AIR TREATMENT SYSTEM
US patent #7,704,463
APCO-X Ultra Air Treatment System
APCO-X Ultra reduces odors (VOCs) and biological contaminants such as mold, bacteria, viruses, and allergens in indoor air. The system is installed in the duct work of the central air system. The award-winning design of APCO-X Ultra uses a unique combination of UVC light and activated carbon cells to clean the air.
IMPORTANT!
- Only qualified technicians should install this product*
- Install in accordance with relevant building codes
- Read instructions carefully including safety warnings
WARNING!
PROTECT EYES FROM UV LIGHT TURN OFF UNIT OR DISCONNECT BEFORE SERVICING
LIT-FAUV-APCO-XU-MAN 010424
*Installation of this product by anyone other than licensed HVAC or electrical contractors voids warranty.
Parts
Installation Notes
APCO-X Ultra is usually installed on the supply side ductjust above the air
system (upstream of a humidifier if there is one) but can also be installed on
the return side if necessary.
The main unit should be oriented so that the air flows past the UV Light first
then into the Matrix Element. Position the main unit so the UV light does not
shine directly on non-uv-resistant materials (filters, humidifiers, flex duct,
etc) and if possible orient it so UV light shines on the cooling coil.
When installing a dual system (a second remote UV Lamp) select a location
inside the air system that will allow it to shine on the greatest surface area
or the area with the most evident microbial growth. To install the secondary
UV light use the Secondary UV Light Installation Instructions on the next
page.
LED Status Indicator
SOLID BLUE = Normal Operation
FLASHING BLUE = Replace UV Lamp
FLASHING RED = UV Lamp Expired
SOLID RED = UV Lamp Failure
Duct Mounting
-
Use gasket to trace cut-line onto duct.
-
Cut hole in sheet metal or duct board.
IMPORTANT! Remove and dispose of cut-out piece of material. -
For sheet metal duct secure mounting plate with Self-tapping Screws J .*
-
Remove paper backing from one side of gasket and fix gasket to the back of the mounting plate.
-
Remove paper backing from back of gasket then fix mounting plate and gasket to the duct.
-
Bend mounting plate flanges around the edges of the hole to secure mounting plate. For duct board use tape on edges of mounting plate for air leaks and additional hold.
- If the backing plate can’t be used install directly with 4 Self-tapping Screws J .
Attach Power Unit to Duct & Mount UV Lamp
-
Fit the Main Unit through hole in duct. If attaching directly to metal duct use 4 Self-tapping Screws J .
If the Backing Plate is used fit the unit over the threaded posts and use 4 Quick Nuts H to secure it. -
Insert UV Lamp.
-
Mount UV Lamp using 2 Quick Nuts H and attach lamp connector (be sure to align the four connector pins).
-
Rotate the cover so it is oriented correctly then attach with thumb screws.
Electrical Configration
IMPORTANT
Before connecting to power determine if the transformer is needed. Turn off
main power source before installation. Always wire according to local and
national electrical codes.
IMPORTANT! Must be wired to constant power – do not connect to blower
relay.
DIRECT TO HVAC PANEL
Power Cord G is connected directly to 18-32V constant power terminals in HVAC
system control panel.
USE TRANSFORMER
Power Cord G wires are spliced to Transformer L 24V leads after Transformer
has been connected to a high voltage source (see installation instructions
included with transformer).
Lamp Replacement
Replace the UV lamp in APCO-X Ultra (model TUVL- 315) every 3 years. Note: UV lamps will continue to emit visible light but lose germicidal effectiveness over time.
CAUTION!
UV lamps contain small amounts of mercury – dispose of lamps in accordance
with local environmental regulations. For more information visit
www.lamprecycle.org
Note: Use of replacement UV lamps other than TUVL- 315 voids warranty.
Replacement Lamp Timer Set
- With the Power Head in hand connect power without the lamp installed.
- For lamp replacement hold the timer set button for 5 seconds to enter timer mode. The LED will flash purple once indicating timer mode.
- Within 5 seconds press the timer set button once, twice or thrice. LEDs will flash 1, 2, or 3 times indicating numbers of years set.
Secondary UV Light Installation(Dual Systems)
The Secondary UV Light (included with APCO-X Ultra Dual) is typically
installed at the coil for enhanced germicidal effectiveness, reduced system
maintenance, and improved indoor air quality.
IMPORTANT!
- Dual System lamps are wired in series – connect both for lamps to light
- Only qualified technicians should install this product
- Install in accordance with relevant building codes
- Read instructions carefully including safety warnings
Installation Notes
Before installing the Secondary UV Light it is necessary to determine the
optimal mounting location inside the air system. First, look for the area with
the heaviest mold growth. Also consider a location that will allow the
germicidal UV Light to shine on the greatest surface area.
Some typical mounting locations:
a Across top of coils
b Coil “A” plate
c Return-side duct
WARNING
PROTECT EYES FROM UV LIGHT TURN OFF UNIT OR DISCONNECT BEFORE SERVICING
Important: Some materials inside the air system (including filter media, flex duct, wiring etc) may not be UV light resistant. Use the optional UV shield (part #TUV-SHIELD-LPC) or cover the materials with reflective tape.
Air Handler Interior Surface Installation
- Determine the optimal position for placement of the UV Lamp.
- Use a utility knife to cut a slit in the insulation on the interior surface.
- Place the magnetic “Z” bracket N directly on the metal surface or remove the magnet and hard-mount the bracket using the Self-tapping Screws J provided. Use foil tape to close the cut in the insulation.
- Use plastic Quick-Nuts to attach the UV lamp to the “Z” bracket as shown.
Coil “A” plate or Duct Installation
- Snap the magnet bracket N apart by bending.
- Drill a 1” hole in the “A”-plate or duct then attach the smaller piece of the bracket with Self-tapping Screws J .
- Insert the UV lamp into the hole then use the plastic Quick-Nuts to attach the UV Lamp to the magnet bracket as shown.
Remote UV Light Configuration
IMPORTANT! Only Dual System models have the electrical capacity and attached
cable to power the Secondary UV Light.
Find the secondary lamp cable on the right underside of the Dual System Main
Unit.
Drill a 1” hole in the air system housing then pass the lamp cable through the
hole. The hole is then sealed with the rubber grommet to minimize air leakage.
Sight Glass Installation
- Find a suitable location on the outside of the duct-work near the UV Lamp installation and apply the warning/lamp replacement sticker K .
- Drill a ½” hole through the circle on the sticker. Press the sight glass I into hole.
- Turn on the power and use the sight glass to confirm that the UV Lamp is operating.
Lamp Replacement
The second germicidal UV Lamp M should be replaced every three years along
with the primary lamp.
Note: UV lamps may continue to emit visible light after three years,
however, germicidal effectiveness falls off over time and will quickly drop to
near zero after three years.
CAUTION!
UV lamps contain small amounts of mercury – dispose of lamps in accordance
with local environmental regulations. For more information visit
www.lamprecycle.org
Note: Note: Use of replacement UV lamps other than TUVL- 315, TUVL- 215,
or TUVL- 115 voids warranty.