INTRODUCTION
  • 15M/49ft Patent Protected Module, Effectively anti-interference.
  • Rotator & Remote control.
  • 12VDC Input, 0-10V Dimming, with Daylight Harvesting and Photocell Function.
  • Attention: please setting the parameters in the state that the light is always on, the light brightness will blink when the sensor receives the signal and it will not receive the signal of “MH” , “CCT” “o” on the remote control.
  • Set fixture on the highest wattage.
PARAMETERS
Voltage Range  12-24VDC
Signal ON/OFF,DIM 0-10V
Frequency 5.8GHz±75MHz
Stand-by Power <30mA
Detection Area Remote Control: 25%/50%/75%/100%
Installation Height 15m/49.21 Max.
Holdtime Remote Control: 5s/30s/1min/3min/5min/10min/20min/30min

Rotating switch: 5s/1min/5min/10min
Daylight Threshold| Remote Control: 2Lux/10Lux/30Lux/50Lux/80Lux/120Lux/200Lux/250Lux/ 300Lux/350Lux/400Lux/Disable
Standby Dimming Level| Remote Control: 10%/20%/30%/50%
Rotating switch: 0%/10%/20%/30%
Standby Period| Remote Control: 0s/10s/30s/1min/5min/10min/30min/60min/+∞
Dusk/Dawn Sensing/ Photocell| Daylight threshold as 30lux/50lux/80lux/120lux/200Lux/ 250Lux/300Lux/350Lux/400Lux Standby period as +∞;
Standby dimming level as 10%/20%/30%
Daylight Harvesting| 1. Choose “Daylight sensor” button then adjust to any value higher than 50LUX
2. Choose “Standby Period” then adjust to 0S
3. Press “DH” daylight harvesting button, till LCD screen show DH-ON
4. Remark:this function cannot be turned off by DH-OFF. but it can be turned off by changing any parameters
Environmental Requirements| In accordance with CE ROHS
Working Temp| -40°C~+70°C
IP Rating| IP65

WARNING

NOTE: Warm up time is 10seconds. After the sensor connects input power first time, the light will keep on 10seconds, then go to dimming to work normally.
NOTE: Factory Default Setting: 100% sensitivity, Hold on time: 1 min Daylight threshold is disable Standby period is 1 min standby dimming Level is 20%.

DAYLIGHT HARVESTING
  1. Choose “Daylight sensor” button then adjust to any value higher than 50LUX
  2. Choose “Standby Period” then adjust to OS
  3. Press “DH” daylight harvesting button, till LCD screen show DH-ON
  4. Remark: this function cannot be turned off by DH-OFF, but it can be turned off by changing any parameters

NICOR HBC5SENSORMW Bi-level Microwave Sensor 5

  1. Natural Light Brightness
  2. Artificial Light Brightness
  3. Preset Lux Value
  4. Light ON
  5. Light OFF
  6. Daylight Harvesting phase

When ambient brightness is lower than preset lux level, sensor will turn on light automatically and keep dimming according to the change of the ambient brightness; when outside is getting darker, the inside will be brighter, and brighter darker.

Light OFF when ambient brightness becomes higher than the preset lux level.

DUSK/DAWN FUNCTION

HBC5SENSORMW is able to differentiate artificial light brightness from natural light after installed inside the fixture, and automatically turn off light when ambient brightness exceeds preset lux level.

NICOR HBC5SENSORMW Bi-level Microwave Sensor 10

  1. LUX OFF
  2. LUX ON
  3. Natural Light
  4. Light off automatically
  5. light on automatically

Precondition of Dusk/Dawn function:

  1. Standby period is +∞;
  2. Standby dimming level is on 10%,20% or 30%;
  3. Daylight threshold is on 30lux/50lux/80lux/120lux/200Lux/250Lux/300Lux/350Lux/400Lux
DETECTION COVERAGE

Ceiling Mounted

A: 0.5-1.0M/S
B: Mounting Height

Wall Mounted

A: Mounting Height

Highest mounting height is 15m
This figure indicates the maximum distance at the highest mounting height with 100% sensitivity.

Well Detected Area    Possibly Detected Area