IMMERGASA 3.023965 Hydraulic Separator Kit for Boilers Installation Guide

June 1, 2024
IMMERGASA

IMMERGASA-LOGO

IMMERGASA 3.023965 Hydraulic Separator Kit for Boilers

Product Information

Specifications

  • Product Name: Hydraulic Separator Kit for Boilers in Cascade
  • Power: 350kW
  • Product Code: 3.023965

Product Usage Instructions

Installation
The hydraulic separator can be installed with a left or right output and can be mounted on the wall or on a base.

  • Floor-Standing Installation
    For floor-standing installation, refer to Figure 1 and follow the instructions provided.

  • Wall Installation
    For wall installation, refer to Figure 2 and follow the steps outlined.

Kit Components

Ref. Description Qty
1 Hydraulic separator 1

Assembly
To assemble the kit, follow these steps:

  1. Refer to the mounting dimensions in Figure 1 for guidance.
  2. Ensure proper installation according to your hydraulic configuration.
  3. After complete assembly, check the tightness of the hydraulic circuit as per regulations.

Main Dimensions
Key Components:

  • Valve sfogo aria (Vent valve)
  • Rubinetto intercettazione (Interception cock)
  • Attacco per sonda (Attachment for probe – not supplied)
  • Separatore idraulico (Hydraulic separator device)
  • Rubinetto di svuotamento (Draining valve)

FAQ

  • Can the kit be installed with any boiler model?
    The kit is compatible with boilers in cascade with a power of 350kW, but specific compatibility may vary. Refer to your boiler manual for details.

  • Are additional components required for installation?
    The kit includes all necessary components for installation. However, additional tools may be needed based on your setup.

THIS SHEET MUST BE LEFT WITH THE USER ALONG WITH THE BOILER INSTRUCTION BOOKLET

General warnings.

  • All products are protected with suitable transport packaging. The material must be stored in dry environments and protected against weathering.
  • This instruction manual provides technical information for installing the kit. As for the other issues related to kit installation (e.g. safety in the work site, environment protection, injury prevention), it is necessary to comply with the provisions specified in the regulations in force and principles of good practice.
  • Improper installation or assembly of the appliance and/or compo-nents, accessories, kit and devices can cause unexpected problems to people, animals and objects. Read the instructions provided with the product carefully to ensure a proper installation. Installation and maintenance must be performed in compliance with the regulations in force, according to the manufacturer’s instructions and by authorised professionally qualified staff, intending staff with specific technical skills in the plant sector, as envisioned by the Law

GENERAL INFORMATION.

  • This kit can be installed with a left or right output and you can decide whether to install the separator on the wall or on a base.
  • The hydraulic separator makes the primary circuit and the second-ary circuit independent. .

IMMERGASA-3-023965-Hydraulic-Separator-Kit-for-Boilers-
FIG-2

PRODUCT OVERVIEW

WALL INSTALLATION

IMMERGASA-3-023965-Hydraulic-Separator-Kit-for-Boilers-
FIG-3

FLOOR-STANDING INSTALLATION

IMMERGASA-3-023965-Hydraulic-Separator-Kit-for-Boilers-
FIG-4

Ref. Kit components description Qty
1 Hydraulic separator 1
2 Wall-mounted right support bracket 1
3 Separator left support 1
4 Separator right support 1
5 Flange gasket DN100 2
6 Screws for dowel 8 x 80 10
7 Nylon dowel 12 x 60 10
8 Screw M16x65 16
9 Stainless steel washer 17x30x3 16
10 Nut M16 16
11 Wall-mounted left support bracket 1

KIT ASSEMBLY.

Proceed as follows to assemble the kit:
Attention: the mounting dimensions shown in figure 1 are indicative and inclusive of the optional ”INAIL Safety devices” kit.
For proper installation refer to the relative hydraulic configuration.

  • Wall-mounted installation.
  • Make 6 holes Ø 12 using the measurements shown in figure 1 referred to the vertical supports (ref. 2 and 11 fig. 2).
  • Insert the 6 dowels (7) in the holes.
  • Attach the vertical supports (2) and (11) to the wall with the 6 screws (6) with dowel (7).
  • Rest the hydraulic separator (1) on the supports (2) and (11).
  • Make the hydraulic connections interposing the relative gaskets (5).
    Once the complete kit is installed, check the tighteness of the hydraulic circuit according to that prescribed by the regulations in force.

Base installation.

  • Make 4 holes Ø 12 using the measurements shown in figure 1 referred to the supports (3) and (4).
  • Insert the 4 dowels (7) in the holes.
  • Set the 2 supports (3) and (4) next to each other and fasten them to the floor with the 4 screws (6) with dowel (7).
  • Rest the hydraulic separator (1) on the supports (3) and (4).
  • Make the hydraulic connections interposing the relative gaskets (5).
    Once the complete kit is installed, check the tighteness of the hydraulic circuit according to that prescrived by the regulations in force.

MAIN DIMENSIONS

IMMERGASA-3-023965-Hydraulic-Separator-Kit-for-Boilers-
FIG-5

  1. Vent valve
  2. Interception cock
  3. Attachment for probe (not supplied)
  4. Hydraulic separator device
  5. Draining valve

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals