HITACHI RAM-280FSPH Inverter Driven Multi-Split System Air Conditioner Instruction Manual
- June 13, 2024
- Hitachi
Table of Contents
RAM-280FSPH Inverter Driven Multi-Split System Air Conditioner
Product Information
The product is an inverter-driven multi-split system air
conditioner. It consists of outdoor units that are specified as
RAM-280FSPH(D) and RAM-335FSPH(D). This manual provides
installation and maintenance instructions for these outdoor
units.
Important Notice: This air conditioner is designed for general
use. It should not be used for specific purposes such as food
preservation, animal care, precision machinery protection, or
preservation of works of art.
Installation Restrictions:
-
Do not install the air conditioner in areas where gas and oil
droplets exist, as it can cause fires, machine deformation,
corrosion, and damage. -
Avoid installation in places with sulfur gas, hot springs, an
acid or alkaline environment, or near the sea (in a salty
environment) to prevent corrosion. -
Avoid installing the outdoor unit where electromagnetic waves
are directly radiated to the electrical box. -
Keep a distance of approximately 3 meters between the indoor
unit, outdoor unit, controller, and cable from strong
electromagnetic waves (e.g., medical equipment). -
Avoid installing the air conditioner in locations where wind
directly affects animals or plants, as it can have adverse effects
on them.
Usage Restrictions:
- Use the wireless remote controller away from lighting equipment
or other sources of interference to ensure proper signal
reception.
Safety Summary:
Before installation, read the safety summary provided in this
manual. Pay attention to danger and caution signs as they indicate
potential risks and hazards. Follow the instructions carefully to
avoid significant harm.
Electrical Works:
-
Ensure proper grounding by following the instructions provided
for ground work. -
When performing electrical work, it is recommended to hire
qualified personnel to avoid electric shock. -
Follow the Installation Manual and relevant regulations and
standards for electrical work to prevent electrical shock and fire
hazards. -
Use specified wires for wiring between products to avoid fire
or electric shock caused by using the wrong wire.
Before installation, please read this manual carefully and keep it properly.
INVERTER-DRIVEN MULTI-SPLIT SYSTEM AIR CONDITIONERS
Outdoor Units
InstallationMaintenance Manual
RAM-280FSPH(D) RAM-335FSPH(D)
This manual makes sure to transfer to the next step of construction, and
finally the customer keeps it. (Transportation and Handling) (Refrigerant
Piping Work) (Electrical Wiring) (Test Run) (Customer)
Important Notice
The air conditioner for general use. Food, animals and plants, precision
machinery and preservation of works of art and other special purpose, please
do not use.
Do not install in the following places. If you have gas and oil droplets exist
around, it will cause fires and machine deformation, corrosion, damage. Oil
(including machine oil) of the droplets, oil gas and more places. The sulfur
gas and hot springs more places.
Do not install in the following places, it will cause corrosion. Near the sea
(in the salty environment). An acid or alkaline environment.
When produce electromagnetic waves used in medical equipment places, please
note that the air conditioner to prevent malfunction.
Do not install the outdoor unit where the electromagnetic wave is directly
radiated to the electrical box.
Do not install the indoor unit, outdoor unit, controller and cable within
approximately 3 meters from strong electromagnetic waves such as medical
equipment.
Do not install in the animals or plants will be directly affected by the wind
to the place, otherwise have adverse effects on plants and animals. Use the
wireless remote controller, since they will be affected by the lighting
equipment, etc., resulting in the receiver to receive signals failed,
therefore as far as possible away from the receiver and the lighting of more
than 1m.
Safety Summary
Before installation, This is a ” Safety Summary ” in the content, be sure to
read, for the correct installation. In this manual to note that the ” Danger”
” Caution”, when the installation error, it may lead to significant harm,
particularly marked.
Therefore, an important part of safety, please be sure to actually follow.
When the installation is complete, and then test run, to confirm whether there
is abnormal. Please follow the manual’s instructions, using the
method, maintenance method for illustration to customers, and the installation
manual and operation manual by the customers really to keep.
Definition for signal words DANGERImmediate hazards which will result in
severe personal injury or death.
About electrical works
Enforcement mattersMachine with a ground terminal, the user must follow the
instructions for ground work.
Prohibitions. Enforcement mattersIndicating the general behavior
(Non-specific object).
When perform electrical work , please have a qualified personnel. Please note
that the construction is not completely by yourself, there will be occurred an
electric shock.
Perform electrical work according to Installation Manual and all the relevant
regulation and standard. If the instructions are not followed, an electrical
shock and fire may occur due to insufficient capacity and inadequate
performance.
The wiring between products, please use the specification wire. Select the
wrong wire, it will cause fire or electric shock.
DANGER Ensure that the wiring terminals are tightened securely with the
specified torques. If not, generating fire or electrical shock at the
terminal’s connection part may occur.
Fix the cables securely. External forces on the terminals could lead to a
fire.
Use an ELB(Earth Leakage Breaker)In the event of fault, there is danger of an
electric shock or a fire if it not used.
Due to electrical wiring, inspection work and open the service cover,
completely turn off the power to implement in order to avoid electric shock.
Check that the ground wire is securely connected. If the unit is not correctly
grounded, it leads electrical shock. Do not connect the ground wiring to gas
piping, water piping, lighting conductor or ground wiring for telephone.
About installation
When installation, make sure you follow the installation manual. If the instructions are not followed, it may result in a water leakage, electric shock or a fire.
Please install the unit where is able to withstand the weight. Strength, and installation is not complete, the body may fall and cause injury.
DANGER
Please do not place flammable gas and have doubts about the place to the installation, it may cause fires and other accidents.
Do not climb air conditioner, or place objects on top, so as to avoid falling damage.
In case of refrigerant leakage occurs, please immediately turn off the fire
source (such as: stoves and other appliances), remove the refrigerant on the
ground, open the doors and windows to ventilation , and contact your service
contractor.
The indoor unit drain pipe do not directly into the drainage ditches. The
biogas will be produced through the drainpipe into the indoor, resulting in
poisoned phenomenon.
66MP1570
1
Use the adequate non-flammable refrigerant(R410A) to the outdoor unit in
refrigerant cycle. Do not charge Oxygen, acetylene or other flammable and
poisonous gases. These types of gases are extremely dangerous can cause an
explosion and fire.
Condensation water drain pipe, please make sure that it can be drained.
Incorrect piping may cause water to enter the house or wet furniture.
Please tighten the flare nut with specification torque. If the torque too
much, it will result in flare nut cracking, and make the refrigerant leakage
phenomenon.
Caution During the field decoration construction, prohibition of the unit
operation, and prepare the unit to prevent dust and defacement.
Before the unit operation, please make sure is the field cleaned finish?
Objects floating in the air, has the smell cleared? Has the unit been cleaned?
To prevent future the unit is not cold or water leakage.
1. Common Items
1.1 Combination of Indoor Unit and Outdoor Unit
Please refer to the table, the selection of outdoor unit and indoor unit number and capacity.
Indoor Unit
Outdoor Unit Model
Combination Capacity of Ratio (For Outdoor Unit)
Combination Quantity
RAM-280FSPH(D)
50~130%
14
RAM-335FPSH(D)
For the system which all indoor units are operated simultaneously, the total
indoor unit capacity should be less or equal to the outdoor unit capacity.
