Autonics M4N-DV-XX Digital Panel Meter Instruction Manual

June 17, 2024
Autonics

DRW170795AA

DIGITAL PANEL METER

M4N SERIES

INSTRUCTION MANUAL

Thank you for choosing our Autonics product.
Please read the following safety considerations before use.

Safety Considerations

※ Please observe all safety considerations for safe and proper product operation to avoid hazards.
※ Safety considerations are categorized as follows.
Warning Failure to follow these instructions may result in serious injury or death.
  Caution Failure to follow these instructions may result in personal injury or product damage.
※ The symbols used on the product and instruction manual represent the following symbol represents caution due to special circumstances in which hazards may occur.

Warning

  1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
    Failure to follow this instruction may result in fire, personal injury, or economic loss.

  2. Install on a device panel to use.
    Failure to follow this instruction may result in fire.

  3. Do not connect, repair, or inspect the unit while connected to a power source.
    Failure to follow this instruction may result in fire.

  4. Check ‘Connections’ before wiring.
    Failure to follow this instruction may result in fire.

  5. Do not disassemble or modify the unit.
    Failure to follow this instruction may result in fire.

Caution

  1. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or product damage.

  2. Use dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire.

  3. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight, radiant heat, vibration, impact, or salinity may be present.
    Failure to follow this instruction may result in fire or explosion.

  4. Keep metal chip, dust, and wire residue from flowing into the unit.
    Failure to follow this instruction may result in fire or product damage.

※ The above specifications are subject to change and some models may be discontinued without notice.
※ Be sure to follow cautions written in the instruction manual and the technical descriptions (catalog, homepage).

Ordering Information

a: Measuring input range

| DC volt input F.S. | DC ampere input F.S.
---|---|---
1| 199.9mV| 199.9μA
2| 1.999V| 1.999mA
3| 19.99V| 19.99mA
4| 199.9V| 199.9mA
Blank| Option| Option

b: Power supply

0 5VDC
1 12-24VDC

c: Measurement functions

V Voltage
A Current
I Scaling(DC4-20mA)※2

d: Measuring input

D DC Type

e: Size

N DIN W48×H24mm

f: Digit

4 1999(3½ Digit)

g: Item

M Meter

※1: M4N series is to measure DC only. AC voltage and AC current is not available to be measured.
※2: 1-5VDC measuring input is optional.

Specifications
Model M4N-DV-ᜡᜡ M4N-DA-ᜡᜡ  M4N-DI-ᜡᜡ
Measurement function DC voltage DC current DC4-20mA
Power supply 5VDC⎓, 12-24VDC⎓
Allowable voltage range 90 to 110% of rated voltage
Power consumption 2W
Display method 7 Segment LED Display(Character height: 10mm)
Max.display range Max. 1999
Display accuracy F.S.±0.2% rdg ±1digit
Sampling cycle 300ms
A/D conversion method Dual intergal method
Response time Approx. 2sec(0 to 1999)
Max.allowable input 150% of measurement input range
Sampling time 2.5 times/sec
Insulation resistance Over 100MΩ(at 500VDC megger)
Dielectric strength 2000VAC 50/60Hz for 1 minute
Noise immunity ±100V the square wave noise(pulse width: 1㎲) by the noise

simulator
Vibration| Mechanical| 0.75mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 1 hour
Malfunction| 0.5mm amplitude at frquency of 10 to 55Hz in each X, Y, Z direction for 10 minutes
Shock| Mechanical| 300m/s²(approx. 30G) in each X, Y, Z direction for 3 times
Malfunction| 100m/s²(approx. 10G) in each X, Y, Z direction for 3 times
Environment| Ambient temperature| -10 to 50℃, storage: -20 to 60℃
Ambient humidity| 35 to 85%RH, storage: 35 to 85%RH
Unit weight| Approx. 44g

※ Environment resistance is rated at no freezing or condensation.

Connections
  1. SOURCE※1
  2. [Position of the decimal point]
  3. INPUT
  4. Hold
  5. Dot
  6. HI

※ 1: 5VDC, 12-24VDC
※ When changing the position of the decimal point, disconnect switching pattern point on PCB and change the decimal point in external terminal socket.
※ When “1” or “-1” is flashes with a certain measurement input, disconnect power supply and
then check the cables.

Dimensions

(unit: mm)

  • Panel cut-out

  • 48×24 Bracket

Mounting
  1. Panel
  2. Max. 10.0mm

※Panel boad tickness should be less than 10.0mm.

Connections of Applications
Simultaneous connection of voltmeter and ammeter
  1. Power of the load
  2. Load
  3. HI
  4. LOW
  5. Voltmeter
  6. Ammeter
  7. DC power supply 1
  8. DC power supply 2

※ 1: Compared to measurement input range, higher measuring voltage needs a multiplier and lower measuring voltage needs a shunt.
※ When using voltmeter and ammeter simultaneously, connect the separated power supply each.
※ (-) terminal of the power and (-) terminal of measurement input are shorted.

Cautions during Use

1. Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
2. 5VAC, 12-24VDC power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
3. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
4. Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.

Connection with the line filter

  1. 110/ 220VAC
  2. Install the line filter close to the panel meter
  3. Panel meter
    a: HI
    b: LOW

Earth ground

Connection with the varistor

  1. 110/ 220VAC
  2. Panel meter
    a: HI
    b: LOW

5. This unit may be used in the following environments.
(1) Indoors (in the environment condition rated in ‘Specifications’)
(2) Altitude max. 2,000m
(3) Pollution degree 2
(4) Installation category II

Major products
  • Photoelectric Sensors
  • Temperature Controllers
  • Fiber Optic Sensors
  • Temperature/Humidity Transducers
  • Door Sensors
  • SSRs/Power Controllers
  • Door Side Sensors
  • Counters
  • Area Sensors
  • Timers
  • Proximity Sensors
  • Panel Meters
  • Pressure Sensors
  • Tachometer/Pulse (Rate) Meters
  • Rotary Encoders
  • Display Units
  • Connector/Sockets
  • Sensor Controllers
  • Switching Mode Power Supplies
  • Control Switches/Lamps/Buzzers
  • I/O Terminal Blocks & Cables
  • Stepper Motors/Drivers/Motion Controllers
  • Graphic/Logic Panels
  • Field Network Devices
  • Laser Marking System (Fiber, Co, Nd: YAG)
  • Laser Welding/Cutting System

Corporation
http://www.autonics.com

HEADQUARTERS:
18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,
South Korea, 48002
TEL: 82-51-519-3232
E-mail: [email protected]

DRW170795AA

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Autonics User Manuals

Related Manuals