Rinnai HSNRP26B PB Series Split Type Wall Mounted Air Conditioner Instruction Manual
- June 1, 2024
- Rinnai
Table of Contents
- Rinnai HSNRP26B PB Series Split Type Wall Mounted Air Conditioner
- Product Information
- Product Usage Instructions
- FAQs
- WARNINGS AND IMPORTANT INFORMATION
- OPERATING CAUTIONS
- ACCESSORIES
- INSTALLATION SUMMARY
- REFRIGERANT PIPING CONNECTION
- AIR EVACUATION
- SPECIFICATIONS
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Rinnai HSNRP26B PB Series Split Type Wall Mounted Air Conditioner
Product Information
Specifications
- Models: HSNRP26B, HSNRP35B, HSNRP50B, HSNRP60B, HSNRP70B, HSNRP80B
- Indoor Unit Models: HINRP26MB, HINRP35MB, HINRP50MB, HINRP60MB, HINRP70MB, HINRP80B, HINRP20MB
- Outdoor Unit Models: HONRP26B, HONRP35B, HONRP50B, HONRP60B, HONRP70B, HONRP80B
- Refrigerant: R32
- Type: Split Type Wall Mounted Air Conditioner
- Manufacturer: Rinnai
Product Usage Instructions
Warnings and Important Information
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE. Always comply with the precautions to avoid dangerous situations.
Installation Summary
This appliance must be installed, maintained, and removed only by an Authorized Person. Follow the manufacturer’s instructions for installation.
Description
The wall-mounted air conditioner is designed for efficient cooling and heating of indoor spaces.
Indoor Installation
Follow the detailed indoor installation instructions provided in the manual.
Outdoor Installation
Ensure proper outdoor installation of the unit for optimal performance. Refer to the manual for detailed steps.
Refrigerant Piping Connection
Connect the refrigerant piping carefully following the instructions to prevent leaks and ensure proper functioning.
FAQs
- Q: What refrigerant does the unit use?
- A: The unit uses R32 refrigerant for efficient cooling.
- Q: Who should install and maintain the appliance?
- A: The appliance should be installed, maintained, and removed only by an Authorized Person as specified by the manufacturer.
“`
MODELS
System HSNRP26B HSNRP35B HSNRP50B HSNRP60B HSNRP70B HSNRP80B Ref Only
Indoor HINRP26MB HINRP35MB HINRP50MB HINRP60MB HINRP70MB HINRP80B HINRP20MB
Outdoor HONRP26B HONRP35B HONRP50B HONRP60B HONRP70B HONRP80B Matching Multi System Only
REFRIGERANT
R32
PB Series Split Type Wall Mounted Air Conditioner Installation Manual
This appliance must be installed in accordance with: · Manufacturer’s
Installation Instructions · Current AS/NZS 3000, AS/NZS 5141, AS/NZS 5149 ·
Local Regulations and Municipal Building Codes
including local OH&S requirements This appliance must be installed, maintained
and removed only by an Authorised Person. For continued safety of this
appliance it must be installed and maintained in accordance with the
manufacturer’s instructions.
REFRIGERANT
WARNINGS AND IMPORTANT INFORMATION
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE. WARNING Always comply with
the following precautions to avoid dangerous situations and to ensure
optimum performance. Failure to carefully read and follow all instructions in
this manual can result in equipment malfunction, property damage, personal
injury and/or death. DANGER: Indicates an imminently hazardous situation
which, if not avoided, will result in personal injury or death. WARNINGS:
Indicates a potentially hazardous situation which, if not avoided, could
result in personal injury or death. CAUTIONS: Indicates a potentially
hazardous situation which, if not avoided, could result in minor or moderate
injury or damage to the appliance. It may also be used to alert against unsafe
practices.
REGULATORY
WARNING This appliance shall be installed in accordance with: Manufacturer’s
Installation Instructions. Current AS/NZS 3000, AS/NZS 5141, AS/NZS 5149.
Local Regulations and Municipal Building Codes including local OH&S
requirements.
This appliance must be installed, maintained and removed ONLY by an Authorised
Person. For continued safety of this appliance it must be installed and
maintained in accordance with the manufacturers instructions. This appliance
uses R32 refrigerant. This appliance is heavy, use 2 people or mechanical
lifting device. Improper lifting may result in serious injury. Take care when
opening or unpacking this appliance. Failure to do so may result in serious
injury or product failure. DO NOT modify the electrical wiring of this
appliance. If the control power wiring is damaged or deteriorated then it must
be replaced by an authorised person. Failure to do so may result in
electricshock,fire,seriousinjuryorproductfailure. DO NOT install the air
conditioner on an unstable or non level surface or where there may be a danger
of it falling. It may result in death, serious injury, or product failure. DO
NOT install the outdoor unit where noise may cause nuisance. DO NOT install
the outdoor unit where it will be exposed to sea wind (salt spray) as this
will reduce durability.
MANDATORY INSPECTION PRIOR TO INSTALLATION
IMPORTANT
Immediately report any damage or discrepancies to the Supplier of the appliance. This appliance was inspected and tested at the time of manufacture and packaging, and released for transportation without known damage. Upon receipt, inspect the exterior for evidence of rough handling in shipment. Ensure that the appliance is labelled correctly for the gas and electrical supply, and/or other services it is intended to be connected to.
For safety and warranty purposes, appliances that may be damaged or incorrect MUST NOT be installed or operated under any circumstances. Installation of damaged or incorrect appliances may contravene local government regulations. Rinnai disclaims any liability or responsibility whatsoever in relation to the installation or operation of damaged or incorrect appliances.
Rinnai
4
PB Series Split AC IM Issue 1
WARNINGS AND IMPORTANT INFORMATION
INSTALLATION
WARNING This appliance shall be installed in accordance with local electrical
safety regulations by an authorised person such as a licensed electrician.
Contact an authorised service technician for repair or maintenance of this
appliance.
Onlyusetheincludedaccessories,parts,andspecifiedpartsforinstallation.Usingnon-
standard
partscancausewaterleakage,electricalshock,fire,andcancausetheunittofail.
Installtheunitinafirmlocationthatcansupporttheunit’sweight.Ifthechosenlocationcannot
support the unit’s weight, or the installation is not done properly, the unit
may drop and cause serious injury and damage.
DO NOT turn on the power until all work has been completed.
When moving or relocating the air conditioner, consult experienced service
technicians for disconnection and reinstallation of the unit.
How to install the appliance to its support, please read the information for
details in “indoor unit installation” and “outdoor unit installation”
sections.
For units that have an auxiliary electric heater, DO NOT install the unit
within 1 meter (3 feet) of any combustible materials.
DO NOT install the unit in a location that may be exposed to combustible gas
leaks. If combustible gasaccumulatesaroundtheunit,itmaycausefire. Install
drainage piping according to the instructions in this manual. Improper
drainage may cause water damage to your home and property.
This appliance is a Type 1 Electrical Appliance.
Make sure the live wire, neutral wire and earth wire in the power socket are
properly connected.
Inadequateorincorrectelectricalconnectionsmaycausefireorelectricshock. The
yellow-green wire in air conditioner is the earthing wire which cannot be used
for other purposes. Improper earthing may cause electric shock.
The circuit breaker must have the functions of magnetic tripping and heat
tripping to prevent short circuit and overload.
Use a standard circuit breaker and fuse conforming with the rating of the
appliances.
The unit must be earthed in accordance with local regulations.
Connect all wiring tightly. Failure to do so may result in electric shock or
product failure.
DO NOT supply power to the unit until all wiring and tubing are completed.
Select an installation location where the components can be mounted securely
and accessible for service and replacement.
Make sure tubing is properly insulated to ensure optimum performance.
Install the drain hose properly for smooth drainage of condensed water.
Make sure to check for and rectify any refrigerant leaks after you install or
repair the unit.
This appliance uses R32 (difluoromethane) refrigerant, which is a flammable
gas class 2.2 according to AS/NZS 1677 and must be handled by a refrigeration
mechanic with appropriate Australian refrigerant handling licence.
Rinnai
5
PB Series Split AC IM Issue 1
WARNINGS AND IMPORTANT INFORMATION
WARNING
WARNINGRiskoffire/flammablematerial.Iftherefrigerantisleaked,togetherwithan
external ignition source, there is a possibility of ignition.
Read the OPERATING INSTRUCTIONS carefully before operation.
Service personnel are required to carefully read the OPERATING INSTRUCTIONS
and INSTALLATION MANUAL before operation.
Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION
MANUAL, and the like.
Certain levels of refrigerant require minimum room sizes. Please ensure that
these minimum room sizes are adhered to for standard installations (up to 10m
pipe length). If larger refrigerant charges than standard are used then please
consult AS/NZS 60335.2.40 to determine the safe
minimumfloorareafortheinstallation.
Make sure that the area has been made safe by having suitable ventilation and
is free from ignition sources before charging or releasing the charge of R32.
Model
HSNRP26B HSNRP35B HSNRP50B HSNRP60B HSNRP70B HSNRP80B
Standard Charge (g)
900
900
1260
1260
1400
1400
Minimum Floor Area (m2)
4.0
4.0
4.0
4.0
4.0
4.0
WARNINGS FOR PRODUCT USE
WARNING
Ifanabnormalsituationarises(likeaburningsmell),immediatelyturnofftheunitanddisconnect
thepower.Callyourdealerforinstructionstoavoidelectricshock,fireorinjury.
DO
NOTinsertfingers,rodsorotherobjectsintotheairinletoroutlet.Thismaycauseinjury,
since the fan may be rotating at high speeds.
DO NOTuseflammablesprayssuchashairspray,lacquerorpaintneartheunit.Thismaycause fireorcombustion.
DO NOT operate the air conditioner in places near or around combustible gases. Emitted gas may collect around the unit and cause explosion.
DO NOT operate your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can cause electrical components to short circuit.
DO NOT expose your body directly to cool air for a prolonged period of time.
DO NOT allow children to play with the air conditioner. Children must be supervised around the unit at all times.
If the air conditioner is used together with burners or other heating devices, thoroughly ventilate theroomtoavoidoxygendeficiency.
In certain functional environments, such as kitchens, server rooms, etc., the use of specially designedair-conditioningunitsishighlyrecommended.
Rinnai
6
PB Series Split AC IM Issue 1
WARNINGS AND IMPORTANT INFORMATION
OPERATION
WARNING DO NOT let the air conditioner run for extended periods when the
humidity is very high or when doors or windows are left open. As this may
result in an excessive operational loading and lead to product failure.
DO NOT cover or place articles on any part of this appliance.
DO NOT touch, operate or clean the air conditioner with wet hands. It may
result in electric shock or product failure.
DO NOT insert hands or other objects through the air inlet or outlet while the
appliance is operating. It may result in electric shock or product failure.
DO NOT
placeaheaterorotherheatingappliancesnearthisappliance,alwaysensuresufficient
ventilation when using this appliance and a heating appliance at the same
time. Failure to do so mayresultinproductmis-operation.
Turnmainpoweroffbeforecleaning.Failuretodosomayresultinfire,electricshock,orproduct
failure.
DO NOT use solvents, abrasives or harsh detergent to clean any part or surface
of this appliance or spray water or allow liquids to enter the indoor unit.
The enclosure of the appliance and remote control can be cleaned using a soft,
damp cloth and a mild detergent.
NEVERtouchthemetalpartsoftheairconditionerwhenyouremovetheairfilter.Itmayresult
in electric shock or product failure.
DO NOT leaveflammablematerialsneartheappliance.Itmayresultinexplosionorfire.
If there is excessive noise, smell or smoke coming from the appliance, turn
the appliance off, isolate the power supply and contact a service agent.
DO NOToperatetheapplianceifithasbeensubmergedintowaterduetoflooding,contacta
serviceagent.Failuretodosomayresultinelectricshock,fire,seriousinjury,orproductfailure.
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they DO NOT play with the
appliance.
The air conditioning system is designed to achieve consumer comfort. It is NOT
designed for commercial applications requiring a controlled atmosphere (i.e.
computer rooms, food preservation, etc.)
DO NOT blocktheinletoroutletofairflow.Itmayresultproductinfailure.
DO NOT drink the condensate water drained from the appliance. This condensate
is not potable and may present a health risk if consumed.
DO NOT expose people, animals or plants directly to the cold or hot discharge
of the appliance. It may result in serious injury.
DO NOT mix the batteries for the remote control with other types of batteries
or mix new batteries with used batteries. Failure to do so may result in
product failure. STOP using the remote control ifthereisabatteryfluidleak.
OPERATION RANGE LIMITATIONS The table below indicates the temperature ranges the air conditioner can be operated within.
MODE
Cool Mode
Heat Mode
Dry Mode
Room Temperature
16°C
< 30°C
16°C
Outdoor Temperature
0°C ~ 50°C
-15°C ~ 24°C
0°C ~ 50°C
Rinnai
7
PB Series Split AC IM Issue 1
WARNINGS AND IMPORTANT INFORMATION
CLEANING AND MAINTENANCE WARNINGS
WARNING
Turnoffthedeviceanddisconnectthepowerbeforecleaning.Failuretodosocancauseelectrical
shock.
DO NOT clean the air conditioner with excessive amounts of water.
DO NOT clean the air conditioner with combustible cleaning agents. Combustible
cleaning agentscancausefireordeformation.
OPERATING CAUTIONS
CAUTION
Turnofftheairconditioneranddisconnectthepowerifyouarenotgoingtouseitforalongtime. Turnoffandunplugtheunitduringstorms. Make sure that water condensation can drain unhindered from the unit.
DO NOT operate the air conditioner with wet hands. This may cause electric shock.
DO NOT use device for any other purpose than its intended use.
DO NOT climb onto or place objects on top of the outdoor unit.
DO NOT allow the air conditioner to operate for long periods of time with doors or windows open, or if the humidity is very high.
ELECTRICAL WARNINGS
WARNING Only use the specified power cord. If the power cord is damaged, it
must be replaced by the
manufacturer,itsserviceagentorsimilarlyqualifiedpersonsinordertoavoidahazard.
Keep power plug clean. Remove any dust or grime that accumulates on or around
the plug. Dirty plugscancausefireorelectricshock.
DO
NOTpullpowercordtounplugunit.Holdtheplugfirmlyandpullitfromtheoutlet.Pulling
directlyonthecordcandamageit,whichcanleadtofireorelectricshock.
DO NOT modify the length of the power supply cord or use an extension cord to
power the unit.
DO
NOTsharetheelectricaloutletwithotherappliances.Improperorinsufficientpowersupply
cancausefireorelectricalshock.
The product must be properly grounded at the time of installation, or
electrical shock may occur.
For all electrical work, follow all local and national wiring standards,
regulations, and the
Installation Manual. Connect cables tightly, and clamp them securely to
prevent external forces from damaging the terminal. Improper electrical
connections can overheat and cause fire, and may also cause shock. All
electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units.
All wiring must be properly arranged to ensure that the control board cover
can close properly. If the control board cover is not closed properly, it can
lead to corrosion and cause the connection
pointsontheterminaltoheatup,catchfire,orcauseelectricalshock.
If connecting power to fixed wiring, an all-pole disconnection device which
has at least 3mm clearances in all poles, and have a leakage current that may
exceed 10mA, the residual current device (RCD) having a rated residual
operating current not exceeding 30mA, and disconnection
mustbeincorporatedinthefixedwiringinaccordancewiththewiringrules.
Rinnai
8
PB Series Split AC IM Issue 1
WARNINGS AND IMPORTANT INFORMATION
FUSE SPECIFICATIONS NOTE The air conditioner’s circuit board (PCB) is designed
with a fuse to provide overcurrent protection.
Thespecificationsofthefuseareprintedonthecircuitboard,suchas: T3.15AL/250VAC,
T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC,etc. NOTE:
FortheunitsusingR32refrigerant,onlytheblast-proofceramicfusecanbeused.
FLUORINATED GASES NOTE This air-conditioning unit contains fluorinated
greenhouse gases. For specific information on
the type of gas and the amount, please refer to the relevant label on the
appliance itself or the “Operation Manual” in the packaging of the outdoor
unit. Installation, service, maintenance and repair of this unit must be
performed by a certified technician.
Productuninstallationandrecyclingmustbeperformedbyacertifiedtechnician. For
equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes
of CO2 equivalent or more, but of less than 50 tonnes of CO2 equivalent, If
the system has a leak detection system installed, it must be checked for leaks
at least every 24 months. Whentheunitischeckedforleaks,properrecord-
keepingofallchecksisstronglyrecommended.
Rinnai
9
PB Series Split AC IM Issue 1
ACCESSORIES
The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items are not included with the air conditioner must be purchased separately.