For the system which all indoor units are not operated simultaneously, the
total indoor unit capacity is available up to maximum against the outdoor unit
capacity.
1.2 Operation temperature range
Condition Item
Cooling
Air inlet temperature of outdoor unit
-5 DB 43 DB
Air inlet temperature of indoor unit ( non-room temperature)
21 DB/15 WB 32 DB/23 WB DB: Dry Bulb WB: Wet Bulb
1.3 Cooling operating instructions The same refrigerant system of indoor unit,
the cooling shall be operated.
1.4 Note This system can not operate within 4 hours of powered, stop reason
code will be displayed “d1-22”, If you want to operate in 4 hours, please
follow the steps to release the protection settings: 1) Please power ON indoor
and outdoor unit. 2) Wait 30 seconds. 3) Press the outdoor unit’s arrangement
of PSW1 above 3 seconds.
2. Transportation and Handling
2.1 When transporting the outdoor unit, please observe the following items,
please state as much as possible to keep the
packaging moved to the location of installation. The hanging method under
packing situation:
Please hang the unit under packing condition with two ropes.
The center of gravity
Handle
Wooden Base
2
2.2 The following is accessory parts of the outdoor unit. Please confirm it before installation.
Accessory
Q’ty
Use Place
Use Method
Pipe Combination
1
Use to connect gas piping.
Please refer the piping work on page 9.
Drain Connector Washer
1
Base condensation water exhaust.
Please refer the foundation work on page 9.
1
3. Before Installation
3.1 The R410A refrigerant pressure higher than R22 about 1.4 times, it is more
susceptible to moisture, acid materials, oil and other impurities influence.
Because of the new refrigerant, refrigerant oil also will be changed.
Therefore, when installation, be careful not to water, impurities, the
existing use of the refrigerant and refrigeration oil mixed in the cycle
system.
The product of the design pressure is 4.15MpaG.
3.2 To avoid accidental mixing of different refrigerant or different refrigerant oil, the sizes of the charging connections have
to be changed. It necessary to prepare the following special R410A tools before performing the installation work.
The measuring machine or tool which will contact the refrigerant, please use specially for the new refrigerant.
Symbol Descriptionfor new and old type refrigerant only for R410A (not for R22)
only for R407C (not for R22) for two type R410A and R407C.
Interchangeability
Reason of Non-Interchangeability and Attention
Measuring Instrument and
with R22
Tool
R407C R410A
(Only for new refrigerant) (Strictly Required)
Use
Pipe Cutter
Cutting PipeRemoving Burrs
Flaring Tool
Extrusion Adjustment Gauge
(Not use)
Pipe Bender
Expanding Tool
Refrigerant
Pipe
Torque Wrench
To ensure the high pressure of R410A, if using flaring tube, make the
dimension of tube larger for R410A. If you continue to use existent products,
shall be used with the flaring tube adjustment gasket (1mm). Using the 1/2H
pipe situation, can not be processed.
(R410A special flaring tool can be used directly in the R407C)
Using the 1/2H pipe situation, can not be processed. Please use the elbow
welding connection.
Using the 1/2H pipe situation, can not be processed. Please use the elbow
welding connection.
R410A for12.715.88;spanner size is up 2mm; existent products can not be used.
For 6.359.5319.05; spanner size is the same.
Flaring for Tubes
Dimensional Control for Extrusion Portion of Tube after Flaring
Bending Expanding Tubes
Connection of Flare Nut
Brazing Tool Nitrogen Gas
Perform correct brazing work.
Strict control against contamination. (Blow nitrogen during brazing)
Brazing for Tubes
Prevention from Oxidation during Brazing
Lubrication Oil
(for Flare
Surface)
Do not use R22 with mineral oil, and products must be
used the same synthetic oil. Synthetic oil absorbs moisture quickly, Therefore, to
Applying Oil to the Flared Surface
avoid damp places.
Measuring Instrument and Tool
Vacuum Drying
Refrigerant Cylinder
Refrigerant Vacuum Pump Change Adapter for Vacuum Pump (Prevent from reverse)
Interchangeability with R22
R407C R410A
Reason of Non-Interchangeability and Attention
(Only for new refrigerant)
Use
(Strictly Required)
(Brown) (Pink)
Check refrigerant cylinder color.
Filled with the gas refrigerant is strictly prohibited Liquid refrigerant
charging is required regarding Nonazeotropic refrigerant.
Refrigerant Charging
The current ones are applicable. However, it is required
to mount a vacuum pump adapter which can prevent Vacuum Pumping
from reverse flow when a vacuum pump stops,
resulting in no reverse oil flow.
3
Manifold Valve
Vacuum Drying
Charging Hose
Refrigerant Change Charging Cylinder
Weight Scale
Refrigerant Gas Leakage Detector
Prohibited
No interchangeability is available due to higher pressure
when compared with R22.
R410A connection diameter1/2 UNF
Vacuum Pumping; Vacuum
R407C connection diameter7/16 UNF
Holding.
Do
not
use
current
ones
(R22)
to
the
different
Refrigerant Charging Check of Pressures
and
refrigerant ; If used, mineral oil will flow into the
cycle and cause sludge, resulting in clogging or compressor failure.
Please use the weight scale.
Refrigerant Charging
The current gas leakage detector(R22) is not applicable due to different detecting method.
Measuring Instrument for Refrigerant Charging
Gas Leakage Check
3.3 The piping and connection parts, use the following R410A. Flare nut and the front part of pipe flare size also changes, according to the following specifications used.
Pipe FlareSize
Piping Diameter d
0
Dimension A 0.4
R407CR22
Unitmm R410A
6.35
9.0
9.1
9.53
13.0
13.2
12.7
16.2
16.6
15.88
19.4
19.7
19.05
23.3
Can not be processed (1/2H material)
Please use the attached flare connecting pipe.
Pipe thickness selected With the design pressure changes, the pipe thickness and material should also be changed.
New Refrigerant Piping Thickness (mm)
Existent Type
New Refrigerant
Pipe Size
R22
R407C
R410A
Thickness Material Thickness Material Thickness Material
6.35
0.6
O
0.8
O
0.8
O
9.53
0.8
O
0.8
O
0.8
O
12.7
0.8
O
0.8
O
0.8
O
15.88
1.0
O
1.0
O
1.0
O
19.05
1.0
O
1.0
O
1.0
1/2H
22.2
1.2
O
1.15
O
1.0
1/2H
25.4
1.2
O
1.0
1/2H
1.0
1/2H
28.6
1.4
O
1.0
1/2H
1.0
1/2H
Department of the connection selected
With the design pressure changes, the connection pipe (elbow etc.) thickness are also part the changes. When use 1/2H material, the bending and flaring can not be processed, so please follow the rules below the minimum thickness choose the appropriate connecting pipe. Please note that the size of flare nut is also part change.
Connection minimum thickness (mm)
Pipe Size
6.35 9.53 12.7 15.88 19.05
R407CR22 0.5 0.6 0.7 0.8 0.8
R410A
0.5 0.6 0.7 0.8 0.8
Pipe Size
22.2 25.4 28.6 31.75 38.1
R407CR22 0.9 0.95 1.0 1.05 1.25
R410A
0.9 0.95 1.0 1.1 1.35
Flare Nut
Pipe
Pipe Size
6.35 9.53 12.7
Flare Nut Size B(mm)
R407C R22
R410A
17
17
22
22
24
26
Pipe Size
15.88 19.05
Flare Nut Size B(mm)
R407C R22
R410A
27
29
36
36
4
4. Installation Work 4.1 Outdoor unit installation place selected (common
items) 1) Make sure the outdoor unit installation space, convenient to the
normal operation and maintenance services.
2) Install the outdoor unit where good ventilation is available, and where it
is dry.
3) Install the outdoor unit where it is in the shade, or it will not be
exposed to direct sunshine or direct radiation from high temperature heat.
4) Install the outdoor unit where the sound from the outdoor unit does not
affect neighbors. 5) Unit air outlet does not directly flow to the plant or
neighbor’s windows. 6) Provide a foundation so that the entire feet of the
outdoor unit can be mounted on the foundation. 7) The place where the heat
exchanger will not inhale the dust and paper scraps. 8) Installed as far as
possible where is without reverse wind (the wind blowing directly against the
fan).
Installed on the roof and no buildings surrounding, and there may be strong
winds blowing directly against the unit. Please note that strong winds do not
blowing directly against the air outlet grille of the unit. 9) Can not be
setting inside the house. 10) Do not place flammable objects near the unit, it
may cause fires. 11) Do not install the outdoor unit where there is a high
level of oil mist, salty air or harmful gases such as sulphur. 12) Do not
install the outdoor unit where the electromagnetic wave is directly radiated
to the electrical box.
13) Install the outdoor unit as far as at least 3 meters from the
electromagnetic wave radiator.
Strong wind blowing directly against the product installation method
Installed on the roof and no buildings surrounding, and there may be strong
winds blowing directly against the unit. Please follow the instructions below:
Please note that strong winds do
When strong winds blowing directly against the air outlet grille.
not blowing directly against the air outlet grille of the unit. When strong winds blowing directly against the air outlet grille of the unit, making the necessary air flow can not ensure that the body will result in failure.
(1) Option the wind break cover plate.
(2) When have a shelter of the wall
Strong winds direction
Wind break cover plate
Wall
Air inlet Let air outlet grille
facing shelter of
the wall or other
buildings.
Air outlet
NoteThe air outlet of outdoor unit suffered strong winds bluster continually,
the fan speed may be due to high speed reversed and damage.
Strong winds
Strong winds Please ensure that service space more than 600mm.
Option The Wind Break Cover Plate Type
Type
Q’ty
WSP-335A
2
When on the roof or open space, the strong
winds will bluster the unit. Please make steel wire cable and others fixed the
unit.
5
4.2 Installation Space
Around the outdoor unit must ensure the maintenance of space as shown below.
- Obstruction in the air inlet side
(a) When the above open
A separate installation
A row installation (two more)
(Unit: mm)
The Side Is Open 200 Above
The Side Has Obstruction 300 Above
300 Above
Front Side
50 Above Front Side
100 Above
With the unit front side same direction.
Front Side
Front Side 100 Above
Note: Must be opened on both sides.
Note: Must install the wind break cover plate (Option), and both sides must be opened.
100 Above
Note: Must install the wind break cover plate (Option), and both sides must be opened.
350 Above
350 Above
(b) When obstruction at the top. A separate installation
300 Below
1000 Above
350 Above 300 Below
350 Above
1000 Above
Note: Must install the wind break cover plate (Option), and both sides must be
opened.
(Unit: mm) A row installation (two more)
300 Below 100 Above
1000 Above
Note: both sides must be opened.
350 Above
300 Below 100 Above
(Setting two sets situation) 1000 Above
350 Above
Note: Must install the wind break cover plate (Option), and both sides must be opened.
6
- Obstruction in the air outlet side (a) When the above open A separate
installation
700 Above Front Side
100 Above
50 Above
With the unit rear side same direction.
Note: Must install the wind break cover plate (Option), and both sides must
one side be opened at least.
350 Above
Note: Must install the wind break cover plate (Option), and both sides must be opened.
(Unit: mm) A row installation (two more)
100 Above
700 Above
Note: Must install the wind
break cover plate
150 Above
(Option), and both sides must be
opened.
(Setting two sets situation)
700 Above
3) Obstruction at both sides (a) When the above open A separate installation
700 Above 350 Above
(b) When obstruction at the top.
(Unit: mm)
A separate installation
1000 Above
1000 Above
500 Above 50 Above
500 Above 100 Above
500 Above 50 Above
500 Above 100 Above
Note: L
0 < L 1/2H 1/2H < L H
(Unit: mm) A
600 Above
1400 Above
When LH, please set the metal framework under the outdoor unit which will make HL, in order to prevent the unit blowing air bypass, and set the metal framework sealed.
- Multiple rows side by side installation (roof, etc.) 300 Above
Even if the right and left sides open, the outdoor unit must be spaced more than 100mm. AB size please refer to the table
L 0 < L 1/2H
A 600 Above
(Unit: mm) B
300 Above
1/2H < L H 1400 Above 350 Above
(Note) When LH, please set the metal framework under the
outdoor unit which will make HL, in order to prevent
the unit blowing air bypass, and set the metal framework sealed.
600 Above
7
Below
21mm Below
(A After Cut Off)
4.3 Foundation Work 1) Anchor bolts installation, lock method and fixed examples.
Unit Base Nut Washer
Anchor Bolt (M12)
Concrete Filled Mortar
4-16 x 23.5 Long Hole
If ensure 170 dimension, and without interference with foundation base, it can
be downward the piping work.
Concrete
Using this type of Anchor Bolts, be sure
to cut off the A .
(Due to remove the pipe cover difficulty)
Anchor Bolt
- To avoid dumping the body resulting noise, or due to gusts and earthquakes caused by inclination. So be sure to make the outdoor units foundation work is really.
Fixed Bracket (Fielded supplied)
To avoid the unit vibration transmitted to the buildings, if necessary to install anti-vibration rubber.
- Confirm the drainage smooth flow
When Defrost operation, the condensation water will be discharged, select the best drainage of areas, the water discharge to drainage ditch. The drain hole position shown at right:
AirInlet DrainHo(le 26) (20)
(Unit: mm)
- Setting shelf use standard parts, when the standard parts width narrower than outdoor unit base bracket, please follow
the figure belowbetween the standard parts shelf and outdoor unit base bracket feet, into the wider flat to withstand
full weight of the outdoor unit.
Outdoor unit base bracket can not fully load the unit weight.
Outdoor unit base bracket can fully load the unit weight.
Outdoor Unit Base Bracket Width100mm
Flat recommended SizeSPHC (Fielded supplied) Unitmm Flat Thickness4.5mm
Hole
Shelf Setting
Shelf Width 60 mm (Standard Parts)
Shelf Setting
Flat Flat Width 100 mm
(560)
8
- The drain connector installation methods:
1. Setting the washer on the drain connector convex (around) upper part.
Drain Connector
2. Meet the base drain holes shape, the drain connector turns right
about 40 ° and into the base.
