TRADE-WIND 7200 Series Barbecue Grill Hoods Installation Guide
- June 1, 2024
- TRADE-WIND
Table of Contents
- TRADE-WIND 7200 Series Barbecue Grill Hoods
- RECOMMENDATIONS:
- INSTALLATION INSTRUCTIONS
- IMPORTANT:ALL DIMENSIONS ARE NOMINAL +/- 1/8″
- **IMPORTANT: EASY STEPS FOR CONVERTING HOOD TO REAR DISCHARGE OPTION (NO
- PART 1: PLANNING THE INSTALLATION
- PART 2: SECURING THE HOOD
- PART 3: ELECTRICAL CONNECTION
- PART 4: USE AND CARE
- T R A D E – W I N D ® V E N T I L A T I O N P R O D U C T S
- ADDENDUM TO INSTALLATION INSTRUCTIONS
- 4. DAMPERS
- 5. ROOF CAPS & WALL CAPS
- 6. ATTACHING DUCT TO HOUSE FRAMEWORK
- 7. DUCT SIZING CHART & AREA CALCULATION
- 8. BEST SMOKE CAPTURE RECOMMENDATIONS
- ROOF CAP DRAWING
- Product Specifications:
- FAQ:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TRADE-WIND 7200 Series Barbecue Grill Hoods
INSTALLATION GUIDE
Before beginning installation, please thoroughly read and become familiar with these instructions. Installation and service must be completed by a qualified installer. Failure to properly install this product may void the warranty.
Please be advised that the TRADE-WIND® 7200 Series BBQ Hood MAY NOT be installed on a Patio or Lanai area that does not have a roof over the BBQ Hood to protect it from direct rain or potential water ingress.This Hood should be installed with a MINIMUM of three (3) feet of weather proof roof coverage on all sides that are not protected from direct rain by an adjacent wall.
It is required that all duct work and roof openings be thoroughly sealed with the applicable tape and/or roof sealant to prevent ingress of water.
Installer: Please leave Installation Instructions with the range hood liner.
Owner: Please keep Installation Instructions for local electrical inspector’s
use and for future reference.
WARNINGS: Must be followed carefully to avoid personal injury.
IMPORTANT: Must be followed carefully to avoid damage and incorrect
installation.
TIPS: Contains helpful information to facilitate installation.
READ AND SAVE THESE INSTRUCTIONS
WARNING! TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer.If you have
any questions, please contact the manufacturer at the address or telephone
number listed in the warranty.
b) Before servicing or cleaning unit, switch power off at service panel, lock
service panel, and lock the service disconnection means to prevent power from
being switched on accidentally. When the service disconnecting means cannot be
locked, securely fasten a prominent warning device, such as a tag, to the
service panel.
CAUTION: For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
WARNING! TO REDUCE THE RISK OF A BBQ TOP GREASE FIRE:
a) Never leave surface units unattended at high settings. Boilovers cause
smoking and greasy spillovers that may ignite.
Heat oils slowly on low or medium settings.
b) Always turn hood ON when cooking at high heat or when flambeing food (i.e.
Crepes Suzette, Cherries Jubilee, Peppercorn Beef Flambe’).
c) Clean ventilating fans frequently. Grease should not be allowed to
accumulate on fan or filter.
d) Use proper pan size. Always use cookware appropriate for the size of the surface element.
WARNING! TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A BBQ TOP GREASE FIRE, OBSERVING THEFOLLOWING:
a) Smother flames with a close-fitting lid, cookie sheet, or metal tray, then
turn off the burner.
b) Never pick up a flaming pan — you will be burned.
c) Do not use water , including wet dishcloths or towels. A violent steam
explosion will result.
d) Use an extinguisher only if:
1.You know you have a Class ABC extinguisher and you already know how to
operate it.
2.The fire is small and contained in the area where it started.
3.The fire department is being called.
4. You can fight the fire with your back to an exit.
e) Follow the BBQ grill manufacturer’s instruction when using gas grills,
cookers, or any propane appliances.
f) Be careful to prevent burns. If the flame does not go out directly,
evacuate and call the fire department.
RECOMMENDATIONS:
Consult a licensed ventilation contractor or qualified technician for proper installation of exhaust ducting. Locate thecooking area for minimum cross drafts-away from doors and windows, when possible.
1. Ducts must be of adequate size and duct runs should be as short as
possible. Where turns are necessary, keepturning radius as large and as smooth
as possible.
2. The ducting must be air tight. Use a minimum of 2 sheet metal screws at
every duct joint. Then, seal the duct jointswith high quality duct tape.
3. Do not use this unit with any solid-state speed control device. 4.
This unit must be grounded
INSTALLATION INSTRUCTIONS
WARNING! TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified person(s)
in accordance with all applicable codes and standards, including fire-rated
construction codes and standards.
b) Sufficient air is needed for proper combustion and exhausting of gasses
through the flue (chimney) of fuel burning equipment to prevent back
drafting.Follow the heating equipment manufacturer’s guidelines and safety
standards such as those published by the National Fire Protection Association
(NFPA) and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE) and the local code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
d) Ducted fans must always be vented to the outdoor.
e) For safe and secure wall mounting, the TRADE-WIND® BBQ Hood should be
mounted to a solid vertical surface of sufficient width to allow for mounting
of the Hood. The horizontal surface should extend from a vertical plane to the
point directly in front of the exhaust roof cap (or wall cap).
f) The Hood should be installed with a MINIMUM of three (3) feet of weather
proof roof coverage on all sides that are not protected from direct rain by an
adjacent wall.
g) It is also required that all duct work and roof openings be thoroughly
sealed with the applicable tape and/or roof sealant to prevent ingress of
water.
WARNING! TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.
CAUTION : To reduce the risk of fire and to properly exhaust air, be sure
to duct air outside. Do not vent exhaust air into spaces within walls,
ceilings, cabinets or into attics, crawl spaces, or garages.
TO ACCESS THE INSTALLATION INSTRUCTIONS FOR YOUR TRADE-WIND® PRODUCT, PLEASE SCAN THE QR CODE:
IMPORTANT:ALL DIMENSIONS ARE NOMINAL +/- 1/8″
**IMPORTANT: EASY STEPS FOR CONVERTING HOOD TO REAR DISCHARGE OPTION (NO
WIRING)**
TOOLS REQUIRED:
- PHILLIPS SCREWDRIVER
- 3/8″ SOCKET DRIVER (EXTENSION IN ELECTRIC
- DRILL IS IDEAL
STEPS:
1. Position hood on its back (preferably up on a table or similar) and remove
all baffle filters. Then raise up the hood with a 2×4 under each side so there
is at least 1” clearance between the hood and table.
2. Remove 4 screws holding the center bar (see diagram above). Make sure to
hold bar with one hand while removing final screw on each side so it doesn’t
fall. Move center bar towards blowers until free of edges, then pull out of
the unit and set aside.
3. Identify the 6 nuts that hold the 2 blowers (3 for each) and remove using
3/8” socket. Set nuts and washers aside. One at a time slide to release
remaining tab and pull blowers out. Set blowers down on back of the hood, as
far forward as wiring allows. Note: No need to touch or change any
wiring/electrical cables.
4. Remove the metal plate (with 10” hole) which was behind the blowers and
set aside.
5. With same socket tool, take off the 8 nuts and washers to release the
other solid plate currently mounted inside the back of the unit. Put in place
where the other plate was (top of unit) and secure using same nuts and
washers.
6. Now set the remaining (solid) plate in place at the back of the unit.
Note: The solid one should now be attached to the top of the unit, and the one
with the 10” hole should be against the back of the unit.
7. Move one blower into place on top of plate and weld screws at the back of
the unit, using tab to slide through both layers of steel (if you have
trouble, pry the slots open with flat head screwdriver). Make sure to slide
tab in as far as possible.
8. Do the same with the second blower (can overlap the first one).
9. Secure the blowers using the same 6 washers and nuts removed in step 3.
10. Make sure flex cable isn’t touching anything, specifically the front face
of the unit. (If necessary twist and bend it out of the way).
11. Put back center bar the same way it came out. It is not reversible, so if
holes don’t line up, flip and try the other way.
Unit is now ready for mounting and installation.
Re-install baffle filters as final step after installation is complete.
PART 1: PLANNING THE INSTALLATION
CAUTION:
1. For general ventilating use only. Do not use to exhaust hazardous or
explosive materials and vapors.
2. To reduce the risk of fire and to properly exhaust air, the hood must be
exhausted to outside air. Never exhaust into a wall, an attic or a concealed
area in the building. This can create a potential hazard.
3. Consult a licensed ventilation contractor or qualified technician for
proper installation of exhaust ducting.
4. Locate the cooking area for minimum cross drafts—away from doors and
windows, when possible.
5. Ducts must be of adequate size and duct runs should be as short as
possible. Where turns are necessary, keep turning radius as large and as
smooth as possible.
6. The ducting must be air tight. Use a minimum of 2 sheet metal screws at
every duct joint.Then, seal the duct joints with high quality duct tape.
7. Only use ductwork constructed of materials deemed acceptable by state,
municipal and local codes.
8. Plan the installation so that all minimum clearances are met or exceeded.
Dimensions shown provide minimum clearances, unless otherwise specified.
WARNING: FOLLOWING ARE MANUFACTURER’S SUGGESTIONS. ALWAYS OBSERVE LOCAL BUILDING CODES.
Hoods installed in custom canopies constructed of combustible materials should be installed with the combustible material structure at 36” above the cooking surface.Hoods installed in custom canopies constructed of non-combustible materials, should be installed with the non-combustible material structure at 36” above the cooking surface. Follow all instructions regarding minimum safe clearances and installation location. Failure to do so may result in a safety hazard or fire. To reduce the risk of fire use only metal ductwork.
FOR IN-LINE & REMOTE VENTILATORS, DUCT SILENCERS, DAMPERS, AND DUCTING
TRADE-WIND® BBQ Hoods with non-internal motors are designed for use with “in-
line” and “remote-mount” ventilators. When planning for installations using
these products, please refer to the Installation Instructions provided with
the ventilator. TRADE-WIND® Duct Silencers are available from your local
TRADE-WIND® dealer. When planning for installation using a duct silencer,
please refer to the Installation Instructions provided with the duct silencer.
Given that most installations are different, a back-draft damper is not
provided with this unit. TRADE-WIND® back draft dampers are also available
from your local TRADE-WIND® dealer. Always install ventilation products with
an approved wall or roof cap. Duct performance is improved by using round,
smooth metal duct work instead of rectangular. Do not rely on duct tape alone
to seal duct joints. Use sheet metal screws as required to support the duct.
PART 2: SECURING THE HOOD
MOUNTING HOLES:
Because the TRADE-WIND® S7200CD Series BBQ Hood was designed for all applications, no mounting holes have been pre-drilled. This allows for custom applications for mounting. The hood should be attached to the framing through the top and back, whenever possible.Remove the filters. Mark and drill screw holes through the hood as required.Secure the hood by driving screws (provided by others) through the screw holes.
NOTE: DRILLING THROUGH STAINLESS STEEL REQUIRES TITANIUM DRILL BITS. BE CAREFUL NOT TO DRILL THROUGH THE UL LABEL OR INTO THE HOOD’S ELECTRICAL COMPONENTS
PART 3: ELECTRICAL CONNECTION
WARNING:
Ensure that the power supply is disconnected before proceeding. Verify that the power supply matches the ratings found on the appliance data label before proceeding. The complete appliance must be properly grounded at all times when electrical power is applied. Do not ground the appliance with the neutral (white) house supply wire. A separate ground wire must be utilized. Failure to complete electrical connections properly may result in damaged or non- functional systems. Follow instructions carefully to ensure proper installation.
It is the owner’s responsibility to ensure that a qualified person performs
the electrical connection of this appliance. The electrical installation,
including minimum supply wire size, must comply with the National Electric
Code ANSI/NFPA 70-1990 (or latest revision) and local codes and ordinances. A
copy of this standard may be obtained from:
National Fire Protection Association, 1 Batterymarch Park, Quincy,
Massachusetts 02169-7471
IMPORTANT: ELECTRICAL REQUIREMENTS
Observe all National and local governing codes and ordinances. Have all
electrical installation done by a qualified electrical installer. This Hood
requires a 120 Volt, 60 Hertz electrical supply of an individual properly
grounded branch circuit protected by a 15 or 20 Amp circuit breaker. The
TRADE-WIND® P7200-12 Series BBQ Hood is supplied with a 6.0 Amp three speed
fan control, the -23 models are supplied with (2) 6.0 Amp three speed fan
controls.
For safety precautions, each Ventilation Hood should be installed in a GFCI protected branch circuit.
INSTRUCTIONS:
Wire Connections: (See Diagram)
There are 3 wires on the front panel that require connection.
BLACK: 120 VOLT AC FROM ELECTRICAL PANEL (USUALLY BLACK)
WHITE: NEUTRAL FROM ELECTRICAL PANEL (USUALLY WHITE)
GREEN: GROUND FROM ELECTRICAL PANEL (USUALLY GREEN)
HOUSE ELECTRICAL PANEL
CAUTION : The neutral wire (white) must only be connected to the white neutral wire coming in from the electrical panel.
PART 4: USE AND CARE
CAUTION : The edges of the stainless steel are extremely sharp. To ensure safety, wear gloves when handling all parts.
WARNING : Do NOT operate the blower / ventilator system without the filters in place, or with dirty, grease laden filters.
FILTER REMOVAL:
Each filter has two aluminum cylindrical knobs, one towards the rear and one towards the front. The front & rear knobs are only for grasping and are permanently connected to the filter. To remove the filter, grasp the front & rear knobs, slide the filter towards the center bar of the hood until the other end of the filter drops down. Grasping the filter, remove it from the hood by now pulling it out of the center bar.
OPERATING CONTROLS:
Always activate the ventilator when using cooking appliances. Activate the
ventilator a few minutes before starting to cook to establish an airflow
pattern within the room. Adjust the fan speed as needed. Adjust the dimmable
halogen lights as desired.
ENERGY SAVING TIPS:
Do not operate the blower at a speed higher than necessary to remove the
cooking exhaust. Turn off the unit once the smoke and cooking odors have been
eliminated. Clean filters and grease laden surfaces often to improve
efficiency.
CARE AND CLEANING:
Proper cleaning is necessary to maintain performance and appearance, while
also ensuring safe operation. The frequency of cleaning should be adjusted
according to the type and amount of cooking. Best results will be achieved by
cleaning soiled components as soon as possible.Filters must be cleaned
regularly.
We recommend washing filters by placing them in the bottom rack of a dishwasher. Locate the holes on the sides of the filter. Put filter in dishwasher with holes facing up, so detergent can enter filters. Dry the filters completely before using again. Rinse and dry with a soft lint-free cloth. Always wipe stainless steel surfaces with the grain. Never wipe across the grain. After cleaning, reinstall the filters carefully. Most common scrubber type pads will scratch the hood.
CAUTION: If a commercially available stainless steel cleaner is used, it is important to read the labels for chlorine compounds. Chlorine is a corrosive substance, DO NOT USE. Follow polish manufacturer’s instructions.
HALOGEN LIGHT BULBS:
Hoods are designed for halogen light bulbs. They can be purchased at most home
and/or grocery stores.
We endeavor to incorporate the best technology provided to our industry, in manufacturing the TRADE-WIND® products, therefore, we reserve the right to change models, mode of operation, and specification without prior notice.
T R A D E – W I N D ® V E N T I L A T I O N P R O D U C T S
What IS Covered:
TRADE-WIND Manufacturing, LLC® warrants its TRADE-WIND® Ventilation Products
to the original user to be free of defects in materials and workmanship for
three (3) years from the date of purchase.
TRADE-WIND Manufacturing, LLC®, at its option, will repair or replace the
complete unit or any defective component without charge. This warranty may be
voided if any unauthorized service, alterations, or repairs are made to the
product.
What is NOT Covered:
- Normal maintenance and service of any product that has been subject to misuse, negligence, accident, or installation inconsistent with the recommended TRADE-WIND® Installation Instructions and TRADE-WIND® Best Practices Guidelines.
- Product used other than for normal in-home use or products used outside of the United States and Canada.
- Damage to the product caused by accident, fire, flood, or other acts of God.
- Service calls to educate the customer in the proper use and care of the product, change fuses, or to reset the circuit breakers.
- Service calls to correct faulty installation, such as performance issues relating to improperly sized ducting or restrictive roof caps, are not covered and will, by default, be charged back to the Homeowner.
- Light bulbs are not covered under warranty.
TRADE-WIND Manufacturing, LLC® disclaims and excludes any liability for implied warranties or for incidental or consequential damages wherever permitted by law. There are no implied warranties of merchantability or fitness for a particular use or purpose. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state.
For Service: If you need service on your TRADE-WIND® Ventilation Product, visit our website at: www.t-wusa.com and click on the warranty tab. Fill out the simple form providing the model number, serial number, date of purchase, and brief description of the problem. Proof of purchase will also be required.
ADDENDUM TO INSTALLATION INSTRUCTIONS
IMPORTANT: Problems caused by the improper installations are not covered
by the manufacturer’s warranty.
IMPORTANT: Undersized and improperly installed duct pipe and/or other
ventilation components will cause excessive static pressure (air resistance),
that may result in rattling, vibration and air buffeting noises, as well as
inadequate ventilation.
1. BUILDING CODES
BBQ Hood Ventilators should be installed by qualified technicians familiar
with state and local building codes.
2. DUCT PIPE & FITTINGS (ELBOWS, TRANSITIONS, ROOF & WALL CAPS)
a.) Use round or rectangular rigid metal duct only. Where possible, use round
duct as it creates the least amount of static pressure. DO NOT USE FLEX DUCT.
b.) All duct sections and fittings (EXCEPT DAMPERS, per Section 4), should
overlap and be connected with at least 3 – 4 equally spaced screws and wrapped
tightly with 2 – 3 layers of Aluminum Foil Metal Duct Tape. This type of duct
tape is more durable than traditional cloth duct tape. DO NOT USE BUTT JOINTS.
c.) For best air flow, elbows and pipe size transition fittings should not be
directly connected to one another. Where possible, always include at least 15
inches of straight pipe between fittings.
3. DUCT PIPE & FITTING SIZES (See Duct Sizing Chart and Area Calculations
section for more details)
IMPORTANT: No portion of any length of duct pipe or fitting should be smaller than the discharge port of the ventilator. This is very important because any type of restriction anywhere in the ventilation system will cause increased static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate ventilation.
DUCT RUNS – LENGTH
a.) Configure the ventilation duct run to be as short and as direct to the
outside as possible. Minimize the number of elbows and transition fittings
used. Complex or long runs should be reviewed by a qualified installer.
b.) No portion of the ducting should be run so that the exhaust air flows
downward. Since exhaust heat rises, forcing the air to flow downward will
cause increased static pressure. As previously mentioned, improperly installed
duct pipe will cause excessive static pressure (air resistance), that may
result in rattling, vibration and air buffeting noises, as well as inadequate
ventilation.
c.) Duct runs for 1200 CFM ventilator models should not exceed 35 linear feet
with two 90-degree elbows and two 45-degree elbows, a damper and a roof or
wall cap. Longer runs or additional elbows will result in decreased
ventilation performance. Each 90-degree elbow is the equivalent of 6 linear
feet of duct pipe; each 45-degree elbow is equivalent to 3 linear feet of duct
pipe.
d.) Always run ventilator ducts to the outdoors. DO NOT terminate a duct into
an attic, basement, garage, crawl space under a house, a chimney, other
ducting or an enclosed room.
4. DAMPERS
IMPORTANT: DO NOT USE ANY TYPE OF DAMPER IN A BBQ HOOD APPLICATION.
In ventilation systems utilizing a roof cap or wall cap with a built-in
damper, remove it. Dampers are unnecessary and will cause increased static
pressure (air resistance), that may result in rattling, vibration and air
buffeting noises, as well as inadequate ventilation.
5. ROOF CAPS & WALL CAPS
The roof cap or wall cap is the termination point of the venting system that allows the exhaust air to exit to the outdoors. All sections of this fitting must have an equal or greater air path area than the ventilator’s discharge port. If any section of the roof cap or wall cap is smaller than the ventilator’s discharge port, the entire ventilation system will lose efficiency and the restriction will cause increased static pressure and decrease performance.
IMPORTANT: Even though the intake side of the roof cap or wall cap may be
properly sized, roof caps or wall caps with built-in dampers must be made so
that when the damper is fully open, the actual open area of the final air path
is equal to or greater than the discharge port of the ventilator. Any
undersized portion of a roof cap or wall cap will cause excessive static
pressure that may result in rattling, vibration and air buffeting noises, as
well as inadequate ventilation.
Do not use “goose-neck style” caps as they significantly restrict natural,
heated air-flow. Do Not use caps with dampers for BBQ Hoods.
ROOF CAP DRAWING
For higher profile roof tile, you may need a taller roof cap. See recommended
dimensions below – Minimizes static pressure and maximizes air flow to ensure
optimum performance of your TRADE-WIND® product.
6. ATTACHING DUCT TO HOUSE FRAMEWORK
The ventilation system should be attached to the framework in such a manner that the weight of the duct and fittings is supported with no stress on the duct joints, fittings or on the ventilator. All ducting should be attached so as to avoid any possible duct vibration from being transferred to the house’s framework.
7. DUCT SIZING CHART & AREA CALCULATION
VENTILATOR DISCHARGE PORT TYPES & SIZES| DUCT TYPE REQUIRED| DUCT SIZE (IN SQ.
IN.)| MINIMUM DISCHARGE SIZE OF ROOFCAP OR WALLCAP UTSIDE OPENING
---|---|---|---
6″ DIAMETER, ROUND| 6″ ROUND METAL DUCT| 28.3″| 28.3″
7″ DIAMETER, ROUND| 7″ ROUND METAL DUCT| 38.5″| 38.5″
8″ DIAMETER, ROUND| 8″ ROUND METAL DUCT| 50.25″/54″| 50.25″/54″
10″ DIAMETER, ROUND| 10″ ROUND METAL DUCT| 78.5″| 78.5″
3.25″ x 10″ RECTANGULAR| 3.25″ x 10″ RECTANGULAR METAL DUCT| 32.5″| 32.5″
The “radius” is one-half the diameter of a round duct, e.g., ½ of a 10” round duct is 5”.3.1416 is “Pi”, the “constant” used when calculating the area of a circle.
8. BEST SMOKE CAPTURE RECOMMENDATIONS
Smoke and hot air from an Outdoor BBQ Grill rises quickly, especially as the BBQ lid is opened. Not only does the smoke rise fast, but it is usually deflected forward (toward the cook) beyond the BBQ hood’s capture area by the shape and position of the BBQ lid itself. Heavy, fast rising smoke is a challenge even for high-performance BBQ hoods, but there are some things you can do to enhance your outdoor BBQ hood’s performance.
a.) Install the hood at the recommended 36” above the cooking surface. If the
hood is installed more than the recommended 36” above the cooking surface,
its’ smoke capture ability declines rapidly. See Drawing A.
b.) Since smoke also expands as it rises, the hood’s sides and front edge
should extend 3” – 6” beyond the front and sides of the cooking surface—see
Drawing B. In this example, the hood is attached to a built-out section of the
wall or to a chase. It is unlikely that smoke rising past the bottom of the
BBQ hood will be captured by the hood. Smoke escaping the hood’s capture area
will typically remain against the ceiling until it is blown out by natural air
currents or until it dissipates.
c.) Turn the hood on high 2 -3 minutes prior to placing food on the grill. If
there is no wind or wind drafts, an upward flowing air “curtain” will be
created by the hood’s suction that moves air up the sides and front of the
cooking surface. This upward moving air curtain will help capture much of the
smoke.
d.) Wind and wind drafts will also negatively affect the capture ability of
high-performance outdoor BBQ hoods. If the BBQ grill is located in a
consistently windy area, e.g., near oceans, large lakes or on hillside
properties, for best BBQ hood performance, a wind-break may be required.
ROOF CAP DRAWING
For higher profile roof tile, you may need a taller roof cap. See recommended dimensions below – Minimizes static pressure and maximizes air flow to ensure optimum performance of your TRADE-WIND® product.
Product Specifications:
-
Model Options: 7236, 723612, 7242, 724212,
7248, 724812, 7254, 725423, 7260, 726023, 7272, 727223 -
Front to Back Dimensions: 32 inches
-
Width Options: 36, 42, 48, 54, 60, 72
inches -
CFM (Cubic Feet per Minute): Ranges from 1200
to 2300 depending on model -
Blower Type: 3-Speed In-line or Internal
Remote Blower
FAQ:
Q: What should I do in case of a BBQ top grease fire?
A: If a grease fire occurs, always turn off the burner and smother flames with a close-fitting lid, cookie sheet, or metal tray. Do not use water to extinguish the fire as it can cause a steam explosion. Follow the manufacturer’s instructions for gas grills or cookers and evacuate if necessary.
Q: Can I use wet dishcloths to extinguish a grease fire?
A: No, using wet dishcloths can lead to a steam explosion. It is recommended to smother the flames with a lid or metal tray and turn off the heat source.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>