hager TXC513 Presence Detector Instruction Manual

June 13, 2024
hager

6LE007293A
TXC513 Presence Detector
Instruction Manual

TXC513 Presence Detector

hager TXC513 Presence Detectorhager TXC513
Presence Detector - Symbol

TXD503
Presence detector/motion detector 360° built-in
Rilevatore di presenza/rilevatore dimovimento KNX 360° da incasso

Safety instructions

Electrical equipment must only be installed and assembled by a qualified electrician in accordance with the relevant installation standards, regulations, directives and safety and accident prevention directives of the country.
Failure to comply with these installation instructions may result in damage to the device, fire or other hazards.
Due to its detection behaviour, the device is not suitable for use in burglary detection or alarm systems.
These instructions are an integral component of the product and must be retained by the end user.

Design and layout of the device
(Figure 1/2)hager TXC513 Presence Detector - Design and layout of the
device

(1) Slot for bus connecting terminals
(2) Security screw fixing point
(3) Unlocking opening
(4) Securing clips
(5) Detector lens with integrated status LED red/ green| (6) Response brightness potentiometer
(7) Delay time potentiometer
(8) Potentiometer cover
(9) Security screw
(10) Fixing springs
(11) Cover for connection department
---|---

Function

Correct use

  • Automatic transmission of switching commands for lighting and scene control via the KNX bus dependent on heat motion and ambient brightness
  • Manual control of KNX functions via remote control (optional, see Accessories)
  • TXD503: Cavity installation
  • TXC513: Surface-mounted installation or installation on mounting boxes according to valid standard (e.g. DIN 4907)

Product characteristics

  • Combination of presence and motion detector with enhanced detection sensitivity in the central presence-detection area
  • Response brightness adjustable
  • Delay time adjustable
  • Master/Slave operation can be parameterised via ETS
  • Optional: Operation modes automatic/semiautomatic are adjustable via IR configuration handheld controller (see Accessories)
  • Test mode

Behaviour during operation
The motion detector detects heat motion caused by people, animals, or objects in accordance with IEC 63180.

  • Will be switched on for the delay time if movements are detected in the detection area and the set light level is undershot. Each detected movement restarts the delay time.
  • Will be switched off if no additional movements are detected in the detection area and the set delay time has elapsed or the set light level is exceeded.

Information for electricians

Installation and electrical connection

DANGER!
Electrical shock when live parts are touched!
An electric shock can lead to death!
Isolate all power before working on the device and cover any live parts in the area!

Selecting installation location
The motion detector must be installed horizontally on the ceiling. It has a detection angle of 360°. The diameter of the detection area depends on the installation height.
At an installation height of 2.5 m, the diameter at ground level is approx. 20 m. The diameter of the inner detection area with enhanced detection sensitivity is 10 m (Figure 3).
hager TXC513 Presence Detector - height greater

At an installation height greater than 2.5 m, the detection area increases. At the same time, the detection sensitivity decreases.
Observe the motion orientation: A distinction is made between “direct approach” and “transverse motion”. Motions transverse to the motion detector can be detected better than motions toward the motion detector (Figure 3).
The device must be completely installed and closed to meet the degree of protection IP41.

  • If used as a presence detector, the device must be installed so that areas with less motion activity (desk, seating area) are within the detection area (Figure 3).

  • Avoid sources of interference in the detection area. Sources of interference, e.g. heating elements, ventilation systems, air conditioners and lamps that are cooling down can cause undesired switching (Figure 4).
    hager TXC513 Presence Detector - undesired switching

  • Select an installation location that is free of vibration. Vibrations can cause undesired switching.

Connecting and installing the built-in variant TXD503 (figure 6)hager
TXC513 Presence Detector - Connecting and installing the built-in
variant

  • Establish installation opening Ø 68 mm.
  • Connect the bus cable.
  • Close cover (11).
  • Insert the two fixing springs (10) through the installation aperture while pressing upwards and allow them to spring back.

Connecting and installing the surface-mounted variant TXC513 (figure 5)hager TXC513 Presence Detector - Connecting and installing the surface-
mounted

  • Feed the connection cable through the cable entry cut-out (13).
  • Install device base under the ceiling using appropriate fixings, a screw & plug set is included. If available, install device socket in a flush-mounted box.
  • Connect the bus cable.
  • Snap device module onto base.
  • Screw in security screw (9).
  • Close cover (8).

Commissioning

The device is in warm-up phase after bus voltage recovery (up to 45s). During this time the status LED is flashing green.

Testing the detection
In test mode, the motion detector works with maximum response brightness. If movement is detected the red LED flashes briefly.

  • Set the potentiometer response brightness (6) to the Test position (figure1/2). The device is in test mode.
  • Carry out test by moving in the detection area.

If the motion detector switches on without motion in the detection area, then sources of interference are present (see Installation location).
After 2 minutes in test mode the device is automatically set to the standard values (500 Lux).

Setting the response brightness
The response brightness is the brightness value saved in the motion detector; when this value is undershot the connected load is switched on if movements are detected. The brightness threshold can be set continuously between approx. 5 and 2000 Lux (daytime operation/brightness-independent).

  • Turn the response brightness potentiometer (6) to the desired position.

Setting the delay time
The delay time is the period of time set in the motion detector which is the shortest time that the lighting is switched on when the light level is undershot and motion is detected.
The delay time can be set between pulse and approx. 5 s to 60 min.

  • Turn the delay time potentiometer (7) to the desired position.

Commissioning with the IR configuration handheld controller
The IR configuration hand-held transmitter can be used to change the values set directly on the device (see Accessories) if the setting has been enabled in the ETS.
A detailed description of the EE807 hand-held controller can be found in the enclosed instructions.

Operation by IR hand-held controller
The IR hand-held transmitter can be used to trigger the actions parameterized with the device.
A detailed description of the EE808 hand-held controller can be found in the corresponding instructions.

Adjusting the detection area
If the detection area of the detector is too wide or covers areas that should not be monitored, the adhesive strips provided can restrict the detection area if required.

system link Loading the physical address and application software
Project planning and commissioning with ETS 5 or newer.
The device is connected and ready for operation.

  • Remove cover (8) if there is one.
  • Set potentiometer delay time (6) Adr/On.
  • Status LED (5) lights up red.
  • Load the physical address into the device.
  • Label the device with the physical address.
  • Load the application software into the device.
  • After completion of the loading process or to cancel, adjust potentiometer delay time. The status LED (5) goes out.
  • Snap on cover

easy link:
Information on the system configuration can be taken from the extensive description of the service module easy link.

Appendix

Technical data

KNX medium TP 1
Configuration mode S-Mode, E-Controller
Rated voltage KNX 30 V SELV
Current consumption KNX  max. 10 mA
Connection mode KNX bus connecting terminal
Response brightness approx. 5 … 2000 Lux
Delay time 5 s … 60 min
Detection angle 360°
Recommended installation height 2.5 m … 3.5 m
Maximum installation height 4 m
Detection area Ø motion (installation height 2.5 m)
transverse motion towards detector ~ 20 m
approach detector ~ 10 m
Detection area Ø presence (Installation height 2.5 m) ~ 10 m
Degree of protection IP41
Ambient temperature  -5 … +45 °C
Storage/transport temperature -20 … +70 °C
Protection class II
Impact resistance IK 04
Operating altitude < 2000 m
Dimensions TXD503 (Ø x H) 85 x 75.8 mm
Dimensions TXC513 (Ø x H) 105 x 61.3 mm

Accessories

IR configuration hand-held transmitter EE807
IR hand-held transmitter EE808

Correct Disposal of this product (Waste Electrical & Electronic Equipment) (Applicable in the European Union and other European countries with separate collection systems).
This marking shown on the product or its literature indicates that it should not be disposed of with other household waste at the end of its working life. To prevent possible harm to the environment or human health from uncontrolled waste disposal, please separate this device from other types of waste. Recycle the device responsibly to promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or their local government office, for details of where and how they can take this device for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This product should not be mixed with other commercial waste for disposal.

Hager Controls, BP10140, 67703 SAVERNE CEDEX, FRANCE
T +33 (0) 3 88 02 87 00
info@hager.com
hager.com – 06.2022

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals