Rinnai RHFE0800F LS Gas Fireplace Instruction Manual

June 1, 2024
Rinnai

Rinnai-logo

Rinnai RHFE0800F LS Gas Fireplace

Rinnai-RHFE0800F-LS-Gas-Fireplace-image

Product Information

Specifications:

  • Models: RHFE0800F, RHFE1000, RHFE1500
  • Type: Gas Fireplace
  • Manufacturer: Rinnai
  • Compatible Models: LS1000, LS1500, RHFE0800SF, RHFE0800DF, RHFE1000S, RHFE1000D, RHFE1500S, RHFE1500D

Product Usage Instructions

Warnings & Important Information:

  • Before using or installing this appliance, read the manual thoroughly.
  • Ensure installation and maintenance are done by an Authorized Person.
  • Follow local OH&S requirements for installation.
  • Perform a mandatory inspection before installation.
  • Avoid modifications to the appliance.
  • Adhere to general safety warnings for safe operation.

General Installation Information:

  • Choose a suitable location for installation.
  • Avoid placing TV or ornaments near the fireplace.

Framing:

  • Refer to framing dimensions for proper installation.
  • Ensure proper cavity ventilation.
  • Follow baseboard and cut-out guidelines.
  • Additional framing notes are provided for reference.

FAQs

  • Q: Can I install the gas fireplace myself?
    • A: No, the gas fireplace must be installed, commissioned, serviced, maintained, and removed ONLY by an Authorized Person.
  • Q: Is it safe to place TV or ornaments near the fireplace?
    • A: It is advised to avoid placing TV or ornaments near the fireplace to prevent any potential hazards.

“`

MODELS
Flametech® – V2 LS1000 – V2 LS1500 -V2

(RHFE0800F) (RHFE1000) (RHFE1500)

LS (V2) – Gas Fireplace
Installation Manual

Congratulations on the purchase of your Rinnai LS – Gas Fireplace. We trust you will have many years of comfort and enjoyment from your appliance.
BEFORE INSTALLING OR USING THIS APPLIANCE IMPORTANT Before proceeding with the operation or installation read this manual thoroughly and gain a full
understanding of the appliance, to ensure safe and correct installation and use.
This appliance must be installed in accordance with: · Manufacturer’s Installation Instructions · Current AS/NZS 3500 · Plumbing Code of Australia (PCA) · Local Regulations and Municipal Building Codes
including local OH&S requirements This system must be installed, commissioned, serviced, maintained and removed ONLY by an Authorised Person. For continued safety of this appliance it must be installed and maintained in accordance with the manufacturer’s instructions.

Rinnai

This manual to suit LS – Gas Fireplace Heater Models:

Flametech® *

LS1000

LS1500

RHFE0800SF RHFE0800DF

RHFE1000S RHFE1000D

RHFE1500S RHFE1500D

*Incorporates Flametech® self burning log technology.
2

RHFE0800F_1000_1500 IM

This appliance MUST be installed, maintained and removed ONLY by an Authorised Person.
WARNING For continued safety of this appliance it MUST be installed and maintained in accordance with the manufacturers instructions.

Rinnai

4

RHFE0800F_1000_1500 IM

WARNINGS & IMPORTANT INFORMATION

BEFORE USING OR INSTALLING THIS APPLIANCE
IMPORTANT Before proceeding with the operation or installation read this manual thoroughly and gain a full understanding of the appliance, to ensure safe and correct use.
Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in personal injury or death.
WARNINGS: Indicates a potentially hazardous situation which, if not avoided, could result in personal injury or death.
CAUTIONS: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury or damage to the appliance. It may also be used to alert against unsafe practices.

WARNING

REGULATORY INFORMATION This appliance shall be installed in accordance with:
Manufacturer’s Installation Instructions.

Current AS/NZS 3000, AS/NZS 3500 & AS/NZS 5601.

Local Regulations and Municipal Building Codes including local OH&S requirements.
This appliance has been certified by the Australian Gas Association. The A.G.A. Certification Number is shown on the data plate.
This appliance MUST be installed, maintained and removed ONLY by an Authorised Person.
For continued safety of this appliance it MUST be installed and maintained in accordance with the manufacturers instructions.

NOTICE TO VICTORIAN CONSUMERS
This appliance MUST be installed by a person licensed with the Victorian Building Authority. ONLY a licensed person will have insurance protecting their workmanship.
So make sure you use a licensed person to install this appliance and ask for your Compliance Certificate.ForfurtherinformationcontacttheVictorianBuildingAuthorityon1300815127.

WARNING

DRESS GUARD WARNINGS
The guard is fitted to this appliance to reduce the risk of fire or injury from burns and no part of it should be permanently removed. For protection of young children or the infirm, a secondary guard is required.
The glass dress guard supplied with this appliance MUST NOT be permanently removed as it fulfilsanoperationalsafetyfunction.Additionaldressguardsincludingfreestandingtypesmay be used in conjunction with, but NOT replace, the dress guard supplied with this appliance.

WARNING

MANDATORY INSPECTION PRIOR TO INSTALLATION
Immediately report any damage or discrepancies to the Supplier of the appliance. This appliance was inspected and tested at the time of manufacture and packaging, and released for transportation without known damage. Upon receipt, inspect the exterior for evidence of rough handling in shipment. Ensure that the appliance is labelled correctly for the gas and electrical supply, and/or other services it is intended to be connected to.
For safety and warranty purposes, appliances that may be damaged or incorrect MUST NOT be installed or operated under ANY circumstances. Installation of damaged or incorrect appliances may contravene local government regulations. Rinnai disclaims any liability or responsibility whatsoever in relation to the installation or operation of damaged or incorrect appliances.
Take care when opening or unpacking this appliance. Failure to do so may result in serious injury or product failure.
Check the label for the correct gas type (refer rating plate, inside the appliance). Refer to local gas authorityforconfirmationofthegastypeifyouareindoubt.

Rinnai

5

RHFE0800F_1000_1500 IM

WARNINGS & IMPORTANT INFORMATION

WARNING

MODIFICATIONS.
DO NOT MODIFY THIS APPLIANCE, modifyingfromoriginalspecificationsmaycreatea dangerous situation and will void your warranty. Failure to comply with these instructions could resultinafireorexplosion,whichcouldcauseseriousinjury,deathorpropertydamage.
DO NOT modify the electrical wiring of this appliance.
If the power cord is damaged or deteriorated then it MUST be replaced by an authorised person. Failuretodosomayresultinelectricshock,fire,seriousinjuryorproductfailure.
Improper installation, adjustments, service or maintenance can cause serious injury, death or property damage. Such work MUST ONLY be performed by an authorised person.

WARNING

GENERAL SAFETY WARNINGS

This appliance is HEAVY, during installation the use of a mechanical lifting aid is recommended, noting that improper lifting may result in serious injury.

WARNING: This heater MUST NOT be used if any of the glass panels are damaged.

Flue terminal MUST always vent directly to outdoors. DO NOT extend the flue vertically or horizontally in ways other than prescribed in this appliance manufacturer’s installation
instructions. ONLYthefluecomponentsspecifiedbyRinnaimustbeused.

When considering installation ensure minimum clearances as follows are adhered to, refer Fig. 1.

Heat radiating from the front of this heater

may over time affect the appearance of

some materials used for flooring such as 400mm carpet, vinyl, cork or timber. This effect may

be amplified if the air in the room contains

cooking vapours, candle vapours and cigarette smoke, etc. To avoid this possibility,

1000mm

it is recommended that a mat or similar

protective sheet be placed in front of the appliance, extending at least 750 mm in front

750mm

of the dress guard. Refer to the installation

manual for mantle clearances, additional

installation information and warnings.

400mm

Note that side and vertical clearances are measured from the edge of the glass.

400mm Fig .1

This appliance MUST NOT be installed where curtains or other combustible materials could come into contact with it. In some cases curtains may need restraining.

This appliance is NOT intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

The appliance is NOTintendedforusebyyoungchildrenorinfirmpersonswithoutsupervision. YoungchildrenandtheinfirmSHOULD be supervised at all times when in the vicinity of this heater while it is in operation.

The heater MUST NOT be located immediately below a power socket outlet.

A dedicated 230 V earthed 10 Amp power point must be used with this appliance.

Suitable ONLY for indoor installation.

DO NOT operate this appliance before leak checking hoses and gas cylinder connection.

NOT to be connected to an LP gas cylinder located indoors.

Please keep this instruction booklet in a safe place for future reference. All dimensions referred tointheseinstructionsareinmillimetres,unlessotherwisespecified.

DO NOT SPRAY AEROSOLS IN THE VICINITY OF THIS APPLIANCE.

DO NOT USE OR STORE FLAMMABLE MATERIALS IN OR NEAR THIS APPLIANCE.

DO NOT PLACE ARTICLES ON OR NEAR THIS APPLIANCE.

Rinnai

6

RHFE0800F_1000_1500 IM

WARNINGS & IMPORTANT INFORMATION

CARTON CONTENTS / ITEM CHECKLIST
The components for LS – Gas Fireplace heaters may be supplied in separate cartons, the following tables list which components are in each carton. Ensure that the components listed for the installation method being installed are present before proceeding with the installation.

CARTON CONTENTS

COMPONENTS DESCRIPTION

(A)

(B)

(C)

Engine

Burn Media

Flue

(1) LS – Gas Fireplace Heater Engine. (2) Glass frame. (3) ½” BSP Flare Adaptor and Nut (packed separately in parts plastic bag). (4) Remote control (batteries included) (5) Operation and Installation manual. (6) Burn media installation guide. (7) Colour burn media placement sheet (attached to the glass frame) (8) Commissioning sheet (attached in a plastic pouch inside engine) (9) Burner media – RHFE0800F ONLY (shipped inside engine) (10) Flue lock bracket and truss screws (x2) (11) Burn media – RHFE1000/1500 ONLY (packaged separately). (12) Flue components and accessory items are ordered separately.

Rinnai

7

RHFE0800F_1000_1500 IM

GENERAL INSTALLATION INFORMATION

LOCATION
When positioning the heater, the main variables governing the location are Flueing and Warm Air Distribution.
This heater MUST NOT be installed where curtains or other combustible materials could come into contact with it. In some cases curtains may need restraining. Refer to “General Safety Warnings” on page 6 for additional safety considerations.
Horizontal and vertical clearances are measured from the edge of the burner box IMPORTANT glass.

400mm 1000mm

400mm

257mm

400mm

Combustible mantles and surrounds can be added to compliment the design provided that they conform to the following clearances requirements.
The minimum clearance from the edge of the burner box glass is 400 mm. The depth of the mantle or surround (A) at this minimum clearance may not exceed 250 mm.
An additional 100 mm of clearance is required for every extra 50 mm of mantle depth. The depth of the mantle or surround (B) at 500 mm of clearance may not exceed 300 mm.
Refer to the section “Wall Lining Installation” starting on page 28 for additional information.
Refer “Cavity Ventilation” on page 9 for cavity ventilation details.
Combustion product spillage testing must be conducted during appliance commissioning. This testing may show a need for additional
NOTE
fixedventilation.

257mm

400mm 1000mm

500mm 400mm

B = 300mm = 250mm
A
400mm

TV & ORNAMENTATION WARNING

CAUTION

INSTALLATION OF TV OR ORNAMENTATION ABOVE THE HEATER
The installation of electrical appliances above and in the vicinity of the heater such as, but not limited to, Plasma TV, LCD TV, Home Theatre Screens, Speakers, etc must comply with their manufacturers’ instructions. It is the responsibility of the installer/end-user to check the installation instructions of these items and to ensure the location is suitable.
This caution also extends to, but is not limited to, ornaments such as: Paintings, Prints, Photographs,Tapestries,Mirrors,StuffedAnimals,etc.
Please note the recommended clearances as per the diagram above. The temperature of the wall surfacedirectlyabovetheappliancemaybeelevatedandmaydiscolourpaintfinishesordistort vinyl wall coverings. For durability of surfaces you should contact the relevant manufacturer for theirspecification.

RINNAI DOES NOT TAKE ANY RESPONSIBILITY FOR ANY DAMAGE OCCURRING TO ANY ITEMS INSTALLED ABOVE AND IN THE VICINITY OF THE HEATER.
WARNING
Use either a shelf or mantle below the TV or ornament or alternately you can construct a recess to mount TV or ornament in. Check the manufacturers installation instructions for these items IDEA and ensure the recess is suitable.

Rinnai

8

RHFE0800F_1000_1500 IM

FRAMING
FRAMING DIMENSIONS Framework of the installation must conform to local building codes. Non-combustible materials need not be used. If the appliance is elevated from the ground within the structure, a base must be constructed using suitable material with supporting joists capable of supporting a minimum of 1.5 times the weight of the appliance.

AS/NZS5601″GASINSTALLATIONS”requiresthatfluecomponentsbesupportedindependently of the appliance.
CAUTION

For the following framing dimensions it is important to be aware that the studs are offset–the cavity needs to be framed based on the centreline of the glass, not the opening size.
Base Board and Cut-outs
To ensure everything lines up and fits properly, it is recommended that on the base the following dimensions are pencilled; glass centreline, unit depth centreline, feet position, gas and room thermistor cut-outs.
Glass centreline

C

D

A

B

E

Gas supply access Thermistor / ambient air access Ø 40 mm

Dimension E assumes 10 mm plaster board Drawing is for a top down view

  • Assumes 10mm plasterboard / All dimensions in mm

RHFE0800F RHFE1000 RHFE1500

A Thermistor / ambient air access – right glass of centreline

50

50

225

B

Gas supply access – left of glass centreline

220

220

220

C

Support feet centres – left of glass centreline

640

740

990

D

Support feet centres – right glass of centreline

360

460

710

E Gas supply / thermistor access – from front of enclosure*

87

87

87

CAVITY VENTILATION
Ventilation areas of at least 2000 mm² each, are required in the cavity, ideally adjacent to the bottom end, and to the top end of the appliance. This is to allow room temperature air to enter the heater cavity at the bottom, and to exit at the top from the hotter areas of the fireplace cavity. This ventilation reduces heat buildup in the cavity and allows the product to run at its highest efficiency. The ventilation can be either via placement of manufactured vents or a specifically sized opening or gap within the structure.
When a material such as wood, susceptible to heat damage, is installed directly above the appliance, it is important to allow a sufficient air gap and fit a non-combustible material underneath. All clearances specified in this manual must be provided.
ADDITIONAL FRAMING NOTES
Plaster board is set 1 mm back from the front edge of the frame to allow for a slim edge plaster finish.
To ensure correct and rattle free performance, the appliance MUST be installed on a flat level support base.
Issuescausedbyrattlingfiresnotinstalledonaflatlevelbase,asdetailedinthisguide,willNOT be covered by warranty.
IMPORTANT

Rinnai

9

RHFE0800F_1000_1500 IM

FRAMING

FRAMING FOR RHFE0800F

IMPORTANT

To prevent the transfer of heat from the heater engine to surfaces (including to surfaces of non-
combustible materials), a minimum 50 mm clearance MUST be maintained. Failure to provide this clearance(especiallyatthenonflueconnectionendoftheheaterengine)maycausepermanent heat damage to adjacent wall materials.

All dimensions are assuming a 10 mm plaster board.

Studs and joists are required directly below the support feet of the appliance.

Framingshownis90x45mmandthefireplatformshownis18mmplywood.

Allowroomunderneaththeapplianceforthegassupplytoenterthefirecavity(min.100mm).

The framing dimensions have the studs offset. This is because the cavity needs to be framed based on the centreline of the Linear glass, NOT the opening size.

Where there is a requirement for a symmetrical installation, the cavity size will need to increase, refer to the diagram below.

80**

845 770

Assumes 10 mm wallboard
49

310

** Maintain 25 mm clearance to combustibles for first 300 mm of flue
1690 (for symmetrical cavity) 1365

Recommended that lintel is left until fire is installed so minimum clearances can be maintained

845

1250 730 Min

520 Min

  • Wallboard cut-outs

500 **

816 *

566 *

1020 Min

~800

257 ±5 *

Min. 50 mm clearance to top and sides

640

360

· All dimensions are assuming 10 mm wallboard · Studs and joists are required below supoort feet of fire · Framing shown is 90 mm x 45 mm · Fire platform shown is 18 mm Plywood · Allow room for gas supply to enter fire cavity through base

Rinnai

10

413+ 425+
+413 mm assumes 10 mm wallboard on both sides of double sided fire. +425 is minimum for single sided fire with 10 mm wallboard to maintain 50 mm clearance to back of fire.
RHFE0800F_1000_1500 IM

FRAMING

FRAMING FOR RHFE1000

IMPORTANT

To prevent the transfer of heat from the heater engine to surfaces (including to surfaces of non-
combustible materials), a minimum 50 mm clearance MUST be maintained. Failure to provide this clearance(especiallyatthenonflueconnectionendoftheheaterengine)maycausepermanent heat damage to adjacent wall materials.

All dimensions are assuming a 10 mm plaster board.

Studs and joists are required directly below the support feet of the appliance.

Framingshownis90x45mmandthefireplatformshownis18mmplywood.

Allowroomunderneaththeapplianceforthegassupplytoenterthefirecavity(min.100mm).

The framing dimensions have the studs offset. This is because the cavity needs to be framed based on the centreline of the Linear glass, NOT the opening size.

Where there is a requirement for a symmetrical installation, the cavity size will need to increase, refer to the diagram below.

80**

945 870

Assumes 10 mm wallboard 49

310

** Maintain 25 mm clearance to combustibles for first 500mm of flue

Recommended that lintel is left until fire is installed so minimum clearances can be maintained

1890 (for symmetrical cavity)

1565 945

1450 830 Min

620 Min

  • Wallboard cut-outs

1016 *

500 **

257 ±5 341

796 Min

~ 575

740

460

· All dimensions are assuming 10 mm wallboard · Studs and joists are required below supoort feet of fire · Framing shown is 90 mm x 45 mm · Fire platform shown is 18 mm Plywood · Allow room for gas supply to enter fire cavity through base

Rinnai

11

Min. 50 mm clearance to top and sides

413+ 425+

+413 mm assumes 10 mm wallboard on both sides of double sided fire.
+425 is minimum for single sided fire with 10 mm wallboard to maintain 50 mm clearance to back of fire.

RHFE0800F_1000_1500 IM

FRAMING

FRAMING FOR RHFE1500

IMPORTANT

To prevent the transfer of heat from the heater engine to surfaces (including to surfaces of non-
combustible materials), a minimum 50 mm clearance MUST be maintained. Failure to provide this clearance(especiallyatthenonflueconnectionendoftheheaterengine)maycausepermanent heat damage to adjacent wall materials.

All dimensions are assuming a 10 mm plaster board.

Studs and joists are required directly below the support feet of the appliance.

Framingshownis90x45mmandthefireplatformshownis18mmplywood.

Allowroomunderneaththeapplianceforthegassupplytoenterthefirecavity(min.100mm).

The framing dimensions have the studs offset. This is because the cavity needs to be framed based on the centreline of the Linear glass, NOT the opening size.

Where there is a requirement for a symmetrical installation, the cavity size will need to increase, refer to the diagram below.

Assumes 10 mm wallboard 49

80**

1195 1120

310

** Maintain 25 mm clearance to combustibles for first 500 mm of flue
2390 (for symmetrical cavity)
2065
1195

1080 Min

1950

870 Min

Recommended that lintel is left until fire is installed so minimum clearances can be maintained

  • Wallboard cut-outs

1516 *

500 **

341 257 ±5

796 Min

~ 575

990

710

· All dimensions are assuming 10 mm wallboard · Studs and joists are required below supoort feet of fire · Framing shown is 90 mm x 45 mm · Fire platform shown is 18 mm Plywood · Allow room for gas supply to enter fire cavity through base

Rinnai

12

Min. 50 mm clearance to top and sides

413+ 425+

+413 mm assumes 10 mm wallboard on both sides of double sided fire.
+425 is minimum for single sided fire with 10 mm wallboard to maintain 50 mm clearance to back of fire.

RHFE0800F_1000_1500 IM

SUPPLY CONNECTIONS

INSTALLING ENGINE INTO CAVITY Using the handholds (white slots on the left hand end and carry bars on the right hand end), carefully lift and slide the heater engine into the enclosure and position in place.
Carry bar position, two carry bars
Hand hold Adjustable Feet Use the feet on all corners of the unit to adjust the fire so that it is level. The feet are adjustable. Having the unit level is critical to the installation, so the wall lining can be installed flush with the frame edge of the appliance. Seismic Brackets In areas where seismic activity can be expected. Secure the heater engine to the bottom of the cavity using the four seismic brackets.

To level the unit and not affect where the feet go, the seismic brackets need to be elevated before the unit is installed into the cavity

Rinnai

13

RHFE0800F_1000_1500 IM

SUPPLY CONNECTIONS
REMOVING THE BURNER BOX GLASS The glass front sits in a narrow channel at the bottom of the fire and is held in place by glass retainer latches positioned at the top, either side of the unit (the 1500 model has an extra glass retainer latch in the centre).
Take care when lifting the glass from the engine noting the glass for the RHFE1500 weighs approximately 7 kg.
IMPORTANT
Removal Procedure: Using a screwdriver, loosen the three screws holding the louvre in place, remove the louvre, and then remove the screws (so the glass can come out) and put the louvre to one side. 1. Push the top glass retainer latches up and slightly to one side to release the top section of the glass. These
will stay in the upright position if moved slightly to one side 2. Using the frame tabs at the top of the glass frame, lift up and gently slide to the right and rotate the glass until
the left section comes free, then move the glass panel to the left to remove the right section.

Push up the latch and slide to the side to release the glass

Glass retainer latch

Glass front tabs

Rinnai

14

RHFE0800F_1000_1500 IM

SUPPLY CONNECTIONS

GAS SUPPLY

WARNING

Gas pipe sizing must consider the gas input to this appliance as well as all other gas appliances inthepremises.Thegasmeterandregulatormustbespecifiedforthetotalgasrate.
A suitable sizing chart such as the one in AS/NZS 5601 should be used.

The use of rubber hose for any gas connection to a fixed appliance is NOT authorised by the manufacturer.

Confirmcorrectgastype(seelabelslocatedontoporrearpanels).Refertolocalgasauthority IMPORTANT forconfirmationofgastypeifyouareindoubt.

Installation of Consumer Piping

The gas supply (consumer piping), termination is inside the heater and enters through the base of the appliance.
A ½” BSP flared nut (A) and a ½” BSP Male Flare x ½” Barrel Union (B) are provided for connection to the consumer piping (C). They are shipped inside the engine attached to on the gas inlet connection of the heater.

B

A

D

C

Once the gas connection is made lock the sliding plate (D) in place to stop the connection rattling, refer to the images right.

Purging Gas Supply

Foreign materials and debris such as swarf,

D

D

filings, etc. MUST be purged / removed from the

gas supply, failure to do so may cause damage

to the gas control valve causing it to malfunction.

Leak Testing the Connection

Plug the end of the consumer piping gas and leak test all joints.

Use a soapy solution to test all gas connections. If a leak is present bubbles will form at the leak
point.Whenfinishedremoveanyresiduewitharag.Preventanysoapysolutionfromcomingin CAUTION contact with electrical components.

ROOM THERMISTOR
Once installed the room temperature thermistor should be set so the bulb on the end is outside of the fire box and into an area where room air will be drawn over it from the lower room ventilation, refer to the image below.
The room temperature thermistor is provided with a 1.5 metre lead and is to be positioned so that itisintheairflowofthecavityventilation.Itmaybemounteddirectlytotheinsideofanairvent IMPORTANT grill. The thermistor MUST be accessible for servicing after the wall linings have been installed.

Rinnai

15

RHFE0800F_1000_1500 IM

SUPPLY CONNECTIONS ELECTRICAL SUPPLY
This heater has a 1.5 m power cord with a three pin plug supplied. The power cord passes through a slot in the front right hand side of the appliance, approximately 150 mm from the front of the unit.

approx. 150 mm
If a power point is used it MUST be 230 V, rated at 10A and MUST be earthed. This power point MUST NOT be located above the heater and a switch provided to electrically isolate the appliance for servicing.
Direct Wired Installations Alternatively the appliance can be direct wired to conceal the power supply.
Aqualifiedelectricianwillneedtobeconsultedwhereadirectwiredinstallationisrequired. A switch is to be provided to electrically isolate the appliance for servicing. IMPORTANT Any such installation must comply with the requirements of AS/NZS 5601, AS/NZS 3000 and any other relevant local regulations.

Rinnai

16

RHFE0800F_1000_1500 IM

FLUEING

Thefollowinginformationisprovidedasabasicoverviewofthefluesystemrequirements.Refer
to the LS – Gas Fireplace, Flue Installation Manualwhichisprovidedwithfluetransition IMPORTANT componentsforcomprehensivedetailsregradingtheinstallationofthefluesystem.

FLUE EXHAUST & AIR INLET CONNECTIONS

The following steps in the installation are critical. If the connections are not secured correctly, then products of combustion could disperse into the room being heated.
WARNING
1. Connect the flue terminal exhaust connection to the flue exhaust outlet, and secure in place (two screws) with the flue locking bracket (supplied in the accessories plastic bag with the remote control).
2. Secure the flue transition to the framing using a wall clip (supplied with LSFKIT01/02 or ASPDFK). 3. Attach the air intake hose to the large air inlet connection on the flue transition (LSFKIT01/02 or ASPDFK)
and secure in place with the supplied cable tie (also supplied), noting that the other end of the air inlet hose is already pre-installed to the appliance.
4. Ensure that the rubber cap remains secured in place on the unused (small) air inlet connection.

Flue exhaust outlet

Flue exhaust locking bracket

Air inlet hose (shown installed)

Air inlet hose (This end is to be fitted to LSFKIT01/02
or ASPDFX)
Air inlet hose (This end is supplied pre-fitted to the appliance)
LSFKIT01/02 (Extension piece not shown)
ASPDFK

Flue exhaust locking bracket (shown installed)
Flue exhaust connection
Flue exhaust locking bracket (shown installed)
Air inlet hose (This end is supplied pre fitted to the appliance)

Air inlet hose
Flue exhaust locking bracket Rinnai

Flue exhaust

connection

Flue exhaust

connection

Large air inlet

connection

17

Small air inlet connection (Rubber cap MUST remain in place)
RHFE0800F_1000_1500 IM

FLUEING

INSTALLATION CONFIGURATION WARNINGS
ONLY the Rinnai flue system components specified in this reference manual MUST be used. Components NOTspecifiedinthesemanuals,whethermanufacturedbyRinnaiorotherwise,are WARNING NOT compatible and MUST NOT be used! Rinnai appliance warranty conditions may be voided if nonRinnaifluecomponentsarefitted.
Use ONLY the supplied silicone grease when lubricating the O-rings.
ONLY an authorised person MUSTinstall,serviceandremovetheRinnaiheater&fluesystem.
Themaximumfluelengthis8.5m(1) and the maximum number of 90° bends is 3 (2). (1) Forevery90°bend,theoverallfluelengthMUSTbereducedby1m.
(2) The90°bendofthefluetransitionpieceisNOTcountedasa90°bend.
LS/Flametechseriesheaterscombustionsettingsarefactorysetfor”longflue”,whichisforflue lengthsthatare3metresorgreater.Forfluelengthsshorterthan3metresitmaybenecessaryto change dip switch setting, refer to the commissioning instructions for full details.
Note 1. When cutting the flue transition for joining to other components the minimum total length MUST NOT be less than 300mm!
NOTE

Note 2. TheallaluminiumflueextensioncomponentMUSTbefittedatthispoint.
NOTE

Note 3. Where stipulated a Minimum 2° fall towards the terminal is required to ensure correct

NOTE

drainageofcondensationformedinthedischargeflue.

Note 4. Where stipulated a Minimum 2° fall towards the appliance is required to ensure correct

NOTE

drainageofcondensationformedinthedischargeflue.

Cut to correct length & discard

!
See Note 1.

Cut to correct length & discard

!
See Note 1.

!
See Note 3.

Cut to correct length & discard

LSFDFK01
!
See Note 1.

!
See Note 3.
Cut to correct length & discard

LSFDFK01 ESPIPE900
!
See Note 1.

!
See Note 3.
DIRECT

LSFKIT01 ! ESWTERM
See Note 2.

!
See Note 3.
DIRECT EXTENDED

LSFKIT01 ESPIPE900 ESWTERM

!
See Note 2.

!
See note 3.
A

Cut to correct length & discard

!
See note 3.
A

!
See Notes 1 & 4.

!
See Notes 2 & 4.

!
See note 3.
Rinnai

A

LSFDFK01

18

LSFKIT01 OFFSET
RHFE0800F_1000_1500 IM

VERTICAL ROOF

VERTICAL ON-WALL

ESWTKIT2
(Flue Terminal, Terminal Adapter,
Wall Plate & Fixings)

C

C

FLUEING

Cut to correct length & discard

!
See Note 3.

27mm

31mm Minimum 70mm

!
See Note 4.
!
See Note 2.

LSFEXTKIT01

!

! See Note 2.

C !

See Note 4.

!

See Note 4.

See Note 1.

!
See Note 2.

C

!

!

See Note 4.

See Note 2.

DOWN & OUT / UNDER UNDER FLOOR

!
See Notes 1 & 3. *

B
Cut to correct length & discard
B
B !
See Note 3.
B B
Rinnai

  • !
    See Notes 2 & 3.

!
See Note 2.

B
19

B B
RHFE0800F_1000_1500 IM

B

FLUEING
FLUE TERMINAL LOCATION
EnsurethatthelocationoftheflueterminalcancomplywiththerequirementsofAS/NZS5601WARNING Fig. 6.2 which is reproduced in part below.
AS/NZ 5601 was current at the time of printing but may have been superseded. It is the installer’s responsibility to ensure that requirements of the current version of AS/NZS 5601 are met. Refer to separately supplied Rinnai LS – Gas Fireplace – Flue Installation Manual for comprehensive flueinstallationdetails.