Name of Accessories Q`ty(pc)
Shape
Name of Accessories Q`ty(pc)
Shape
Manual
2~3
Remote controller
1
Drain joint
(for cooling &
1
heating models)
Seal
(for cooling &
1
heating models)
Mounting plate
1
Anchor
Mounting plate fixing screw
5~8 (depending on models)
5~8 (depending on models)
Battery
2
Remote controller
holder(optional)
1
Fixing screw for
remote controller
2
holder(optional)
Small Filter (Need to be installed on the back of main air filter by the authorised technician while installing the machine)
1~2 (depending on models)
Name
Connecting pipe assembly
Magnetic ring and belt (if supplied, please refer to the wiring diagram to
install it on the connective cable. )
Shape
Liquid side Gas side
1 2 3
Cm
6 . 3 5 9 . 5 2 9 . 5 2 12. 7 1 6 19
Quantity (PC)
Parts you must purc hase separately. Consult the dealer about the proper pipe
size of the unit you purchased.
Pass the belt through the hole of the Magnetic ring to fix it on the cable
Varies by model
Rinnai
10
PB Series Split AC IM Issue 2
Indoor Unit
1
12cm
15cm
2
2.3m
12cm
INSTALLATION SUMMARY
Select Installation Location
44
Determine Wall Hole Position
5
6
Attach Mounting Plate
-Indoor Unit
Drill Wall Hole
7
Connect Piping
8
Connect Wiring
Prepare Drain Hose
Rinnai
Wrap Piping and Cable
9
8 STEP
Mount Indoor Unit
11
PB Series Split AC IM Issue 2
DESCRIPTION
NOTE: The installation must be performed in accordance with the requirements of local and national standards. The installation may be slightly different in different areas.
1
2 4
5
3 2
4 6
5 7
8
9
10
1 Air-break switch 3
6 7 8
11
11
1
1 Wall Mounting Plate 2 Front Panel 3 Power Cable (Some Units) 4 Louver
2
5
Functional Filter (On Back of Main Filter – Some Units)
6 Drainage Pipe
7 Signal Cable 8 Refrigerant Piping
9 Remote Controller
10 Remote controller Holder (Some Units)
11 Outdoor Unit Power Cable (Some Units)
NOTE ON ILLUSTRATIONS
Illustrations in this manual are for explanatory purposes. The shape of the
indoor unit may vary from model to model.
Rinnai
12
PB Series Split AC IM Issue 2
INDOOR INSTALLATION
Installation Instructions Indoor Unit
PRIOR TO INSTALLATION
Before installing the indoor unit, refer to the label on the product box to
make sure that the model number of the indoor unit matches the model number of
the outdoor unit.
Step 1: Select installation location Before installing the indoor unit, you
must choose an appropriate location. The following are standards that will
help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
Good air circulation Convenient drainage Noise from the unit will not disturb
other people Firm and solid–the location will not vibrate Strong enough to
support the weight of the unit A location at least one meter from all other
electrical devices (e.g., TV, radio, computer) DO NOT install unit in the
following locations:
Near any source of heat, steam, or combustible gas
Near flammable items such as curtains or clothing
Near any obstacle that might block air circulation
Near the doorway
In a location subject to direct sunlight
If there is no fixed refrigerant piping: NOTE ABOUT WALL HOLE:
If there is no fixed refrigerant piping:
While choosing a location, leave ample room for a wall hole (see Drill wall
hole for connective piping step) for the signal cable and refrigerant piping
that connect the indoor and outdoor units. The default position for all piping
is the right side of the indoor unit (while facing the unit). However, the
unit can accommodate piping to both the left and right.
Refer to the following diagram to ensure correct distance from walls and
ceiling:
MUST be 12cm or more
MUST be 15cm or more
Top
MUST be 12cm or more
Left Side
Bottom
Right Side
Recommended 2.0m or more
Step 2: Attach mounting plate to wall
The mounting plate is the device on which you will mount the indoor unit.
Remove the screw that attaches the mounting plate to the back of the indoor
unit.
Screw
Secure the mounting plate to the wall with the screws provided. Make sure that
mounting plate is flat against the wall.
NOTE FOR CONCRETE OR BRICK WALLS
If the wall is made of brick, concrete, or similar material, drill 5mm-
diameter holes in the wall and insert the sleeve anchors provided. Then secure
the mounting plate to the wall by tightening the screws directly into the clip
anchors.
Rinnai
13
PB Series Split AC IM Issue2
5-7mm
INDOOR INSTALLATION
W
Step 3: Drill wall hole for connective piping
1. Determine the location of the wall hole based on the position of the
mounting plate. Refer to Mounting Plate Dimensions.
2. Using a 65mm or 90mm (depending on
CAUTWION
When drilling the wall hole, make sure to avoid wires, plumbing, and other
sensitive components.
models) core drill, drill a hole in the wall.
Make sure that the hole is drilled at a slight downward angle, so that the
3. Place the pWrotective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.
outdoor end of the hole is lower than the indoor end by about 5mm to 7mm. This will ensure proper water drainage.
Wall
Indoor
Outdoor
MOUNTING PLATE DIMENSIONS Different models have difsferent mounting plates. For the different customisation requirements, the shape of the mounting plate may be slightly
different. But the installation dimensions are the
same for the same size of indoor unit.
CorrectWorientation of Mounting Plate
s
PIPE HOLE ANDWWALL CLEARANCE DIMENSIONS
Umsoeutnhteinfgolblorawciknegt.dDiaigmreanmsssiotnosloocfattheetuhneitapedpgroepsraiarteessueprpvilcieedhtooleesnfsourrethme
iinnidmouomr uwnaitllreclleaatirvaentcoesthcean
be applied whilst hanging the bracket. See Page 13. Theinformation is also
supplied on the packaging.
HINRP26MB
402mm
130mm
s 403mm 133mm
HINRP35MB
68mm
38mm
s HINRP50MB HINRP60MB
184mm 45mm 40mm
Pipe hole Ø 45 mm
Bracket
450mm
519mm
Pipe hole Ø 45 mm
214mm
Edge of Indoor Unit
Rinnai
234mm
Pipe hole Ø 65 mm
Bracket
45mm
HINRP70MB
95mm 503mm
HINRP80MB
70mm
215mm
Bracket
Pipe hole Ø 90 mm
53mm
97mm
14
Pipe hole Ø 65 mm
Edge of Indoor Unit
136mm 579mm
Pipe hole Ø 90 mm
Edge of Indoor Unit
149mm
PB Series Split AC IM Issue 2
INDOOR INSTALLATION
Step 4: Prepare refrigerant piping The refrigerant piping is inside an
insulating sleeve attached to the back of the unit. You must prepare the
piping before passing it through the hole in the wall. 1. Based on the
position of the wall hole relative
to the mounting plate, choose the side from which the piping will exit the
unit. 2. If the wall hole is behind the unit, keep the knock-out panel in
place. If the wall hole is to the side of the indoor unit, remove the plastic
knock-out panel from that side of the unit. This will create a slot through
which your piping can exit the unit. Use needle nose pliers if the plastic
panel is too difficult to remove by hand.
Knock-out Panel
3. If existing connective piping is already embedded in the wall, proceed
directly to the Connect Drain Hose step. If there is no embedded piping,
connect the indoor unit’s refrigerant piping to the connective piping that
will join the indoor and outdoor units. Refer to the Refrigerant Piping
Connection section of this manual for detailed instructions.
NOTE ON PIPING ANGLE Refrigerant piping can exit the indoor unit from four
different angles:Left-hand side,Right-hand side, Left rear, Right rear.
Step 5: Connect drain hose
By default, the drain hose is attached to the lefthand side of unit (when
you’re facing the back of the unit). However, it can also be attached to the
right-hand side. To ensure proper drainage, attach the drain hose on the same
side that your refrigerant piping exits the unit. Attach drain hose extension
(purchased separately) to the end of drain hose.
Wrap the connection point firmly with Teflon tape to ensure a good seal and to
prevent leaks.
For the portion of the drain hose that will remain indoors, wrap it with foam
pipe insulation to prevent condensation. Remove the air filter and pour a
small amount of water into the drain pan to make sure that water flows from
the unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to the follo.wing figures.
CORRECT
Make sure there are no kinks or dent in drain hose to ensure proper drainage.
NOT CORRECT
Kinks in the drain hose will create water traps.
CAUTION
Be extremely careful not to dent or damage the piping while bending them away
from the unit. Any dents in the piping will affect the unit’s performance.
NOT CORRECT
Kinks in the drain hose will create water traps.
NOT CORRECT Do not place the end of the drain hose in water or in containers that collect water. This will prevent proper drainage.
PLUG THE UNUSED DRAIN HOLE
To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided.
Rinnai
15
PB Series Split AC IM Issue 2
INDOOR INSTALLATION
BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE REGULATIONS
1. All wiring must comply with local and national electrical codes,
regulations and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical
Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work
immediately. Explain your reasoning to the client, and refuse to install the
unit until the safety issue is properly resolved.
4. Supply Voltage should meet data label requirements (220 ~ 240 V).
Insufficient power supply can cause malfunction, electrical shock, or fire.
5. If connecting power to fixed wiring, a surge protector and main power
switch should be installed.
6. If connecting power to fixed wiring, a switch or circuit breaker that
disconnects all poles and has a contact separation of at least 1/8in (3mm)
must be incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
7. Only connect the unit to an individual branch circuit outlet. Do not
connect another appliance to that outlet.
8. Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose wiring can cause the terminal
to overheat, resulting in product malfunction and possible fire.
10. Do not let wires touch or rest against refrigerant tubing, the
compressor, or any moving parts within the unit.
11. If the unit has an auxiliary electric heater, it must be installed at
least 1 metre away from any combustible materials.
12. To avoid getting an electric shock, never touch the electrical components
soon after the power supply has been turned off. After turning off the power,
always wait 10 minutes or more before you touch the electrical components.
WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO
THE SYSTEM.
Step 6: Connect signal and power cables The signal cable enables communication
between the indoor and outdoor units. You must first choose the right cable
size before preparing it for connection.
Cable Types For cable types or equivalent, please refer to AS/NZS 3000 & local
rules and regulations.
Minimum Cross-Sectional Area of Power and Signal Cables (for reference)
Rated Current of Appliance (A)
Nominal CrossSectional Area (mm2)
3 and 6
0.75
6 and 10
1
10 and 16
1.5
16 and 25
2.5
25 and 32
4
32 and 40
6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit.
NOTE: Please choose the right cable size according to local and national rules (Recommended tables are for reference only).
WARNING
ALL WIRING MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM
LOCATED ON THE BACK OF THE INDOOR UNIT’S FRONT PANEL.
Rinnai
16
PB Series Split AC IM Issue 2
INDOOR INSTALLATION
1. Open front panel of the indoor unit. 2. Using a screwdriver, open the wire
box cover
on the right side of the unit. This will reveal the terminal block.
Front view Terminal block
Wire cover
Screw Cable clamp
Back view (For some units only)
Knock-out panel
NOTE: For the units with conduit tube to connect the cable, remove the big
plastic knoonck-out panel to create a slot through which the conduit tube can
be installed. For the units with five-core cable, remove the middle small
plactic knock-out panel to create a slot through which the cable can exit. Use
needle nose pliers if the plastic panel is too difficult to remove by hand.
NOTE ABOUT WIRING
THE WIRING CONNECTION PROCESS MAY DIFFER SLIGHTLY BETWEEN UNITS AND REGIONS.
Step 7: Wrap piping and cables Before passing the piping, drain hose, and the
signal cable through the wall hole, you must bundle them together to save
space, protect them, and insulate them..
1. Bundle the drain hose, refrigerant pipes, and signal cable as shown below:
Indoor Unit
Space behind unit Refrigerant piping Insulation tape Signal wire Drain hose
3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Facing the back of the unit, remove the plastic panel on the bottom left-
hand side.
5. Feed the signal wire through this slot, from the back of the unit to the
front.
6. Facing the front of the unit, connect the wire according to the indoor
unit’s wiring diagram, connect the u-lug and firmly screw each wire to its
corresponding terminal.
CAUTION
DO NOT MIX UP LIVE AND NULL WIRES This is dangerous, and can cause the air
conditioning unit to malfunction.
7. After checking to make sure every connection is secure, use the cable
clamp to fasten the signal cable to the unit. Screw the cable clamp down
tightly.
8. Replace the wire cover on the front of the unit, and the plastic panel on
the back.
DRAIN HOSE MUST BE ON BOTTOM
Make sure that the drain hose is at the bottom of the bundle. Putting the
drain hose at the top of the bundle can cause the drain pan to overflow, which
can lead to fire or water damage.
DO NOT INTERTWINE SIGNAL CABLE WITH OTHER WIRES
While bundling these items together, do not intertwine or cross the signal
cable with any other wiring.
2. Using adhesive vinyl tape, attach the drain hose to the underside of the
refrigerant pipes.
3. Using insulation tape, wrap the signal wire, refrigerant pipes, and drain
hose tightly together. Double-check that all items are bundled.
DO NOT WRAP ENDS OF PIPING
When wrapping the bundle, keep the ends of the piping unwrapped. You need to
access them to test for leaks at the end of the installation process (refer to
Electrical Checks and Leak Checks section of this manual).
Rinnai
17
PB Series Split AC IM Issue 2
INSDTOAOLRLAINTSIOTNALLATION
Step 8: Mount indoor unit
If you installed new connective piping to the outdoor unit,do the following:
1. If you have already passed the refrigerant piping through the hole in the
wall, proceed to Step 4.
2. Otherwise, double-check that the ends of the refrigerant pipes are sealed
to prevent dirt or foreign materials from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant pipes, drain hose, and
signal wire through the hole in the wall.
4. Hook the top of the indoor unit on the upper hook of the mounting plate.
5. Check that unit is hooked firmly on mounting by applying slight pressure
to the left and right-hand sides of the unit. The unit should not jiggle or
shift.
6. Using even pressure, push down on the bottom half of the unit. Keep
pushing down until the unit snaps onto the hooks along the bottom of the
mounting plate.
7. Again, check that the unit is firmly mounted by applying slight pressure
to the left and the right-hand sides of the unit.
If refrigerant piping is already embedded in the wall, do the following:
1. Hook the top of the indoor unit on the upper hook of the mounting plate.
2. Use a bracket or wedge to prop up the unit, giving you enough room to
connect the refrigerant piping, signal cable, and drain hose.
3. Connect drain hose and refrigerant piping (refer to Refrigerant Piping
Connection section of this manual for instructions).
4. Keep pipe connection point exposed to perform the leak test (refer to
Electrical Checks and Leak Checks section of this manual).
5. After the leak test, wrap the connection point with insulation tape.
6. Remove the bracket or wedge that is propping up the unit.
7. Using even pressure, push down on the bottom half of the unit. Keep
pushing down until the unit snaps onto the hooks along the bottom of the
mounting plate.
UNIT IS ADJUSTABLE
Keep in mind that the hooks on the mounting plate are smaller than the holes
on the back of the unit. If you find that you don’t have ample room to connect
embedded pipes to the indoor unit, the unit can be adjusted left or right by
about 30-50mm, depending on the model.
30-50mm
30-50mm
Move to left or right
Rinnai
18
PB Series Split AC IM Issue 2
OUTDOOR INSTALLATION
Installation Instructions Outdoor Unit
Install the unit by following local codes and
Inrestgaulllathtieounnsit, tbhyefroellmowaiyngbeyoduifrfLeorcsalilghtly
RbeegtuwlaeteionnsdaifnfedreMnutnriecgipiaolnBsu. ilding Codes. They may be
differ slightly between states.
60cm above
3>03oc0nm0lemftm on leNft Air inlet
650mm 65incmfroinntfront
(Wall or obstacle) Air inlet
fr1o0mcmback wall >100mm from back wall
600mm from above
M
Air outlet
MAINTENANCE ACCESS
600mm oonn60rPriicggmhhtt
DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets Near a public street,
crowded areas, or where noise from the unit will disturb others
Near animals or plants that will be harmed by hot air discharge Near any
source of combustible gas In a location that is exposed to large amounts of
dust In a location exposed to a excessive amounts of salty air
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind:
Installation Instructions Outdoor unit
Step 1: Select installation location Before installing the outdoor unit, you
must
Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds. See Figures below.
choose an appropriate location. The following are
standards that will help you choose an appropriate
location for the unit. Strong
Proper installation locations meet the
wind
following standards:
Strong wind
Wind Baffle
Meets all spatial requirements shown in Installation Space Requirements above.
Strong wind
Good air circulation and ventilation
Firm and solid–the location can support the unit and will not vibrate
Noise from the unit will not disturb others
Protected from prolonged periods of direct sunlight or rain
Where snowfall is anticipated, raise the unit above the base pad to prevent
ice buildup and coil damage. Mount the unit high enough to be above the
average accumulated area snowfall. The minimum height must be 46 cm.
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful
not to obstruct air flow around the unit.
If the unit is frequently exposed to salty air (seaside):
Use outdoor unit that is specially designed to resist corrosion.
Installation
Rinnai
19
PB Series Split AC IM Issue 2
OUTDOOR INSTALLATION
Step 2: Install drain joint(Heat pump unit only)
Before bolting the outdoor unit in place, you must install the drain joint at
the bottom of the unit. Note that there are two different types of drain
joints depending on the type of outdoor unit.
If the drain joint comes with a rubber seal (see Fig. A ), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the
outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of
the unit.
4. Connect a drain hose extension (not included) to the drain joint to
redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. B ), do the
following:
1. Insert the drain joint into the hole in the base pan of the unit. The
drain joint will click in place.
2. Connect a drain hose extension (not included) to the drain joint to
redirect water from the unit during heating mode.
D B
Step 3: Anchor outdoor unit The outdoor unit can be anchored to the ground or
to a wall-mounted bracket with bolt (M10). Prepare the installation base of
the unit according to the dimensions below. UNIT MOUNTING DIMENSIONS The
following is a list of different outdoor unit sizes and the distance between
their mounting feet. Prepare the installation base of the unit according to
the dimensions below.
A
Air inlet
Air inlet
Air outlet
Base pan hole of outdoor unit Seal
Seal
Drain joint
(A)
(B)
IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to
ensure swift water drainage. If water drains too slowly, it can freeze in the
hose and flood the unit.
H W
Rinnai
20
PB Series Split AC IM Issue 2
OUTDOOR INSTALLATION
Outdoor Unit Dimensions (mm) W x H x D
805 x 554 x 330 890 x 673 x 342
Mounting Hole Pitch Dimensions
Pitch A (mm) 511
Pitch B (mm) 317
663
354
To install the unit on the ground or on a concrete mounting platform, do the
following: 1. Mark the positions for four expansion bolts
based on dimensions chart on Page 21. 2. Pre-drill holes for expansion bolts.
3. Place a nut on the end of each expansion bolt. 4. Hammer expansion bolts
into the pre-drilled
holes. 5. Remove the nuts from expansion bolts, and
place outdoor unit on bolts.
6. Put washer on each expansion bolt, then replace the nuts.
7. Using a wrench, tighten each nut until snug.
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIMES.
To install the unit on a wall-mounted bracket, do the following:
CAUTION
Make sure that the wall is made of solid brick, concrete, or of similarly
strong material. The wall must be able to support at least four times the
weight of the unit.
1.Mark the position of bracket holes based on dimensions chart.
2. Pre-drill the holes for the expansion bolts. 3. Place a washer and nut on
the end of each
expansion bolt. 4. Thread expansion bolts through holes in
mounting brackets, put mounting brackets in position, and hammer expansion
bolts into the wall. 5. Check that the mounting brackets are level. 6.
Carefully lift unit and place its mounting feet on brackets. 7. Bolt the unit
firmly to the brackets. 8. If allowed, install the unit with rubber gaskets to
reduce vibrations and noise.
Rinnai
21
PB Series Split AC IM Issue 2
OUTDOOR INSTALLATION
Step 4: Connect signal and power cables The outside unit’s terminal block is
protected by an electrical wiring cover on the side of the unit. A
comprehensive wiring diagram is printed on the inside of the wiring cover.
WARNING
7. Insulate unused wires with PVC electrical tape. Arrange them so that they
do not touch any electrical or metal parts.
8. Replace the wire cover on the side of the unit, and screw it in place.
Cover
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO
THE SYSTEM. 1. Prepare the cable for connection:
USE THE RIGHT CABLE
Please choose the right cable refer to ” Cable types” on page 16.
Screw
NOTE: If the cable clamp looks like the following, please select the
appropriate through-hole according to the diameter of the wire.
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit. NNOOTTEE:
:CInhoNoosreththAemaeprpicrao,pprilaeatesecachboleosiezethe right
accacbolerdsinizge tahcecoMrdininigmtuomthCeirMcuinitimCumrreCntircCuaitrrying
CAamppacaictiytyininddicicaateteddoonntthheennaammeeppllaattee ooff tthhee
uunniitt..
a. Using wire strippers, strip the rubber jacket from both ends of cable to
reveal about 40mm of the wires inside.
b. Strip the insulation from the ends of the wires. c. Using a wire crimper,
crimp u-lugs on the
ends of the wires.
PAY ATTENTION TO LIVE WIRE
While crimping wires, make sure you clearly distinguish the Live (“L”) Wire
from other wires.
WARNING
ALL WIRING WORK MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING
DIAGRAM LOCATED INSIDE OF WIRE COVER OF THE OUTDOOR UNIT .
2. Unscrew the electrical wiring cover and remove it. 3. Unscrew the cable
clamp below the terminal
block and place it to the side. 4. Connect the wire according to the wiring
diagram, and firmly screw the u-lug of each wire to its corresponding
terminal. 5. After checking to make sure every connection is secure, loop the
wires around to prevent rain water from flowing into the terminal. 6. Using
the cable clamp, fasten the cable to the unit. Screw the cable clamp down
tightly.
Buckle Three size hole: Small, Large, Medium
When the calbe is not fasten enough, use the buckle to prop it up , so it can
be clamped tightly.
WInirNinogrtohf ATemrmerinicaal Block
1. Remove the wire cover from the unit by loosening the 3 screws.
2. Dismount caps on the conduit panel. 3. Temperarily mount the conduit
tubes(not
included) on the conduit panel. 4. Properly connect both the power supply and
low voltage lines to the corresponding terminals on the terminal block. 5.
Ground the unit in accordance with local codes. 6. Be sure to size each wire
allowing several inches longer than the required length for wiring. 7. Use
lock nuts to secure the conduit tubes.
Terminal block Over 40mm
Connecting cable
G
Power supply cord
Conduit panel
Wire Cover
Please select the appropriate through-hole according to the diameter of the
wire.
Rinnai
22
PB Series Split AC IM Issue 2
REFRIGERANT PIPING CONNECTION
When connecting refrigerant piping, do not let substances or gases other than
the specified refrigerant enter the unit. The presence of other gases or
substances will lower the unit’s capacity, and can cause abnormally high
prefsescutrteheinptehrfeorrmefaringceeraantidonenceyrcgley.eTffihcisiecnacny
ocaf tuhseeuenxipt.loNsoiomninaanl d eifnfijcuieryn.cy is tested on units with
a pipe length of 5 metres.
ANNmoointtieemooumnnpPPipiipepereunLLeoefnn3ggmtthehtres is required to
minimise vibration & excessive noise.
RTTehhfeeerlleetnonggtththheootfafbrreleefrfirbgigeeelrorawanntftoppripispipnineggcwifiwiclilallatiafoffenfcestcothntehtehpeeprmefroafroxmrimmanuacmnecelaennadngdet
neenregrygeyfofiepfcfiiehcneiecignyhcoytfootfhfpethipueinnuigtn..Nit.oNmoinmailnal
eefffificciieennccyy
iisstteesstteeddoonnuunnititsswwitihthaappipipeelelennggththoof 5f
5mmeteretrse.s. AA mmiinniimmuumm ppiippee rruunn
ooff33mmeettrreessisisrereqquuirireeddtotommininimimisiseevvibibraratitoionn&&execxecesssisviveennooisiese.
.
RReeffeerrttootthheettaabblelebbeelolowwfofor
rspspeecicfiificacatitoionnssoonnthtehemmaxaixmimumumlelnegntghthanadnddrdorpohpehigehigthotfopfippiinpgin.
g.
Model
Maximum Length andDrop Height of Refrigerant Piping per Unit Model
Capacity (kW)
Length (m)
Mx Drop Height (m)
R32 Inverter Split Air Conditioner
<4.4 4.4 and <7
25 30
10 20
7 and<10.5
50
25
CCoonnnneeccttioionnInInstsrtuructcitoionns s- RefRriegferirgaenrtaPnipt iPnigping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
90°
cCaroentonceuct tainodnflaIrnesthtreumcptrioopnersly.ThRisewfirlligerant Piping
ensure efficient operation and minimise the
need for future maintenance.
Oblique Rough Warped
1. Measure the distance between the indoor anedtooucutdtoaonrduflnaits.
2. Usinegeaffipciipeentcouptteerra,tciount tahnedpmipineima
ilistetlethleonger than the measured distance.
3. Make sure that the pipe is cut at a perfect 90° angle.
Warped
DO NOT DEFORM PIPE WHILE CUTTING
BTeakeextcraarecanroetftuol dnaomt atoged, admenatg, oer, dent, or
ddeeffoorrmm the ppiippeewwhhileilecuctutitntign.gT.hTishmisawy ill
dardavsetircsaellyyarfefedcutctehethheeahteinagtienfgficeiefnficcyieonfcy
othfethueniut.nit.
Rinnai
23
PB Series Split AC IM Issue 2
REFRIGERANT PIPING CONNECTION
Step 2: Remove burrs Burrs can affect the air-tight seal of refrigerant piping
connection. They must be completely removed. 1. Hold the pipe at a downward
angle to prevent
burrs from falling into the pipe. 2. Using a reamer or deburring tool, remove
all
burrs from the cut section of the pipe.
Pipe Reamer
Point down
PIPING EXTENSION BEYOND FLARE FORM
Outer Diameter of Pipe (mm)
A (mm)
Min.
Max .
Ø 6.35 Ø 9.52 Ø12.7 Ø 16 Ø 19
0.7
1.3
1.0
1.6
1.0
1.8
2.0
2.2
2.0
2.4
Flare form
A
Step 3: Flare pipe ends Proper flaring is essential to achieve an airtight
seal. 1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign materials from entering the pipe. 2.
Sheath the pipe with insulating material. 3. Place flare nuts on both ends of
pipe. Make sure they are facing in the right direction, because you can’t put
them on or change their direction after flaring.
Flare nut
Copper pipe
Pipe
6. Place flaring tool onto the form. 7. Turn the handle of the flaring tool
clockwise
until the pipe is fully flared. 8. Remove the flaring tool and flare form,
then
inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use excessive torque or
to deform the piping in any way. You should first connect the low-pressure
pipe, then the high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the minimum bending radius is
10cm.
4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend
beyond the edge of the flare form in accordance with the dimensions shown in
the table below.
Radius 10cm
Instructions for Connecting Piping to Indoor Unit
1. Align the center of the two pipes that you will connect.
Refrigerant piping
Rinnai
Indoor unit tubing
Flare nut Pipe
24
PB Series Split AC IM Issue 2
REFRIGERANT PIPING CONNECTION
2. Tighten the flare nut as tightly as possible by hand.
3. Using a spanner, grip the nut on the unit tubing.
4. While firmly gripping the nut on the unit tubing, use a torque wrench to
tighten the flare nut according to the torque values in the Torque
Requirements table below. Loosen the flaring nut slightly, then tighten again.
Outer Diameter of Pipe (mm) Ø 6.35
Ø 9.52 Ø 12.7
Ø 16 Ø 19
TORQUE REQUIREMENTS
Tightening Torque (N·m) 18~20
32~39
Flare dimension(B) (mm)
8.4~8.7
13.2~13.5
49~59
16.2~16.5
57~71 67~101
19.2~19.7 23.2~23.7
Flare shape
90 °± 4 45 °±2
B
R0.4~0. 8
DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must
not exceed torque requirements shown in the table above.
InInsstrturucctitoionnssffoorrCCoonnnneeccttiinng PipientgotOo uOtudtodooroUrnUitnit
1. Unscrew the cover from the packed valve on the side of the outdoor unit.
2. Remove protective caps from ends of valves.
3. Align flared pipe end with each valve, and tighten the flare nut as
tightly as possible by hand.
4. Using a spanner, grip the body of the valve. Do not grip the nut that
seals the service valve.
6. Loosen the flaring nut slightly, then tighten again.
7. Repeat Steps 3 to 6 for the remaining pipe.
USE SPANNER TO GRIP MAIN BODY OF VALVE
Torque from tightening the flare nut can snap off other parts of valve.
Connection
Valve cover
5. While firmly gripping the body of the valve, use a torque wrench to tighten the flare nut according to the correct torque values.
Rinnai
25
PB Series Split AC IM Issue 2
AIR EVACUATION
Preparations and Precautions
Air and foreign matter in the refrigerant circuit can 8. If there is a change in system pressure, refer
cause abnormal rises in pressure, which can damage
to Gas Leak Check section for information
the air conditioner, reduce its efficiency, and cause
injury. Use a vacuum pump andem, awnhificohldcgaanudgaemtoage
evacuate the refrigerant circuit, removing any
9. 9.
non-condensable gas and moisture from the system.
on how to check for leaks. If there is no change in system pressure, unscrew
the cap from the packed valve (high pressure valve).
Insert hexagonal wrench into the packed valve (high pressure valve) and open
the valve by
Evacuation installation
should be and when
puenriftoisrmreeldocuapteodno. imnittihael
system.
turning the wrench in a 1/4 counterclockwise turn. Listen for gas to exit the system, then
BEFORE PERFORMING EVACUATION
Check to make sure the connective pipes between the indoor and outdoor units
are connected properly . Check to make sure all wiring is connected
properly.
EEvvaaccuuaattioionnInInsstrtruucctitoionnss
close the valve after 5 seconds. 10. Watch the Pressure Gauge for one minute
to make sure that there is no change in pressure. The Pressure Gauge should
read slightly higher than atmospheric pressure. 11. Remove the charge hose
from the service port.
Flare nut
1. Connect the charge hose of the manifold gauge to service port on the
outdoor unit’s low pressure valve.
2. Connect another charge hose from the manifold gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed. 4. Turn on the vacuum pump to
evacuate the
system. 5. Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG (-10 5Pa).
Manifold Gauge
Compound Pressure gauge gauge Manifold Gauge
-76cmHg
Low pressure valve Pressure hose /
Charge hose
High pressure valve
Charge hose Vacuum pump
Cap
valve body valve stem
12. Using hexagonal wrench, fully open both the high pressure and low
pressure valves.
13. Tighten valve caps on all three valves (service port, high pressure, low
pressure) by hand. You may tighten it further using a torque wrench if needed.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the
stopper. Do not try to force the valve to open further.
Low pressure valve
6. Close the Low Pressure side of the manifold gauge, and turn off the vacuum
pump.
7. Wait for 5 minutes, then check that there has been no change in system
pressure.
Rinnai
26
PB Series Split AC IM Issue 2
AIR EVACUATION
Note on Adding Refrigerant
Some
ssyysstteemmssrereqquuiriereaadddititoionnalaclhcahragrignigndgedpeepnednindginognopnippeipleenlgetnhgs.thThs.eTshtaensdtarnddpairpdepleipnegtlehnvgatrhiesvaries
accorddinnggttoololoccaal lreregguulaltaitoionsn.sF.or example, in one are,
the standard pipe length may be 7.5m.
In ootthheerraarreeaass, ,ththeestsatnadnadradrdpipeiplenlegnthgtihs 5ism5.
mTh.eTrheefrirgeefriagnetrsahnotuslhdobueldchbaergcehdarfgroemd
tfhroemsetrhvieceservice port poonrthoenotuhtedoouotrduonoirt’usnloitw’s
lopwrespsruersesuvraelvvea.lvTeh.e
aTdhdeiatidodniatilorneafrlirgeefriagnetratnotbtoe
bcheacrhgaerdgecdancabnebcealculated
cuaslicnuglattheedfuoslilnogwtihnegffoollromwuinlag: formula:
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe Length (m)
Air Purging Method
< Standard pipe length Vacuum Pump
Additional Refrigerant
N/A
Standard pipe Vacuum Pump length
Liquid Side: Ø 6.35 R32:
(Pipe length standard length) x 12g/m
Liquid Side: Ø 9.52 R32:
(Pipe length standard length) x 24g/m
Rinnai
27
PB Series Split AC IM Issue 2
ELECTRICAL AND GAS LEAK CHECKS
Before Test Run
Only perform test run after you have completed the following steps: ·
Electrical Safety Checks Confirm that
the unit’s electrical system is safe and · operating properly · Gas Leak
Checks Check all flare nut
connections and confirm that the system is · not leaking · Confirm that gas
and liquid (high and low
pressure) valves are fully open ·
EleeccttrriiccaallSSaafefettyyCChheeckcsks
After installation, confirm that all electrical wiring is installed in
accordance with local and national regulations, and according to the
Installation Manual.
