NIPSCO ER 3-100-G Cabinet Current Transformer Owner’s Manual

June 1, 2024
NIPSCO

NIPSCO ER 3-100-G Cabinet Current Transformer

USE
For commercial and industrial installations, purchased and installed by customers. To enclose 600-volt insulation class current transformers on indoor or outdoor meter installations. For installing two or three current transformers only with provisions to bypass, remove, or replace while energized.

REVISION SUMMARY: Convert to current format. Emphasize Erickson cabinets intended for outdoor use require the additional purchase of a vent kit.

REFERENCE(S): (All references are latest revision; unless noted)

National Standard(s)

  • National Electrical Code® (NEC® ) 408.56: Minimum Spacings
  • NEC 408.58: Panelboard Marking

SPECIFICATIONS

GENERAL

  1. Cabinets shall meet all requirements of the above-referenced specifications, where applicable unless otherwise noted below.
  2. All current carrying parts shall be designed based on 1,000 amperes per square inch capacity for copper and 700 amperes per square inch for aluminum.
  3. All dimensions shown are minimum.
  4. Spacing between opposite polarity live parts and between live parts and ground mounted on the same surface not over 600 volts shall be a minimum of two inches and one inch, respectively.
  5. Cabinets shall be marked by the manufacturer with voltage, current rating, number of phases for which they are designed, and manufacturer’s name or trademark to be visible after installation, without disturbing interior parts or wiring.
  6. For use on single-phase 3-wire 240-volt, 3-phase 3-wire 240-volt delta, and 3-phase 4-wire 208Y/120 volt; 400 amperes maximum.

CABINET

  1. Material: Minimum 0.10″ aluminum or 14-gauge steel with enamel finish
  2. The front door or cover shall be hinged on the right (looking from the front of the cabinet) and equipped with a sealing device that ensures one padlock seal will effectively prevent the door or cover from opening.
  3. Line and load lug will accept one 600 KCM – #4 or two 350 KCM – 1/0 copper or aluminum conductors. One lug is provided per phase and neutral, line, and load.

Minimum Dimensions

Width (in)

W/O

Insulator Barriers

| With

Insulator Barriers

25| 20

Configuration

NIPSCO-ER-3-100-G-Cabinet-Current-Transformer-FIG-1

Connections

  1. Line connections shall be made on the top connection plate.
  2. Load connections shall be made on the bottom connection plate.

Current Transformer (CT) Primary Connection Plate:

  1. Material: 1/4″ × 3″ × 4″ copper or aluminum
  2. Drilled and tapped for current transformer, cable lug, and by-pass jumper bolts.
  3. The drawing shows six plates for mounting three 600 bolt class current transformers. When only two current transformers are required, omit neutral and provide a center phase link.

Neutral Connection Plate:

  1. Material: Copper or aluminum
  2. Drilled and tapped for cable lug bolts, #10 – 24 potential tap screws, and mounting bolts.

Mounting Bolts:

For CT’s:

  1. Material: Steel, zinc-plated, 1/2″ – 13 thread × 2-1/2″ long with flat washer and hex head nut
  2. Eight are required for two CTs / 12 are required for three CTs

For Cable Lugs:

  1. Material: Steel, zinc-plated, 1/2″ – 13 thread × 2-1/2″ long with flat washer and hex head nut
  2. Six are required for two CTs / eight are required for three CTs

For Jumper:

  1. Material: Steel, zinc-plated, 1/2″ – 13 thread × 2-1/2″ long with flat washer and hex head nut
  2. Four are required for two CTs / six are required for three CTs

For Insulator Bus:

  1. Material: Steel, zinc-plated, 1/4″ – 20 × 2-1/2″
  2. Eight Required

For Potential Tap:

  1. Material: Steel, zinc-plated, #10 – 24 × 1/2″ with washer

Lugs:

  1. One-hole cable terminal lug furnished for 500 KCM or larger
  2. Material: Copper
  3. Six are required for two CTs / eight are required for three CTs

Knockouts/Hubs

  1. Size and location by the customer when required.

CT MOUNTING AND BYPASS

  1. CTs, lug landing pads, and neutrals shall be rated at 400 amps.
  2. CTs provided by NIPSCO.
  3. The line and load lug provided shall accept one 600 KCM – #4 or two 350 KCM – 1/0 copper or aluminum conductors. One lug is provided per phase and neutral as shown in Section 3.4, line and load.

Configuration

NIPSCO-ER-3-100-G-Cabinet-Current-Transformer-FIG-2

OUTDOOR CABINET

  1. The door or front cover shall be rain-tight; the top shall be protected with a rain shield.
  2. NIPSCO requires vendor-specific vent kits to be purchased and installed per vendor specification on Erickson cabinets intended for outdoor use.
  3. All conduits shall enter the cabinet through the sides, bottom, or rain-tight top hub.
  4. All hardware shall be rust-resistant.

APPROVED MANUFACTURERS


Manufacturer

| ****

Phases

| ****

Wires

| ****

Number of CT’s

| Catalog Number
---|---|---|---|---
Indoor / Outdoor
Erickson Electrical Equipment 475 Bonnie Ln.

Elk Grove Village, Illinois

| 1 or 3| 3| 2| 1182-1 (Note 1)
3| 4| 3| 1182-2 (Note 1)


Milbank Manufacturing Co. 4801 Deramus

Kansas City, Missouri 64141

| 1| 3| 2| NIPM-413
3| 3| 2| NIPM-433
3| 4| 3| NIPM-434
Note-1: For outdoor cabinets, Erickson cabinets require the purchase and installation of an additional vent kit. Milbank cabinets do not require an additional vent kit.

  • Document is considered current only when viewed electronically on the Company’s Intranet.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals