this menu that appears when you select the segmented calibration option, you can specify the number of points you want to calibrate the device. It’s a maximum of 10.
8.2.4 Automatic Calibration (START)
VWD5W
From this menu, you can start your automatic calibration by pressing the PRG key according to the selected calibration method in 8.2.2. section. During the calibration that will start according to your chosen meta; You can see the calibration point to be determined on the first line by the ignored segment number and on the second line the unprocessed value read on the sensor. You can scroll through the segments, ie the calibration points, with the UP and DOWN keys. You can confirm the segment you want to specify with the PRG key while the sensor is in position for calibration. DONE will appear on the screen for a very short period of time.
8.3 Display Menu [DISP]
8.3.1 Choice of decimal point location (POINT)
SRLQW
In the value that appears on the display in run mode, you can set the position of the decimal point in this menu. This value, which is ‘2’ in the factory settings, indicates how many decimal places to display after a call. If you select ‘0’, only the whole number appears on the screen.
8.3.2 Tare Function Settings (TARE)
WDUH
In this menu you can define the Tare Function and its properties. From the EVENT menu you can select the Tare Function type: When the unit is in operation mode, each time the UP key is pressed;
]H52
ZERO: Then the value read on the sensor is equal to zero and the Tare state LED is lit.
SUVHW U.]HU2
PRESET: Then, the value read on the sensor is equalized to the specified value
and the Tare status LED is lit.
REPEATED ZERO: The first time it is pressed, the value read on the sensor is
equal to zero and the Tare status LED is lit. When it is pressed later, the
read value returns to the state before the key is activated and the Tare
status LED is turned off.
U.SUVW
REPEATED PRESET: When pressed for the first time, the value read on the sensor
is equalized to the specified value and the Tare status LED is lit. When it is
pressed later, the read value returns to the state before the key is activated
and the Tare status LED is turned off.
19
In the PrSet option, you can specify the value to be equalized when the Tare
key is pressed. If your EPA300, which is specially manufactured according to
your order, has the Digital Tare Input module, you can make settings from the
INPUT menu under the Tare menu. The EDGE option determines which edge of the
edge signal coming from the Tare function is activated. RISE for rising edge,
FALL for falling edge. For example; When you connect this signal to a button,
the RISE option activates the tare when the button is pressed and the FALL
option when the button is released after the button is pressed. In the FILTR
option, you can specify how many milliseconds the modulated signal is to be
controlled. By default, this value is 100 ms.
With the BUTTON menu, you can select whether the tare button ( ) on the front
can be used. If the button is set to “Off” position, the tare button on the
front side is not used, only the rear tare input can be used.
8.3.3 Screen Refresh Rate (REFRS)
UHIUV
Indicates how many milliseconds the value displayed on the screen will be refreshed. By default this value is 100 ms; To reduce or reduce the on-screen vibrations, or reduce the duration of your device’s response to movement of the sensor.
8.3.4 Blocking the on Screen Volatility (FILTR)
IL/WU
Your EPA300 is programmed to display the signals received from its connected sensor in the most accurate way on the screen by processing them with special algorithms. But; You can solve this problem by filtering from this menu in the event of a trembling of the value displayed on the screen due to various reasons such as noise in the vicinity, disturbances in the sensor. There are three different filtering methods for this:
1. AVRGE (Average Calculation): When you activate this filter by turning the STATE option ON, your device will refresh the value that appears on the display after you have read as many values from the sensor as you would select COUNT. For example; COUNT will default to 500, and your device will refresh the value on the screen after you have taken 500 samples from the sensor, that is, after reading it, taking the average of these values. Accordingly, increasing COUNT will reduce flicker on the screen; But your device will slow the response of the sensor to its rapid movement.
2. LQE(Lineer Quadratic Estimation): You can also activate this filter, also known as a thick filter, by turning the STATE option ON. If you decrease the default COVARIANCE of 500, the flicker on the screen will decrease; But your device will slow down the reaction of the sensor to its rapid movement.
20
3. HYS (Hysteresis): You can activate the hysteresis filter by turning the STATE option ON. With this filter, which has two parameters named Delta and A.Error, the value read from the sensor is not reflected on the screen until it changes to Delta. When the sum of the nonreflected values on the screen is equal to A.Error, the display is updated with the average of these values
8.3.5 Setting the LED Bar
ED5.JU.
The led bar on the display normally moves from left to right as the value read from the sensor increases. You can change this direction as you like or move the scale value in reverse direction
2XW
‘,63
E$5.JU.
(Press 3 times)
,Q9U6
If you want the led bar to move from right to left, enter the Invers menu and set the normally OFF position to ON and confirm with the PRG and exit.
6&$/(
You can move the led bar between the values you want, for this purpose enter the SCALE menu under the Bar.Gr. menu and turn the on position to the off position. SLO. and S-HI. menus will be added under the Bar.Gr. menu. Enter the S-HI value for the end of the led bar and S-LO value for the start of the led bar and confirm with PRG.
8.4 Secure Menu [SECUR]
8.4.1 Hide Menu (HIDE)
+LGH
You can hide the menus ON you do not want the operator to see your device to use them.
+G.D// +G.2XW +G.&/E +G.GVS +G.I2X
All menus except Secure are hidden. The Output menu is hidden. The Calib menu is hidden. The Display menu is hidden. The Quick Set change menu is hidden. See 7.3.
21
8.4.2 Lock Menu (LOCK)
/2&+
If you have not set a password before, you will see NPASS in the display when you enter this menu. Press the PRG key to set the desired password here. Then use the DOWN and UP keys to select the menus you want to lock. Definition of the menus are same as 8.4.1. Menu Hiding section.
8.4.3 Setting the Password (PASS) SDVV.
Use this menu item to set a password or to change the password you have
previously set. If no password was previously set; When you enter this menu,
the display will show NPASS. Press the PRG key to set the desired password
here. If the password has already been set; The display shows PASS? Will
appear and you will be asked to enter this password. After inputting the
password, the display will show NPASS. You can specify your new password here
and confirm it with the PRG key.
8.4.4 Return the Factory Settings (FTRY) IWU
You can return your EPA300 to factory settings from the time box you desire. Press the PRG key to return to the factory settings. You need to enter 12345, which is the factory password for PASS password menu.
8.4.5 Restart the Device (RESET) UHVHW
In any case, press the PRG key to come back to this menu to restart your device. The device will automatically power off and on and start working.
NOTE: The EPA 300 can be used with the instrument panel only, without the need for relay outputs.
ORDER CODING: When ordering your EPA 300 process controller, you can use the following coding format.
Model EPA300
Supply Voltage
220V – 220 VAC 24V – 24 VAC/DC
Analog Output Signal Type
Empty No Analog Output V0 – 0-10V output V1 – 0-5V output V3 – 0.5-4.5V
output A0 – 0-20mA output A4 – 4-20mA output
EPA300
X
XXX
XX
XX
X
Input Signal Type
P – Potentiometric V – 0-10V V1 – 0-5V V3 – 0.5-4.5V A – 4-20mA A0 – 0-20mA M
– 3.33mV/V L – 2mV/V N – 2.5mV/V C – CANopen
Communication Type
Empty – No communication S1 – RS232 communication S2 – RS485 communication S3
– USB communication S4 – CANopen communication
External Tare
Empty – No External Tare T – External Tare
- Optionally Dual Analog Output can be requested. In this case, it is necessary to add “2” code at the beginning of the desired signal output at order coding. Sample Product Code: EPA300-P-220V-S2-2A4-T
22
Seller Company’s: Name: Address: Phone: FAX: E-mail: Invoice Date and No:
Delivery Date and Address:
Signature, Cachet
9. WARRANTY DOCUMENT
Product Brand: ESKON Product Code: EPA-300 Serial No: Warranty Time: 2 Years
This product is guaranteed for 2 years against manufacturing defects. Non-
warranty situations: 1. Mechanical damages 2. Damages in case of
transportation 3. User errors
Other cases than these cases are under the manufacturer’s warranty.
23
References