3 The drain connector is equivalent to VP16.
4 The drainpipe is field supplied.
NoteThe drain connector which is installed for defrosting or reservoir condensation
water to discharge.
Base Drain Hole
Washer
5. Refrigerant Piping Work
5.1 Refrigerant Pipe 1) Refrigerant pipe selection 1.1 Please prepare the
refrigerant pipe by field supplied. 1.2 Select clean copper pipes. Make sure
there is no dust and moisture inside of the pipes.
Cut off the refrigerant piping, use the pipe cutter. Blow the inside of the
pipes with nitrogen or dry air, to remove any dust or foreign materials before
connecting pipes. (Avoid using a saw or grinding stone tools so easy to
produce powder.)
Cautions for refrigerant piping work (for example)
Hole of wall
When installing pipe through the wall. Secure a cap at the end of the pipe
Attach a cap or vinyl tape
Do not place the pipe directly on the ground.
Attach a cap or vinyl tape
Attach a cap or vinyl tape
Rainwater can enter
Rubber band
- Piping Direction The pipe can be connected in four directions.
Base Pipe Hole
Liquid Piping Connection (A Flare Nut)
Gas Piping Connection (B Piping Connection, combined with Flange combination)
Size
A B
RAM-280FSPH(D) 12.7 28.6
RAM-335FSPH(D) 12.7 28.6
(Unit: mm)
Pipe Combination (accessory parts)
Connecting Pipe Set (Flare Nut) Gas Side Piping
210
Rear Piping (Knock Out Hole)
Front Piping (Knock Out Hole)
Front Piping Cover
Front Piping (Knock Out Hole)
Rear Piping Cover
Rear Piping (Knock Out Hole)
Right Piping (Knock Out Hole) Bottom Piping (Knock Out Hole)
Rear Piping (Knock Out Hole)
Please press the cover and push down, then carefully removed it.
Front Piping Cover
9
B Connecting Pipe
Set (Welding) Gas Pipe Size
Rear
Rear Piping Cover
Open the service cover essentials
1 Please remove the left screw, and press cover by your hand, then remove the
screw.
2 Please press the cover and push down, then carefully removed it.
Services Cover (3 Hooks)
- Refrigerant piping fixation methods: Connect the indoor unit and the outdoor unit with field-supplied refrigerant piping. Suspend the refrigerant piping at certain points and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc. (If touched, abnormal sound may occur due to the vibration of the piping. Pay special attention in case of short piping length.)
(Fixation Methods Example) Outdoor Unit
Piping fixation Interval
Pipe Size
20Less 25~40
Maximum Interval 1.0m
1.5m
Indoor Unit
10
- Refrigerant piping limitation and multi-kit pipe: Because the longer pipe,
can cause air conditioner cooling and heating reduced capacity, so this factor
to be considered for selected piping specifications.
Piping Connection Example
Outdoor
These figures show examples of 4 indoor units combined with one outdoor unit.
The refrigerant pipes are shown as single line in the diagrams. However,
liquid line piping and gas line piping are required in the field piping work.
NO.0 Indoor
NO.1 Indoor
NO.2 Indoor
NO.3 Indoor
Maximum Piping Length
Actual Length Equivalent Length The Total Length
The outdoor unit is higher than
that of indoor unit. Maximum Lift
between
The outdoor unit is lower than that
Outdoor Unit of indoor unit.
and Indoor Unit
Between each indoor unit
Maximum
Between Each Multi-Kit and Each Indoor Unit
Piping Length Between Multi-kit “a” And the Farthest Indoor Unit
L1L2l 3150m Below L1L2l 3190m Below L1L2l0l1l2l 3300m Below
H 150m Below H 140m Below H 215m Below l 0l 1l 2l 315m Below l 440m Below
The First Multi-Kit Pipe (a) And L1 Connection Pipe
Outdoor Unit Model RAM-280FSPH(D)
Gas/Liquid Pipe Size ( mm)
28.6 / 12.7
Multi-kit And Connection
Pipe
Others Multi-kit Pipe And Connection Pipe
RAM-335FPS(D) Indoor Unit Total Capacity (kW)
27 23~26.99 15~22.99
15
28.6/12.7
Gas/Liquid Pipe Size ( mm) 28.6/12.7 25.4/9.53 22.2/9.53
19.05/9.53
1: E-N55HT (Header Branch), It can be used that each indoor unit distribution and connection.
Multi-Kit Pipe Type
E-NP452S
Multi-Kit Pipe Type E-NP452S E-NP282S E-N55HT 1
11
Multi-kit pipe please follow the requirement, remove the no used pipe, other
pipes will be welded into the multi-kit pipe,
otherwise it will result in reducing cooling capacity.
Line Branch Pipe
Type
E-NP282S
E-NP452S
Gas Piping
Liquid Piping
Header Branch Pipe Type
E-N55HT
Gas Piping
Liquid Piping
5)Setting of the multi-kit pipe The multi-kit pipe which is connected to the
indoor unit, be sure to use an optional part of the multi-kit pipe set, in
order to prevent the uneven distribution of the refrigerant and causing the
unit’s capacity reduction. Do not connect using the connector. 1) Line branch
(use the line branch pipe), As shown below Main pipe (The pipe between each
multi-kit pipe or the pipe between outdoor units to first multi-kit pipe.)
Main BranchThe multi-kit pipe has two multi-kit pipes which connect with more
than one indoor unit. Setting ConditionLimited to third branch pipe, but only
two main branches.
12
Setting ways of branch pipe:
Best installationsituation
Third B3ranch
Outdoor First B1ranch
Second B2ranch Sec2ond Main Branch
First M1 ainBranch
Third 3Branch
OutdoFoirrs1t BranchSecond2Branch X Wrong
First Main1Branch Seco2ndMain Branch
Allowing installation situation
Outdoor Second 2Branch Third3 Branch First1Branch
Outdoor First 1Branch
Second2Branch Third B3ranch Fou4rthBranch
First M1 ainBranch
Sec2ondMain
First Ma1inBranch
Second M2ainBranch
The line branch pipe fixed limits
X Wrong
Horizontal
The branch pipe must be set in the same plane.
Outdoor unit connection pipe shall ensure that the straight pipe above 0.5m.
Up
Up
Straight Pipe
0.5m Above Up
Same Horizon Plane
Down
Vertical
Down
It is divided into two kinds which is up and down.
Up
Up
Straight Pipe 0.5m Above
Upward Branch
Tilt Angle Within 30°
Tilt Angle (A Direction)
Downward Branch
Straight Pipe 0.5m Above
Down
2) Header branch (use the header branch pipe), As shown below
Down
Correct Setting
Indoor Unit
Header Branch Pipe
Header Branch Pipe
Main Pipe
Wrong Setting Main Pipe
Main Pipe NoteThe header branch pipe cannot be continuous installation.
13
Indoor Unit Header Branch Pipe
The header branch pipe fixed limits
The header branch pipe must be installed horizontally.
- Mixing setting of line branch and header branch, as shown below
Correct Setting
Maximum length 40m
Correct Setting
First Branch
First Branch
Wrong Setting
Header Branch Pipe
Indoor Unit
Second Branch
Header Branch Pipe
Maximum length 40m
Note: 1.The line branch pipe can not be connected after the header branch
pipe. 2.The first branch pipe can not use the header branch pipe.
