Danfoss ADAP-KOOL Refrigeration Controls User Guide
- June 4, 2024
- Danfoss
Table of Contents
- ADAP-KOOL Refrigeration Controls
- Product Information
- Specifications
- Product Usage Instructions
- Data Communication Overview
- System Units and Controllers
- Installation Guidelines
- Replacing Controllers or Gateways
- Q: What is the maximum number of controllers that can be
- Q: Which communication interfaces are supported by AK-SM 850
ADAP-KOOL Refrigeration Controls
Product Information
Specifications
- Product Name: Danfoss Refrigeration Control Systems
- Communication Options: Lon, Modbus, Ethernet
- Compatible Controllers: AK series with extension modules
- System Units: AK-SM 820, AK-SM 850, AK-SM 880
- Network Connectivity: IP, RS485 bus, TP 78 BUSS
- Cable Requirement: Category 5 or higher for IP network
connections
Product Usage Instructions
Data Communication Overview
The Danfoss refrigeration control systems utilize various forms
of communication including Lon, Modbus, and Ethernet. Proper
cabling, termination, and installation of repeaters are essential
for efficient data communication.
System Units and Controllers
The system units include AK-SM 820, AK-SM 850, and AK-SM 880,
which can connect multiple controllers from the AK series with
extension modules.
Installation Guidelines
For IP network connectivity, ensure that cables meet at least
category 5 standards. Follow the recommendations in the manual for
proper installation, termination of cables, and when to use
repeaters.
Replacing Controllers or Gateways
If a controller or gateway needs replacement, follow the
guidelines provided in the manual to ensure proper visibility on
the network and seamless integration.
Frequently Asked Questions (FAQ)
Q: What is the maximum number of controllers that can be
connected to AK-SM 820?
A: Up to 32 controllers can be connected to AK-SM 820.
Q: Which communication interfaces are supported by AK-SM 850
and AK-SM 880?
A: AK-SM 850 and AK-SM 880 support Lon, Modbus, Ethernet, and
AK-PI 200 protocol interface with DANBUSS communication.
Design guide
Data communication between ADAP-KOOL® Refrigeration Controls
ADAP-KOOL® Refrigeration control systems
Introduction
This installation manual covers the data communication systems installed in
Danfoss refrigeration control systems.
Within this guide descriptions and specifications will be shown that supports
the data communication interface with Danfoss refrigeration controls systems.
The recommendations mentioned in this document are intended as instructions for the market’s refrigeration engineers and electricians who install Danfoss refrigeration controls.
Data communication
System unit
Controllers
Repeater
System operation
The guide describes: – The various forms of communication – Cable to be used – Length of cable – Termination of cable – When to install a repeater and – How do the individual controllers become visible on the network – What happens if a controller has to be replaced – What happens if the gateway has to be replaced
ADAP-KOOL® only The above communication systems are used for internal
communication between ADAP-KOOL® refrigeration control systems. The devices
are not designed to communicate with equipment manufactured by other
manufacturers.
IP network In the case of controllers and system units that can be connected
to an IP network, installation should be carried out on the basis of the
requirements that apply to an IP network, i.e. cables must be at least
category 5.
Contents
Introduction ……………………………………………………………………… 2 A little about controllers and
system units ………………………….3
Communication survey……………………………………………………………………. 3 System
units………………………………………………………………………………………. 4 Addressing of controllers in the
network……………………………………… 6 Replacement of controllers in the network
………………………………….. 6 Replacement of system units in the network ………………………………. 6
Requirements to installation………………………………………………7
Important…………………………………………………………………………………………… 7 Lon RS 485 –
bus………………………………………………………………………………… 8 MOD – bus
…………………………………………………………………………………………10 Lon TP 78 – bus
………………………………………………………………………………… 12 DANBUSS…………………………………………………………………………………………..
14 Combinations of net…………………………………………………………16 Bridge
……………………………………………………………………………………………….. 16 Repeater
……………………………………………………………………………………………17
2
Design guide RC8AC902 © Danfoss 2017-06
Data communication
A little about controllers and system units
Communication survey
The table below shows which controllers can communicate with which system
units and with what form of data communication. The summary is valid as of
ultimo 2015, but the ADAP-KOOL® Refrigeration Control System is continually
being extended.
System operation AK-ST 500 AK-EM 1003) AK-EM 800 AKM1)
System unit
AK-SM 800 series2)
Controller serie / type
AK – controllers with extension modules AK-CC, AK-PC, AK-LM, AK-CH EKC 3xx EKC
202, AK-CC 210 EKC 302, AK-CC 250, 350, AK-PC, AK-CT AK-CC 450, 550 AK-PI 200
AK-CM (communication module) + AK-XM DGS, SLV, Wattnote, Power meter, light
control (3. party)
Lon Mod- Lon DAN-
IP
RS485 bus TP 78 BUSS
x
x
x
x
x
x
x
(x)
x
x x
x
(x)
x
x
x
AK-SM 350 AK-SM 720
AK – controllers with extension modules AK-CC, AK-PC, AK-LM, AK-CH EKC 3xx EKC 202, AK-CC 210 EKC 302, AK-CC 250, 350, AK-PC, AK-CT AK-CC 450, 550 AK-PI 200 DGS, SLV
x
x
x
x
x
x
x
(x)
x
x
x
(x)
x
x
AK-SC 255, 355
AK-CM (communication module) + AK-XM AK – controllers with extension modules AK-CC, AK-PC, AK-LM, AK-CH AK-CC 750 (TP 78 version) EKC 302, AK-CC 250, 350, 450, 550, AK-CT EKC 202, 4xx, 5xx, AK-CC, AK-PC
x2)
x
x2)
x
x
x
x
x x x
AKM
EM 100
AKA 245
x
AKA, AKC, AKL
AK – controllers with extension modules AK-CC, AK-PC, AK-LM, AK-CH
x
EKC 202, 302, 3xx, 4xx, 5xx, AK-CC 210
x
AK-CC 450, 550
x
- AKM can receive alarms and logs from an AK-SM 720 and AK-SM 350. The connection is made via an analogue modem, a GPS modem or an IP network.
- Can be delivered in two versions: – Standard Lon-RS485 – Retro-fit Lon TP
- Together with AK-SM 350 and AK-SM 720 only.
Data communication
Design guide RC8AC902 © Danfoss 2017-06
x x x
3
System units
A brief summary is presented here of the communication options for the various
system devices:
AK-SM 820 Up to 32 controllers can be connected, which can communicate on: –
Lon – Modbus – External I/O modules via AK-CM 101C – Ethernet communication
for other AK-SM or AK-SC devices – AK-PI 200 protocol interface with DANBUSS
communication
AK-SM 850, AK-SM 880 Up to 120 controllers can be connected, which can
communicate on: – Lon – Modbus – External I/O modules via AK-CM 101C –
Ethernet communication for other AK-SM or AK-SC devices – AK-PI 200 protocol
interface with DANBUSS communication
AK-SM 880 it can be delivered in a version, which can communicate in 4 x TP 78
or AK-CM 101A.
AK-SM 720 There are three forms of data communication: – A Lon RS485 bus, to
which up to 199 devices can be connected. – A Modbus, to which up to 120
devices can be connected. – Ethernet communication for other AK-SM devices, to
which up to
199 addresses can be connected.
The system device can communicate with: – AK-CC, AK-PC controllers – EKC with
either Lon RS485 or Modbus communication – AK-PI 200 protocol interface with
DANBUSS communication – AK-PI 300 protocol interface for Daikin devices –
Other AK-SM 720 devices – AKM and AK-EM 800 via agent.
AK-SM 350 This device can record up to 65 (99) readings. A reading could for
example be a directly mounted temperature sensor or an external device with a
temperature sensor, where the readings is loaded via data communication. There
are four forms of data communication: – A Lon RS485 – A Modbus – RS485 TP
(Third Party) To which gas detectors, type GD, can be
connected – Ethernet communication for other AK-SM 720 or AK-SC devices.
AK-SM 350 can communicate with: – EKC with either Lon RS485 or Modbus
communication – AK-CC, AK-PC controllers – Gas detectors type GD – AK-PI 200
protocol interface with DANBUSS communication – Ethernet communication for
other AK-SM or AK-SC devices.
Lon RS485 Modbus
Total up to 32 devices
IP network
Lon RS485 Modbus
Total up to 120 devices
IP network
Lon RS485 (max. 199 devices)
Modbus (max. 120 devices)
Total on bus: Lon RS 485 + Modbus: max. 199 devices
IP network (max. 199 addresses) Total AK-SM 720 + AK-PI 200 + IP + bus: max.
200 devices.
A repeater must be added if there are more than 120 devices on the Lon RS485
communication.
Lon RS485 Modbus RS 485 TP
IP network
Total up to 65 (99) devices
4
Design guide RC8AC902 © Danfoss 2017-06
Data communication
AK-SC 255 / AK-SC 355 AK-SC 255 and 355 are available in 2 versions: – Modbus
- Lon TP 78 communication – Modbus + Lon RS485 communication
– Ethernet communication for other AK-SC or AK-SM devices.
The system device can communicate with: – External I/O modules via AK-CM 101C or 101A (depending on
model) – All controllers where the communication is supported by: Modbus, Lon, TP78).
Gateway type AKA 245 This system device is equipped with DANBUSS data communication and Lon RS485 data communication. It can control the communication of up to 120 controllers. The controllers can be distributed between Lon and DANBUSS by setting a continuous Lon address range of up to 119 addresses. The system device can create communication for type AKM system software. The system device can communicate with: – AKC controllers – EKC controllers with a Lon RS 485 communication – AK-CC, AK-PC controllers – AK-EM 800 via Agent
Modbus Lon RS485 / TP 78 IP network
DANBUSS Total up to 120 devices
Lon RS485
Data communication
Design guide RC8AC902 © Danfoss 2017-06
5
Addressing of controllers in the network
1. Connect voltage 2. Set the address in the respective controllers
If you should inadvertently give two or more controllers the same address,
only the first controller will be visible from the system device. 3. The
system device must know the controllers. The following will occur depending on
the communication type:
Here, the system device must scan the network. The service PIN function on
each controller cannot send the address to the system device.
DANBUSS On DANBUSS, the addresses must be set before the power is switched on.
The system device will find the controllers on the network itself.
Lon RS485 Or better: The system device can scan the network and find all connected controllers. This scan function must be started manually in the system device.
Modbus, TP78
Replacement of controllers in the network
Settings The system operation includes functions to copy a controller’s
settings. This function can be used where a controller is to be replaced with
the same software version. After swapping, the settings are copied back onto
the controller.
Address Remember to reset the address of the controller with the same address
and get the controller to notify the system device again. (You should also do
this yourself if you are retaining the existing LON module). Here, the
controller can send a service PIN to the system device.
Modbus, TP78 The system device will scan the network and find the controllers
that have been replaced. This scan function must be started manually in the
system device.
Lon RS485 · AK-SC 255, 355, SM 850
The system device will scan the network and find the controllers that have
been replaced. This scan function must be started manually in the system
device. · AK-SM 350, 720, AKA 245 Here, the controller will send a service PIN
to the system device.
DANBUSS On DANBUSS the system device will find the controllers on the network
itself.
Replacement of system units in the network
If you replace the system device, all settings and data can be retrieved and
reloaded with a backup function. See user Guide for the respective system
device, so you can see how the setup and the collected data is retained. ·
Terminate data communication inputs as previously · Set the system device
address · Load the controller addresses up to the system device.
AK-SM 820, 850, 880 Set the address to the same value as on the previous
system device. Then start the Rescan function.
AK-SM 350 No address needs to be set on AK-SM 350. Start the scan function to
find all connected controllers.
AK-SM 720 Set the address to the same value as on the previous system device.
The scan function can then be started to find all connected controllers.
AK-SC 255, 355 Set the address to the same value as on the previous system
device. Then start the Rescan function.
Gateway type AKA 245 Set the system address using the AKA 21 operating device.
On the DANBUSS communication, the Gateway will find the controllers itself. On
Lon RS485 the scan function can be activated from the AKA 21 operating module.
This function is called “Press Enter to scan LON bus”. NB! When the scan
function is used, all alarm priorities in all connected EKC controllers will
be deleted and returned to their factory settings.
6
Design guide RC8AC902 © Danfoss 2017-06
Data communication
Requirement to installation
Cable type Cables twisted in pairs must be used, and they may be provided with
a screen. Some types of communication require a cable with a screen to be
used. · Examples
For Lon RS485, Modbus, RS485 Third party – General ‘EIA 485’ recommendation: –
Belden 9841, 24 AWG, 1 pair with screen – Belden 3107A, 22 AWG, 2 pairs with
screen – Smartwire 043006AL, 22 AWG, 1 pair with screen – Alpha wire 6453, 22
AWG, 1 pair with screen – Carol C4841A, 24 AWG, 1 pair with screen – Dätwyler
Uninet 3002 4P 4 pairs with screen(CAT5 cable) For Lon TP78 communication –
Level 4 cable general recommendation: – Belden 7703NH, 22 AWG, 1 pair with
screen – Belden 7704NH, 22 AWG, 2 pair with screen – Smartwire 106500, 22 AWG,
1 pair with screen
Wires with larger cross-section than AWG 22 is not recommended. ( Eg. AWG 20
and 19).
Conductors The wires in the cable that is connected to the controller must be
correct. Although there are four wires in the cable inside the screen, you
cannot simply choose colours freely. The wires are twisted in pairs, i.e. 2
and 2, and you must use a pair that is twisted around each other.
If there are several “vacant” wires in the cable, they must be used for
nothing else than data communication.
Cable length A cable length must not exceed 1200 m. A repeater must be used
for longer lengths than 1200 m.
See the additional requirements for the respective communication forms.
Important!
Cable tray
Our experience indicates that problems can occur with communication due to the
following weaknesses:
Long wire ends Do not strip more of the cable insulation than strictly
necessary. Max. 3-4 cm. Continue the twisting of the cables right up to the
terminals.
Min.10-15 cm
Max. 3-4 cm
Stubs Avoid stubs on the cable. Feed the cable right to the end and then back again.
When the cable is ducted with other cables, there is a strong risk that electrical noise will be transferred. Keep away from live cables.
When the cable is ducted in a cable tray, the cable must be fed out and right up to the controller. The fast solution where only wires are fed out will cause problems.
Cabinet mounting When controllers are installed in a cabinet, internal cable ducting must also comply with the relevant requirements. Use this cable ducting when one or more controllers are installed in a cabinet. (The short connections between controllers must also be of the correct cable types.)
Noise sources Keep the cable away from electrical noise sources and power cables (relays, contactors and especially electronic ballast for strip lights are strong noise sources). A distance of at least 10-15 cm will be sufficient.
Min. 10-15 cm
Cable length extremities Each section of data communication must be terminated
correctly. See the relevant communication form on the following pages.
Termination with a resistance of 120 . Either directly on the terminals or
with a switch.
Screen See the respective communication forms.
Keep a distance to relays, their cables and other things emitting electric
noises.
When controllers are fitted in a cabinet door, the cables are usually kept
together in bundles of cables. Here the bundle with data communication,
display and digital input signals must be kept separate from other cables that
emit noise.
Data communication
Design guide RC8AC902 © Danfoss 2017-06
7
Lon RS 485 – bus
System unit
Wiring
See also page 7.
This data communication is primarily used in controllers in the series: ·
EKC.. · AK-CC, AK-PC…
The system devices must be: · System manager from the serie AK-SM · System
manager from the serie AK-SC · Gateway type AKA 245
The cable is connected from controller to controller, and no branches are
allowed on the cable. The System Manager can be inserted in middle of network.
(However, not AK-SC 255 and 355, which have a fixed termination = ON.) See
page 9 for drawing.
If the cable length exceeds 1200 m a repeater must be inserted
If the data communication cable runs through an electrically noisy environment
which impairs the data signal, one or more repeaters must be added to
stabilise the signal. The repeater is placed so that the length of the cable
is evenly distributed.
See page 17 for more information on repeaters.
Number of controllers The total number of controllers on an LON RS485 connection is determined by the system device and can vary between 32 and 200. See the summary of system options on page 4.
Conductors
The two wires are looped from device to device. There are no polarisation
requirements. (On some controllers, the clamps are designated A and B. On
others there is no designation. Otherwise the connections are identical.)
If a screen is used, ensure screen is connected to system device and any
repeaters. A screen must always be looped from device to device. The screen
must not be connected to anything else. (The screen is earthed inside the
system device and must not be earthed in any other way.)
8
Design guide RC8AC902 © Danfoss 2017-06
Data communication
Cable sections/termination
System unit Termination = Off
Repeater System unit Termination = On
When all cables have been mounted on the different units, the cable must be
terminated. A section must be terminated at both ends. The section must be
terminated using either an external resistor or a contact. Please see the
relevant device. A repeater will normally terminate two cable sections. The
termination should be made with a 120-ohm resistor. (The resistor can be in
the range 100 to 130 ohms.)
A repeater will always terminate two cable sections.
Data communication
Design guide RC8AC902 © Danfoss 2017-06
9
MOD – bus
System unit
Wiring
See also page 7.
This data communication can be used in the serie: · EKC.. · AK-CC · AK-CT
The system device must be: · System manager type AK-SM · System manager type
AK-SC
The cable must be with screen.
The cable is connected from controller to controller, and no branches are
allowed on the cable. The System Manager can be inserted in middle of network.
(However, not AK-SC 255 and 355, which have a fixed termination = ON.) See
page 11 for drawing.
If the cable length exceeds 1200 m a repeater must be inserted
If the data communication cable runs through an electrically noisy environment
which impairs the data signal, one or more repeaters must be added to
stabilise the signal. The repeater is placed so that the length of the cable
is evenly distributed.
See page 17 for more information on repeaters.
32
Number of controllers The total number of controllers on MOD bus connection can be up to 120. See the summary of system options on page 4.
Conductors
The wires are looped from device to device. A is connected to A B is connected
to B.
The screen must be connected to the system device, all controllers and any
repeaters. A screen must always be looped from device to device. The screen
must not be connected to anything else. (The screen is earthed inside the
system device and must not be earthed in any other way.)
10
Design guide RC8AC902 © Danfoss 2017-06
Data communication
Cable sections / termination
System unit Termination = Off
Repeater System unit Termination = On
When all cables have been mounted on the different devices, the cable must be
terminated. A section must be terminated at both ends. The section must be
terminated using either an external resistor or a contact. Please see the
relevant device. A repeater will always terminate two cable sections.
The termination should be made with a 120-ohm resistor. (The resistor can be
in the range 100 to 130 ohms.)
Data communication
Design guide RC8AC902 © Danfoss 2017-06
11
Lon TP 78 – bus
System unit
See also page 7.
This data communication is no longer recommended for new installation, Danfoss
can provide units for retro-fit: · System controller type AK-SC 255, 355 and
AK-SM 8xx · AK-CM – communication modules · AK-CC – Case control (TP 78
version)
Wiring
System unit
Cables with screen must be used.
The cable is connected from controller to controller, and no branches are
allowed on the cable. System Manager AK-SM 8xx can be inserted in middle of
network. (However, not AK-SC 255 and 355, which have a fixed termination =
ON.) See page 13 for drawing.
A cable section must not be longer than 1200m. A repeater must be used for
longer sections.
The sum of all sections must not exceed 1200m. A repeater must be used if the
sum is greater.
If the data communication cable runs through an electrically noisy environment
which impairs the data signal, one or more repeaters must be added to
stabilise the signal. The repeater is placed so that the length of the cable
is evenly distributed.
See page 17 for more information on repeaters.
Number of controllers The total number of controllers on a TP 78 connection is determined by the controlling unit and can be up to 120. See the summary of system options on page 4.
Conductors
The two wires are looped from device to device. There are no polarisation
requirements.
The screen must be connected to the system manager and any repeaters. A screen
must always be looped from device to device. The screen must not be connected
to anything else. (The screen is earthed inside the device and must not be
earthed in any other way.)
12
Design guide RC8AC902 © Danfoss 2017-06
Data communication
Cable sections / termination
System unit Termination = Off
When all cables have been mounted on the different devices, the cable must be
terminated.
A section must be terminated at the end of each sections. Termination is
performed with the resistors (terminations) supplied. If one or more of the
sections is not used, the termination on the clamp row should be retained.
A repeater will always terminate two cable sections. A section after a
repeater must be terminated at both ends.
System unit. Termination: All = On
Data communication
Design guide RC8AC902 © Danfoss 2017-06
13
DANBUSS
System unit
Wiring
See also page 7.
This data communication is no longer recommended for new installation, Danfoss
can provide units for retro-fit: · AK-CC. The system device must be a gateway
type: · AKA 245 or · Interface module AK-PI 200 + a AK-SM unit
Cable must be with screen. The cable is connected from controller to
controller, and no branches are allowed on the cable. If the cable length
exceeds 1200 m a repeater must be inserted.
If the data communication cable runs through an electrically noisy environment
which impairs the data signal, one or more repeaters must be added to
stabilise the signal. The repeater is placed so that the length of the cable
is evenly distributed. See page 17 for more information on repeaters.
Nubmer of controllers The total number of controllers on an Danbuss connection is determined by the controlling device and can vary between 60 and 120. See the summary of system options on page 4.
Conductors
The wires are looped from device to device. L (K3) is connected to L (K3) and
H (K4) to H (K4).
The screen must be connected to screen (k1) on all controllers and any
repeaters. The screen must not be connected to anything else. (The screen is
earthed inside the system device and must not be earthed in any other way.)
14
Design guide RC8AC902 © Danfoss 2017-06
Data communication
Cable sections / termination
System unit. Termination = On
System unit. Termination = On
When all cables have been mounted on the different units, the cable must be
terminated. The termination is made using changeover switches and bow
contacts. A section must be terminated at both ends. The section must be
terminated using either an external resistor or a contact. Please see the
relevant device. A repeater will always terminate two cable sections.
The termination should be made with a 120-ohm resistor. (The resistor can be
in the range 100 to 130 ohms.)
Data communication
Design guide RC8AC902 © Danfoss 2017-06
15
Combinations of net
Bridge
A bridge is a signal transition from one type of data communication to a
different type. A bridge has no address. Multiple bridges and bridge types can
be mixed on a common loop. Lon FTT 10 to Lon RS 485 and reverse A bridge type
TP78-05 can be used. Code no. = 084B22 55.
Lon TP 78 to Lon RS 485 and reverse A bridge type TP78-04 can be used. Code
no. = 084B2254.
Lon TP 78 to Lon FTT10 and reverse A bridge type TP78-02 can be used. Code no.
= 084B2252.
DANBUSS to AK-SM 720 Protocol interface AK-PI 200 can be used. Literature no.
= RS8EX.
16
Design guide RC8AC902 © Danfoss 2017-06
Data communication
Repeater
A repeater is a device that refreshes the signal so that the signal can be
read further out on the communication line. Location-recommended to be in
middle of loop so distance is split in half. A repeater has no address.
Lon RS 485 A repeater from the company “Phoenix” can be used: Danfoss code no
= 084B2241 (type AKA 223) On Lon RS485 the communication speed is set to 78.1
kbps on the repeater.
MOD-bus A repeater from the company “Phoenix” can be used: Danfoss code no. =
084B2240 (type AKA 222). On Modbus the communication speed is set to 38.4 kbps
on the repeater. (A cable section with SLV must be set to 19.2 kbps.)
Lon TP 78 A repeater type TP78-01 can be used.
DANBUSS A repeater from the company “Phoenix” can be used: Danfoss code no. =
084B2240 (type AKA 222). On DANBUSS the communication speed is set to 4.8 kbps
on the repeater. A on the repeater must be connected to DANBUSS-terminal L. B
on the repeater must be connected to DANBUSS-terminal H.
Data communication
Design guide RC8AC902 © Danfoss 2017-06
17
ADAP-KOOL0174
LonWorks® is a registered trademark, belonging ECHELON Corporation.
Danfoss can accept no responsibility for possible errors in catalogues,
brochures and other printed material. Danfoss reserves the right to alter its
products without notice. This also applies to products already on order
provided that such alternations can be made without subsequential changes
being necessary in specifications already agreed. All trademarks in this
material are property of the respecitve companies. Danfoss and Danfoss
logotype are trademarks of Danfoss A/S. All rights reserved.
18
Design guide RC8AC902 © Danfoss 2017-06
Data communication
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>