Opening into a building

g

S

T

C T
f T

a j

Door h
n j

e

T

P

h

k
I k

j

d

T

e

d

g

Z

M

b

T

LEGEND: I = Mechanical air inlet M = Gas meter P = Electricity meter or fuse box S = Structure

See Note 1

Direction of discharge

T = Flue terminal Z = Fan-assisted appliance only

Shading indicates prohibited area for flue terminals

T See Note 1

g T

Min. Clearances

(mm)

Ref.

Item

Fan Assisted

Below eaves, balconies and other projections:

a · Appliances up to 50 MJ/h input

200

· Appliances over 50 MJ/h input

300

b From the ground, above a balcony or other surface *

300

c Front a return wall or external corner *

300

From a gas meter (M) (see 5.11.5.9 for vent terminal location of regulator )

d (see Table 6.6 for New Zealand requirements)

1000

e From an electricity meter or fuse box (P)

500

f From a drain pipe or soil pipe

75

g Horizontally from any building structure* = or obstruction facing a terminal

500

h From any other flue terminal , cowl, or combustion air intake

300

Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a

building with the exception of sub-floor ventilation:

· Appliances up to 150 MJ/h input *

300

j · Appliances over 150 MJ/h input up to 200 MJ/h input *

300

· Appliances over 200 MJ/h input up to 250 MJ/h input *

500

· Appliances over 250 MJ/h input *

1500

· All fan-assisted flue appliances , in the direction of discharge

1500

k From a mechanical air inlet, including a spa blower

1000

Vertically below an openable window, non-mechanical air inlet, or any other opening into a building with the exception of sub-floor ventilation:

· Space heaters up to 50 MJ/hr input

150

n

· Other appliances up to 50 MJ/hr input

500

· Appliances over 50 MJ/h input and up to 150 MJ/h input

1000

· Appliances over 150 MJ/h input

1500

i
iii
ii
i Minimum clearance 500mm to nearest part of roof ii Minimum clearance 25mm to any combustible materials iii Decktite or lead collar flashing * – unless appliance is certified for closer installation – Prohibited area below electricity meter or fuse box extends to ground level. NOTES: 1 Where dimensions c, j or k cannot be achieved an equivalent horizontal distance measured diagonally from the nearest discharge point of the terminal to the opening may be deemed by the Technical Regulator to comply. 2 See Clause 6.9.4 for restrictions on a flue terminal under a covered area. 3 See Figure J3 for clearances required from a flue terminal to an LP Gas cylinder. A flue terminal is considered to be a source of ignition. 4 For appliances not addressed above acceptance should be obtained from the Technical Regulator. FIGURE 6.2 (in-part) MINIMUM CLEARANCES REQUIRED FOR FAN-ASSISTED FLUE TERMINALS, ROOM-SEALED APPLIANCE TERMINALS AND OPENINGS OF OUTDOOR APPLIANCES

Theflueterminalshouldbepositionedawayflammablematerials.
WARNING

Rinnai

20

RHFE0800F_1000_1500 IM

FLUE COMPONENTS

LSFDFK01 (Direct Flue Kit for Rinnai Flamefires)
Internal Wall Plate
External Wall Plate

FLUEING

LSFKIT01 (Flue Adaption Kit)
Transition Extension Pipe

LSFKIT02 (Extended Flue Adaption Kit)
Co-ax Vertical Terminal

Flue Terminal

Silicon Grease

22mm x6

7mm x2

Mounting/Securing Screws
ESBEND
Co-ax Bends & Pipe Locating Spacer x2
BOTH spacers are required for all offset and extended offset installations!

Flue Transition

Spacer

Flue Transition

3x Co-ax Pipe

Co-ax Bends & Pipe Locating Spacers x 2

(This manual also included)
ESPLATE
External Wall Plate

Wall Clip

Silicon Grease

Transition Extension Pipe

22mm x3

7mm x2

Mounting/Securing Screws

(This manual also included)
LSFEXTKIT01
Transition Extension Pipe

Spacer

ESROOFCOWL

Wall Clip

Extension Pipe

ESPIPE900
Co-ax Pipe

Co-ax Vertical Terminal

Spacer Silicon Grease
ESWTERM
External Wall Plate

Wall Clips x5 Silicon Grease x2 (This manual also included)

ESWFG

Flue Guard

Wall Clip
Rinnai

Flue Terminal

22mm x6

7mm x2

Mounting/Securing Screws

ESWTKIT2 (On-Wall Terminal Kit)

Wall Clip

Terminal Adaptor Flue Terminal

21

External Wall Plate

M4 x 22mm 8g x 10mm

x3

x2

Mounting/Securing Screws
RHFE0800F_1000_1500 IM

COMMISSIONING

GENERAL INFORMATION
Accessing the commissioning instructions installed in the bottom of the unit will not normally occur during installation, which is why the instructions are detailed in this section of the manual.
NOTE
For servicing and maintenance purposes the commissioning instructions are also included in the service manual. The location of the commissioning instruction pouch within the appliance is as follows:
RHFE1500 – Located to the right hand side of the gas control
RHFE0800F/1000 – Located tucked in behind the Wi-Fi module

When performing the commissioning, the appliance electrical power will need to be connected. Exercise CAUTION as there is potential for electric shock from the exposed wiring and circuitry. WARNING DO NOT leave the appliance unattended when power is connected and the panels are removed.
Installation and commissioning must be carried out by an Authorised person.
Wiring inside this appliance may be at 240V potential.
DO NOTtestforgasescapeswithanopenflame.
LS-GasFireplaceheatershavetwodipswitchsettingsforfluelength. IMPORTANT L-F (Long Flue) this is the factory set default and in general will not require alteration.
S-F (Short Flue) refer to service manual or contact Rinnai for further details.
During commissioning the plastic push buttons on the PCB are required to be pressed to make adjustments. DO NOT use mechanical items such as screwdrivers to depress these button as this may lead to breakage.
GAS PRESSURE SETTING
The LS – Gas Fireplace heaters come with the high and low operating pressures factory pre-set.
IMPORTANT Gas Supply and Burner pressures MUST BE checked during installation and prior to the installationoftheburnmedia.Thisistobedonewiththeglassoffandbeforetheburnmedia* is added. Make adjustments if the unit is not operating correctly after all other possible other causes have been eliminated.
Inlet supply pressure to the appliance MUST be checked and set within the operating parameters of the appliance in all instances. If the appliance cannot be adjusted to perform correctly contact Rinnai for advice.
Confirmgastype:thisapplianceavailableineitherNaturalorPropanegas,checklabellingontop paneltoverifygastype.Contactlocalgasauthoritytoconfirmgassupplytypeifyouareindoubt.

  • For heaters fitted with the Flametech® burner media (models RHFE0800SF/DF), the two large logs supplied with the burn media are also the main burners for these appliances. As such it is necessary to temporarily install these logs onto the aeration sleeves during commissioning.
    The pressures can be checked by operating the buttons on the control panel PCB through the front access panels of the heater before the wall lining has been installed, or by pulling out the control panel PCB and accessing the buttons through the opening from the front of the appliance as shown right.
    Check the pressures against those printed on the data plate of the appliance. If the data plate is not easily accessible the pressures are also detailed on the next page. Even if no adjustment of the gas pressures is required, access to the ‘SET’ button may be required to proceed to the next setting.

Rinnai

22

RHFE0800F_1000_1500 IM

COMMISSIONING
COMMISSIONING THE PCB
PCB commissioning steps are ONLY to be done if the PCB is being replaced or after a gas conversion.
IMPORTANT
1. Turn on the gas and power supply. 2. Press the ‘Test’ button, the display will now show the gas code (A1 = Natural, L1 = Propane). Press the
‘Up’ and ‘Down’ buttons to obtain the gas code for the unit, and press ‘Set’ to lock in the code.

Commissioning of the PCB is now complete and the gas pressures can now be checked. ROOM THERMISTOR OFFSET

The PCB has an additional LED display sequence which will appear after the gas code. This is for
thesettingofroomthermistoroffset.Bydefaultthisisfactorypre-setto0 (0°C) and ONLY needs IMPORTANT adjustmentifthereissignificantvariationinthethermistorreadingandtheactualtemperatureof
the room. Adjustment of this setting is typically NOT required and is NOT part of commissioning.

Thermistor Offset Adjustment

When required adjustment of the offset can be made in 1/3°C steps to ±5°C. Pressing the ‘Up’ button offsets the temperature +°C, pressing the ‘Down’ button offsets the temperature -°C. Refer below for the full adjustment range.

± Display Value 0 ± Temp. Offset °C 0

12 1/3 2/3

3 4 5 6 7 8 9 10 11 12 13 14 15 1 1 1/3 1 2/3 2 2 1/3 2 2/3 3 3 1/3 3 2/3 4 4 1/3 4 2/3 5

GAS CONTROL SOLENOIDS Gas control RHFE0800F/1000

Gas control RHFE1500 (additional solenoid)

1

1

Rinnai

2 4
3
1 Inlet pressure test point screw 2 Pilot pressure test point screw

2

3

4

3 Pilot pressure adjustment screw 4 Main burner pressure test point screw

23

RHFE0800F_1000_1500 IM

COMMISSIONING

GAS PRESSURES RHFE0800SF/DF

Gas Type

Natural Propane Unit
S-F L-F S-F L-F

Gas rate Hi Gas rate Lo

35 32 15

35 32 15

MJ/hr

LH RH injector Ø Aeration sleeve LH RH

2.0 4.5 x 1

1.30 mm
9 x 2

Pilot

0.98

2.0

PL

0.20

0.25

kPa

PH

0.95 0.79 1.70 1.35

RHFE1500S/D

Gas Type

Natural Propane Unit
S-F L-F S-F L-F

Gas rate Hi Gas rate Lo

40 37 14

40 37 14

MJ/hr

Main injector Ø

2.3

1.4

LH RH injector Ø

1.6

Aeration sleeve centre

22.5

0.95 mm
N/A

Aeration sleeve LH RH

21

17

Pilot

0.98

2.0

RHFE1000S/D

Gas Type

Natural Propane Unit
S-F L-F S-F L-F

Gas rate Hi Gas rate Lo

34 31 15

32 29 14

MJ/hr

LH RH injector Ø

2.8

Aeration sleeve LH RH

22

1.7 mm
0

Pilot

0.98

2.0

PL

0.19

0.40

kPa

PH

0.80 0.65 1.85 1.57

PL

0.3

1.0

PF

0.87

2.0

kPa

PA

0.59

1.0

PH

0.80 0.67 1.90 1.54

S-F = Short Flue Setting L-F = Long Flue Setting LH = Left Hand RH = Right Hand

PL = Main burner on Low PF = Main burner on High PA = All burners on Low PH = All burners on High

SETTING GAS PRESSURES

The sequence will vary slightly depending on the model:

IMPORTANT Linear 800, 1000: PL > PH

Linear 1500:

PL > PF > PA > PH

Checking the Supply Pressure
1. Remove the inlet test point screw and connect the manometer hose. 2. Press the heater ‘ON/OFF’ button to start the ignition sequence, ensuring the correct inlet pressure is available
with all other gas appliances operating on high. 3. Press the heater ‘ON/OFF’ button to stop the heater operation. 4. Disconnect the manometer hose and replace the inlet test point screw.

Rinnai

24

RHFE0800F_1000_1500 IM

COMMISSIONING

Setting the Pilot Pressure

IMPORTANT

Beforecommencingwiththesettingoftheburnerpressuresthecorrectfluelength MUST be set.
ThefluelengthdipswitchisfactorysettoL-F(longflue).Forinformationregarding the S-F(shortflue)setting,refertotheservicemanualorcontactRinnai.

1. Remove the pilot test point screw and connect the manometer hose.
2. Press the heater ‘ON/OFF’ button to start the ignition sequence, ensuring the correct inlet pressure is available with all other gas appliances operating on high.
3. Press the ‘Test’ button twice, the heater will light to main burner on its lowest setting (stage 1) and the display will show PL.
4. Adjust the pilot pressure as required by manually adjusting the pilot pressure adjustment screw. Press the ‘ON/OFF’ button to stop the heater operation.
5. Disconnect the manometer hose and replace the pilot test point screw.
Setting the Operating Pressure
1. Remove the main burner test point screw and connect the positive manometer hose.
2. Press the heater ‘ON/OFF’ button to start the heater.
3. Press the ‘Test’ button twice, the heater will light to the main burner on its lowest setting (stage 1) and the digital display will show PL.
4. Press the ‘Up’ or ‘Down’ buttons to set the pressure for the appropriate gas type. Press the ‘Set’ button once to save the setting.
For RHFE1500 ONLY:
5. The display will now show PF (main burner stage 3). Press the ‘Up’ or ‘Down’ buttons to set the pressure for the appropriate gas type. Press the ‘Set’ button once to save the setting.
6. The display will show PA (main burner stage 4). Press the ‘Up’ and ‘Down’ buttons to set the pressure for the appropriate gas type. Press the ‘Set’ button once to save the setting. It can take several seconds for the solenoid to open and the pressure to stabilise.

7. The display will show PH (main burner stage 7). Press the ‘Up’ or ‘Down’ buttons to set the differential for the appropriate gas type. Press the ‘Set’ button once to save the setting.
8. For RHFE0800F/1000 the display will show: For RHFE1500 the display will show: 70 If the display does not change, then there is a commissioning error – repeat steps.
9. Press the ‘ON/OFF’ button to stop the unit. 10. Remove the manometer hose and replace the gas control test point screw.
Commissioning is now complete.

Rinnai

25

RHFE0800F_1000_1500 IM

COMMISSIONING

BURN MEDIA INSTALLATION

IMPORTANT

Due to the number of steps involved, separate instructions have been supplied with each burn media type and a colour placement sheet is also provided attached to burner box glass.
Experience has shown that the majority of performance problems are caused by burn media being installed incorrectly, as such correct placement of the burn media is critical. Ensure you have read through and understood the supplied burn media instructions before attempting installation. It is important to place the burn media in the correct position as incorrect placement cancreatecarbonbuild-upandaffecttheheatersperformance.

Malfunctions due to incorrect burn media placement are NOT covered by warranty.

The appliance MUST NEVER be used with other burn media or burn media that is damaged.

TheburnmediasetsaredifferentandcanNOT be interchanged, please ensure you have ordered the correct set before installation.

TEST OPERATION AND LIGHTING SEQUENCE
It may take approximately two hours of operation for the burn media to achieve their full flame pattern and glow. During the initial burning-in period, some smoke and smell may be experienced. The appliance should run on a high setting in a well ventilated room until these dissipate. It is important to check the flame pattern during this time.
ABNORMAL FLAME PATTERN
Each Rinnai Gas Fireplace heater has a distinct flame pattern. The flame should look the same every time you operate your heater, after an initial warm up period of approximately 15 minutes.
Abnormal flame performance and/or pattern can indicate a problem with your heater, such as blocked gas injectors, incorrectly installed / inadequate flue system or the artificial logs/burn media may have shifted from when the heater was first installed.
There are some warning signs that could indicate a problem. If any of the signs below occur, please contact Rinnai.

NORMAL FLAME PATTERN

ABNORMAL FLAME PATTERN

Keysignsofabnormalflameperformance:
· Appliance turns ‘OFF’ soon after start up and does not relight. · Continued difficulty or delay in establishing a flame · Flame appears overly orange- yellow. · Flame appears either very short or very long. · Flame only burns part way across the burner. · Severe soot building up on the inside of the glass or on logs. · Continuous unusual smell from the appliance. · Continued difficulty or delay in establishing a flame. · Severe soot building up on the inside of the glass.

SOOT BUILD UP

Beadvisedthatappliancesincorporatingalivefueleffect,anddesignedtooperatewithluminous NOTE flames,mayexhibitslightcarbondeposition,thisisnormaloperation.

Rinnai

26

RHFE0800F_1000_1500 IM

COMMISSIONING
CHECK Wi-Fi CONNECTIVITY
Part of the installation process is to test the Wi-Fi connectivity and correct operation with the appliance, with the owner/customer. When the power is on the Wi-Fi LED should flash and then turn a solid red to indicate everything is ready for setup via a smart device.
Summary of how the app works
Wi-Fi module in the fire, once installed and has power connected, is on. Homeowner downloads the Rinnai Wi-Fi app on their smart device. Through the app, the Wi-Fi in the fire links (pairs) to the homeowners smart device. Homeowner, through the app setup process, then links the Wi-Fi in the fire to the Wi-Fi router in the home–this essentially makes the smart device the fireplace controller. If unable to connect, the Wi-Fi board must be reset
RESETTING Wi-Fi MODULE
If there is a problem with the Wi-Fi connectivity, there may be a requirement for you to reset the Wi-Fi module E
of the appliance. With the appliance in the ON / Standby state do the following: 1. Take a thin non-metallic card (similar to the size and thickness of a credit card).
2. Use the diagram and table below locate the narrow gap in the heaters lower frame D.
D

Model RHFE800 shown for reference

E

!

A

Heater Model Location of reset point. (A)

RHFE0800F 265mm

RHFE1000 350mm

RHFE1500 650mm

3. Using your card, gently press down to reset the Wi-Fi module.
4. Restart your app and follow the app instructions.
If this doesn’t work switch the power off and then back on again to reset the heater and retry the resetting procedure, if the issue is still unable to be resolved contact Rinnai for advice.

INSTALLATION CHECKLIST & INSTALLATION RECORD

It is the responsibility of the installer to complete both the “Installation Checklist” and the “Installation Record” on pages 16 and 17 of the operation manual at the completion of installation.
IMPORTANT

Rinnai

27

RHFE0800F_1000_1500 IM

WALL LINING INSTALLATION

IMPORTANT

There are some aspects of the wall lining installation that are critical to the safe operation of the appliance. Anairgapofatleast3mmaroundthefireiscriticalto the safe operation of the LS – Gas Fireplace to ensure air flowinandaroundtheunit.

Avoidgettingplasterintheairgaparoundthefireedges.

ADDITIONAL NOTES:

Whilethefireissafewheninstalledwithcombustiblewall linings in accordance with these instructions, please be aware that the wall will go through hot and cold cycles and can reach temperatures of up to 80 °C. This could impactthedurabilityoftimberorwallpaperfinishes.

If screws are used (maximum length 25 mm) around the edge, ensure they do no interfere with the working parts ofthefire(latches,IRreceiver,On/Offbutton).

Wall lining up to edge

Cut-out ref. RHFE0800F

Minimum A
Maximum

816 x 566 830 x 580

RHFE100 1016 x 341 1030 x 355

RHFE1500 1516 x 341 1530 x 355

  • 3mm Air Gap

B

816 x 566 1016 x 341 1516 x 341

C

810 x 560 1030 x 355 1510 x 355

    • Wall lining up to edge

Below is an image to highlight the position and names of the different LS – Gas Fireplace framing components. Adjust as and where necessary, depending on the wall lining being installed.

Lining support rails (adjustable/removable)
Finishing trim (accessory)

Edges

Rinnai

28

RHFE0800F_1000_1500 IM

Minimum 3 mm air gap MUST be maintained
around the fire 1 2
5 0

PLASTERBOARD WALL WITH PLASTERED FINISH (wall flush with front of heater only)

WALL LINING INSTALLATION
No combustible materials within 50mm of top of heater engine

Note: Any wall linings that extend beyond the front face if the fire MUST BE rated non-combustible.
Refer drawings about thick wall linings and recess installations for details.

Adhesive is recommended

A

Wallboard Support MUST be used for combustible wallboard and is designed for wallboard thicknesses of 10, 13, and 20 mm allowing for 1 mm setback for the Finishing Trim or plaster finish

Wallboard Plaster finish
Wallboard cut out A
Wallboard edge finished (not a Rinnai supplied part)

Wallboard cut out A

Wallboard Support

A (1 : 1)

Edges

20 mm setting for combustible options

13 mm board

10 mm board
Wallboard Support

Rinnai

6
Note: When fitting the Wallboard Support panels, the tabs for 10 and 13 mm boards need to be trimmed off as indicated. If not using the optional Finishing Trim around the edge of the wallboard then the latches can be snapped off, otherwise the Wallboard Support panels and wallboard will need to have clearance applied to allow proper fitting.

29

RHFE0800F_1000_1500 IM

WALL LINING INSTALLATION
EDGE FINISHING OPTIONS (applicable to any installation method)

Rinnai optional Finishing Trim, only suitable where wall lining is at least 1mm set back from front face of fire

Adhesive is recommended in place of screws as permanent fixing across the top of the fire

Wallboard Support MUST be used for combustible wallboard and is designed for wallboard thicknesses of 10, 13, and 20 mm allowing for 1 mm setback for the Finishing Trim or plaster finish

Wallboard cut out A

Finishing Trim latch
A

A (1 : 1) with optional Rinnai Finishing Trim

Finishing Trim

Cut-out size B

Cut-out size C with 3 x 8 recess

3 Minimum air gap 3

A (1:1) with wallboard edge finish (no plaster or trim finish)
With this bigger gap there is a risk that the wallboard support panel and the finishing trim clips will be visible. Consider this before utilising this method

Rinnai

30

8
A (1:1) with rebated wallboard edge finish
This method will produce a closer fit to the fire but does make the front edge vulnerable to damage
RHFE0800F_1000_1500 IM

TILED OR SECOND SKIN WALL LININGS (combustible and non-combustible options)
Wall linings less then 20 mm may be combustible providing the wallboard support is installed
Adhesive or mechanical fixing Mechanical fixings not recommend across the top of the fire, adhesive is best
Opening size C minimum
Adhesive or mechanical fixing
With Wallboard Support removed the wall lining must be non-combustible for at least 300 mm up wall

3 mm air gap 5 0

WALL LINING INSTALLATION
No combustible materials within 50mm of top of heater engine
Backing or support board MUST be non-combustible below timber lintel line if Wallboard Support has been removed Wallboard Support optional in this configuration
No combustible materials within 50mm of top of heater engine
Backing or support board must be non-combustible below timber lintel line Wallboard Support removed. Backing board cut to clear lips and latches.

3 mm minimum air gap 120 5 0

Rinnai

Opening size
25
C minimum 31

RHFE0800F_1000_1500 IM

5 0 5 0

WALL LINING INSTALLATION NON-COMBUSTIBLE THICK WALL LININGS
Adhesive or mechanical fixing With Wallboard Support removed or wall lining protruding beyond the fire front the wall lining must be non-combustible for at least 300 mm up wall
Opening size C minimum
With Wallboard Support removed or wall lining protruding beyond the fire front the wall lining must be non-combustible for at least 300 mm up wall

No combustible materials within 50mm of top of heater engine
Backing or support board must be non-combustible below timber lintel line Ensure clearance around glass trim latches Wallboard Support removed Finish Trim latches can be removed
No combustible materials within 50mm of top of heater engine

Adhesive or mechanical fixing
Opening size C minimum

Ensure clearance around glass trim latches
Wallboard Support removed
Finish Trim latches will need to be allowed for if Finishing Trim is going to be used

Rinnai

32

RHFE0800F_1000_1500 IM

NON-COMBUSTIBLE RECESS INSTALLATIONS

WALL LINING INSTALLATION
No combustible materials within 50mm of top of heater engine

Front protruding panels Flush with Frame

45°
non-combustible lintel

3 mm minimum air gap
5 0

400 400

Any materials within this area must be rated as non-combustible

Walls must not protrude beyond the front boundry line

Opening size C minimum

50
Front edge of frame
No combustible materials within 50mm of top of heater engine

non-combustible lintel if required
45°

Any materials within this area must be rated as non-combustible
Walls must not protrude beyond the front boundry line
Opening size C minimum

50
Front edge of lips

3 mm minimum air gap
5 0

This panel must be non-combustible up to timber lintel level
Wallboard Support optional in this configuration
Finishing Trim or plaster finish appropriate for high temperature applications (up to 100°C) or panel edge finish (refer flush panel finishing solutions)

Rinnai

33

RHFE0800F_1000_1500 IM

SPECIFICATIONS

TABLE 1. APPLIANCE DETAILS

Model Number Model Name General Description
Features
Installation Number of Burners Combustion System
Flue Type
Convection Fan Gas Connection Remote Control Operation Ignition Gas Types Appliance Data Plate location Ignition Power Supply Power Con. Stand-by / Hi W

RHFE0800SF/DF

RHFE1000S/D

RHFE1500S/D

Flametech®

LS1000

LS1500

Inbuilt, Fan Exhaust Balanced Flued Convection Flame Fire with IR & WiFi Remote Control.

Burning log effect single / double sided glass front

Convection fan, top warm air outlet, mesh dress guard Inbuilt ONLY.

2

1

3

Multi-port burners, forced exhaust.
Forced Combustion, twin chamber coaxial flue system, provides air for combustion to the appliance and allows expulsion of combustion products
to atmosphere. Results in `room sealed’ appliance.

Single drum 180mm x 60mm (diameter) 2 speed – centrifugal ½ ” BSP, the gas supply terminates inside the heater–lower left hand
side of the appliance. Infra Red (IR) type. 2 x CR2450 button batteries / Wi- Fi via app.
ON/Standby (Manual button), IR Remote control, Smartphone App.

Continuous spark electronic ignition.

NG, Propane (AU) / NG, Universal LPG (NZ Only!)

Bottom panel, front inside of appliance. Continuous Spark Electronic Ignition.

240 V 50 Hz, 1500 mm cord is supplied with a 3 pin plug.

<8 / 50

Flame Failure Thermocouple

Overheat Switch (Bi-metal strip)

Safety Devices

Fan delay (Bi-metal strip)

Electrical Fuse

Power Failure Protection

Glass

Ceramic Glass.

Dress Guard

Wire Mesh

Glass seal material

Woven fibreglass chord – Hytex® 1000 by mid Mountain USA.

Log Set

Flametech® Self burning log technology

Ceramic

Ceramic

Noise Level

dB(A)

37 – 45

Fan

2 speed fan. Heat is distributed from the top of the appliance.

Weight – Packaged / Unit kg

100 / 120

100 / 125

110 / 140

Input – (Low / Hi)

MJ/h

15 / 35

14 / 34

14 / 40

Output – (Low / Hi) *

kW

3.1 / 7.7

3.1 / 7.4

3.1 / 8.5

Heating Area – (Low / Hi) ** m²

71 / 123

69 / 118

79 / 135

  • Will vary according to gas type and flue configuration ** Will vary depending on geographical location

Data Plate Location

On the base of the combustion chamber, on left hand side, on the convection fan access panel.

On the base of the combustion chamber, towards the left hand
side, between gas
control and convection fan access panel.

Rinnai

34

RHFE0800F_1000_1500 IM

TABLE 2. DIMENSIONS

A

Engine Width

B

Engine Height

C

Glass Centre – Right

D

Glass Centre – Left

E

Depth – Minimum, Single sided

F Depth – Face to face, Double sided

RHFE800S/SF/D/DF 1245
966 ± 5 519 726 435 435

SPECIFICATIONS

RHFE1000S/D 1435
741 ± 5 619 816 435 435

RHFE1500S/D 1935
741 ± 5 869 1066 435 435

All dimensions are in mm

WARNING

Fascia protrusion is approximately 1mm.
Above dimension are for the engine ONLY. For framing dimensions refer to section “Framing” starting on page 9.

A

C

D

E

435 min. singled sided

F

435 face-to-face double sided

B

B

Adjustable feet on all models

A

C

D

A

C

D

Glass dimensions 800 800 x 505 mm 1000 1000 x 280 mm 1500 1500 x 280 mm

B

Rinnai

35

RHFE0800F_1000_1500 IM

SPECIFICATIONS WIRING DIAGRAM

L LED

LED

L

10 1 10 1

10

1

10

1

bl
r bl

1

3

bl

2

DIP SW

LC

gr/y

AC 230-240V F
gr/y
1 br 2 bl

ER

gy

or

w w

bl

r

5A N

1 2 345678
SP

Diagram Notes:

RHFE1500—- Model only

RHFE800-F— Model only

gr/y

2 1

bk

br 2

4

bl 1

3

w OH.TH2

BL SC gr/y

4 4 bl r
1 1 bk w

LOW 4

MED 3

HI

2

COM 1

HI bl 2

COM w 1

LO y

3

r bl

bl

1 2 1 2 3

1 2 3 4 5 6 7 8 9

r bk w
13 12 1110 9 8 7 6 5 4 3 2 1

FM TR

pl

1 2

gy 3

6

or 2

5

y1

or

p w

w bl r w w y y w

POV

SV 4 SV 3 SV 2 SV 1
1

12 11 10 9 8 7 6 5 4 3 2 1 3 2 1

r bl

bl

bl r

FR2 FR1

bk bk
43 21

w w bk bk

OH.TH1

R.TH

TF
w
w

CONTROL DISPLAY UNIT

RCR

ON OFF
ON/OFF BUTTON

Rinnai

WIRING DIAGRAM UNI CONTROL MODEL 2 Linear Collection 2 Burners and Combustion Fan and LED’s Issue A

36

RHFE0800F_1000_1500 IM

NOTES

Rinnai

37

RHFE0800F_1000_1500 IM

NOTES

Rinnai

38

RHFE0800F_1000_1500 IM

NOTES

Rinnai

39

RHFE0800F_1000_1500 IM

innai Australia Pty Ltd

ABN 74 005 138 769 | AU45204

100 Atlantic Drive, Keysborough, Victoria 3173 P.O. Box 460, Braeside, Victoria 3195 Tel: (03) 9271 6625 Fax: (03) 9271 6622

National Help Line Tel: 1300 555 545* Fax: 1300 555 655 Monday to Friday, 8.00 am to 5.00 pm EST.

*Cost of a local call may be higher from mobile phones.

For further information visit www.rinnai.com.au or email enquiry@rinnai.com.au

innai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your innai appliance. If your appliance requires service, please call our National Help Line. innai recommends that this appliance be serviced every 2 years.

With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.

13579_H

40

RHFE0800F_1000_1500 IM Issue 8 – FEB 2024

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals