GTO 1000 Automatic Gate Operator Instruction Manual

June 1, 2024
GTO

GTO 1000 Automatic Gate Operator

GTO-1000-Automatic-Gate-Operator-image

Specifications

  • Product: GTO/PRO 1000 Series Automatic Gate Operator
  • Intended Use: Vehicular Swing Gates
  • Class Categories: Class I, Class II, Class III
  • Safety Standard: UL 325

Product Usage Instructions

Safety Instructions

Before installing or using the automatic gate operator, read and understand all instructions provided in the manual. Take caution as the operator produces a high level of force. Keep clear of the unit during operation and exercise caution at all times.

Powering The System

Ensure proper power supply to the system. Follow instructions on connecting the transformer to power the gate operator. Refer to page 20 of the manual for details on using solar panels for powering the system.

Control Board Settings

Adjust control board settings as needed. Refer to page 23 of the manual for information on configuring DIP switches and potentiometers for optimal performance.

Setting Your Personal Transmitter Code

Secure your gate by setting a personal transmitter code. Follow the instructions on page 25 of the manual to set up your unique code for operating the gate.

Mounting the Receiver

Properly mount the receiver according to the guidelines provided in the manual. Refer to page 26 for step-by-step instructions on mounting the receiver for effective communication with the transmitter.

FAQs

  • Q: What are the Class Categories for Vehicular Gate Operators?
    • A: The Class Categories include Residential Vehicular Gate Operator-Class I and Commercial/General Access Vehicular Gate Operator-Class II.
  • Q: How can I convert metric units to English equivalents?
    • A: Use the conversion chart provided in the manual. For example, to convert centimeters to inches, multiply by 0.3937.
  • Q: Where can I find the serial number of the gate operator?
    • A: The serial number is located on the control box cover. Refer to this number when contacting GTO for service or support.

“`

Installation Manual for the

¨

75

LISTED

Series

Automatic Gate Operator

for Vehicular Swing Gates

WARNING!
READ ALL INSTRUCTIONS CAREFULLY AND COMPLETELY before attempting to install and use this automatic gate operator. This gate operator produces a high level of force. Stay clear of the unit while it is operating and exercise caution at all times.

This product meets and exceeds the requirements of UL 325, the standard which regulates gate operator safety, as established and made effective March 1, 2000, by Underwriters Laboratories Inc.

, INC.
3121 Hartsfield Road · Tallahassee, Florida, USA 32303 Telephone (800) 543-GATE or 850-575-0176 · Fax 850-575-8912 · www.gtoinc.com

© 2000 GTO, Inc.

RB918 rev-04/22/02

GTO/PRO 1000 series automatic gate operators are intended for use with vehicular swing gates. These operators can be used in Class I, Class II and Class III applications.
VEHICULAR GATE OPERATOR CLASS CATEGORIES
Residential Vehicular Gate Operator-Class I: A vehicular gate operator (or system) intended for use in a home of one-to-four single family dwelling, or a garage or parking area associated therewith.
Commercial/General Access Vehicular Gate Operator-Class II: A vehicular gate operator (or system) intended for use in a commercial location or building such as a multifamily housing unit (five or more single family units), hotel, garages, retail store, or other building servicing the general public.
Industrial/Limited Access Vehicular Gate Operator­Class III: A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
Restricted Access Vehicular Gate Operator­Class IV: A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.

Conversion Chart

Converting Metric Units to English Equivalents
When You Know Multiply By To Find

centimeters meters kilograms

0.3937 3.2808 2.2046

inches feet pounds

Symbol
in. (or “) ft. (or ‘) lb. (or #)

Converting English Units to Metric Equivalents
When You Know Multiply By To Find

inches feet pounds

2.5400 0.3048 0.4535

centimeters meters kilograms

Symbol
cm m kg

Converting Temperature

deg. Celsius

(ºC x 1.8) + 32 deg. Fahrenheit ºF

deg. Fahrenheit

(ºF-32) ÷ 1.8 deg. Celsius

ºC

FOR YOUR RECORDS
Please record the serial number (located on the control box cover), and the date and place of purchase in the spaces provided below. Refer to this information when calling GTO for service or assistance with your automatic gate operator.

Serial Number ____ Date of Purchase ____ Place of Purchase ____ Remember to keep all receipts for proof of purchase.

KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE

BEFORE INSTALLING THIS GATE OPERATOR: Read these instructions carefully and completely to become familiar with all
parts and installation steps.

IMPORTANT SAFETY INSTRUCTIONS

Because automatic gate operators produce high levels of force, all system designers, installers, and consumers have an obligation to know the potential hazards associated with improperly designed, installed, or maintained gate operator systems. Keep in mind that the gate operator is just one component of the total gate operating system. Each component must work in unison to provide the consumer with convenience, security, and safety.

This manual contains various safety precautions and warnings for the system designer, installer, and consumer. Because there are many possible applications of the gate operator, the safety precautions and warnings contained in this manual cannot be completely exhaustive in nature. They do, however, provide an overview of the safe design, installation, and use of this product. CAREFULLY READ AND FOLLOW ALL SAFETY PRECAUTIONS, WARNINGS, AND INSTALLATION INSTRUCTIONS TO ENSURE THE SAFE SYSTEM DESIGN, INSTALLATION, AND USE OF THIS PRODUCT.

The precautions and warnings in this manual are identified with

this warning symbol. The symbol identifies

conditions that can result in damage to the operator or its components, serious injury, or death.

Because GTO automatic gate operators are only part of a total gate operating system. It is the responsibility of the designer, installer, and purchaser to ensure that the total system is safe for its intended use.

To Manually Open and Close the Gate, follow the procedure below:

Disconnecting the Operator
1. Turn control box OFF. 2. Remove hairpin clip, clevis pin, and
washer from front mount. 3. Pull front mount away from gate bracket.
The gate can be opened and closed manually when the gate operator is disconnected.
NOTE: Substitute Master® Pin Locks for the clevis pins to prevent unauthorized removal of the operator from the gate (see Accessory catalog).

CAUTION: Disconnect the operator only when the gate the control box power switch is OFF and the gate is NOT moving.
Front Mount

Washer Hairpin Clip

Clevis Pin Gate Bracket

1

IMPORTANT SAFETY INSTRUCTIONS

For The System Designer
WARNING: To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. This operator is intended for use only on vehicular gates. Pedestrians must be supplied with a separate walkthrough gate (see Entrapment Protection illustration on page 6).
3. When designing a system that will be entered from a highway or main thoroughfare, make sure the system is placed far enough from the road to prevent traffic congestion.
4. The gate must be installed in a location that ensures adequate clearance between it and adjacent structures when opening and closing to reduce the risk of entrapment. Swinging gates shall not open into public access areas.
IMPORTANT SAFETY INSTRUCTIONS for the Installer
WARNING­To reduce the risk of injury or death:
I. Before Installation 1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Verify this operator is proper for the type and size of gate, and its frequency of use.
3. Make sure the gate has been properly installed and swings freely in both directions. Repair or replace all worn or damaged gate hardware prior to installation. A freely moving gate will require less force to operate and will enhance the performance of the operator and safety devices used with the system.
4. Review the operation of the system to become familiar with its safety features. Understand how to manually open and close the gate by disconnecting the operator (see page 1).
5. This gate operator is intended for vehicular gates ONLY. A separate entrance or gate must be installed for pedestrian use (see page 6). NO ONE SHOULD CROSS THE PATH OF A MOVING GATE.
II. During Installation 1. Install the gate operator on the inside of the property and fence line. DO NOT install an operator on the outside of the gate where the public has access to it.
2. Be careful with moving parts and avoid close proximity to areas where fingers or hands could be pinched.
3. The installation of additional safety equipment such as safety edges (or photoelectric sensors) is suggested for augmented protection against entrapment (see page 6).
4. Determine the best obstruction sensing setting for this installation. The gate MUST stop and reverse on contact with an obstruction or when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.
5. Mount access controls away from the gate (minimum distance is 10 feet). The user must have full view of the gate but be unable to touch it while operating the controls.
6. Secure outdoor or easily accessed gate operator controls in order to prohibit unauthorized use of the gate. 2

IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS for the Installer
III. After Installation 1. Review ALL safety instructions with the consumer/end user and explain the basic operation and safety systems of the entire gate operator system, including disconnecting the operator for manual operation of the gate. 2. Attach the warning signs (included) to each side of the gate to alert public of automatic gate operation. Take a photo of warning signs installed on gate. Record the date of the photo for your reference.
3. SAVE THESE INSTRUCTIONS.
Leave a copy of the IMPORTANT SAFETY INSTRUCTIONS section of this manual with the consumer/end user.
3

IMPORTANT SAFETY INSTRUCTIONS
Secondary Means of Protection Against Entrapment
As specified by Underwriters Laboratories Inc. UL 325 (30A.1.1), automatic gate operators shall have provisions for, or be supplied with, at least one independent primary and one independent secondary means to protect against entrapment. GTO gate operators utilize Type A, an inherent (i.e., built-in) entrapment sensing system, as the primary type of entrapment protection. The GTO/PRO 1000 series operators have provisions for the connection of Type B1 or B2 protection to be used as the secondary type of entrapment protection, if desired.
1. For gate operators utilizing a non-contact sensor (Type B1) in accordance with UL 325 (51.8.4 [h]):
A. Refer to the sensor manufacturer’s instructions on the placement of non- contact sensors for each type of application.
B. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is still moving.
C. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a moving gate or barrier.
2. For gate operators utilizing a contact sensor (Type B2) in accordance with UL 325 (51.8.4 [i]):
A. One or more contact sensors shall be located at the leading edge, bottom edge, and post mounted both inside and outside of a vehicular swing gate system.
B. A hard wired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subjected to mechanical damage.
C. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall function under the intended end-use conditions.

ENTRAPMENT ALARM (UL 325; 30A.1.1A)
The GTO/PRO 1000 series operators are designed to stop and reverse for 2 seconds when the gate comes in contact with an obstruction or when an object activates the non-contact sensors. Additionally, these operators are equipped with an audio entrapment alarm which will function if the unit obstructs twice while opening or closing. This alarm will sound for a period of 5 minutes or until the operator receives an intended signal (e.g., transmitter signal) and the gate returns to a fully open or fully closed position.

+ BATT ­

PWR. SW.

STATUS

CAULOTOSE INERTIA SOEBNSST.R.

LEARN R GB

RED BLK ORG
BLU GRN CLS EDG
OPN EDG RED BLK ORG BLU GRN CLS EDG OPN EDG GRN ORG BLU WHT

18~VAC~ SO­ LA+R

POWER IN

FIRST OPERATOR

SECOND OPERATOR

ALARM

ACCESSORY

RCVR

Entrapment Alarm (bottom right of control box)
4

IMPORTANT SAFETY INSTRUCTIONS
For The Consumer/End User
WARNING: To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Distribute and discuss copies of the IMPORTANT SAFETY INSTRUCTIONS section of this manual with all persons authorized to use your gate.
3. Always keep people and objects away from the gate and its area of travel. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
4. Your automatic gate is not for pedestrian use. If pedestrian traffic is expected near the gate, a walk-through gate must be installed for this purpose (see page 6).
5. Do not allow children or pets near your gate. Never let children operate or play with gate controls. Keep the remote controls away from children and unauthorized users; store controls where children and unauthorized users cannot access them.
6. If push buttons or key switches are installed, they should be within sight of the gate, yet located far enough from it (at least 10 feet) so the gate cannot be touched while it is in operation. Do not operate any control without watching the movement of the gate.
7. Do not activate your gate operator unless you can see it and can determine that its area of travel is clear of people, pets, or other obstructions.
8. It is your responsibility to make sure that the installer posted warning signs on both sides of your gate. If any of these signs or warning decals become damaged, illegible or missing, replace them immediately. Contact your installer or GTO for replacements.
9. If electric safety edge sensors (or photoelectric sensors) have been installed (see page 6) they should be tested monthly for proper function.
10. KEEP GATES PROPERLY MAINTAINED. Clean the push-pull tube with a soft, dry cloth and apply silicone spray to it at least once per month.
11. Test your gate operator monthly and service it regularly. The gate MUST stop and reverse on contact with an obstruction or when an object activates the non-contact sensors. If these functions are observed to operate improperly, discontinue use and have the operator serviced immediately.
12. To operate this equipment safely, YOU must receive detailed instructions on disconnecting the operator for manual gate operation (see page 1). If you feel you have not received full and proper instructions, contact your installer.
13. Disconnect the operator only when the control box power switch is OFF and the gate is NOT moving.
14. SAVE THESE INSTRUCTIONS
5

IMPORTANT SAFETY INSTRUCTIONS

Required Safety Precautions for Gates
Install Warning Signs
Warning signs alert people of automatic gate operation and are required when installing the GTO/PRO 1000 and series gate operators. Furthermore, a walk- through gate must be installed if pedestrian traffic is expected near the vehicular gate. We recommend the GTO Bulldog Pedestrian Gate Lock (see Accessory Catalog) for controlled access.

Bulldog Pedestrian Gate Lock
(recommended, not included)
Pedestrian Gate

Safety Edge
(suggested, not included)

Warning Sign

Vehicular Gate
Safety Edge
(suggested, not included)
Entrapment Protection
GTO’s internal obstruction settings, even when properly adjusted, may not be sensitive enough to prevent bodily injury in some circumstances. For this reason, safety devices such as safety edge sensors (or photoelectric sensors), which stop and reverse gate direction upon sensing an obstruction, are suggested for augmented protection against entrapment.

! WARNING

Warning Signs
The warning signs (at left) must be installed on both sides of the gate (see page 7 for details).

Moving Gate Can Cause Injury Or Death
1. KEEP CLEAR! Gate may move at any time.
2. Do not allow children to operate gate or play in gate area.
3. This gate is for vehicles only. Pedestrians must use a separate entrance.

6

IMPORTANT SAFETY INSTRUCTIONS
These warning labels should be found at the locations specified below. If any of them are missing, immediately contact your installer for replacements.
! WARNING ! WARNING

Moving Gate Can Cause Injury Or Death
1. KEEP CLEAR! Gate may move at any time. 2. Do not allow children to operate gate or
play in gate area. 3. This gate is for vehicles only. Pedestrians
must use a separate entrance.
warning signs (2 enclosed) to be installed on each side of the gate (3­5 feet above the bottom of the gate)

MOVING GATE
Can Cause Injury or Death
1. KEEP CLEAR! Gate may move at any time. 2. Do not allow children to operate gate or play in gate area. 3. This gate is for vehicles only. Pedestrians must use
separate entrance.
warning labels (2) installed on each side of operator housing

Series
Conforms to UL 325 STANDARDS

Maximum Gate: 500 lb. (226.7 kg); 16 ft. (4.8 m)

C

US Voltage: 12 Vdc; Frequency: 0 Hz; Power: 41.4 W

LISTED

Class I, II and III Vehicular Swing Gate Operator.

9901178 Serial Number: 1000-xxxxxxx

TO MANUALLY OPEN AND CLOSE THE GATE: 1. Turn control box power switch OFF. 2. Disconnect front mount from gate bracket. 3. Pull front mount away from gate bracket.

Disconnect operator ONLY when the control box power switch is OFF and the gate is NOT moving.

GTO, Inc. Tallahassee, Florida USA

RB2000

product identification and manual operation instruction label (1) installed on control box cover

7

Technical Specifications

GTO/PRO 1000 Series Swing Gate Operators

DRIVE · Low friction screw drive (linear actuator) rated for -30 oF to +200 oF. Powered by a 12 V motor with
integral case hardened steel gear reducer. Motor speed reduced to 220 rpm. Generates 330 ft.. lb. of torque at 12 V; · 90º opening time: 15 s to 17 s, depending on weight of gate.
POWER · The GTO/PRO 1000 system is powered by a 12 Vdc, 7.0 Ah, sealed, rechargeable battery · Battery charge for GTO/PRO 1000 is maintained by a 120 Vac, 18 Vac (20 VA) transformer rectified to
14.5 Vdc through the GTO Control Board. Two (2) blade-style control board fuses are rated for 15 A. NOTE: The transformer should not be connected directly to any battery. Do not replace fuses higher ampere rated fuses; doing so will void the warranty and may damage the control board. · Battery charge maintained by GTO Solar Panel Charger: float voltage 14.5 Vdc output from a 193/8″ x 81/2″ silicon alloy panel. Generates minimum of 5 W at 300 mA. Gated diode on the control board prevents battery discharge. NOTE: The solar charger should not be connected directly to any battery.
CONTROL · GTO microprocessor-based control board is set for single leaf, pull- to-open gate installations. DIP
switches can be adjusted to accommodate an optional kit for push-to-open gates (see Accessory Catalog). · Control board has temperature compensated circuits. · A circuit on control board regulates charging. “Sleep draw” is 40 mA; “active draw” is 2 to 5 A. · Auto-memorization of digital transmitter code. · GTO remote-mounted RF receiver tuned to 318 MHz. · Limit controls are mechanical. Adjustable range of push-pull tube is 71/2″ to 111/2″. Operator length
with push-pull tube fully retracted is 333/4″, mounting point to mounting point. · Adjustable auto-close timer (OFF to 120 s), inertia, and obstruction sensitivity using three (3)
potentiometers. · Power terminal block accommodates a transformer and solar panels. · DIP switches simplify setup of gate operator. · Accessory terminal block fully compatible with push button controls, digital keypads, safety loops, etc. · Control board allows connection of safety edge sensors and photoelectric sensors. · Audio entrapment alarm sounds if unit encounters an obstruction twice while opening or closing.
OPERATIONAL CAPACITY · Depending upon length of the gate and the number of operational cycles per day, the GTO/PRO 1000
can operate gates weighing up to 500 pounds, if all proper installation procedures have been followed. Ball bearing hinges should be used on all gates weighing over 250 pounds.

Gate Length

Gate Capacity Chart (estimated number of cycles based on use with a transformer)

16 ft.

135

120

105 NONE NONE NONE NONE

14 ft. 12 ft. 3.5-10 ft.

145 155 165 50 lb.

130 140 150 100 lb.

115 125 135 150 lb.

100 110 120 200 lb.

70 80 90 300 lb.

NONE 40 50
400 lb.

NONE NONE
10 500 lb.

Gate Weight

NOTE: An operation cycle is one full opening and closing of the gate. The numbers shown in this chart are for single gate applications, cycles for dual gate applications will be about half of those with a single gate.

These are the recommended guidelines when using the ac transformer (included) to trickle charge the battery. See page 20 for information about maximum cycles provided by the GTO/PRO 1000 when using the GTO Solar Panel.
These specifications are subject to change without notice.
8

Parts Identification
Single Gate Operator and Hardware

4 1/2″ x 4 1/2″ Setback Template (1)
SpeaegeInss5taallnadtio6ninofththeeInPsotsat lBlaratcioknet MAsasneumablly

Gate Opener (1)

Gate Bracket (1)

® AUTOMATIC GATE OPENERS

4 1/2′ Power Cable (1)

Customer Support Card (1)

Closed Position

Stop Plate (1)

Post Bracket (2)

Post Pivot Bracket (1)

8″ Nylon Cable Tie (14)

Hardware

3/8″ x 8″ Bolt (4)
3/8″ x 3″ Bolt (2) 3/8″ x 2″ Bolt (1) 5/16″ x 1-3/4″ Bolt (1) 3/8″ x 1-1/8″ Clevis Pin (2)
Hairpin Clip (2)
9

2″ Receiver Mounting Screw (1)

3/8″ Washer (9) 3/8″ Lock Washer (7)
5/16″ Washer (1) 3/8″ Nut (7) 5/16″ Nut (1)

Single Gate Operator Parts List
Control Box and Electrical Components
Battery (1)

Transformer (1)

Receiver (1)

GTO Transmitter(1) ! WARNING

Control Box Lid (1)

Control Box (1)

Moving Gate Can Cause Injury Or Death
1. KEEP CLEAR! Gate may move at any time. 2. Do not allow children to operate gate or
play in gate area. 3. This gate is for vehicles only. Pedestrians
must use a separate entrance.
Warning Signs (2)

Tools Needed · Power Drill · Open End Wrenches — 3/8″, 7/16″, 1/2″, and 9/16″ · 3/8″ Drill Bit · Hacksaw or Heavy Duty Bolt Cutters · Slotted (Flat Bladed) Screwdriver · Phillips Screwdriver · Tape Measure · Level · Wire Strippers · C-Clamps — small, medium, and large
ALSO, YOU WILL NEED THESE ITEMS BEFORE YOU BEGIN THE INSTALLATION (Some of these items can be found in the Accessory Catalog on page 42):

· The gate needs a stop post for the open position. This post is not provided. See page 16, Installation of the Positive Stops for more information.

· Additional low voltage wire (16 gauge) will be needed; length depends upon the distance between the transformer power supply and the control box. See page 20, Powering the System and the Accessory Catalog.

· If your gate is more than 1000′ away from an ac power source you will need to use at least one GTO Solar Panel to trickle charge the battery. See the Accessory Catalog.

· If your fence post is made of wood and is less than 6″ in diameter or 6″ square, see page 14.

· If your fence post is larger than 6″ in diameter you will need threaded rods or carriage bolts longer than 8″. See page 15.

· If you have thin walled tube or panel gates, see page 14 for Recommended Reinforcement Examples.

· Depending on the type of gate, a horizontal cross member or mounting plate may be needed to mount the front of the operator and gate bracket to the gate. See page 11, step 2; page 15, step 10.

· Power cables 25′ and 40′ long are available for mounting your control box away from the gate (i.e., in a more secure location). See the Accessory Catalog.

10

Installation Overview

Pull-to-Open Gates (Gate Opens into the Property)
The diagram below is an example of a pull-to-open installation on a chain link fence and single gate. If you are installing a push-to-open gate system, see Push-to-Open Installation starting on page 30. Mounting the operator on a masonry colum
n requires special procedures; see Column Installation Information on page 35 before proceeding.

Receiver

Control Box with Battery
120 Volt indoor
Transformer
(surge protector
not supplied)

Run 1000′ (max.) of low
voltage wire to control
box from transformer
(wire not included).

Gate Swings Evenly and Freely
Hung Firmly and Plumb
Post Bracket Assembly Single Gate Opener

Horizontal Cross Member

Gate Bracket

Warning Sign

Power Cable

Closed Position Positive Stop Plate

Fence Post Set in Concrete
PVC conduit (not included)
to protect wire from lawn
mowers and weed eaters.

Preparing the Gate
Step 1:
The gate must be in proper working order, plumb, level and swinging freely on its hinges. Do not use wheels on gate. The gate must move smoothly and evenly throughout its swing, without binding or dragging on the ground. Gates over 250 pounds should have ball bearing hinges with grease fittings.

Step 2:
The fence post must be strongly secured in the ground with concrete so it will not twist or flex when the operator is powered. It is important to position the operator near the centerline of the gate to keep the gate from twisting and flexing. The addition of a horizontal or vertical cross member may be necessary (if one is not already in place) to provide a stable area to which the gate bracket can be secured.
For the operator to function properly, Steps 1 & 2 must be complete before proceeding to the next step.

Horizontal Cross Member Vertical Cross Member

11

Post Bracket Assembly

Determining The Mounting Position of The Post Bracket Assembly and The Gate Bracket

Step 3:
Join the post bracket assembly using the 3/8″ x 2″ bolt in the center holes as shown. Fasten a 3/8″ washer and nut on the end of the bolt. DO NOT overtighten nut because the post pivot bracket will need to be adjusted later.

3/8″ x 2″ Bolt
Post Bracket Post Pivot Bracket
Post Bracket 3/8″ Washer 3/8″ Lock Washer 3/8″ Nut

Step 4:
Attach the post bracket assembly and the gate bracket to the operator with the clevis pins and washers. Secure the clevis pins with hairpin clips.

Clevis Pin

Rear Mount

Front Mount Operator

Clevis Pin

Operator Washer

Gate Bracket

Hairpin Clip Post Bracket Assembly

Washer Hairpin Clip

Step 5:
With the gate in the open position (at least 80o and no more than 110o from the closed position), determine the position of the post bracket assembly and the gate bracket. While holding the operator in a level position (use a level), clamp these parts in their respective positions on the fence post and the gate.

Post Bracket Assembly

Level Opener

Fence Post

AUTOMATIC GATE OPENERS®

LEVEL horizontal cross member

Gate Bracket

Gate In Open Position

12

Step 6
Study the 4 1/2″ x 4 1/2″ setback template (see insert) provided with this manual. Once you are familiar with its illustrations, cut and save the template from the insert. The template will determine the correct position of the post pivot bracket before mounting the operator on the fence post.

Remove hairpin, clevis pin, and washer from operator and close the gate. Rest disconnected operator on cross member of gate. Stand inside property next to fence post and place one end of template over center of gate hinge. Place the other end of template over the post pivot bracket hole (either of the two mounting holes in post pivot bracket can be used) where the operator will be attached. Be sure to hold the template at a 90º angle between these two points and measure 4 1/2″ back from the center of the gate hinge. You will need to rotate the post pivot bracket or the entire post bracket assembly to align it with the square angle of the template. THE ANGLE BETWEEN THE GATE HINGE AND THE POST PIVOT BRACKET MUST MATCH THE ANGLE OF THE SETBACK TEMPLATE.

NOTE: When you move the post pivot bracket, be sure one of the post bracket holes is aligned with the rest of the assembly (center hole should already have bolt through it). Flipping the Post Pivot Bracket gives more position options.

After verifying that you have complied with the 4 1/2″ x 4 1/2″ setback, insert the 5/16″ x 1 3/4″ bolt through the aligned holes of the post bracket and post pivot bracket (illustrated below) and fasten it with the 5/16″ washer and nut. IMPORTANT: If you loosened the clamp on the post bracket to achieve the 4 1/2″ x 4 1/2″ setback, tighten it in its new position and recheck gate bracket with the gate in its open position (move the gate bracket and re-clamp it if necessary).
Examples of a 4 1/2″ x 4 1/2″ Setback

Pull-to-Open Installation Center of Gate Hinge

5/16″ x 1 3/4″
bolt

4 1/2″
90o 4 1/2″

GATE

Metal Post Post
Bracket
5/16″ x 1 3/4″
Bolt
Post
Pivot Bracket

Washer

Center of Gate Hinge

GATE
4 1/2″ Pull-to-Open Installation
90o 4 1/2″

IMPORTANT

Closed Position Make sure there is
adequate clearance
between opener and
gate in the open and
closed positions
Open Position
Verify the Position of the Gate Bracket and Post BracketAssembly:
With the gate in the open position, make sure the following conditions are met: 1. The operator is level. 2. The 4 1/2″ x 4 1/2″ setback measurement is correct (Step 6). 3. There is sufficient clearance between operator and gate in the open and closed positions.
13

Installation of Mounting Hardware

The post bracket position determines both the leverage and efficiency of the operator, and the clearance between the operator and the gate in the open and closed positions.

The post bracket is designed with a curvature that works well with installations on both round and square fence posts.

Since the post bracket carries the entire back thrust of the active operator, it is absolutely necessary that it be mounted

with bolts that completely penetrate the fence

post.

On wooden posts, it is best to use a metal plate

Wooden Post Metal Plate Wooden Post Metal Plate

or washer between the nuts and the gate post to

prevent the operator from pulling the bolts and

washers through the wood.

NOTE: Any fence post under 6″ in diameter or 6″ square should be made of metal not wood.

Post Bracket

Post Bracket

Fence Post

Metal Plate

Post Pivot Bracket

Post PivotBracket

Special Flat (Column Mount) Post Bracket
Post Pivot Bracket

For best installations on flat wooden posts, columns, steel plates or other flat mounting, use the special flat column mount post bracket. (see Accessory Catalog.)

Greater than 6″ diameter post Center of Gate Hinge

On round posts of 6″ diameter or larger, the post pivot bracket may not be needed for the installation. Just use the two post brackets by themselves.

4 1/2″ 4 1/2″
Pull-to-Open Installation

IMPORTANT: We strongly recommend reinforcing thin walled tube and panel gates as shown to prevent damage to gate and operator.

Reinforcement Examples
Steel Pipe Cut in Half (not supplied)

Gate Bracket Thin Walled Tube Gate

Panel Gate
Gate Bracket 1″ x 6″ Wood Reinforcement
(not supplied)

14

Installing The Post Bracket Assembly and Gate Bracket

Step 7:
Mark the holes in the middle of the bracket slots so there will be some room for adjustment when mounting the post bracket assembly and the gate bracket on the fence post and gate cross member. Then remove the operator and brackets from the fence and gate.

Step 8:
Drill 3/8″ holes in the fence post as marked.

Mark fence post and drill 3/8″ holes

EXAMPLES TOP VIEW

Step 9:
Install the post bracket assembly using (4) 3/8″ x 8″ bolts, nuts, washers and lock washers provided. Cut off the ends of the bolts extending beyond the tightened nuts.

Post Bracket Assembly

SIDE VIEW

Round Metal Post Square Metal Post

NOTE: if the fence post has a diameter greater than 6″, it will be necessary to use threaded rods or carriage bolts longer than 8″ (not supplied).

Square Wood Post

Cut off excess bolt with hack saw or bolt cutters

Round Wood Post

Step 10:
Drill 3/8″ holes in the gate cross member and mount the gate bracket with the 3/8″ x 3″ bolts, washers nuts, and lock washers provided. Cut off the ends of the bolts extending beyond the tightened nuts with hacksaw or bolt cutters.

Gate In Open Position LEVEL horizontal cross member
Mark gate bracket holes and drill 3/8″ holes

Gate Bracket Mounting Examples

FRONT VIEW

SIDE VIEW

Round Tube & Chain Link Gate

FRONT VIEW

SIDE VIEW
Mounting Plate Created for Decorative Gate (required but not supplied)

Square Tube Gate

Cut off excess bolt with hack saw or bolt cutters

15

Mounting the Operator

Step 11:
Attach the operator to the securely mounted post bracket assembly and gate bracket using the clevis pins and hairpin clips or optional Master Pin Locks (see Accessory Catalog). Check the level of the operator, and adjust the post bracket assembly if necessary.
AUTOMATIC GATE OPENERS®
Installation of the Positive Stops (Open and Closed Positions)
The positive stops hold the gate firmly in the open and closed positions. The positive stops also form the boundaries of the gate operating arc and help stabilize the gate. Moreover, a stable gate helps to maintain the long life of your automatic gate opener system. To further enhance the stability and security of your gate, install the optional GTO Automatic Gate Lock (see Accessory Catalog).
Note: If you are installing dual gate operators, install all positive stops at the same time. Please refer to Installing a Dual Gate System beginning on page 36.
Step 12:
With the gate in the maximum open position, measure approximately 2/3 of the distance to the end of the gate from the hinges and place a mark on the ground directly under the gate. Install the open position stop at this mark. The open position stop post can be made of wood, metal or concrete and should be secured firmly in the ground (we recommend seating in concrete). When the open position stop post is in the ideal position, the gate will strike the post just as the operator motor shuts down.
Step 13:
Remove the hairpin, clevis pin, and washer from the operator and close the gate (be sure to support operator). Install the closed position stop plate on the end of the gate frame at mid-height. Extend the stop plate to make contact with the fence post at that position.
NOTE: Use appropriate hardware for the type of gate (U-bolts if you have a tube or chain link gate, wood or lag screws for wood gates, etc.). This hardware is not provided.
16

At this stage of the installation, the operator should be installed on the gate and the open and closed position stops should be in place.
Check List · The gate is plumb, level, and swings smoothly on its hinges. · After measuring with the 4 1/2″ x 4 1/2″ setback template, the post bracket assembly
was bolted to the fence post. · A plate or support was added for the gate bracket (if necessary). · The operator is level and mounted on the centerline of the gate.
Closed Position Stop Plate Gate In Closed Position Open Position Stop Post (set in concrete)
Gate In Open Position
Open Position Stop Post (set in concrete)
17

Mounting the Control Box
Step 14
Mount the control box using the nylon cable ties (provided) or another secure mounting method. The control box must be mounted at least 3 feet above the ground to protect it from rain splash, snow, etc., and at least 3 feet from an ac power source to prevent electrical interference.

Step 15
Make sure the control box power switch is in the OFF position. Unscrew and remove the control box cover and slide the battery into position with its terminals to the left (see illustration). Push battery down until it fits snugly in control box. Connect the BLACK battery wire to the NEGATIVE (­) battery terminal. Connect the RED battery wire to the POSITIVE (+) terminal. Pay close attention to the color of the wires. If the wires are connected incorrectly, the control board will be damaged. NEVER insert the battery with the terminals to the right.

RED BLK ORG
BLU GRN CLS EDG
OPN EDG RED BLK ORG BLU GRN CLS EDG OPN EDG GRN ORG BLU WHT
Strain Relief

+ BATT ­

PWR. SW.

STATUS

CAULOTOSE INERTIA SOEBNSST.R.

LEARN R GB

18~VAC~ SO­ LA+R

POWER IN

FIRST OPERATOR

SECOND OPERATOR

ALARM

ACCESSORY

RCVR

Strain Relief

12 V Battery

Lock Nut Hub Sealing Nut

RED wire to POSITIVE (+) terminal RED
BLACK
BLACK wire to NEGATIVE (­) terminal
HINT: A dab of household petroleum jelly on the battery terminals will help prevent corrosion.

Step 16

Operator Power Cable

Strip approximately 3/16″ of insulation from each wire of the power

cable. Twist each exposed wire tightly (there are five [5] wires

inside the power cable sheath). Loosen sealing nut on strain relief

hub at bottom of control box. Insert power cable into control box

through strain relief. Thread approximately 4″ of the power cable

into the control box and retighten sealing nut until the power cable

locks into place.

18VAC SOLAR ~~ ­ +

RED BLK ORG BLU GRN CLS EDG OPN EDG RED BLK ORG BLU GRN CLS EDG OPN EDG GRN ORG BLU WHT
ON

SEQ1 SEQ2

LEARN

R GB

Correct

Wrong

Wrong

POWER IN FIRST OPERATOR

SECOND OPERATOR ALARM ACCESSORY RCVR

Terminal

Terminal

Terminal

Wire Block

Wire Block

Wire Block

Power Cable from First Operator

Insert the stripped power cable wires into the appropriate terminals on the FIRST OPERATOR terminal block. The green wire should be inserted into the GRN terminal, the blue wire into BLU, the orange wire into ORG, black wire into BLK, and the red wire into the RED terminal.
Tighten the set screws against the end of the wires. A dab of petroleum jelly on each terminal will help prevent corrosion.

18

AUTOMATIC GATE OPENERS

Step 17:

Push-Pull Tube

Carefully insert the power cable plug into the coupling at the

rear of the operator. Turn the plug until it aligns with the pins

in the coupling. Push the plug into the coupling until it stops.

Finger tighten the sleeve nut to lock the plug in position.

Replace the control box cover and fasten it with (4) screws. Turn the control box power switch ON. The control board will energize in approximately 15 seconds.

Setting The Closed Gate Position

Step 18:
Reattach front mount to gate bracket using clevis pin, washer, and hairpin clip. Press the transmitter to activate the operator and see how far the gate closes. The push-pull tube will initially extend only 71/2″ until it is adjusted (maximum extension of operator is 111/2″).

Step 19:
To increase the degree of gate closure, loosen the stroke adjustment knob on the bottom of the operator housing and move it about 1/8″ towards the gate bracket (Fig A). Finger tighten the knob. (DO NOT USE PLIERS OR OTHER TOOLS TO TIGHTEN KNOB) Press the transmitter to check the closing distance. To decrease the degree of gate closure, move the stroke adjustment knob away from the gate bracket (Fig B).

Stroke Adjustment for Pull-to-Open Application
Figure A
Moving knob toward the gate bracket increases gate closure.
Stroke Adjustment Knob

Figure B
Moving knob away from the gate bracket decreases gate closure

Step 20:
Repeat the procedure in Step 19 until the gate closes firmly as the operator motor shuts down. Each time you adjust the knob, finger tighten it before pressing the transmitter button to check your adjustment.
If the push-pull tube has been extended too far (i.e., if the knob is too close to the gate bracket), the gate will immediately reverse and open after closing. When the knob setting is correct, the gate will close firmly, but not sharply, against the positive stop plate. The motor will run for one-half second after the gate closes against the stop plate. If the motor continues to run for more than one second, the push-pull tube is overextended and further adjustment is necessary. If the motor strains too long against the stop plate, the fuse on the control board (above FIRST OPERATOR terminal) will be blown. This blade-style 15 ampere fuse (sold by most automotive supply stores) can be easily replaced.
NEVER use a fuse rated higher than 15 amperes!
19

Powering The System
IMPORTANT:
· The GTO transformer is intended for indoor use. If the transformer can only be plugged into an outside electrical outlet, a weatherproof housing or cover (available at local electrical supply stores) must be used.
· All low voltage wire for powering the GTO/PRO must be 16 gauge dual conductor, multi-stranded, direct burial wire (see Accessory Catalog). Do not exceed 1000 ft. of wire.
· If your gate is more than 1000 ft. from an ac power source you will need to use at least one (1) 5 watt Solar Panel; see Accessory Catalog. Also, refer to the Solar Panels and Gate activity chart below.

Solar Panels and Gate Activity

This table and map illustrate the maximum number of cycles per day to expect in a particular area, using GTO’s 5 watt solar panels (see Accessory Catalog). Figures are shown for winter (minimum sunlight) and do not account for use of any accessory items. Accessories connected to your system will draw additional power from the battery.
NOTE: GTO/PRO Dual Gate Systems REQUIRE A MINIMUM OF TWO (2) 5 W solar panels or ONE (1) 10 W panel for adequate charging power.

Winter Ratings

Zone 1 Zone 2 Zone 3

12 volt Single Gate (one 5 W panel) 4

8

13

12 volt Single Gate (two 5 W panels) 8

16

26

12 volt Single Gate (three 5 W panels) 11 12 volt Dual Gates (two 5 W panels) 4 12 volt Dual Gates (three 5 W panels) 7

20

30

8

13

13

20

;;;;;;;;;;;;;;;;;;;;;;;;;Zone 3

Connecting the Transformer

Step 21:
Make sure the power switch is OFF before proceeding to the next step.

Step 22:

Select the electrical outlet into which you will plug the

transformer. Measure the distance from this electrical outlet

to the control box following the path where the wire will be

laid. After you have measured how much wire is needed, cut

it to the appropriate length.

20

IMPORTANT INFORMATION ABOUT LOW VOLTAGE WIRE
The only wire acceptable for use with GTO products is 16 gauge multi-stranded, low voltage, PVC sheathed wire. This particular gauge enables the transformer to provide an adequate charge through the control board to the battery at distances up to 1000 ft.
DO NOT use telephone wire or solid core wire. Unlike multi-stranded wire, these types of wire are inadequate for use with your gate operator system. Telephone wire and solid core wire do not deliver enough voltage for your gate operator to function, and will cause the system to go into a condition known as “low voltage lockout.”
Never splice wires together. Splicing permits corrosion and seriously degrades the wire’s ability to carry an adequate current.

Step 23
Lay the measured length of low voltage wire in a trench following a path from the selected electrical outlet to the control box. Wires coming up from the ground should be run through PVC conduit to protect them from lawn mower blades, weed eaters, and grazing animals. Be sure to bury the wire laid in the trench.
Step 24
Feed the low voltage wires upward through the strain relief opening on the lower left of the control box. Pull 6″ to 8″ of wire into the control box and tighten the strain relief screw to secure the wires.

Strain Relief Screw Low Voltage Wire from AC Transformer

+ BATT ­

PWR. SW.

STATUS

CAULOTOSE INERTIA OBSSETNRSU.CT

18~VAC~ SO­ LA+R

POWER IN

FIRST OPERATOR

RED BLK ORG
BLU GRN CLS EDG
OPN EDG RED BLK ORG BLU GRN CLS EDG OPN EDG GRN ORG BLU WHT

LEARN R GB

SECOND OPERATOR

ALARM

ACCESSORY

RCVR

Operator Power Cable PVC Conduit

WARNING! DO NOT PLUG THE TRANSFORMER INTO AN OUTLET DURING THIS STEP. THE TRANSFORMER MUST ONLY BE PLUGGED INTO AN OUTLET DURING STEP 27!

Step 25
Strip 3/16″ off the ends of the low voltage wire and twist tightly. Attach these ends to the 18VAC terminals located on the POWER IN terminal block (see illustration at right). Be certain not to let the exposed wires touch each other.
Insert one transformer wire into an 18VAC terminal. Insert the other transformer wire into the remaining 18VAC terminal. The transformer wires can be connected to 18VAC terminals regardless of color.
Tighten set screws against exposed end of wires. A dab of household petroleum jelly on each terminal will help prevent corrosion.

RED BLACK

RED BLK ORG BLU GRN CLS EDG OPN EDG RE

18VAC SOLAR ~~ ­ +
POWER IN FIRST OPERATOR

SECOND OPER

Correct

Wrong

Wrong

Power Cable from First Operator

Terminal

Terminal

Terminal

Wire Block

Wire Block

Wire Block

21

Low Voltage Wire from AC Transformer

Spade Tongue Terminal
(not provided)
Red
Black

Step 26:
Strip 1/2″ off the ends of the low voltage wire and attach ends to the transformer terminals; red lead to (RED), black lead to (BLK).
A dab of household petroleum jelly on each terminal will help prevent corrosion.
We suggest crimping a spade tongue terminal (not provided) to the end of each wire before attaching it to the transformer.
Be certain wire ends do not touch each other!

Step 27:
Plug in the transformer. We strongly recommend using a surge protector.
Step 28:
Turn control box ON.
HINT: keep a few mothballs in the control box to discourage insects from entering it and damaging the control board.
22

CONTROL BOARD SETTINGS

DIP switches
The four DIP switches on the control board match the operator with the type of gate on which it is mounted. For example, gates may pull-to-open or push-to- open. Prior to packaging, the GTO/PRO 1000 control board was configured for single swing gates that pull-to-open (open into the property). If your gate type matches this configuration, you DO NOT need to adjust the DIP switches; proceed to the Potentiometers section on the next page.

NOTE: To change the DIP switch settings, you must turn the control box power switch OFF; move the switch; then turn the power back ON. Use a small screwdriver to move the switches.

DIP switches

PULL/PUSH: Set to PULL for swing gates that pull-to-open [factory setting]; PUSH for swing gates that push-to-open (see Push to Open Installation on pages 30-31). NOTE: The direction a gate opens is determined by standing inside the property and facing toward the gate. SNGL/DUAL: Set to SNGL for a single gate leaf [factory setting]; DUAL for dual gate leaves. SEQ1: Controls the opening order of dual gate leaves. See Setting the Control Board for Dual Gate Installations on page 39 for more information. (the factory setting is OFF). SEQ2: Controls the opening order of dual gate leaves. See Setting the Control Board for Dual Gate Installations on page 39 for more information. (the factory setting is OFF).

+ BATT ­

PWR. SW.

STATUS

PULL/PUSH SNGL/DUAL
SEQ1 SEQ2
AUTO6C0 LOSE
120 OFF
INERTIA

ON 1234

OBSTRUCT SENS.

MIN

MAX

LEARN

MAX
MOINBSSETNRSU.CT

SPNUGLLL//SPDEUUQSA1HL SEQ2

MAX MIN
LEARN
RBG

RED BLK ORG
BLU GRN CLS EDG
OPN EDG RED BLK ORG BLU GRN CLS EDG OPN EDG GRN ORG BLU WHT

18~VAC~ SO­ LA+R

POWER IN

FIRST OPERATOR

SECOND OPERATOR

ALARM

ACCESSORY

RCVR

23

Potentiometers
The three (3) potentiometers on the control board operate like a volume control on a radio. They control the auto close timer, inertia, and obstruction sensitivity of the operator. Use a small slotted screwdriver to turn the arrow in the center of the potentiometer. Clockwise rotation increases the setting (MAX). Counterclockwise rotation decreases the setting (MIN).

AUTOCLOSE
60

AUTO CLOSE (auto close timer): Determines how long the gate will remain open before it automatically closes. The limits are OFF to 120 seconds. The factory setting is OFF.

OFF

120

INERTIA

MIN

MAX

OBSTRUCT SENS.

PULL/PUSH SNGL/DUAL
SEQ1 SEQ2

ON 1234

MIN

MAX

LEARN

R BG

RCVR

INERTIA: Fine tunes obstruction sensitivity in the opening and closing modes. INERTIA allows the operator to attempt to push an obstruction clear of the gate path. When INERTIA is set to MIN the operator will obstruct quickly (i.e,. will attempt to push an obstruction briefly); when set to MAX, the operator will obstruct slowly (will attempt to push against an obstruct for a longer period). The factory setting is MIN.
OBSTRUCT SENS. (obstruction sensitivity): Determines the amount of force exerted by the gate on an obstruction before the operator stops and reverses. The gate will exert minimum force before obstructing when set to MIN. When set to MAX, the operator will exert maximum gate force before obstructing (i.e., the operator will require greater resistance before stopping and reversing.). The factory setting is MIN.
READ WARNING BELOW!

NOTE: Heavy gates and gates with high wind resistance may require the OBSTRUCT SENS. potentiometer to be set closer to MAX to prevent the operator from obstructing. Keep in mind, however, that while you must determine the best setting for smooth gate operation, you must ALSO determine the lowest possible setting for safe gate operation.
ALWAYS KEEP SAFETY AT THE TOP OF YOUR LIST WHEN ADJUSTING OR
SERVICING YOUR AUTOMATIC GATE OPERATOR!

WARNING!
All three potentiometers were set to minimum at the factory. The OBSTRUCT SENS. potentiometer MUST be adjusted above the factory setting for your GTO/PRO 1000 series operator to function properly. If the potentiometer is left at MIN, your gate operator may “obstruct” (i.e., stop and reverse) as soon as it is activated.
BE SURE TO PROPERLY RETEST THE GATE OPERATOR AFTER MAKING ANY ADJUSTMENTS; FAILURE TO DO SO MAY RESULT IN SERIOUS INJURY OR DEATH.

24

Setting Your Personal Transmitter Code
All GTO transmitters are set to a standard code at the factory and are ready to activate your automatic gate operator. For your safety and security, however, we strongly recommend that you replace the factory setting with your own personal code. Follow the directions below:
1. Remove the Transmitter Cover
Grasp the sides of the access cover and slide it away from the transmitter button (see illustration). When the access cover is removed, the battery and the DIP switches will be exposed. To set a new code, use a small screwdriver to move the switches.
, Inc.

2. Set the transmitter DIP Switches
There are nine (9) transmitter DIP switches; each of which can be placed in three different positions (+, 0, ­). DO NOT set all the switches in the same position, such as all +, all 0, or all ­. Once the DIP switches have been set to a personal code, replace and close the access cover.
WARNING: No other adjustments should be made inside the transmitter.

3. “Teach” the New Code to Control Board Memory
A. Turn control box power switch OFF. B. Unscrew and remove the control box cover. C. Press and hold the LEARN button on the control board,
and turn the power switch ON. Release LEARN button. Wait 15 seconds for the receiver to charge. D. Press and hold transmitter button until the red STATUS LED comes ON. E. Release transmitter button. The new code is stored in control board memory.

STATUS LED

STATUS

AUTOCLOSE
60

OFF

120

INERTIA

PULL/PUSH SNGL/DUAL
SEQ1 SEQ2

ON 1234

MIN

MAX

OBSTRUCT SENS.

MIN

MAX

LEARN

R BG

RCVR

25

Mounting the Receiver
Use the transmitter to check the range of the receiver before permanently mounting it. Consider the following when mounting the receiver:
· Receiver cable length is 10 feet (receivers with a longer cable are available as special order items; call the GTO Sales Department). NEVER splice receiver cable!
· Run the cable through PVC conduit to protect it from damage. · DO NOT run cable through metal conduit because the receiver signal range will
be decreased. · DO NOT run cable in a conduit containing ac wiring. · DO NOT mount receiver on a metal fence or post­ doing so will decrease signal
range. · DO NOT overtighten the mounting screws; the receiver housing could be warped
and the weather seal damaged. · The receiver range can vary from 50 to 100 feet depending upon weather,
topography, and external interference.
FCC Regulation This device complies with FCC rules Part 15. Operation is subject to the following conditions: 1. This device may not cause harmful interference. 2. This device must accept an interference that may cause undesired operation. Transmitter distance may vary due to circumstances beyond our control. NOTE: The manufacturer is not responsible for any radio or TV interference caused by unauthorized modifications to this equipment. Such modifications could void the user’s authority to operate the equipment.
26

Connecting Additional Safety Devices
The GTO/PRO 1000 series operators are equipped with built-in obstruction sensitivity. The operator is designed to stop and reverse the gate for 2 seconds when it comes in contact with an obstruction. However, obstruction sensitivity, even when properly adjusted, may not be sensitive enough to prevent bodily injury in some circumstances. To augment your protection against entrapment, GTO suggests using safety edge sensors or photoelectric sensors. When installed, safety edges (or photoelectric sensors) must be mounted in compliance with UL 325, Underwriters Laboratories safety standard for gate operators. Review page 4 for information about mounting requirements for safety edges (“contact sensors”) and photoelectric sensors (“non-contact sensors”).
Refer to the sensor manufacturer’s instructions for information about installing these devices on a vehicular gate.
Make sure the control box power switch is OFF before connecting safety device wiring to the terminal blocks.
Insert the safety device wires into the CLS EDG terminal (located on the FIRST OPERATOR terminal block) for the gate closing mode. Connect the safety device ground wire to the GRN terminal. Connect the safety device wires for the gate opening mode to the OPN EDG terminal in the same manner.
If your are installing a dual gate system, connect the safety device wires to the CLS EDG and OPN EDG terminals on the SECOND OPERATOR terminal block as described above.
MAKE SURE TO GROUND THE SAFETY DEVICES AT THE GRN TERMINAL! THE CONTROL BOARD COULD BE DAMAGED IF THE SAFETY DEVICES ARE NOT GROUNDED!

RED BLK ORG BLU GRN CLS EDG OPN EDG RED BLK ORG BLU GRN CLS EDG OPN EDG GRN ORG BLU WHT
ON

18VAC SOLAR ~~ ­ +
POWER IN FIRST OPERATOR

SEQ1 SEQ2

LEARN

R BG

SECOND OPERATOR ALARM ACCESSORY RCVR

Power Cable from First Operator
Ground Wire Wire from Close Safety Edge
or Photoelectric Sensor

Ground Wire
Wire from Open Safety Edge or Photoelectric Sensor

PLEASE NOTE: Safety edge sensors and photoelectric sensors are neither included with nor required for the GTO/PRO 1000 series gate operators.

27

Compatible Safety Devices
Although GTO strongly recommends the use of safety devices, we do not endorse any specific brand names. Below is a list of some products compatable with GTO operators systems, some of which require their own power supply. Check with the individual manufacturer for specific power needs. Only use products that are certified and listed to be in compliance with national and regional safety codes.
Safety Edges
Miller Edge, Inc. MC-22 ME-110 through 113 ME-120 ME-123 MG-020 MT-21 and 22 MU-22
Tapeswitch Corporation 101-B and BMT 102-A, B, BP, BPH 107-RS and LS 121-BP 131-A and AMT 141-BMH 191-S IL
Photoelectric Beams
Texas Optoelectronics, Inc. Industrial Photobeam
EMX Industries, Inc. IRB-4X
NOTE: This is not an exhaustive list of compatible safety devices.
28

Connecting Accessories
Make sure the control box power switch is OFF before connecting accessories.
The ACCESSORY terminal block is the connection point for accessories such as push buttons, safety loops, intercoms, etc. The ACCESSORY terminal marked GRN (green) is the common ground for all accessories. GRN is paired with the terminals shown below when connecting accessories to the control board.
IMPORTANT: Make sure to twist exposed wires tightly and insert them into the terminals without loose strands. Tighten set screws against exposed end of wires. A dab of household petroleum jelly in each terminal will help prevent corrosion.

WHT (white) used with GRN
(green):
Functions as a normally open contact. This is the most frequently used pairing for a doorbell button, keypad, or key switch.

GRN ORG BLK WHT
ON

SEQ1 SEQ2

LEARN

R BG

ALARM ACCESSORY RCVR

First contact will start the gate. Second contact will stop the gate. Third contact will reverse the gate.

Low Voltage Wire from Doorbell Button

NOTE: Never use a lighted doorbell button! It will discharge the battery and the gate operator will fail to operate.

BLU (blue) used with GRN (green):
Functions as a normally open contact. This pairing is typically used for free entry and free exit devices.
First contact will open the gate.
NOTE: If the gate is in the open position and begins to close, the activation of the accessory device will reopen the gate. In communities where the use of a emergency entry device is mandatory, it should be connected to these terminals.

GRN ORG BLU WHT
ON

SEQ1 SEQ2

LEARN

R BG

ALARM ACCESSORY RCVR

Low Voltage Wire from Entry Devices

ORG (orange) used with GRN

GRN ORG BLU WHT
ON

(green):

SEQ1 SEQ2

LEARN

Functions as a normally open contact. This pairing is frequently used for safety loops.

R BG

This connection will not open your gate. The safety loop will

ALARM ACCESSORY RCVR

activate only while the gate is in use. When using this combination,

the gate will remain open or reopen if it is closing.

Low Voltage Wire from Safety Loops

29

Post Bracket Assembly

Push to Open Installation
Determining The Mounting Position of The Post Bracket Assembly
Swinging gates shall not open into public access areas!
A “Push-to-Open” gate opens out from the property. A Push-to-Open Kit is required for this type of installation (see Accessory Catalog). If you have a pull-to-open gate (gate opens into the property), return to page 12; step 5.
The operator is installed while the gate is in the closed position.
Step PTO-1:
With the gate closed, adjust the post bracket assembly and the gate bracket until the operator is level. While holding the operator level, use C-clamps to temporarily keep these parts in their respective positions on the fence post and gate.

3/8″ x 2″ Bolt
Post Bracket Post Pivot Bracket
Post Bracket 3/8″ Washer 3/8″ Lock Washer 3/8″ Nut

Center of Gate Hinge
4 1/2″
90 o 4 1/2″
Special Post Pivot Bracket for Push-to-Open Installation
Step PTO-2:
While gate is closed, stand inside the gate next to the fence post. Using the setback template (insert) measure 4 1/2″ back from center of hinge, then make a 90º angle toward the gate and measure 4 1/2″. This is the point where either one of the holes at the end of the post pivot bracket should be. You will need to rotate the post pivot bracket or the entire post bracket assembly to align it with the square angle of the template.
NOTE: When you move the post pivot bracket, be sure one of the post bracket holes is aligned with the rest of the assembly (center hole should already have bolt through it). Flipping the Post Pivot Bracket gives more position options.
After verifying that you have complied with the 4 1/2″ x 4 1/2″ setback, insert the 5/16″ x 1 3/4″ bolt through the aligned holes of the post bracket and post pivot bracket and fasten it with the 5/16″ washer and nut.
30

Open Position Stop Extended Position (gate open)
Retracted Position (gate closed) Closed Position Stop
Round Post
Post Pivot Bracket can be moved to achieve the 4 1/2″ x 4 1/2″ dimensions.

Step PTO-3:
With the gate in the fully closed position and the operator retracted, swing the operator to the gate. Mark reference points for bolt holes on gate cross member through middle of gate bracket slots. The operator must be level. (Some vertical adjustment is possible by sliding the post bracket assembly up and down.) Drill 3/8″ holes into the gate cross member as marked. Fasten gate bracket to cross member using (2) 3/8″ x 3″ bolts, washers, lock washers and nuts. Attach the operator to the post bracket assembly and gate bracket using clevis pins, washers, and hairpins clips.

Fence Post

Gate Post and Gate Cross Member (In Closed Position)

LEVEL

Operator
LEVEL
POST PIVOT BRACKET level with the horizontal surface of the GATE BRACKET

Step PTO-4:
Make sure the control box power switch is OFF. Use a small screwdriver to move the PULL / PUSH DIP switch to PUSH. Replace control box cover. Turn power switch ON. The control board is now configured to push the gate open.
Step PTO-5:
Press the transmitter to activate the operator and determine the degree of gate opening. Initially, the operator will extend only 7″ to 8″ until it is adjusted (the maximum extension of operator is 11 1/2″).

LEVEL
PULL/PUSH SNGL/DUAL
SEQ1 SEQ2

ON 1234

OBSTRUCT SENS.

MIN

MAX

LEARN

Step PTO-6:
To increase degree of gate opening, loosen the stroke adjustment knob on the bottom of the operator housing and move it about 1/8″ toward the gate bracket (see Fig. A). Finger tighten the knob­DO NOT USE PLIERS OR OTHER TOOLS TO TIGHTEN KNOB. Press the transmitter to check your adjustment. To decrease the degree of gate opening, move the stroke adjustment knob away from the gate bracket (see Fig B).
Step PTO-7:
NOTE: Each time you adjust the knob, finger tighten it before pressing the transmitter button to check your adjustment.

Stroke Adjustment for Push-to-Open Installation
Figure A
Moving knob toward gate bracket increases gate opening.
Stroke Adjustment Knob

Moving knob away from gate bracket decreases gate opening.

Figure B

Repeat the procedure in step PTO-6 until the gate stops firmly (but not sharply) against the open position stop plate. The motor will continue to run for one-half second after the gate opens against the stop plate. If the motor continues to run for more than one second, the operator is overextended and further adjustment is necessary. If the motor strains too long against the stop plate the fuse on the control board (for the FIRST OPERATOR terminal) will be blown. This blade-style 15 ampere fuse (sold by most automotive supply stores) can be easily replaced.

NEVER use a fuse rated higher than 15 amperes! 31

Maintenance and Troubleshooting Guide

If your gate operator does not function properly after it is installed, use this guide before calling the GTO Service Department.
· On all gates weighing 250 lb. or more, routinely grease the ball bearing hinges at least 4 times a year; more frequently if the gates are near a coastal area.
· Keeping a few mothballs in the control box will discourage insects from entering it and damaging the control board.
· Clean the push-pull tube with a soft, dry cloth and apply silicone spray to it at least once per month.
If the Operator Does Not Work
Check the Green LED on the Control Board:
IF THE LED IS OFF- This condition indicates a transformer power failure.
1. Test the transformer for voltage with a voltmeter. The acceptable range can be found in the VOLTAGE LIMITS chart on the next page. If the transformer test shows no voltage, then test the electrical outlet for voltage. If the outlet test shows voltage, then the transformer is dead and must be replaced. Allow the new transformer 12 hours to charge the battery before using the gate operator.
2. If the transformer test shows voltage, check the POWER IN terminal block on the control board for voltage. If the terminal block shows no voltage, look for broken or spliced wires.
Check the Red STATUS LED on the Control Board:
IF THE LED IS ON­but the unit is not working 1. Check the battery in your transmitter and replace with a fresh one if needed. 2. Verify that the power cable is securely connected. 3. Replace the control board fuse if it is blown (15 ampere fuse only – DO NOT USE A HIGHER RATED FUSE!).
IF THE LED IS OFF­ 1. Make sure the ON / OFF switch at the bottom of the control box is set to ON. 2. Check all connections for looseness and corrosion.
IF THE LED IS FLASHING­ The system may be in a condition known as “low voltage lockout” (i.e., inadequate voltage supplied for the gate operator to function.
1. Test (using a voltmeter) the voltage output of the transformer (18.0 to 22.0 Vac) or solar panel (18.0 to 22.0 Vdc) at the control board power terminal block. A. If the voltage is low or not reading, load test the battery at a electronics store and call your dealer for a replacement battery if necessary. B. If the voltage is low or not reading, test the transformer and electrical outlet. Replace the transformer if necessary and let the battery recharge for 12 hours before using the gate operator. C. Check the control board for damage or corroded connections. D. Make sure that telephone or solid core wire is not being used to connect the transformer to the control board.
32

If the Operator is Working
The Gate CLOSES Then Opens Again on its Own:
1. Check the position of the mounting brackets and readjust if necessary. 2. Check the gate for binding or hinge damage. 3. Check the position of the stroke adjustment knob.
The Gate OPENS Then Closes Again on its Own:
1. Check the position of the mounting brackets and readjust if necessary. 2. Check the gate for binding or hinge damage. 3. Check the position of the stroke adjustment knob.
VOLTAGE LIMIT CHART 18 Vac Transformer __ 18.0 to 22.0 Vac 5 W Solar panel (single) _ 18.0 to 22.0 Vdc 300 mA
measure voltage at panel and control box. 12 V Battery ____ 12.0 to 13.5 Vdc 7.0 Ah Charging circuit ___
12.0 to 14.8 Vdc
measure voltage with battery connected
The GTO, Inc. Technical Service Department is open Monday ­ Thursday 7:30 A.M. ­ 5:30 P.M.
and Friday 8:00 A.M. ­ 12:00 P.M. (Eastern Time)
Telephone 800-543-1236 Telephone 850-575-4144
Fax 850-575-8950 · Web site: www.gtoinc.com E-Mail: [email protected]
33

Warranty and Repair Service
If the GTO gate operator system is not operating properly, please follow the steps below:
1. First, check the Troubleshooting Guide (see page 32).
2. Call your dealer or installer for assistance.
3. If your dealer or installer is unable to resolve the problem, call the GTO Service Department at 850-575-4144 to discuss the problem with a service technician. Refer to the serial number (located on the control box cover) and date of purchase when calling for assistance.
4. If repair or replacement is necessary, you will be assigned a Return Goods Authorization Number (RGA).
5. Carefully pack the component(s) authorized for return and ship freight prepaid to: GTO, Inc., 3121 Hartsfield Road, Tallahassee, Florida, USA 32303.
NOTE: GTO products returned without an RGA Number (on the outside of package in LARGE BOLD PRINT) or shipped freight collect WILL NOT be accepted by the factory.
6. If the repair service or replacement is covered by warranty, GTO, Inc. will pay shipping costs (equal to United Parcel Service ground rate) for return to owner.
®
AUTOMATIC GATE OPERATORS

Limited Two Year Warranty

GTO/PRO 1000 series automatic gate operators are warranted by the manufacturer against defects in materials and manufacturer workmanship for a period of two (2) years from the date of purchase, provided recommended installation procedures have been followed.
In the case of product failure due to defective material or manufacturer workmanship within the two (2) year warranty period, the operator will be repaired or replaced (at the manufacturer’s option) at no charge to the customer, if returned freight prepaid to GTO, Inc., 3121 Hartsfield Road, Tallahassee, Florida, USA 32303. IMPORTANT: Call 850-575-4144 or Fax 850-575-8950 for a Return Goods Authorization (RGA) number before returning to factory. Products received at the factory without an RGA number will not be accepted. Replacement or repaired parts are covered by this warranty for the remainder of the two (2) year warranty period or six (6) months, whichever is greater. GTO will pay the shipping charges (equal to United Parcel Service ground rate) for return to the owner of items repaired under warranty.
The manufacturer will not be responsible for any charges or damages incurred in the removal of the defective parts for repair, or for the reinstallation of those parts after repair. This warranty shall be considered void if damage to the product(s) was due to improper installation or use, tampering, connection to an improper power source, or if damage was caused by lightning, wind, fire, flood, insects or other natural agent. This warranty gives you specific legal rights, and you may also have other rights which may vary from state to state. This warranty is in lieu of all other warranties, expressed or implied. NOTE: Verification of the warranty period requires copies of receipts or other proof of purchase. Please retain these records.
After the two (2) year warranty period has expired, GTO or one of its authorized service centers will make necessary repairs for a nominal fee. Call GTO at 850-575-4144 for more information.
34

Column Installation Information
READ THE FOLLOWING CAREFULLY BEFORE INSTALLING THE GTO/PRO 1000 AND GTO/PRO 1200 ON GATES THAT ARE MOUNTED ON COLUMNS MADE OF MASONRY, BRICK, ROCK, etc.
Attaching a gate operator to a gate mounted on a masonry column requires special procedures. Here’s how to check your installation to minimize problems:
Open the gate to the 90º position, then measure the distance between the back of the gate and the face of the column. If there is at least a 6 1/4″ clearance, you may not have to make any special modifications. However, you must measure the post pivot bracket position using 4 1/2″ x 4 1/2″ setback, as described on page 13 of this manual, to verify that the gate hinge sits far enough from the column to give your installation the proper setback distance. If you do not have the proper clearance or setback distance, the operator may operate the gate for a while, but eventually the unit will become nonfunctional. To prevent this problem, we suggest the following installation method: A. The simplest solution is to install the operator in a push-to-open configuration (push-to-open bracket(s) are required; see accessories on page 43). The crucial 4 1/2″ setback is actually easier to achieve this way and clearance is no longer a problem, since the operator will be pushing the gate away from the column instead of pulling it toward the column. It is recommended that you place a steel plate between the operator mounting brackets and masonry surface for additional strength. B. If a push-to-open option is impossible due to traffic hazards, terrain, etc., another option is to re-hang the gate. You might hang it on a post, either in the center of the column or at the back corner, or move the gate to the back corner of the columns. C. The most difficult solution is to notch a pocket in the column to accommodate the operator and power cable. This is not a job for the inexperienced!
35

GTO/PRO Dual Gate System Installation
Second Unit Parts List

GTO Operator (1)

Post Pivot Bracket (1) Gate Bracket (1)

® AUTOMATIC GATE OPENERS
25′ Power Cable (1)

Closed Position Stop Plate (1)
8″ Nylon Cable Tie (6)

Strain Relief (1) Customer Support Card (1)
Post Bracket (2)
Hardware (Actual Size)

3/8″ x 8″ Bolt (4) 3/8″ x 3″ Bolt (2) 3/8″ x 2″ Bolt (1) 5/16″ x 1-3/4″ Bolt (1) 3/8″ x 1-1/8″ Clevis Pin (2)
Hairpin Clip (2)

3/8″ Washer (9) 3/8″ Lock Washer (7)
5/16″ Washer (1) 3/8″ Nut (7) 5/16″ Nut (1)
36

Installing the Second Unit
The diagram below is of a dual gate, pull-to-open (open-in) installation on a chain link fence and gates. “Pull-to-Open” dual gates open into the driveway. If you are installing a “Push-to-Open” gate system see “Pushto-Open Installation” starting on page 30.

Receiver

Gate Swings Evenly and Freely Hung Firmly and Plumb

Control Box with Battery
120 Volt Indoor Transformer
(surge protector not supplied)

Post Bracket Assembly First Gate Operator

Second Gate Operator

Gate Bracket Power Cable

Closed Position Positive Stop Plates

Concrete Poured Around Gate Post

Run 1000′ (max.) of low voltage wire to control box from transformer (wire not included).
Step D-1:

PVC conduit (not included)

Second Operator Power Cable

to protect from lawn

low voltage wire mowers and weed

eaters.

in

PVCIlcloundsutirt (anottiioncnludBed)

Turn back to page 11 and repeat Steps 1 through 11 to install the second unit.

Step D-2:
Install open position stops for both gates. See Step 12, page 16.

Step D-3:
Remove the hairpin clips, clevis pins, and washers from the operators and close the gates. Install the closed position stop plate on the gate that you want to close second. Extend the stop plate to make contact with the leading edge of the other gate.

Step D-4:
A dual gate system requires a closed position positive stop for the gate that closes first. Install a closed position positive stop in driveway directly below the gate (see illustration at right).

Gate Hinge

Ground Stop
(beneath gate)

Gate Hinge

Closed Position
Stop Plates

The gate leaf must open
80° (min.) to 110° (max.)

The gate leaf must open
80° (min.) to 110° (max.)

Open Position Stop

Wood, metal, or concrete
post set in concrete.

Open Position Stop

37

Step D-5:
Attach the closed position stop plate vertically to the inside bottom of the gate that will close first. When the gate is in closed position, the positive stop plate should rest against the ground stop installed in Step D-4.

Mount Vertically

Closed Position Stop Plate mounted
on the gate leaf that CLOSES FIRST

FRONT VIEW

SIDE VIEW
Closed Position Stop Plate

Low Profile Ground Stop
in Center of Driveway

Connecting the Second Operator to the Control Board
Step D-6:
Turn power switch OFF. Remove the control box cover. Using a steel punch or screwdriver, remove the thin plastic knockout in the second operator connector hole at the bottom of the control box. Work from the inside out to avoid damaging the control board.

RED BLK ORG
BLU GRN CLS EDG
OPN EDG RED BLK ORG BLU GRN CLS EDG OPN EDG GRN ORG BLU WHT
Strain Relief

+ BATT ­

PWR. SW.

STATUS

CAULOTOSE INERTIA SOEBNSST.R.

LEARN R GB

18~VAC~ SO­ LA+R

POWER IN

FIRST OPERATOR

SECOND OPERATOR

ALARM

ACCESSORY

RCVR

Lock Nut Hub Sealing Nut
Lock Nut

Hub Sealing Nut
First Operator Power Cable Second Operator Power Cable

Step D-7:
Insert the strain relief into the knockout hole and finger tighten it in the control box. Insert the stripped end of second operator cable up through bottom of strain relief (if necessary, loosen the strain relief). Pull approximately 4″ of wire into the control box and retighten the strain relief on the black sheath of the power cable.

18VAC SOLAR ~~ ­ +

RED BLK ORG BLU GRN CLS EDG OPN EDG RED BLK ORG BLU GRN CLS EDG OPN EDG GRN ORG BLU WHT
ON

SEQ1 SEQ2

LEARN

R BG

POWER IN FIRST OPERATOR

SECOND OPERATOR ALARM ACCESSORY RCVR

RED BLACK ORANGE BLUE GREEN RED BLACK ORANGE BLUE GREEN

Low Voltage Wire from AC Transformer

Power Cable

Power Cable

from First Operator from Second Operator

38

Step D-8:
Insert the stripped power cable wires into the appropriate terminal on the SECOND OPERATOR terminal block. The green wire should be inserted into the GRN terminal, the blue wire into BLU, the orange wire into ORG, black wire into BLK, and the red wire into the RED terminal.
Tighten the set screws against the stripped end of the wires. A dab of petroleum jelly on each terminal will help prevent corrosion.

Step D-9:
Cut slot into driveway and lay PVC conduit in this slot. Pull the 25 foot power cable for the second operator through the conduit (see Illustration B on page 37).
® AUTOMATIC GATE OPENERS

Step D-10:
Carefully insert the power cable plug into the coupling at the bottom of the operator housing. Turn the plug until it aligns with the pins in the operator coupling. Tighten the sleeve nut to lock the plug into place.
NOTE: DO NOT attempt to splice the power cable, and DO NOT remove the connector from the end of the cable. If you need a longer cable, 35 foot and 40 foot power cables are available (see Accessory Catalog).
Setting the Control Board for Dual Gate Installations
DIP Switches
The Control Board DIP switches must be set to accommodate your particular type of installation. Since the SNGL / DUAL, SEQ1, and SEQ2 DIP switches are used by dual gate operator systems, they will be discussed in the following steps.

Step D-11:
Make sure the control box power switch is OFF.
Step D-12:
Unscrew and remove the control box cover. Use a small screwdriver to move the SNGL / DUAL DIP switch to DUAL (see illustration).
The order of gate operation (“sequencing”) must now be determined for your dual gate operators to function properly.
Refer to the illustrations on the next page.
NOTE: The terms “FIRST OPERATOR” and “SECOND OPERATOR” refer to a unit wired to the terminal block of the same name.
39

PULL/PUSH SNGL/DUAL
SEQ1 SEQ2

ON 1234

OBSTRUCT SENS.

MIN

MAX

LEARN

Step D-13
BOTH OPERATORS OPEN SIMULTANEOUSLY BOTH OPERATORS CLOSE SIMULTANEOUSLY SEQ1 = ON SEQ2 = OFF If SEQ1 is set to ON, and SEQ2 is set to OFF, the FIRST OPERATOR and SECOND OPERATOR open and close simultaneously.
FIRST OPERATOR OPENS FIRST, SECOND OPERATOR CLOSES FIRST SEQ1 = OFF SEQ2 = ON If SEQ1 is set to OFF, and SEQ2 is set to ON, the FIRST OPERATOR will open first, and the SECOND OPERATOR will close first (see illustration).
FIRST OPERATOR OPENS FIRST, FIRST OPERATOR CLOSES FIRST SEQ1 = ON SEQ2 = ON If SEQ1 is set to ON, and SEQ2 is set to ON, The FIRST OPERATOR opens and closes first.

PULL/PUSH SNGL/DUAL
SEQ1 SEQ2

ON 1234

OBSTRUCT SENS.

MIN

MAX

LEARN

PULL/PUSH SNGL/DUAL
SEQ1 SEQ2

ON 1234

OBSTRUCT SENS.

MIN

MAX

LEARN

PULL/PUSH SNGL/DUAL
SEQ1 SEQ2

ON 1234

OBSTRUCT SENS.

MIN

MAX

LEARN

BOTH OPERATORS OPEN SIMULTANEOUSLY SECOND OPERATOR CLOSES FIRST

SEQ1 = OFF SEQ2 = OFF
If both SEQ1 and SEQ2 are set to OFF, the FIRST OPERATOR and SECOND OPERATOR open simultaneously. The SECOND OPERATOR will close first.

PULL/PUSH SNGL/DUAL
SEQ1 SEQ2

STEP D-14
Replace the control box cover. Turn the control box power switch ON and allow the control board 15 seconds to energize. Set the closed gate positions for the first and second operators (review step 18 on page 19).

Your automatic gate operator system is configured for dual pull-to-open gates.

40

ON 1234

OBSTRUCT SENS.

MIN

MAX

LEARN

®
AUTOMATIC GATE OPERATORS
Accessories from GTO, Inc.
Available through your dealer.
41

Accessories Available Through Your Dealer

1 23 4 56 789
0

GTO Digital Keypad (F300) The weatherproof digital keypad can be easily installed as a wired or wireless keypad for all GTO swing and slide gate operators, and as a wired keypad for the Bulldog Pedestrian Gate Lock. It can be programmed to recognize fifteen different personal identification number (PIN) codes. Each code is face programmable with additional security features built in. Requires 3 AA batteries (not included). Can also accommodate most garage doors and other gate openers. If used as a wired keypad, 16 gauge standard, low voltage direct burial wire will be required (see RB509).

MORDEECLUEN2I9VIHV4EEERDRDSAOLLF

Garage Door Receiver (RB709) Allows the use of the same GTO remote transmitter (see Dual and Triple Transmitters) to control the gate operator and garage door opener. Compatible with most garage door openers.

®

SECURITY GATE LOCK

, Inc.

GTO Entry Transmitter (RB741) The GTO Entry Transmitter, with adjustable code settings, is standard equipment with all GTO gate operator systems. Battery included.
GTO Dual Transmitter (RB742) GTO Triple Transmitter (RB743) The two and three button transmitters are used for the remote control of two or three gate operators and garage door openers (See Garage Door Receiver). Battery included.

GTO Key Chain Mini Transmitter (RB744) This miniature version of the GTO entry transmitter has the same adjustable code settings. Battery included.
Push Button (Doorbell) Control (RB101) Unlighted doorbell button for remote entry or exit control. Connects directly to the control board using 16 gauge stranded, low voltage, direct burial wire (not included, see RB 509).

ELECTRONGAICUASTTECEOURMLITOAY LCTOICKCK ®

GTO Automatic Gate Lock (FM144) for closed position pull-to-open applications A MUST for added security. The plated steel bolt lock has a zinc plated steel housing and is driven by a 4 ampere solenoid. This horizontal electronic lock is used with all GTO low voltage swing gate operator systems (not to be used with GTO/PRO AC powered operators) for additional security and stability. Comes with a keyed manual release.
GTO Automatic Gate Lock (FM142) for open position or push-to-open applications Similar to FM144, but used to secure gates in the open position or for push- to-open gate applications (not shown).
GTO Bulldog Pedestrian Gate Lock (FM500) Similar to the Automatic Gate Lock but designed for horizontal use only on “walk-through” gates without automatic operators. The Bulldog is an affordable solution to protecting swimming pool areas, playgrounds, tennis courts, boat docks, etc., from unwanted access. Includes control box and keyed manual release. Can be used with the GTO Digital Keypad (F300).

GTO Exit Wand (FM138) The GTO Exit Wand is designed for residential and agricultural applications and is compatible with all the GTO/PRO automatic gate opener models. The Exit Wand is an electromagnetic sensor, which offers ‘hands free’ operation of automatic gate openers with a 12 ft. radius of detection of vehicles in motion.

42

ACCESS-ories
Column Mount Lock Receiver (433IH) For mounting the Automatic Gate Lock or Bulldog Pedestrian Lock in areas with limited space between the gate and post, such as brick columns or walls.
Column Mount Bracket (349IH) For column installation of the GTO/ PRO 1000 series operators. Designed for mounting the Post Pivot Bracket on masonry columns or any flat surface. Two Brackets are required for each operator.
Push To Open Bracket (348IH) Required when GTO/PRO 1000 series gate operator(s) must push the gate open, such as on a sloping driveway or where space prevents gate(s) from opening inward (pulled open). Order two PTO brackets for conversion of a dual swing gate installation.
Splice Kit – Above Ground (RB707) For providing secure and moisture resistant above ground splices for solar panels, key pads, push buttons and other accessories using GTO low voltage wire. Splice Kit – Direct Burial (RB708) When direct burial wire running below ground needs to be spliced the RB708 splice kit must be used.
Replacement Receivers The AQ201: Receiver with a 10 ft. cable (included). The AWQ325: Receiver with a 25 ft. cable. The AWQ350: Receiver with a 50 ft. cable. The AWQ400: Receiver with a 100 ft. cable.

Master® Pin Lock (RB975) for GTO/PRO 1000/1200 Master® Pin Lock (FM320) for GTO/PRO 2000/2200
The pin lock is a substitute for the clevis pin at either or both mounting points of the GTO/PRO 1000 operator arms and the gate bracket end of the GTO/PRO 2000. They help prevent theft of the operator arm while allowing quick release of the operator when necessary.
GTO Low Voltage Wire (RB509) The 16 gauge dual conductor, multistranded, direct burial low voltage wire is required to connect the control board to the solar panel or the AC transformer. This wire is also required for installation of some accessories such as keypads, locks, or push buttons (available in 1000′ rolls and specially cut lengths).

Standard Replacement Power Cables for Gate Operators The PRO 4.5C (AW201): 4.5 ft. power cable included with GTO/PRO 1000 gate operators with serial numbers. The PRO 25C (AW202): 25 ft. power cable included with GTO/PRO 1000/1200 gate operators with serial numbers. The PRO 40C (AC109): 40 ft. power cable for GTO/PRO 1000 series operators.

43

ACCESS -ories
Operator Solar Panel (FM123 ) – Improved, Amorphous Silicon This 10 watt solar panel is a battery charger for use with GTO/PRO Low Voltage Automatic Gate Operator systems. Particularly suited for remote installations, the solar panel comes with tubular steel support, mounting clips, wire connectors, and 8 ft. of low voltage wire (for longer lengths, see RB509). All GTO low voltage operators are pre-wired for solar panels. Installation in some regions of the world will require multiple panels for adequate charging power. Recommended for GTO/PRO 2000/2200, GTO/PRO SL-1000/SL-1200.
Operator Solar Panel (FM122 ) – Improved Amorphous Silicon The 5 watt solar panel is a battery charger for use with GTO/PRO Low Voltage Automatic Gate Operator systems. Particularly suited for remote installations, the solar panel comes with tubular steel support, mounting clips, wire connectors, and 8 ft. of low voltage wire (see Low Voltage Wire for longer wire). All GTO low volatge operators are pre-wired for solar panels. Installation in some regions of the world will require multiple panels for adequate charging power. Recommended for GTO/PRO 1000, GTO/PRO 1200 and the GTO Bulldog Gate Lock.
Dual gate installations require minimum of two (2) 5 watt solar panels for adequate charging power.
Transformers for charging the gate operator battery RB566 ­ Standard 18 volt, 20 VA, AC transformer for GTO/PRO 1000 series gate operators with serial numbers.
Bulldog Replacement Charger RB421 ­ Standard 12 volt DC charger (not shown) for maintaining battery included with the Bulldog Pedestrian Gate Lock.
Replacement Batteries RB500 ­ The standard 12 volt, 7.0 ampere-hour, maintenance-free battery for all GTO/PRO gate operators. This is the only battery approved for use with GTO gate operators. Battery life 3 to 5 years.
RB422 ­The 12 volt, 1.2 ampere-hour version for use with the Bulldog Pedestrian Gate Lock.
26 Amp Hour Battery Kit (FB296) This large 12 volt, 26 ampere-hour, maintenance-free battery is for the GTO/PRO gate operators. It will supply additional power for increasing the number of open and close cycles. The kit comes with the battery and wiring harness for easy installation. Battery life 3 to 5 years.
GTO NEMA Box (FM317) GTO’s NEMA 4X rated weatherproof box is large enough (14″ W x 6″ D x 16″ H) to accommodate all add-on items necessary for custom gate operator installations. It is made of fire retardant ABS plastic and comes with a heavy duty 14 gauge steel backing plate for mounting accessories. The unique, lockable cover (use the Master® Pin lock RB975 for added security) can be completely removed for easier access during installation and service.
The NEMA box is standard on all GTO/PRO AC powered operators.
GTO, Inc. gate operator accessories are warranted by the manufacturer against defects in materials and workmanship for a period of one year, unless otherwise stated, from the date of purchase provided recommended installation procedures have been followed. Warranty is considered void if damage was due to improper installation or use, connection to an improper power source, or was caused by lightning, wind, fire, flood, insects, or other natural agent.
44

Installation Check List
The installation of this operator conforms to CLASS __. The installer verifies that (each item except safety edges must be checked):
Recommended safety edges were installed. Customer was informed that this gate is for vehicular use ONLY. Pedestrians MAY NOT use this gate. A separate gate or entrance was installed for pedestrian use. Closed position stop plate was securely fastened. The position of the post bracket assembly complies with the 4 1/2″ x 4 1/2″ setback requirement. All power cables, receiver cables, and transformer plugs were securely fastened. Petroleum jelly was applied to the control board terminals. All warning signs and labels were installed as specified in the IMPORTANT SAFETY INSTRUCTIONS. Safety instructions were reviewed with the customer. A copy of the IMPORTANT SAFETY INSTRUCTIONS was given to the customer. Customer was instructed about disconnecting the operator for manual operation of the gate. Customer was instructed about proper use of transmitter and (or) other entry controls. Customer was asked to fill out customer support card and mail it to GTO, Inc. Customer was asked to retain all receipts (receipts provide proof of warranty). Customer was asked to retain IMPORTANT SAFETY INSTRUCTIONS, etc. for future reference. The completed installation was photographed from both the front and back of the gate. Photo was dated.

Customer’s Signature

Date

Installer’s Signature

Date

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GTO User Manuals

Related Manuals