Header Branch Pipe
Line Branch Pipe
5.2 Refrigerant Piping Work
- Confirm that the stop valves of outdoor unit are closed.
- Please connect the piping between indoor and outdoor unit. When tightening the joints of piping, in the inside and outside of flare piping, please coated with a layer of refrigerant oil [ Field-supplied (Idemitsu Kosan Co., Ltd. Synthetic oil” FVC68D”)], and in accordance with the provisions of tightening torque with double spanner to tighten. After tightening, please confirm the gas leakage once more. During brazing, please blowing nitrogen into the piping. Please connect the pipe which use the attached flange combination, while use the attached washer to replace the original washer.
- Connect the indoor unit and the outdoor unit with field-supplied refrigerant piping. Suspend the refrigerant piping at certain points and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc. (If touched, abnormal sound may occur due to the vibration of the piping. Pay special attention in case of short piping length.)
- Please perform the air-tight test. Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check joints of the liquid line and the gas line stop valves. Perform the air-tight test. Connect a manifold gauge to the check joints of the liquid and gas stop valves in the outdoor unit. Do not open the stop valves. Apply nitrogen gas pressure of 4.15MPaG.
Required Torque
Spindle Valve Torque Nm
Piping Size (mm) Tightening Torque
and Flare Nut
Nm
Gas
Liquid
6.35(1/4″)
20
20~25
7~9
9.53(3/8″)
40
12.7(1/2″)
60
Hexagonal Wrench
15.88(5/8″)
80
Gas
Liquid
19.05(3/4″)
100
10mm
5mm
Spindle valve of Gas Check Valve
Spindle valve of Liquid Check Valve
(1) After connection piping and before implementation the airtight test, please remove the liquid and gas stop valve caps, the spindle valve ensures that be closed with tightening torque Nm. Tightening the flare nut do not use more than the torque marking on the table, too large torque will result in the spindle valve leakage.
Do Not Apply the Double Spanner Work Here. Refrigerant Leakage Shall Occur.
Stop Valve
Flare Nut
Double Spanner Work
14
(2) After locking work is completed, please implement air leakage test.
Note1. The work that after use the flare nut to connect pipe and stop valve,
will be effective. 2. Because check joints and flare nut can not connect, so
please use the charging hoses. The spindle valve cap of stop valve is removed,
due to internal O-ring and thread will be opened, the voices caused by gas
emitting, which has nothing to do with the leakage. 3. Do not apply an
abnormal big force to the spindle valve at the complete opening (5.0 N-m or
smaller).
5) Insulate the unions and flare-nuts at the piping connections completely.
Insulate the liquid piping and gas piping completely to avoid decreasing of
performance and dewing on the surface of the pipe.
6) In order to prevent rainwater invasion, the unit, make sure to install the
pipe cover, and installation thermal insulation material where the pipe is
through the unit, so that it can not have gaps happening.
5.3 Vacuum 1) Details stop valve operation, please refer to the attention of
nameplate inside service cover description. 2) Connect a manifold gauge to the
check joints at both sides. Continue vacuum pumping work until the pressure
reaches-0.1MPa (750mmHg) or lower for one to two hours. 3) After vacuum
pumping work, stop the manifold valve’s valve, stop the vacuum pump and leave
it for one hour. Check to ensure that the pressure in the mani-fold gauge does
not increase. 4) Because check joints and flare nut can not connect, so please
use the charging hoses. After the work, please tighten the flare nut with 16N
· m of torque. 5) Check for any gas leakage at the flare nut connections, or
brazed parts by gas leakage tester or foaming agent. The following is
recommended for foam testing fluid [Field-supplied (NUPRO “SNOPP” or Yokogawa
& Co., Ltd.” “)], component is not clear which is general household cleaners
do not use the liquid as a foam testing.
6) Vacuum drying determination example
Vacuum Degree Vacuum Degree Vacuum Degree
Outside air temperature 23
After the vacuum pump stop, the vacuum degree rebound phenomenon Vacuum pump
stop
Outside air temperature 20 System without water System with water
System with water,
System with water,
outside air
outside air
(
temperature 20
temperature 10
Vacuum Time (min) Vacuum Time and Vacuum Degree
Vacuum Time (min) The system includes water vacuum time and vacuum degree
System without water, outside air temperature do not affect
Vacuum Time (min)
Figure3Outside air temperature vacuum time and vacuum degree
Note1. When remove the spindle valve cap of stop valve, there may be slight refrigerant leakage sound is normal.
2. Use tools and measuring instruments only for the new refrigerant (R410A)
which directly touch refrigerant.
3. If vacuum degree of -0.1MPa (-750mmHg) is not available, it is considered
that leakage exists. Check for any gas leakage once again. If no leakage
exists, operate the vacuum pump for one to two hours.
Please implement vacuum drying determination, to confirm whether water exists within the system. If moisture is present, please extend the vacuum time or installation the drying filter until no moisture is present within the system. Be sure to do this work, otherwise in the future the unit could easily lead to failure, and difficult to handle.
5.4 The Additional Refrigerant
- Outdoor unit has been filled with refrigerant, but still based on the length of pipe filled with an appropriate amount of refrigerant. The
filling amount of refrigerant, please following the liquid piping length and the capacity of the indoor unit calculation, the results please
fill in ”
“.
Calculation formula
WAdditional refrigerant of liquid pipe (kg) = W11+W12+W13
W1112.7 liquid pipe length (m)
×0.12 (kg)=
additional refrigerant (kg)
Model
The factory refrigerant charging
weight (kg)
Additional refrigerant upper limit
(kg)
W129.53 liquid pipe length (m) W136.35 liquid pipe length (m)
×0.07 (kg)= ×0.03 (kg)=
RAM-280FSPH(D)
6.5
RAM-335FSPH(D)
7.8
13.5
W Total=
(kg)
-
Fully open the gas line stop valve and slightly open the liquid line stop valve.
-
Cooling operation, then for charging refrigerant, connect the gauge manifold using
charging hoses with a refrigerant charging cylinder to the check joint of the liquid line
stop valve. (Refrigerant charging quantity of tolerance in the ± 0.1kg around.)
-
Fully open the liquid line stop valve after completing refrigerant charge.
-
Finally, please lock the spindle valve cap of liquid stop valve in according with the following tightening torque.
The cap tightening torque
Liquid 20 Nm
Gas
49 Nm
·Additional refrigerant W
exceeds the amount of additional refrigerant filling upper limit, adjust the
length of piping, such that W does not exceed the value of upper limit.
15
- Please be sure to perform the air-tight test.
Additional refrigerant too more or too less, will result in compressor failure or others abnormal condition, be sure to charge refrigerant according to calculate values.
Liquid piping must be implemented thermal insulation. (To prevent poor performance, and low pressure pipe surfaces to prevent condensation.)
Outdoor Unit
Liquid Stop Valve Gas Stop Valve
Mani-Fold Gauge Vacuum Pump
Nitrogen Bottle (Use for Brazing and Air-Tight Test)
Refrigerant Cylinder (R410A) Weight Scale
Be sure to check the refrigerant leakage. If a large refrigerant leakage, it
will happen the following phenomena
1. Lack of oxygen.
Gas Piping Liquid Piping
Indoor Unit
5.5 Caution of The Refrigerant Leakage
Branch Pipe Thermal Insulation Material Wrapped
Work
Air conditioner installation in room, in case of refrigerant leakage,
refrigerant concentration must not exceed the limits of concentration. The
products use non-flammable, non-toxic safety refrigerant R410A, if the indoor
unit refrigerant leakage filled entire the room, there will be a choking
hazard to happen. Especially multiple indoor unit and outdoor unit of the
long-distance piping connection, the amount of refrigerant more than
individual air-conditioner. So, make sure the indoor unit installation in the
room, even in case of refrigerant leakage, immediate disposal of the
refrigerant concentration should also lower than the limits concentration.
Please calculate limits refrigerant concentration by the following formula
The total amount of refrigerant within the system (kg)
Installation the product of the room indoor volume (m3) limits refrigerant
concentration
R410A (0.3kg / m3)
The calculation result, if installation products of the room more than the limits concentration, but when the air conditioner must be installed, please choose a treatment method according to the following
- Setting refrigerant leakage detector alarms linked mechanical ventilation devices. (See below) (Per 1 ton cooling capacity should be more than 0.4 m3/min ventilation capacity. Cooling capacity in the following table, according to the outdoor unit capacity.)
- Between adjacent room to set the effective ventilation mouth (such as opening mouth of no door or opening mouth which need to set more than 0.15% floor area on the upper and lower of the door), so that the leakage refrigerant concentration below the limit’s concentration.
Example The total amount of refrigerant within the system: 20kg
Refrigerant Pipe Refrigerant Pipe
TiMnoysRt oSommall Room
(VVeenntitlialatitoinon MMoouuthth) )
Outdoor Unit OuOtudtodooror
Indoor Unit IndInodoor or
Small Room
Medium Room The Room
Large Room
mechanical ventilation devicesrefrigerant leakage detector alarms devices
(Note(11) )Whetherit is alarge room,mediumroom, smallroom,
tinyroom2t0hkegamount of (Note(22)le)Tahkeagroeormefrmiguesrat
nntoatreexcaelle2d0kthges.lim0.i3tskrge/frmig3erant concentration of 0.42kg /
m3.
Outdoor Unit OutdMooordUenl it
Model
Cooling Capacity R410A
RAM-280FSPH(D)
4.11Ton
RAM-335FSPH(D) 4.11 Ton
New refrigerant R410A product notes: Since R410A is a non-azeotropic
refrigerant, when refrigerant leakage, the refrigerant will result in weight
percent composition changes, so can not directly add refrigerant treatment,
must be re-processing system.
5.6 Caution of Measure Pressure Data from The Check Joints
Measure pressure data of work, please from the check joints of gas line stop
valve (right figure ) and the check joints of piping line (right figure ) to
connect. And then, please according to the different operation state, to
change high and low pressure position of the connection. The details, please
refer to the following description of the table.
The check joints of gas line stop valve
Cooling Low pressure
The check joints of piping line
High pressure
The check joints of liquid line When vacuum, maintenance services
stop valve
use to charge the refrigerant specially.
16
5.7 Refrigerant Recovery Methods
When the unit must be moved and outdoors refrigerant must be recovered, please
follow these steps to implement the operation. 1) Please close the gas line
stop valve, liquid line stop valve and the mani-fold
gauge. 2) Please turn on the power source. 3) Setting to ON of outdoor unit
electrical board DSW1-1, please implement cooling
operation, then closed the liquid line stop valve, and refrigerant recovered
operation will be started. 4) When the low-pressure (gas line stop valve) side
of the pressure display 0.01MPa (-100mmHg), please action rapidly according
the following instructions
1.Please close the gas line stop valve. 2. Setting to OFF of outdoor unit
electrical board DSW1-1. (Unit stop). 5) Please turn off the power source.
DIP Switch (DSW1-1 Setting To ON)
Liquid Stop Valve
Mani-Fold Gauge
Gas Stop Valve
Please do not let low-pressure gauge to measure the pressure is lower than-0.01MPa.
When the refrigerant recovered operation, the low pressure is less than-0.01MPa, will result in compressor Caution failure.
6. Electrical Wiring
CAUTIONAll the field wiring and electrical components must comply with local codes.
6.1 Wiring Capacity
- The indoor and outdoor unit transmission cable of the connection is a non- polar.
transmission cable (non-polar) Outdoor
Indoor
Indoor
- The type of earth leakage breaker required for the ” high-speed type ” (active time less than 0.1 sec.), when to buy, please pay
special attention. 3) Around the unit installed over current breaker, the
manual switch and earth leakage breaker (ELB) should be separated, but need
set up it together.
-
Outdoor unit power supply specification for the 3230V / 380V 60Hz
-
Wiring capacity, please according to the following table.
Item Model
Power Supply
3 60Hz
Maximum Current
(A)
ELB (Earth Leakage Breaker)
Power Switch
Number of Poles
Rating Sensitivity Current (mA)
Rating Current
(A)
1
Switch Capacity
(A)
2
Fuse Capacity
(A)
2
Power Supply
Size
Earth Wire Size
(mm2) (mm2)
3
4
Transmission Cable Size
5
RAM-280FSPH
230V
37
3
RAM-335FSPH
2-Core Shielded
100
60
60
50
14
5.5
Twist Pair Cable
0.75mm2
RAM-280FSPHD
380V
23
4
RAM-335FSPHD
Total Length
30
40
40
25
8
3.5
1000m
Below
Note: When earth leakage breaker specification selection, please according to
above table (Note: The earth leakage breaker of power supply 380V must use 34
wire)
Wiring Example
Piping thermal insulation material, Please use can withstand high temperature
gas piping of the heat resistant specification products.
17
6.2 Wiring Essential The power source cord and transmission cable ,please
according to the following essentials
to implement. 1) To prevent electric shock accidents, in the electrical
wiring, maintenance and other operations before to open the services cover,
please turn off power supply completely before implementation. 2) Be sure the
indoor unit power supply connects with each indoor unit which are all same
outdoor unit. And all indoor unit, please install the inverter corresponding
type earth leakage breaker (ELB) and the manual switch. 3) The transmission
cable of the connection must be sure to connect the wiring with the same
refrigerant cycle system of the unit. (On the outdoor unit, the refrigerant
piping is connected to the indoor unit, its transmission cable is also sure to
connect the same indoor unit.) Refrigerant piping and the transmission cable
if connected with a different refrigeration cycle, there will be abnormal
operation occurred. 4) The transmission cable of indoor and outdoor unit and
the transmission cable of the connection between indoor units (DC5V), use
2-core shielded twist pair cable (0.75mm2 above). At the same time, the total
length must be at 1000m below. 5) The transmission cable of the connection,
use 2 core wire. (Do not use more than the 3-core wire.)
6) Does Power supply voltage match the rating voltage within±10% Due to higher
or lower voltage, the unit will be damaged. 7) Check the capacity of the
electrical wires. If the power source capacity is too low, the system cannot
be started due to the voltage
drop. 8) Indoor and outdoor unit is not grounded, electric shock and other
accidents may be occurred, be sure to implement grounding
fortifications. The grounding must use the grounding resistance 100 or less of
three kinds of grounding fortification, make construction by qualified
electrical personnel. 9) To prevent electric shock accidents, in the
electrical wiring, maintenance and other operations before to open the
services cover, please turn off power supply completely before implementation.
Caution of indoor and outdoor unit connection wiring construction The
transmission cable of indoor and outdoor unit and the 220V power source cord,
be sure to keep the distance of more than 5 ~ 6cm. Therefore, do not use the
coaxial cable. If the transmission cable and power source cord connecting
wrong, will cause the PCB of the outdoor unit burning, please pay special
attention. 10) Indoor and outdoor unit’s power source cord and connection
wiring methods:
18
- Wiring connection port After wiring, must be implemented sealing to prevent water invasion inside the metal conduit pipe.
Make sure the distance between the terminal plugs, terminal plugs shall be attached the insulation tape or insulation sleeve.
Insulation Tape or Insulation Sleeve.
Rear Cover
Earth Wiring
Cord Band Operation 1. When wire through the cord band
appropriately tighten it, as show below. 2. Make sure the cord with high and
low pressure sensor isolation. 3. Tighten the cord to be isolated with pipe,
compressors, other components and metal plate edge.
Fold the wire and reserve for a maintenance operation the desired length.
Prevent need to remove the wiring plug for maintenance.
Caution
When using shielded wiring, metal band must be fixed at the shielded coating
surface.
Press the metal band by pincher, after inserting the shielded wire to metal
band.
Earth Wiring Transmission Line
Shielded Wiring Metal Band Tighten the metal band with screws below the
terminal.
Core (MVVS or CVVS)
Caution
Using the metal conduit pipe, do not let the metal conduit pipe inside the
outdoor unit, once inserted into the unit, due to fear of touching the
compressor or piping causing damage.
Piping Cover
Power Source Line
Metal Conduit Pipe
7. Dip Switch (DSW) Setting of Outdoor Unit
TURN OFF all power sources before setting. Without turning OFF, the switches
do not work, and the contents of the setting are invalid. ( indicates the
position of dip switches.)
- Transmission method setting More than one outdoor unit share the same
transmission line, need to set refrigerant cycle number and end terminal
resistance.
Setting of refrigerant cycle number
(Tens Digit)
Ref. Cycle NO. Setting
(Last Digit)
Alignment
position
Flat blade
screwdriver
ExampleRef. Cycle NO.25
Pin.2 Setting at the ON’ Rotation to
5′
Setting of end terminal resistance DSW5
Before leaving the factory
Cancellation of end resistance
Outdoor Unit Indoor Unit
DSW4 DSW5
RSW1 RSW2
Setting of end terminal resistance (PCB of outdoor unit)
The unit before leaving the factory, No. 1 pin of DSW 5 is set at the “ON”
side. In the case that the outdoor unit’s quantity in the same H-link is 2 or
more, set No. 1 pin of DSW 5 at the “OFF” side from the 2nd unit. If only one
outdoor unit is used, no setting is required.
19
2)Lift difference setting
Setting the lift difference between the outdoor unit and indoor unit. Please
use the DIP switch (DSW6) of the outdoor unit PCB (PCB1), setting each
function according to the following table.
Function Dip Switch
Outdoor unit lower than indoor unit 20~30m
Outside of the left item
DSW6
Before leaving the factory
Outdoor Unit
Outdoor unit higher than indoor unit
Outdoor Unit
NO.0
NO.1
NO.2
- Others setting switch ( indicates the position of dip switches.)
Outdoor unit lower than indoor unit
20
8. Test Run
Before Test Run
Before test run, please re-confirm the installation whether there are
problems, also confirm the following points.
In addition, please confirm it with the outdoor unit attached the installation
manual.
- Refrigerant piping and the transmission cable if connected with a different refrigeration cycle, there will be abnormal operation occurred.
- Please use the 500V electrical resistance tester to confirm the electrical parts between terminals and earth electrical resistance must be 1M more than. If 1M or less, that poor the electrical insulation, please do not operation the unit. (Do not input the power source to the terminal No.1,2 of transmission wiring.)
- When power source wiring phase error, the unit can not be operated, and the remote controller display alarm code 05 . Currently, please refer to the electrical box caution nameplate, check the phase of the first side and replace it. The phase of the replacement work, please process under the power source turn off.
- Does the oil heater of the outdoor unit have been powered? (Before using,
please input power source more than 12 hours.)
Test Run
When installation is completed, perform test run according to the following procedure, and make sure that whether the abnormal operation, then hand over the system to the customer. 1) Outdoor unit the gas stop valve and the liquid stop valve, make sure full open state. 2) Please implement the test run of the indoor unit in turn, confirm the refrigerant cycle system and the electrical wiring system is the same. (While more than one indoor unit operation, the system is unable to confirm the consistency.) 3) Please according to the following procedure to test run, and make sure that whether the abnormal operation. 3.1 Depress the “MODE” and the “CHECK” switches together for more than 3 seconds. The “TEST RUN” and the counting number of the connected units are indicated on the remote control switch. When cooling operation test run, it should be at room temperature DB 21 , WB 15 , outside air temperature DB -5 or more.(Outside air temperature DB -5 below, air conditioner can not be operated.) Using a remote controller to operation more than one indoor unit, please confirm whether the number of the units display. If no indication appears or the number of the units indicated is smaller than the actual number of the units, some abnormalities exist, please confirm it again. Depress the “MODE” switch again to set the desired mode of operation. 3.2 Depress “RUN/STOP” switch. The “TEST RUN” operation will be started. (The 2 hours OFF- TIMER will be set, and the “TEST RUN” operation will be finished after 2 hours unit operation or by depressing the “RUN/STOP” switch again.) 3.3 To end the test run, wait for 2 hours or push “RUN/STOP” switch again.
Number of The Unit
0
1
2
3
4
…
10
11
…
63
01 02 03 04 05 … 11 12 … 64 Timer Setting
Display Left Two Digit
Ref. Cycle NO.
0
1
2
3
4
…
10
11
…
63
01 02 03 04 05 … 11 12 … 64 Timer Setting
Display Right Two Digit
NoteAfter the product stops operation, in order to recover the piping
refrigerant to the outdoor unit, the compressor continues to operate a period
of time (most about 10 minutes). Also, when the test run, it is not the
product failure or abnormal.
When test running, the protection device will be activated for some
abnormality, the controller’s operation indicator is still blinking, display
“Alarm” (abnormality), while the setting temperature display will show alarm
code.
Setting temperature and setting timer display changes:
Setting Timer Display
Setting Temperature Display
23
Abnormality
Occurred Setting Temperature
01 01
01
(Display in sequence)
Abnormality Indoor Unit No.
F
Unit Type (Unit Code)
Abnormality Indoor Content of Abnormality
Unit Refrigerant
(Alarm Code)
Cycle
01
Total Number of Indoor Units Are the Same Refrigerant System with
The Abnormal Indoor Unit.
At this time, please refer to page 22 of the alarm code to confirm the leading
cause and treatment. If you can not handle, please contact your contractor for
assistance.
21
Alarm Code
Code Distinction
Content of Abnormality
Leading Cause
01 Indoor Unit
Indoor Unit Activation of Protection Device (Float Activation of Float Switch (High water Level Drain Pan, Abnormality of
Switch)
Drainpipe, Float Switch or Drain Pan)
02 Outdoor Unit Outdoor Unit Activation of Protection Device
Activation of High Pressure Switch (4.15MPa); Air Conditioner Outdoor Unit Fan Motor Lock.
03 Wiring
Transmission Abnormality between Indoor and Incorrect Wiring, Loose Terminals, Disconnect Wire, Blowout of Fuse,
Outdoor
Outdoor Unit Power OFF.
04 Inverter 05 Wiring
Transmission Abnormality between Inverter PCB and Outdoor PCB
Inverter PCB – Outdoor PCB Transmission Failure (Loose Connector, Wire Breaking, Blowout of Fuse), Abnormal fan motor controller transmitted, “04” the lower right will be “Signal flashing”.
Abnormality Power Source Phases
Incorrect Power Source Phases, Connection to Reversed Phases, Open-Phases.
06 Voltage
Abnormality Inverter Voltage
Outdoor Voltage Drop, Insufficient Power Capacity.
07
Decrease in Discharge Gas Superheat
Refrigerant
Cycle System
08
Increase in Discharge Gas Temperature
Excessive Refrigerant Charge, Failure of Thermistor, Incorrect Wiring,
Incorrect Piping Connection, Expansion Valve Locking at Opened Position
(Disconnect Connector).
Insufficient Refrigerant Charge, Pipe Clogging, Failure of Thermistor,
Incorrect Wiring, Incorrect Piping Connection, Expansion Valve Locking at
Closed Position (Disconnect Connector).
11
Abnormality Inlet Air Thermistor (Indoor)
Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
12 13 Indoor Unit
Thermistor 14
Abnormality Outlet Air Thermistor (Indoor)
Abnormality Freeze Protection Thermistor (Indoor)
Abnormality Gas Piping Thermistor (Indoor)
Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
19
Activation of Protection for Indoor Fan Motor
Fan Motor Overheat, Locking.
21
Abnormality High Pressure Thermistor (Outdoor)
22
23
Outdoor Unit Thermistor
24
29
Abnormality Outdoor Air Thermistor
Abnormality Discharge Pipe Thermistor (Outdoor)
Abnormality Heat Exchanger Liquid Pipe Thermistor (Outdoor)
Thermistor Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
Abnormality Low Pressure Thermistor (Outdoor)
31 System
35
Incorrect Capacity Setting of Outdoor and Indoor Incorrect Capacity Code Setting of Combination; Excessive or
Unit
Insufficient Indoor Unit Total Capacity Code (outside of 80~120%)
Incorrect Setting of Indoor Unit No.
Duplication of Indoor Unit No. In Same Ref. Gr., or The Connection Unit Number Exceeds the Maximum Number of Combination.
38 Outdoor Unit
Abnormality of Picking Up Circuit for Protection Failure of Protection Detecting Device (Incorrect Wiring of Outdoor
(Outdoor)
PCB)
43
Activation of Low Pressure Decrease Protection Defective Compressor (Failure of Compressor of Inverter, Loose
Device
Power Supply Connection)
44 Pressure
45
Activation of Low Pressure Increase Protection Device
Activation of High Pressure Increase Protection Device
Overload at Cooling, High Temperature at Expansion Valve Locking (Loose
Connector)
Overload Operation (Clogging, Short-Pass), Pipe Clogging, Excessive
Refrigerant, Inert Gas Mixing.
47
Activation of Low Pressure Decrease Protection Insufficient Refrigerant, Pipe Clogging, Expansion Valve Locking at
Device (Vacuum Operation Protection)
Open Position (Loose Connector).
48 Outdoor Unit
Activation of Inverter Overcurrent Protection Device
Overload Operation, Compressor Failure.
51
53 Inverter
54
55
Abnormality Inverter Current Sensor IPM Protection Activation Activation of Inverter Fin Thermistor Protection Inverter Failure
Current Sensor Failure.
Driver IC Error Signal Detection (Protection for Overcurrent, Low Voltage)
Abnormality Fin Thermistor, Heat Exchanger Clogging, Fan Motor Failure.
Inverter PCB Failure
57 Outdoor Unit Activation of Outdoor Fan Controller Protection Abnormality Fan Controller Protection (Overcurrent), Fin Overheat
EE Compressor
b1 Wiring
b5
Compressor Protection Alarm Incorrect Outdoor Unit Address Number or Unit
Number Setting
Number of Indoor Units Connected Error.
Compressor Occurred Three Times of Abnormality within 6 Hour. Over 64 Number Is Set for Address or Refrigerant Cycle. Connection of Non-H-LINK- Indoor Unit More Than 17 Units.
PSRemote control operation indicator flashes once every 2 seconds, the symbol
of between the indoor unit and remote control for the
transmission abnormally (connector loss, loose, incorrect wiring, and
disconnection). 4) Finally, please deliver the guarantee, operation manual,
and installation manual, etc. to the customer to keep it.
DangerBefore the preparation of test running, please do not start running, be
sure implementation to confirm the electrical wiring, etc.
22
Test Run and Maintenance Record
MODEL:
SERIAL. No.
CUSTOMER’S NAME AND ADDRESS:
COMPRESSOR MFG. No. DATE:
1. Is the rotation direction of the indoor coil fan correct?
2. Is the rotation direction of the outdoor coil fan correct?
3. Are there any abnormal compressor sounds?
4. Has the unit been operated at least twenty (20) minutes?
5. Check Room Temperature
Inlet: No. 1 DB /WB , No. 2 DB /WB , No. 3 DB /WB , No. 4 DB /WB ,
Outlet:
DB /WB ,
DB /WB ,
DB /WB ,
DB /WB ,
Inlet: No. 5 DB /WB , No. 6 DB /WB , No. 7 DB /WB , No. 8 DB /WB ,
Outlet:
DB /WB ,
DB /WB ,
DB /WB ,
DB /WB ,
6. Check Outdoor Ambient Temperature
Inlet: DB
, WB
Outlet: DB
, WB
7. Check Refrigerant Temperature: Operating Mode (Cool)
Discharge Gas Temperature:
Td=
Liquid Pipe Temperature:
Te=
8. Check Pressure
Discharge Pressure:
Pd=
Suction Pressure:
Ps=
MPa MPa
9. Check Voltage
Rated Voltage:
V
Operating Voltage:
L1-L2
V L1-L3
V L2-L3
V
Starting Voltage:
V
Phase Imbalance:
1-
V Vm
=
10. Check Compressor Input Running Current
Input:
kW
Running Current: A
A
11. Is the refrigerant charge adequate?
12. Do the operation control devices operate correctly?
13. Do the safety devices operate correctly?
14. Has the unit been checked for refrigerant leakage?
15. Is the unit clean inside and outside?
16. Are all cabinet panels fixed?
17. Are all cabinet panels free from rattles?
18. Is the filter clean?
19. Is the heat exchanger clean?
20. Are the stop valves open?
21. Does the drain water flow smoothly from the drain pipe?
23
66MP1570-A2
Printed in Philippines
24