BEFORE TEST RUN
Check Grounding Work
Measure grounding resistance by visual detection and with grounding resistance
tester. Grounding resistance must be less than 0.1 .
DURING TEST RUN
Check for Electrical Leakage During the Test Run, use an electroprobe and
multimeter to perform a comprehensive electrical leakage test.
If electrical leakage is detected, turn off the unit immediately and call a
licensed electrician to find and resolve the cause of the leakage. immediately
and call a licensed electrician to find
WARNING RISK OF ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL CODES, AND MUST BE
INSTALLED BY A LICENSED ELECTRICIAN.
Gas Leak Checks
There are two different methods to check for gas leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe
connection points on the indoor unit and outdoor unit. The presence of bubbles
indicates a leak.
Leak Detector Method
If using leak detector, refer to the device’s operation manual for proper
usage instructions.
AFTER PERFORMING GAS LEAK CHECKS After confirming that the all pipe connection
points DO NOT leak, replace the valve cover on the outside unit.
Check-point of indoor unit
Check-point of outdoor unit
D
B
C
A
A: Low pressure stop valve B: High pressure stop valve C& D: Indoor unit flare nuts
Rinnai
28
PB Series Split AC IM Issue 2
TEST RUN
Test Run Checks
Perform the Test Run for at least 30 minutes.
1. Connect power to the unit.
2. Press the ON/OFF button on the remote controller to turn it on.
3. Press the MODE button to scroll through the following functions, one at a
time:
· COOL Select lowest possible temperature · HEAT Select highest possible
temperature
4. Let each function run for 5 minutes, and perform the following checks:
List of Checks to Perform
PASS/FAIL
No electrical leakage
Unit is properly grounded
All electrical terminals properly covered
Indoor and outdoor units are solidly installed
All pipe connection points do not leak
Outdoor Indoor
(2):
(2):
Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function properly
Unit performs HEAT function properly
Indoor unit louvers rotate properly
Indoor unit responds to remote controller
During operation, the pressure of the refrigerant circuit will increase. This
may reveal leaks that were not present during the initial leak check. Take
time during the Test Run to double-check that all refrigerant pipe connection
points do not have leaks. Refer to Gas Leak Check section for instructions. 5.
After the Test Run is successfully completed,
and you confirm that all checks points in List of Checks to Perform have
PASSED, do the following: a. Using remote control, return unit to
normal operating temperature. b. Using insulation tape, wrap the indoor
refrigerant pipe connections that was left uncovered during the indoor unit
installation process.
IF AMBIENT TEMPERATURE IS BELOW 17°C
DO NOT use the remote controller to turn on the COOL function when the ambient
temperature is below 17°C. In this instance, use the MANUAL CONTROL button to
test the COOL function. 1. Lift the front panel of the indoor unit, and
raise it until it clicks in place. 2. The MANUAL CONTROL button is located
on the right-hand side of the unit. Press it 2 times to select the COOL
function. 3. Perform Test Run as normal.
Manual control button
Rinnai
29
PB Series Split AC IM Issue 2
CHECKLIST
FINAL CHECKLIST
The checklist is ONLY to be completed by an Authorised Person.
IMPORTANT
Check Item
What can happen if not checked
Is the indoor unit installed securely?
Falling, vibration, noise
Has an inspection been made to check for gas leakage? Has all thermal
insulation been completed (vapour pipes, liquid pipes, indoor portions of the
drain hose extension)? Is the drainage secure?
Are the electric wires installed correctly?
Is the wiring in accordance within the specifications? Are all inlets /
outlets of the indoor and outdoor units free of any obstructions? Are the stop
valves open?
No cooling or heating
Condensation
Water leakage No cooling or heating, may cause electrical shock or electrical
fire. Operation failure, electrical fire No cooling or heating
No cooling or heating
Are the pipes designed for use with R32?
Pipe or pipe connection leakage
Has a leak test been carried out for the pipe connections?
Pipe connection leakage
Has air purging been carried out?
No cooling or heating
Has the appliance been tested for correct operation?
No cooling or heating
Is the end user fully aware of the operating procedure?
Incorrect operation
Ifyouhaveanswerednotoanyoftheabove,youmustcheckandcorrectbeforeappliancehand- overtocustomer.
Rinnai
30
PB Series Split AC IM Issue 2
SPECIFICATIONS
RINNAI-PBSeriesHi-WallSplitSystem Nominal Capacity
HSNRP26B
kW
2.65
HSNRP35B 3.55
Power Supply to Outdoor Unit
V – Ph – Hz 220~240 – 1 – 50
Recommended Circuit Breaker
A
16
16
Connectivity
–
Wi-Fi Enabled
Demand Response Enabling Device
–
DRED Enabled
Cooling
Rated Capacity
kW
2.65
3.5
Capacity Range
1.00-3.50
1.50-4.90
Rated Power Input
W
530
790
Rated Current (Range)
A
2.5
3.8
AEER
W/W
4.98
4.42
TCSPF (Hot & Humid / Mixed / Cold)
8.02 / 7.497 / 7.887
7.00 / 6.76 / 7.07
Star Rating (Hot & Humid / Mixed / Cold)
–
6.5 / 5.5 / 6.0 STAR
5.0 / 5.0 / 5.5 STAR
Heating
Rated Capacity
kW
2.7
3.8
Capacity Range
1.40-4.00
1.80-5.10
Rated Power Input
W
510
830
Rated Current (Range)
A
2.5
5
ACOP
W/W
5.273
4.564
HSPF (Hot & Humid / Mixed / Cold)
5.79 /5.35 / 4.96
6.23 / 5.22 / 4.50
Star Rating (Hot & Humid / Mixed / Cold)
–
4.0 / 3.5 / 3.0 STAR
4.5 / 3.5 / 3 STAR
Maximum Input Power (Cooling / Heating)
W
2300
2300
Maximum Input Current (Cooling / Heating)
A
10.5
10.5
Suitable Area Coverage (up to 2.6m insulated ceiling) Indoor Unit Model No.
m²
11-17
HINRP26MB
16-23 HINRP35MB
Air Flow (Turbo / Hi / Med / Lo / Min)
L/s
175 / 139 / 100 / 83 / 56
183 / 147 / 106 / 86 / 58
Moisture Removal
L/h
1.00
1.20
Air Flow (Turbo / Hi / Med / Lo / Min)
m3/h
630 / 500 / 360 / 300 / 200
660 / 530 / 380 / 310 / 210
Sound Pressure Level @ 1m (Turbo / Hi / Med / Lo / Min)
dB(A)
46.4 / 39 / 32.5 / 30 / 24.5
46.7 / 39 / 32.5 / 30 / 24.5
Air Swing Louvres Type
–
4-way swing
Dimensions
Dimension (W x H x D)
mm
802 x 200 x 295
802 x 200 x 295
Packing (W x H x D)
965 × 370 × 282
1010 x 385 x 307
Net / Gross Weight
kg
8.5 / 11.1
8.5 / 11.1
Operating Range
Cooling
°C
16 ~ 32
16 ~ 32
Heating
0 ~ 30
0 ~ 30
Outdoor Unit Model No.
HONRP26B
HONRP35B
Sound Power Level Sound Pressure Level @ 1m
dB(A)
57.8
58.5
55.5
55.5
Dimensions
Dimension (W x H x D) Packing (W x H x D)
mm
805 x 330 x 554
915 x 370 x 615
805 x 330 x 554 915 x 370 x 615
Refrigerant
Net / Gross Weight Charged Volume
kg
32.2 / 34.9
kg
0.9
32.2 / 34.9 0.9
Pipe Size: Liquid / Gas
mm
6.35mm / 9.52mm
6.35mm / 9.52mm
Maximum Pipe Length
m
25
25
Chargeless Length
10
10
Extra Charge for Lengths >10m
g/m
12
12
Maximum Vertical Separation
m
10
10
Ambient Temperature Limits
Cooling Heating
°C
0 ~ 52
-15~24
0 ~ 52 -15~24
Capacities tested in accordance with AS/NZS 3823.2, with 5m interconnecting pipe length. With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.
Rinnai
31
PB Series Split AC IM Issue 2
SPECIFICATIONS
RINNAI-PBSeriesHi-WallSplitSystem Nominal Capacity
HSNRP50B
kW
5
HSNRP60B 6
Power Supply to Outdoor Unit
V – Ph – Hz
Recommended Circuit Breaker
A
20
20
Connectivity
–
Wi-Fi Enabled
Demand Response Enabling Device
–
DRED Enabled
Cooling
Rated Capacity
kW
5.0
6.0
Capacity Range
2.10-7.20
2.10-7.20
Rated Power Input
W
1280
1750
Rated Current (Range)
A
5.8
8.0
AEER
W/W
3.90
3.42
TCSPF (Hot & Humid / Mixed / Cold)
6.19 / 5.83 / 6.17
5.86 / 5.61 / 5.99
Star Rating (Hot & Humid / Mixed / Cold)
–
4.5 / 4.0 / 4.5 STAR
4.0 / 4.0 / 4.0 STAR
Heating
Rated Capacity
kW
5.4
6.5
Capacity Range
2.50-7.80
2.50-7.80
Rated Power Input
W
1340
1686
Rated Current (Range)
A
6
8.2
ACOP
W/W
4.019
3.847
HSPF (Hot & Humid / Mixed / Cold)
4.89 / 4.31 / 3.71
5.31 / 4.29 / 3.52
Star Rating (Hot & Humid / Mixed / Cold)
–
3.0 / 2.5 / 2.0 STAR
3.5/ 2.5 / 1.5 STAR
Maximum Input Power (Cooling / Heating)
W
3600
3600
Maximum Input Current (Cooling / Heating)
A
15.5
15.5
Suitable Area Coverage (up to 2.6m insulated ceiling) Indoor Unit Model No.
m²
23-33
HINRP50MB
27-40 HINRP60MB
Air Flow (Turbo / Hi / Med / Lo / Min)
L/s
264 / 222 / 167 / 139 / 89
264 / 222 / 167 / 139 / 89
Moisture Removal
L/h
1.80
2.10
Air Flow (Turbo / Hi / Med / Lo / Min)
m3/h
950 / 800 / 600 / 500 / 322
950 / 800 / 600 / 500 / 322
Sound Pressure Level @ 1m (Turbo / Hi / Med / Lo / Min)
dB(A)
47.1 / 44.5 / 38 / 34.5 / 28
47.1 / 44.5 / 38 / 34.5 / 28
Air Swing Louvres Type
–
4-way swing
Dimensions
Dimension (W x H x D)
mm
971 x 228 x 321
971 x 228 x 321
Packing (W x H x D)
1067 x 385 x 312
1205 x 400 x 317
Net / Gross Weight
kg
11.1 / 14.4
11.1 / 14.4
Operating Range
Cooling
°C
Heating
Outdoor Unit Model No.
HONRP50B
HONRP60B
Sound Power Level
dB(A)
65.2
65.2
Sound Pressure Level @ 1m
59.5
59.5
Dimensions
Dimension (W x H x D)
mm
890 x 342 x 673
890 x 342 x 673
Packing (W x H x D)
995 x 398 x 740
995 x 398 x 740
Net / Gross Weight
kg
38.3 / 41.4
38.3 / 41.4
Refrigerant
Charged Volume
kg
1.26
1.26
Pipe Size: Liquid / Gas
mm
6.35mm / 12.7mm
6.35mm / 12.7mm
Maximum Pipe Length
m
30
30
Chargeless Length
10
10
Extra Charge for Lengths >10m
g/m
12
12
Maximum Vertical Separation
m
20
20
Ambient Temperature Limits
Cooling Heating
°C
0 ~ 50
-15 ~ 24
0 ~ 50 -15 ~ 24
Capacities tested in accordance with AS/NZS 3823.2, with 5m interconnecting pipe length. With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.
Rinnai
32
PB Series Split AC IM Issue 2
SPECIFICATIONS
RINNAI-PBSeriesHi-WallSplitSystem Nominal Capacity
HSNRP70B
kW
7
HSNRP80B 8
Power Supply to Outdoor Unit
V – Ph – Hz
Recommended Circuit Breaker
A
25
25
Connectivity
–
Wi-Fi Enabled
Demand Response Enabling Device
–
DRED Enabled
Cooling
Rated Capacity
kW
7.15
7.8
Capacity Range
3.20-8.0
3.20-8.0
Rated Power Input
W
1920
2200
Rated Current (Range)
A
10.5
10.5
AEER
W/W
3.53
3.39
TCSPF (Hot & Humid / Mixed / Cold)
5.36 / 5.14 / 5.37
5.38 / 5.21 / 5.48
Star Rating (Hot & Humid / Mixed / Cold)
–
3.5 /3.5 / 3.5
3.5 / 3.5 / 3.5
Heating
Rated Capacity
kW
7.8
8.3
Capacity Range
2.20-8.8
2.20-8.8
Rated Power Input
W
1990
2280
Rated Current (Range)
A
10.8
10.8
ACOP
W/W
3.734
3.611
HSPF (Hot & Humid / Mixed / Cold)
Star Rating (Hot & Humid / Mixed / Cold)
–
4.97 / 4.32 / 3.82 3.0 / 2.5 / 2.0
4.96 / 4.20 / 3.66 3.0 / 2.5 / 2.0
Maximum Input Power (Cooling / Heating)
W
4050
4050
Maximum Input Current (Cooling / Heating)
A
17.5
17.5
Suitable Area Coverage (up to 2.6m insulated ceiling)
m²
32-47
32-47
Indoor Unit Model No.
HINRP70MB
HINRP80B
Air Flow (Turbo / Hi / Med / Lo / Min)
L/s
382 / 303 / 250 / 229 / 147
382 / 303 / 250 / 229 / 147
Moisture Removal Air Flow (Turbo / Hi / Med / Lo / Min)
L/h
2.40
3.00
m3/h
1375 / 1090 / 900 / 825 / 530 1375 / 1090 / 900 / 825 / 530
Sound Pressure Level @ 1m (Turbo / Hi / Med / Lo / Min)
dB(A)
57.645 / 45 / 39 / 33.5 / 29.5 57.645 / 45 / 39 / 33.5 / 29.5
Air Swing Louvres Type
–
4-way swing
Dimensions
Dimension (W x H x D)
mm
1082 x 234 x 337
1082 x 234 x 337
Packing (W x H x D) Net / Gross Weight
1155 x 415 x 315
kg
13.5 / 17.1
1155 x 415 x 315 13.5 / 17.1
Operating Range
Cooling
°C
Heating
Outdoor Unit Model No.
HONRP70B
HONRP80B
Sound Power Level
dB(A)
65
66.5
Sound Pressure Level @ 1m
61
61
Dimensions
Dimension (W x H x D) Packing (W x H x D)
mm
890 x 342 x 673
995 x 398 x 740
890 x 342 x 673 995 x 398 x 740
Refrigerant
Net / Gross Weight Charged Volume
kg
42.4 / 46.7
kg
1.4
42.4 / 46.7 1.4
Pipe Size: Liquid / Gas
mm
6.35mm / 15.9mm
6.35mm / 15.9mm
Maximum Pipe Length
m
50
50
Chargeless Length
10
10
Extra Charge for Lengths >10m
g/m
12
12
Maximum Vertical Separation
m
25
25
Ambient Temperature Limits
Cooling Heating
°C
-15 ~ 50
-15 ~ 24
-15 ~ 50 -15 ~ 4
Capacities tested in accordance with AS/NZS 3823.2, with 5m interconnecting pipe length. With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.
Rinnai
33
PB Series Split AC IM Issue 2
NOTES
Rinnai
34
PB Series Split AC IM Issue 2
NOTES
Rinnai
35
PB Series Split AC IM Issue 2
CONTACTS
innai Australia Pty Ltd
ABN 74 005 138 769 | AU45204
100 Atlantic Drive, Keysborough, Victoria 3173 P.O. Box 460, Braeside, Victoria 3195 Tel: (03) 9271 6625 Fax: (03) 9271 6622
National Help Line Tel: 1300 555 545* Fax: 1300 555 655 Monday to Friday, 8.00 am to 5.00 pm EST.
*Cost of a local call may be higher from a mobile phone. (National calls from public phones in Australia are free.)
For further information visit www.rinnai.com.au or email enquiry@rinnai.com.au
innai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your innai appliance. If your appliance requires service, please call our National Help Line. Rinnai recommends that this appliance be serviced once a year.
With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.
Rinnai
36
PB Series Split AC IM Issue 2 March 2024
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>