IDEAL INDUSTRIES EMEA Lever and Gen II Lever Wire Connectors Push In Wire Connectors User Manual

June 17, 2024
IDEAL INDUSTRIES EMEA

IDEAL INDUSTRIES EMEA Lever and Gen II Lever Wire Connectors Push In Wire

Connectors

Installation Instructions

Lever & Gen II Lever Wire Connectors

  • Models 52, 53, 55, L2, L3 & L5
    • Do not exceed the rating of these connectors
    • Turn OFF the power before removing or installing connectors
    • Wiring must comply with all applicable electrical regulations
    • COPPER TO COPPER ONLY. Do not use aluminum wire.
    • Incorrect use of these connectors can cause electrical fires, personal injury or death
    • Use only one conductor per port
    • Strip wires back 9 – 10mm (52, 53 & 55) / 11-12mm (L2, L3 & L5)
    • For solid and rigid stranded wire, grip the wire firmly and insert the conductor into the open port (the lever does not need to be open)
    • For flexible stranded wire (>7 strands) lift the lever and insert the conductor into an open port. Close lever
    • Verify conductors are fully inserted to the back of the connector.
    • To remove a wire, lift the lever and pull out the wire

IDEA- INDUSTRIES-EMEA-Lever -and-Gen-II-Lever-Wire-Connectors-Push-In-Wire-
Connectors-FIG-2

Specifications

Specifications| Model 52 2-Port| Model 53 3-Port| Model 55 5-Port
---|---|---|---
Rating| 24 Amp / 450V / 85°C
Depth| 21 mm
Width| 11.9 mm| 16.1 mm| 24.5 mm
Height| 11.7 mm
Wire Combination Range| Solid, Rigid Stranded and Flexible Wires| 0.2mm2-2.5mm2

Specifications| Model L2 2-Port| Model L3 3-Port| Model L5 5-Port
---|---|---|---
Rating| 32 Amp / 450V / 85°
Depth| 18.6 mm
Width| 13.3 mm| 18.9 mm| 30.4 mm
Height| 8.8 mm
Wire Combination Range| Solid and Rigid Stranded| 0.2mm2 – 4.0mm2
Flexible Wires| 0.14mm2 – 4.0mm2

Push-In Wire Connectors

  • Models 32, 33, 34, 87, 88 90 & 39
    • Do not exceed the rating of these connectors.
    • Turn OFF the power before removing or installing connectors.
    • Wiring must comply with all applicable electrical regulations.
    • COPPER TO COPPER ONLY. Do not use on aluminum wire.
    • Incorrect use of these connectors can cause electrical fires, personal injury or death.
    • These connectors are suitable for solid and semi-rigid (<7 strands) conductors. They are not suitable or rated for use with flexible cable with >7 strands.
    • Strip wires back 13mm.
    • Grip the wire firmly and push the conductor into an open port.
    • Use only one conductor per port.
    • Connectors are reusable on solid wires of the same wire gauge or larger. If reusing connectors, cut and re-strip conductors.
    • In order to remove a wire, pull and twist the wire back and forth.
    • DO NOT RE-USE connector on stranded wire

IDEA- INDUSTRIES-EMEA-Lever -and-Gen-II-Lever-Wire-Connectors-Push-In-Wire-
Connectors-FIG-4


Specifications

| Model 32 Red

2- Port

| Model 33 Orange 3-Port| Model 34 Yellow 4-Port| Model 87 Grey

5- Port

| Model 88 Blue

6- Port

| Model 90 Black

8- Port

| Model 39 Blue

3- port

---|---|---|---|---|---|---|---
Rating| 32 Amp / 450V / 105°C maximum| 24 Amp / 450V / 105°C maximum| 41A/450/105°C
Depth| 19.81 mm| 18.52 mm| 18.52 mm| 18.21 mm| 19.8 mm
Width| 13.21 mm| 17.53 mm| 20.83 mm| 23.03 mm| 15.32 mm| 35.03 mm| 21.7 mm
Height| 9.65 mm| 9.02 mm| 15.42 mm| 9.02 mm| 11.4 mm
Wire Combination Range| Solid wire| 0.75mm2 to 4.0mm2| 0.75mm2 to 4.0mm2| 2.0-6.0mm2
Stranded wire*| 1.5mm2 to 2.5mm2| 1.5mm2 to 2.5mm2| 2.5-6.0mm2

SpliceLine Wire Connectors

Model 42

  • Do not exceed the rating of these connectors.
  • Turn OFF the power before removing or installing connectors.
  • Wiring must comply with all applicable electrical regulations.
  • COPPER TO COPPER ONLY. Do not use aluminum wire.
  • Incorrect use of these connectors can cause electrical fires, personal injury or death.
  • These connectors are suitable for solid and semi-rigid (<7 strands) conductors. They are not suitable or rated for use with flexible cable with >7 strands.
  • Strip wires back 13mm.
  • Grip the wire firmly and push the conductor into an open port.
  • Use only one conductor per port.
  • Connectors are reusable on solid wires of the same wire gauge or larger. If reusing connectors, cut and re-strip conductors
  • To remove a wire, pull and twist the wire back and forth.
  • DO NOT RE-USE connector on stranded wire.

IDEA- INDUSTRIES-EMEA-Lever -and-Gen-II-Lever-Wire-Connectors-Push-In-Wire-
Connectors-FIG-6

Model Colour Rating Wire Range
42 Orange 32A / 450V /105°C Solid: 0.5mm2 – 4.0mm2

Stranded*: 1.0mm2 – 2.5mm2

Stranded wire is limited to ≤ 7 strands

CONTACT

  • IDEAL INDUSTRIES EMEA
    • Unit 3, Europa Court, Europa Boulevard, Warrington, Cheshire, WA5 7TN, UK
    • +44 (0)1925 444446 | +49 (0)32221098955 | 33 (0)1 70 77 83 20 |
    • Fax: +44 (0)1925445501 |
    • eur.sales@idealindustries.com
    • idealind.com
  • IDEAL GmbH
    • Esslinger Strasse 7,
    • D – 70771 Leinfelden-Echterdingen, Germany

idealind.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals