Rinnai HSNRP26B PB Series Split Type Wall Mounted Air Conditioner Instruction Manual

June 1, 2024
Rinnai

Rinnai-logo

Rinnai HSNRP26B PB Series Split Type Wall Mounted Air Conditioner

Rinnai-HSNRP26B-PB-Series-Split-Type-Wall-Mounted-Air-Conditioner-
image

Product Information

Specifications

  • Models: HSNRP26B, HSNRP35B, HSNRP50B, HSNRP60B, HSNRP70B, HSNRP80B
  • Indoor Unit Models: HINRP26MB, HINRP35MB, HINRP50MB, HINRP60MB, HINRP70MB, HINRP80B, HINRP20MB
  • Outdoor Unit Models: HONRP26B, HONRP35B, HONRP50B, HONRP60B, HONRP70B, HONRP80B
  • Refrigerant: R32
  • Type: Split Type Wall Mounted Air Conditioner
  • Manufacturer: Rinnai

Product Usage Instructions

Warnings and Important Information

READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE. Always comply with the precautions to avoid dangerous situations.

Installation Summary

This appliance must be installed, maintained, and removed only by an Authorized Person. Follow the manufacturer’s instructions for installation.

Description

The wall-mounted air conditioner is designed for efficient cooling and heating of indoor spaces.

Indoor Installation

Follow the detailed indoor installation instructions provided in the manual.

Outdoor Installation

Ensure proper outdoor installation of the unit for optimal performance. Refer to the manual for detailed steps.

Refrigerant Piping Connection

Connect the refrigerant piping carefully following the instructions to prevent leaks and ensure proper functioning.

FAQs

  • Q: What refrigerant does the unit use?
    • A: The unit uses R32 refrigerant for efficient cooling.
  • Q: Who should install and maintain the appliance?
    • A: The appliance should be installed, maintained, and removed only by an Authorized Person as specified by the manufacturer.

“`

MODELS
System HSNRP26B HSNRP35B HSNRP50B HSNRP60B HSNRP70B HSNRP80B Ref Only

Indoor HINRP26MB HINRP35MB HINRP50MB HINRP60MB HINRP70MB HINRP80B HINRP20MB

Outdoor HONRP26B HONRP35B HONRP50B HONRP60B HONRP70B HONRP80B Matching Multi System Only

REFRIGERANT
R32

PB Series Split Type Wall Mounted Air Conditioner Installation Manual

This appliance must be installed in accordance with: · Manufacturer’s Installation Instructions · Current AS/NZS 3000, AS/NZS 5141, AS/NZS 5149 · Local Regulations and Municipal Building Codes
including local OH&S requirements This appliance must be installed, maintained and removed only by an Authorised Person. For continued safety of this appliance it must be installed and maintained in accordance with the manufacturer’s instructions.
REFRIGERANT

WARNINGS AND IMPORTANT INFORMATION

READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE. WARNING Always comply with the following precautions to avoid dangerous situations and to ensure
optimum performance. Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death. DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in personal injury or death. WARNINGS: Indicates a potentially hazardous situation which, if not avoided, could result in personal injury or death. CAUTIONS: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury or damage to the appliance. It may also be used to alert against unsafe practices.
REGULATORY
WARNING This appliance shall be installed in accordance with: Manufacturer’s Installation Instructions. Current AS/NZS 3000, AS/NZS 5141, AS/NZS 5149. Local Regulations and Municipal Building Codes including local OH&S requirements.
This appliance must be installed, maintained and removed ONLY by an Authorised Person. For continued safety of this appliance it must be installed and maintained in accordance with the manufacturers instructions. This appliance uses R32 refrigerant. This appliance is heavy, use 2 people or mechanical lifting device. Improper lifting may result in serious injury. Take care when opening or unpacking this appliance. Failure to do so may result in serious injury or product failure. DO NOT modify the electrical wiring of this appliance. If the control power wiring is damaged or deteriorated then it must be replaced by an authorised person. Failure to do so may result in electricshock,fire,seriousinjuryorproductfailure. DO NOT install the air conditioner on an unstable or non level surface or where there may be a danger of it falling. It may result in death, serious injury, or product failure. DO NOT install the outdoor unit where noise may cause nuisance. DO NOT install the outdoor unit where it will be exposed to sea wind (salt spray) as this will reduce durability.

MANDATORY INSPECTION PRIOR TO INSTALLATION

IMPORTANT

Immediately report any damage or discrepancies to the Supplier of the appliance. This appliance was inspected and tested at the time of manufacture and packaging, and released for transportation without known damage. Upon receipt, inspect the exterior for evidence of rough handling in shipment. Ensure that the appliance is labelled correctly for the gas and electrical supply, and/or other services it is intended to be connected to.

For safety and warranty purposes, appliances that may be damaged or incorrect MUST NOT be installed or operated under any circumstances. Installation of damaged or incorrect appliances may contravene local government regulations. Rinnai disclaims any liability or responsibility whatsoever in relation to the installation or operation of damaged or incorrect appliances.

Rinnai

4

PB Series Split AC IM ­ Issue 1

WARNINGS AND IMPORTANT INFORMATION
INSTALLATION
WARNING This appliance shall be installed in accordance with local electrical safety regulations by an authorised person such as a licensed electrician. Contact an authorised service technician for repair or maintenance of this appliance.
Onlyusetheincludedaccessories,parts,andspecifiedpartsforinstallation.Usingnon- standard partscancausewaterleakage,electricalshock,fire,andcancausetheunittofail. Installtheunitinafirmlocationthatcansupporttheunit’sweight.Ifthechosenlocationcannot support the unit’s weight, or the installation is not done properly, the unit may drop and cause serious injury and damage.
DO NOT turn on the power until all work has been completed.
When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the unit.
How to install the appliance to its support, please read the information for details in “indoor unit installation” and “outdoor unit installation” sections.
For units that have an auxiliary electric heater, DO NOT install the unit within 1 meter (3 feet) of any combustible materials.
DO NOT install the unit in a location that may be exposed to combustible gas leaks. If combustible gasaccumulatesaroundtheunit,itmaycausefire. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
This appliance is a Type 1 Electrical Appliance.
Make sure the live wire, neutral wire and earth wire in the power socket are properly connected. Inadequateorincorrectelectricalconnectionsmaycausefireorelectricshock. The yellow-green wire in air conditioner is the earthing wire which cannot be used for other purposes. Improper earthing may cause electric shock.
The circuit breaker must have the functions of magnetic tripping and heat tripping to prevent short circuit and overload.
Use a standard circuit breaker and fuse conforming with the rating of the appliances.
The unit must be earthed in accordance with local regulations.
Connect all wiring tightly. Failure to do so may result in electric shock or product failure.
DO NOT supply power to the unit until all wiring and tubing are completed.
Select an installation location where the components can be mounted securely and accessible for service and replacement.
Make sure tubing is properly insulated to ensure optimum performance.
Install the drain hose properly for smooth drainage of condensed water.
Make sure to check for and rectify any refrigerant leaks after you install or repair the unit.
This appliance uses R32 (difluoromethane) refrigerant, which is a flammable gas class 2.2 according to AS/NZS 1677 and must be handled by a refrigeration mechanic with appropriate Australian refrigerant handling licence.

Rinnai

5

PB Series Split AC IM ­ Issue 1

WARNINGS AND IMPORTANT INFORMATION

WARNING

WARNINGRiskoffire/flammablematerial.Iftherefrigerantisleaked,togetherwithan external ignition source, there is a possibility of ignition.
Read the OPERATING INSTRUCTIONS carefully before operation.

Service personnel are required to carefully read the OPERATING INSTRUCTIONS and INSTALLATION MANUAL before operation.
Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION MANUAL, and the like.
Certain levels of refrigerant require minimum room sizes. Please ensure that these minimum room sizes are adhered to for standard installations (up to 10m pipe length). If larger refrigerant charges than standard are used then please consult AS/NZS 60335.2.40 to determine the safe minimumfloorareafortheinstallation.
Make sure that the area has been made safe by having suitable ventilation and is free from ignition sources before charging or releasing the charge of R32.

Model

HSNRP26B HSNRP35B HSNRP50B HSNRP60B HSNRP70B HSNRP80B

Standard Charge (g)

900

900

1260

1260

1400

1400

Minimum Floor Area (m2)

4.0

4.0

4.0

4.0

4.0

4.0

WARNINGS FOR PRODUCT USE

WARNING

Ifanabnormalsituationarises(likeaburningsmell),immediatelyturnofftheunitanddisconnect thepower.Callyourdealerforinstructionstoavoidelectricshock,fireorinjury.
DO NOTinsertfingers,rodsorotherobjectsintotheairinletoroutlet.Thismaycauseinjury, since the fan may be rotating at high speeds.

DO NOTuseflammablesprayssuchashairspray,lacquerorpaintneartheunit.Thismaycause fireorcombustion.

DO NOT operate the air conditioner in places near or around combustible gases. Emitted gas may collect around the unit and cause explosion.

DO NOT operate your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can cause electrical components to short circuit.

DO NOT expose your body directly to cool air for a prolonged period of time.

DO NOT allow children to play with the air conditioner. Children must be supervised around the unit at all times.

If the air conditioner is used together with burners or other heating devices, thoroughly ventilate theroomtoavoidoxygendeficiency.

In certain functional environments, such as kitchens, server rooms, etc., the use of specially designedair-conditioningunitsishighlyrecommended.

Rinnai

6

PB Series Split AC IM ­ Issue 1

WARNINGS AND IMPORTANT INFORMATION

OPERATION
WARNING DO NOT let the air conditioner run for extended periods when the humidity is very high or when doors or windows are left open. As this may result in an excessive operational loading and lead to product failure.
DO NOT cover or place articles on any part of this appliance.
DO NOT touch, operate or clean the air conditioner with wet hands. It may result in electric shock or product failure.
DO NOT insert hands or other objects through the air inlet or outlet while the appliance is operating. It may result in electric shock or product failure.
DO NOT placeaheaterorotherheatingappliancesnearthisappliance,alwaysensuresufficient ventilation when using this appliance and a heating appliance at the same time. Failure to do so mayresultinproductmis-operation.
Turnmainpoweroffbeforecleaning.Failuretodosomayresultinfire,electricshock,orproduct failure.
DO NOT use solvents, abrasives or harsh detergent to clean any part or surface of this appliance or spray water or allow liquids to enter the indoor unit. The enclosure of the appliance and remote control can be cleaned using a soft, damp cloth and a mild detergent.
NEVERtouchthemetalpartsoftheairconditionerwhenyouremovetheairfilter.Itmayresult in electric shock or product failure.
DO NOT leaveflammablematerialsneartheappliance.Itmayresultinexplosionorfire.
If there is excessive noise, smell or smoke coming from the appliance, turn the appliance off, isolate the power supply and contact a service agent.
DO NOToperatetheapplianceifithasbeensubmergedintowaterduetoflooding,contacta serviceagent.Failuretodosomayresultinelectricshock,fire,seriousinjury,orproductfailure.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they DO NOT play with the appliance.
The air conditioning system is designed to achieve consumer comfort. It is NOT designed for commercial applications requiring a controlled atmosphere (i.e. computer rooms, food preservation, etc.)
DO NOT blocktheinletoroutletofairflow.Itmayresultproductinfailure.
DO NOT drink the condensate water drained from the appliance. This condensate is not potable and may present a health risk if consumed.
DO NOT expose people, animals or plants directly to the cold or hot discharge of the appliance. It may result in serious injury.
DO NOT mix the batteries for the remote control with other types of batteries or mix new batteries with used batteries. Failure to do so may result in product failure. STOP using the remote control ifthereisabatteryfluidleak.

OPERATION RANGE LIMITATIONS The table below indicates the temperature ranges the air conditioner can be operated within.

MODE

Cool Mode

Heat Mode

Dry Mode

Room Temperature

16°C

< 30°C

16°C

Outdoor Temperature

0°C ~ 50°C

-15°C ~ 24°C

0°C ~ 50°C

Rinnai

7

PB Series Split AC IM ­ Issue 1

WARNINGS AND IMPORTANT INFORMATION

CLEANING AND MAINTENANCE WARNINGS
WARNING Turnoffthedeviceanddisconnectthepowerbeforecleaning.Failuretodosocancauseelectrical shock.
DO NOT clean the air conditioner with excessive amounts of water.
DO NOT clean the air conditioner with combustible cleaning agents. Combustible cleaning agentscancausefireordeformation.

OPERATING CAUTIONS

CAUTION

Turnofftheairconditioneranddisconnectthepowerifyouarenotgoingtouseitforalongtime. Turnoffandunplugtheunitduringstorms. Make sure that water condensation can drain unhindered from the unit.

DO NOT operate the air conditioner with wet hands. This may cause electric shock.

DO NOT use device for any other purpose than its intended use.

DO NOT climb onto or place objects on top of the outdoor unit.

DO NOT allow the air conditioner to operate for long periods of time with doors or windows open, or if the humidity is very high.

ELECTRICAL WARNINGS
WARNING Only use the specified power cord. If the power cord is damaged, it must be replaced by the manufacturer,itsserviceagentorsimilarlyqualifiedpersonsinordertoavoidahazard.
Keep power plug clean. Remove any dust or grime that accumulates on or around the plug. Dirty plugscancausefireorelectricshock.
DO NOTpullpowercordtounplugunit.Holdtheplugfirmlyandpullitfromtheoutlet.Pulling directlyonthecordcandamageit,whichcanleadtofireorelectricshock.
DO NOT modify the length of the power supply cord or use an extension cord to power the unit.
DO NOTsharetheelectricaloutletwithotherappliances.Improperorinsufficientpowersupply cancausefireorelectricalshock.
The product must be properly grounded at the time of installation, or electrical shock may occur.
For all electrical work, follow all local and national wiring standards, regulations, and the
Installation Manual. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections can overheat and cause fire, and may also cause shock. All electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units.
All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection pointsontheterminaltoheatup,catchfire,orcauseelectricalshock.
If connecting power to fixed wiring, an all-pole disconnection device which has at least 3mm clearances in all poles, and have a leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual operating current not exceeding 30mA, and disconnection mustbeincorporatedinthefixedwiringinaccordancewiththewiringrules.

Rinnai

8

PB Series Split AC IM ­ Issue 1

WARNINGS AND IMPORTANT INFORMATION
FUSE SPECIFICATIONS NOTE The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection.
Thespecificationsofthefuseareprintedonthecircuitboard,suchas: T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC,etc. NOTE: FortheunitsusingR32refrigerant,onlytheblast-proofceramicfusecanbeused.
FLUORINATED GASES NOTE This air-conditioning unit contains fluorinated greenhouse gases. For specific information on
the type of gas and the amount, please refer to the relevant label on the appliance itself or the “Operation Manual” in the packaging of the outdoor unit. Installation, service, maintenance and repair of this unit must be performed by a certified technician. Productuninstallationandrecyclingmustbeperformedbyacertifiedtechnician. For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more, but of less than 50 tonnes of CO2 equivalent, If the system has a leak detection system installed, it must be checked for leaks at least every 24 months. Whentheunitischeckedforleaks,properrecord- keepingofallchecksisstronglyrecommended.

Rinnai

9

PB Series Split AC IM ­ Issue 1

ACCESSORIES

The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items are not included with the air conditioner must be purchased separately.

Name of Accessories Q`ty(pc)

Shape

Name of Accessories Q`ty(pc)

Shape

Manual

2~3

Remote controller

1

Drain joint

(for cooling &

1

heating models)

Seal

(for cooling &

1

heating models)

Mounting plate

1

Anchor
Mounting plate fixing screw

5~8 (depending on models)
5~8 (depending on models)

Battery

2

Remote controller

holder(optional)

1

Fixing screw for

remote controller

2

holder(optional)

Small Filter (Need to be installed on the back of main air filter by the authorised technician while installing the machine)

1~2 (depending on models)

Name
Connecting pipe assembly
Magnetic ring and belt (if supplied, please refer to the wiring diagram to install it on the connective cable. )

Shape
Liquid side Gas side
1 2 3

Cm
6 . 3 5 9 . 5 2 9 . 5 2 12. 7 1 6 19

Quantity (PC)
Parts you must purc hase separately. Consult the dealer about the proper pipe size of the unit you purchased.

Pass the belt through the hole of the Magnetic ring to fix it on the cable

Varies by model

Rinnai

10

PB Series Split AC IM ­ Issue 2

Indoor Unit

1
12cm

15cm

2

2.3m

12cm

INSTALLATION SUMMARY

Select Installation Location
44

Determine Wall Hole Position

5

6

Attach Mounting Plate

-Indoor Unit

Drill Wall Hole
7

Connect Piping
8

Connect Wiring

Prepare Drain Hose
Rinnai

Wrap Piping and Cable

9

8 STEP

Mount Indoor Unit

11

PB Series Split AC IM ­ Issue 2

DESCRIPTION

NOTE: The installation must be performed in accordance with the requirements of local and national standards. The installation may be slightly different in different areas.

1
2 4
5

3 2

4 6

5 7

8

9

10

1 Air-break switch 3
6 7 8

11

11

1
1 Wall Mounting Plate 2 Front Panel 3 Power Cable (Some Units) 4 Louver

2

5

Functional Filter (On Back of Main Filter – Some Units)

6 Drainage Pipe

7 Signal Cable 8 Refrigerant Piping

9 Remote Controller
10 Remote controller Holder (Some Units)
11 Outdoor Unit Power Cable (Some Units)

NOTE ON ILLUSTRATIONS
Illustrations in this manual are for explanatory purposes. The shape of the indoor unit may vary from model to model.

Rinnai

12

PB Series Split AC IM ­ Issue 2

INDOOR INSTALLATION

Installation Instructions ­ Indoor Unit

PRIOR TO INSTALLATION
Before installing the indoor unit, refer to the label on the product box to make sure that the model number of the indoor unit matches the model number of the outdoor unit.
Step 1: Select installation location Before installing the indoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
Good air circulation Convenient drainage Noise from the unit will not disturb other people Firm and solid–the location will not vibrate Strong enough to support the weight of the unit A location at least one meter from all other
electrical devices (e.g., TV, radio, computer) DO NOT install unit in the following locations:
Near any source of heat, steam, or combustible gas
Near flammable items such as curtains or clothing
Near any obstacle that might block air circulation
Near the doorway
In a location subject to direct sunlight

If there is no fixed refrigerant piping: NOTE ABOUT WALL HOLE:
If there is no fixed refrigerant piping:
While choosing a location, leave ample room for a wall hole (see Drill wall hole for connective piping step) for the signal cable and refrigerant piping that connect the indoor and outdoor units. The default position for all piping is the right side of the indoor unit (while facing the unit). However, the unit can accommodate piping to both the left and right.
Refer to the following diagram to ensure correct distance from walls and ceiling:

MUST be 12cm or more

MUST be 15cm or more
Top

MUST be 12cm or more

Left Side

Bottom

Right Side

Recommended 2.0m or more

Step 2: Attach mounting plate to wall
The mounting plate is the device on which you will mount the indoor unit.
Remove the screw that attaches the mounting plate to the back of the indoor unit.

Screw
Secure the mounting plate to the wall with the screws provided. Make sure that mounting plate is flat against the wall.

NOTE FOR CONCRETE OR BRICK WALLS
If the wall is made of brick, concrete, or similar material, drill 5mm- diameter holes in the wall and insert the sleeve anchors provided. Then secure the mounting plate to the wall by tightening the screws directly into the clip anchors.

Rinnai

13

PB Series Split AC IM ­ Issue2

5-7mm

INDOOR INSTALLATION
W

Step 3: Drill wall hole for connective piping
1. Determine the location of the wall hole based on the position of the mounting plate. Refer to Mounting Plate Dimensions.
2. Using a 65mm or 90mm (depending on

CAUTWION
When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.

models) core drill, drill a hole in the wall.
Make sure that the hole is drilled at a slight downward angle, so that the

3. Place the pWrotective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.

outdoor end of the hole is lower than the indoor end by about 5mm to 7mm. This will ensure proper water drainage.

Wall

Indoor

Outdoor

MOUNTING PLATE DIMENSIONS Different models have difsferent mounting plates. For the different customisation requirements, the shape of the mounting plate may be slightly

different. But the installation dimensions are the

same for the same size of indoor unit.

CorrectWorientation of Mounting Plate

s

PIPE HOLE ANDWWALL CLEARANCE DIMENSIONS
Umsoeutnhteinfgolblorawciknegt.dDiaigmreanmsssiotnosloocfattheetuhneitapedpgroepsraiarteessueprpvilcieedhtooleesnfsourrethme iinnidmouomr uwnaitllreclleaatirvaentcoesthcean
be applied whilst hanging the bracket. See Page 13. Theinformation is also supplied on the packaging.

HINRP26MB

402mm
130mm

s 403mm 133mm

HINRP35MB
68mm

38mm

s HINRP50MB HINRP60MB

184mm 45mm 40mm

Pipe hole Ø 45 mm

Bracket

450mm

519mm

Pipe hole Ø 45 mm

214mm
Edge of Indoor Unit

Rinnai

234mm

Pipe hole Ø 65 mm

Bracket

45mm

HINRP70MB

95mm 503mm

HINRP80MB

70mm

215mm

Bracket
Pipe hole Ø 90 mm

53mm

97mm

14

Pipe hole Ø 65 mm

Edge of Indoor Unit

136mm 579mm

Pipe hole Ø 90 mm

Edge of Indoor Unit

149mm
PB Series Split AC IM ­ Issue 2

INDOOR INSTALLATION

Step 4: Prepare refrigerant piping The refrigerant piping is inside an insulating sleeve attached to the back of the unit. You must prepare the piping before passing it through the hole in the wall. 1. Based on the position of the wall hole relative
to the mounting plate, choose the side from which the piping will exit the unit. 2. If the wall hole is behind the unit, keep the knock-out panel in place. If the wall hole is to the side of the indoor unit, remove the plastic knock-out panel from that side of the unit. This will create a slot through which your piping can exit the unit. Use needle nose pliers if the plastic panel is too difficult to remove by hand.
Knock-out Panel
3. If existing connective piping is already embedded in the wall, proceed directly to the Connect Drain Hose step. If there is no embedded piping, connect the indoor unit’s refrigerant piping to the connective piping that will join the indoor and outdoor units. Refer to the Refrigerant Piping Connection section of this manual for detailed instructions.
NOTE ON PIPING ANGLE Refrigerant piping can exit the indoor unit from four different angles:Left-hand side,Right-hand side, Left rear, Right rear.

Step 5: Connect drain hose
By default, the drain hose is attached to the lefthand side of unit (when you’re facing the back of the unit). However, it can also be attached to the right-hand side. To ensure proper drainage, attach the drain hose on the same side that your refrigerant piping exits the unit. Attach drain hose extension (purchased separately) to the end of drain hose.
Wrap the connection point firmly with Teflon tape to ensure a good seal and to prevent leaks.
For the portion of the drain hose that will remain indoors, wrap it with foam pipe insulation to prevent condensation. Remove the air filter and pour a small amount of water into the drain pan to make sure that water flows from the unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to the follo.wing figures.

CORRECT
Make sure there are no kinks or dent in drain hose to ensure proper drainage.

NOT CORRECT
Kinks in the drain hose will create water traps.

CAUTION
Be extremely careful not to dent or damage the piping while bending them away from the unit. Any dents in the piping will affect the unit’s performance.

NOT CORRECT
Kinks in the drain hose will create water traps.

NOT CORRECT Do not place the end of the drain hose in water or in containers that collect water. This will prevent proper drainage.

PLUG THE UNUSED DRAIN HOLE

To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided.

Rinnai

15

PB Series Split AC IM ­ Issue 2

INDOOR INSTALLATION

BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE REGULATIONS
1. All wiring must comply with local and national electrical codes, regulations and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.
4. Supply Voltage should meet data label requirements (220 ~ 240 V). Insufficient power supply can cause malfunction, electrical shock, or fire.
5. If connecting power to fixed wiring, a surge protector and main power switch should be installed.
6. If connecting power to fixed wiring, a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring. The qualified technician must use an approved circuit breaker or switch.
7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that outlet.
8. Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
10. Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.
11. If the unit has an auxiliary electric heater, it must be installed at least 1 metre away from any combustible materials.
12. To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 10 minutes or more before you touch the electrical components.

WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.
Step 6: Connect signal and power cables The signal cable enables communication between the indoor and outdoor units. You must first choose the right cable size before preparing it for connection.
Cable Types For cable types or equivalent, please refer to AS/NZS 3000 & local rules and regulations.

Minimum Cross-Sectional Area of Power and Signal Cables (for reference)

Rated Current of Appliance (A)

Nominal CrossSectional Area (mm2)

3 and 6

0.75

6 and 10

1

10 and 16

1.5

16 and 25

2.5

25 and 32

4

32 and 40

6

CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit.

NOTE: Please choose the right cable size according to local and national rules (Recommended tables are for reference only).

WARNING
ALL WIRING MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM LOCATED ON THE BACK OF THE INDOOR UNIT’S FRONT PANEL.

Rinnai

16

PB Series Split AC IM ­ Issue 2

INDOOR INSTALLATION

1. Open front panel of the indoor unit. 2. Using a screwdriver, open the wire box cover
on the right side of the unit. This will reveal the terminal block.
Front view Terminal block
Wire cover
Screw Cable clamp
Back view (For some units only)
Knock-out panel
NOTE: For the units with conduit tube to connect the cable, remove the big plastic knoonck-out panel to create a slot through which the conduit tube can be installed. For the units with five-core cable, remove the middle small plactic knock-out panel to create a slot through which the cable can exit. Use needle nose pliers if the plastic panel is too difficult to remove by hand.

NOTE ABOUT WIRING
THE WIRING CONNECTION PROCESS MAY DIFFER SLIGHTLY BETWEEN UNITS AND REGIONS. Step 7: Wrap piping and cables Before passing the piping, drain hose, and the signal cable through the wall hole, you must bundle them together to save space, protect them, and insulate them..
1. Bundle the drain hose, refrigerant pipes, and signal cable as shown below:
Indoor Unit
Space behind unit Refrigerant piping Insulation tape Signal wire Drain hose

3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Facing the back of the unit, remove the plastic panel on the bottom left- hand side.
5. Feed the signal wire through this slot, from the back of the unit to the front.
6. Facing the front of the unit, connect the wire according to the indoor unit’s wiring diagram, connect the u-lug and firmly screw each wire to its corresponding terminal.
CAUTION
DO NOT MIX UP LIVE AND NULL WIRES This is dangerous, and can cause the air conditioning unit to malfunction.
7. After checking to make sure every connection is secure, use the cable clamp to fasten the signal cable to the unit. Screw the cable clamp down tightly.
8. Replace the wire cover on the front of the unit, and the plastic panel on the back.

DRAIN HOSE MUST BE ON BOTTOM
Make sure that the drain hose is at the bottom of the bundle. Putting the drain hose at the top of the bundle can cause the drain pan to overflow, which can lead to fire or water damage.
DO NOT INTERTWINE SIGNAL CABLE WITH OTHER WIRES
While bundling these items together, do not intertwine or cross the signal cable with any other wiring.
2. Using adhesive vinyl tape, attach the drain hose to the underside of the refrigerant pipes.
3. Using insulation tape, wrap the signal wire, refrigerant pipes, and drain hose tightly together. Double-check that all items are bundled.
DO NOT WRAP ENDS OF PIPING
When wrapping the bundle, keep the ends of the piping unwrapped. You need to access them to test for leaks at the end of the installation process (refer to Electrical Checks and Leak Checks section of this manual).

Rinnai

17

PB Series Split AC IM ­ Issue 2

INSDTOAOLRLAINTSIOTNALLATION

Step 8: Mount indoor unit
If you installed new connective piping to the outdoor unit,do the following:
1. If you have already passed the refrigerant piping through the hole in the wall, proceed to Step 4.
2. Otherwise, double-check that the ends of the refrigerant pipes are sealed to prevent dirt or foreign materials from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant pipes, drain hose, and signal wire through the hole in the wall.
4. Hook the top of the indoor unit on the upper hook of the mounting plate.
5. Check that unit is hooked firmly on mounting by applying slight pressure to the left and right-hand sides of the unit. The unit should not jiggle or shift.
6. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.
7. Again, check that the unit is firmly mounted by applying slight pressure to the left and the right-hand sides of the unit.
If refrigerant piping is already embedded in the wall, do the following:
1. Hook the top of the indoor unit on the upper hook of the mounting plate.
2. Use a bracket or wedge to prop up the unit, giving you enough room to connect the refrigerant piping, signal cable, and drain hose.

3. Connect drain hose and refrigerant piping (refer to Refrigerant Piping Connection section of this manual for instructions).
4. Keep pipe connection point exposed to perform the leak test (refer to Electrical Checks and Leak Checks section of this manual).
5. After the leak test, wrap the connection point with insulation tape.
6. Remove the bracket or wedge that is propping up the unit.
7. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.
UNIT IS ADJUSTABLE
Keep in mind that the hooks on the mounting plate are smaller than the holes on the back of the unit. If you find that you don’t have ample room to connect embedded pipes to the indoor unit, the unit can be adjusted left or right by about 30-50mm, depending on the model.

30-50mm

30-50mm

Move to left or right

Rinnai

18

PB Series Split AC IM ­ Issue 2

OUTDOOR INSTALLATION
Installation Instructions ­ Outdoor Unit

Install the unit by following local codes and
Inrestgaulllathtieounnsit, tbhyefroellmowaiyngbeyoduifrfLeorcsalilghtly RbeegtuwlaeteionnsdaifnfedreMnutnriecgipiaolnBsu. ilding Codes. They may be differ slightly between states.

60cm above

3>03oc0nm0lemftm on leNft Air inlet

650mm 65incmfroinntfront

(Wall or obstacle) Air inlet

fr1o0mcmback wall >100mm from back wall

600mm from above

M

Air outlet

MAINTENANCE ACCESS

600mm oonn60rPriicggmhhtt

DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets Near a public street, crowded areas, or where noise from the unit will disturb others
Near animals or plants that will be harmed by hot air discharge Near any source of combustible gas In a location that is exposed to large amounts of dust In a location exposed to a excessive amounts of salty air
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind:

Installation Instructions ­ Outdoor unit
Step 1: Select installation location Before installing the outdoor unit, you must

Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds. See Figures below.

choose an appropriate location. The following are

standards that will help you choose an appropriate

location for the unit. Strong

Proper installation locations meet the

wind

following standards:

Strong wind

Wind Baffle

Meets all spatial requirements shown in Installation Space Requirements above.

Strong wind

Good air circulation and ventilation
Firm and solid–the location can support the unit and will not vibrate
Noise from the unit will not disturb others
Protected from prolonged periods of direct sunlight or rain
Where snowfall is anticipated, raise the unit above the base pad to prevent ice buildup and coil damage. Mount the unit high enough to be above the average accumulated area snowfall. The minimum height must be 46 cm.

If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow around the unit.
If the unit is frequently exposed to salty air (seaside):
Use outdoor unit that is specially designed to resist corrosion.

Installation

Rinnai

19

PB Series Split AC IM ­ Issue 2

OUTDOOR INSTALLATION
Step 2: Install drain joint(Heat pump unit only)
Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. Note that there are two different types of drain joints depending on the type of outdoor unit.
If the drain joint comes with a rubber seal (see Fig. A ), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. B ), do the following:
1. Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
2. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

D B

Step 3: Anchor outdoor unit The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolt (M10). Prepare the installation base of the unit according to the dimensions below. UNIT MOUNTING DIMENSIONS The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions below.
A
Air inlet
Air inlet
Air outlet

Base pan hole of outdoor unit Seal
Seal

Drain joint

(A)

(B)

IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit.

H W

Rinnai

20

PB Series Split AC IM ­ Issue 2

OUTDOOR INSTALLATION

Outdoor Unit Dimensions (mm) W x H x D
805 x 554 x 330 890 x 673 x 342

Mounting Hole Pitch Dimensions

Pitch A (mm) 511

Pitch B (mm) 317

663

354

To install the unit on the ground or on a concrete mounting platform, do the following: 1. Mark the positions for four expansion bolts
based on dimensions chart on Page 21. 2. Pre-drill holes for expansion bolts. 3. Place a nut on the end of each expansion bolt. 4. Hammer expansion bolts into the pre-drilled
holes. 5. Remove the nuts from expansion bolts, and
place outdoor unit on bolts.
6. Put washer on each expansion bolt, then replace the nuts.
7. Using a wrench, tighten each nut until snug.
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIMES.

To install the unit on a wall-mounted bracket, do the following:
CAUTION
Make sure that the wall is made of solid brick, concrete, or of similarly strong material. The wall must be able to support at least four times the weight of the unit.
1.Mark the position of bracket holes based on dimensions chart.
2. Pre-drill the holes for the expansion bolts. 3. Place a washer and nut on the end of each
expansion bolt. 4. Thread expansion bolts through holes in
mounting brackets, put mounting brackets in position, and hammer expansion bolts into the wall. 5. Check that the mounting brackets are level. 6. Carefully lift unit and place its mounting feet on brackets. 7. Bolt the unit firmly to the brackets. 8. If allowed, install the unit with rubber gaskets to reduce vibrations and noise.

Rinnai

21

PB Series Split AC IM ­ Issue 2

OUTDOOR INSTALLATION

Step 4: Connect signal and power cables The outside unit’s terminal block is protected by an electrical wiring cover on the side of the unit. A comprehensive wiring diagram is printed on the inside of the wiring cover.
WARNING

7. Insulate unused wires with PVC electrical tape. Arrange them so that they do not touch any electrical or metal parts.
8. Replace the wire cover on the side of the unit, and screw it in place.
Cover

BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM. 1. Prepare the cable for connection:
USE THE RIGHT CABLE
Please choose the right cable refer to ” Cable types” on page 16.

Screw
NOTE: If the cable clamp looks like the following, please select the appropriate through-hole according to the diameter of the wire.

CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. NNOOTTEE: :CInhoNoosreththAemaeprpicrao,pprilaeatesecachboleosiezethe right accacbolerdsinizge tahcecoMrdininigmtuomthCeirMcuinitimCumrreCntircCuaitrrying CAamppacaictiytyininddicicaateteddoonntthheennaammeeppllaattee ooff tthhee uunniitt..
a. Using wire strippers, strip the rubber jacket from both ends of cable to reveal about 40mm of the wires inside.
b. Strip the insulation from the ends of the wires. c. Using a wire crimper, crimp u-lugs on the
ends of the wires.
PAY ATTENTION TO LIVE WIRE
While crimping wires, make sure you clearly distinguish the Live (“L”) Wire from other wires.
WARNING
ALL WIRING WORK MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM LOCATED INSIDE OF WIRE COVER OF THE OUTDOOR UNIT .
2. Unscrew the electrical wiring cover and remove it. 3. Unscrew the cable clamp below the terminal
block and place it to the side. 4. Connect the wire according to the wiring
diagram, and firmly screw the u-lug of each wire to its corresponding terminal. 5. After checking to make sure every connection is secure, loop the wires around to prevent rain water from flowing into the terminal. 6. Using the cable clamp, fasten the cable to the unit. Screw the cable clamp down tightly.

Buckle Three size hole: Small, Large, Medium

When the calbe is not fasten enough, use the buckle to prop it up , so it can be clamped tightly.
WInirNinogrtohf ATemrmerinicaal Block
1. Remove the wire cover from the unit by loosening the 3 screws.
2. Dismount caps on the conduit panel. 3. Temperarily mount the conduit tubes(not
included) on the conduit panel. 4. Properly connect both the power supply and
low voltage lines to the corresponding terminals on the terminal block. 5. Ground the unit in accordance with local codes. 6. Be sure to size each wire allowing several inches longer than the required length for wiring. 7. Use lock nuts to secure the conduit tubes.

Terminal block Over 40mm

Connecting cable
G
Power supply cord

Conduit panel

Wire Cover
Please select the appropriate through-hole according to the diameter of the wire.

Rinnai

22

PB Series Split AC IM ­ Issue 2

REFRIGERANT PIPING CONNECTION

When connecting refrigerant piping, do not let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high prefsescutrteheinptehrfeorrmefaringceeraantidonenceyrcgley.eTffihcisiecnacny ocaf tuhseeuenxipt.loNsoiomninaanl d eifnfijcuieryn.cy is tested on units with a pipe length of 5 metres.
ANNmoointtieemooumnnpPPipiipepereunLLeoefnn3ggmtthehtres is required to minimise vibration & excessive noise.
RTTehhfeeerlleetnonggtththheootfafbrreleefrfirbgigeeelrorawanntftoppripispipnineggcwifiwiclilallatiafoffenfcestcothntehtehpeeprmefroafroxmrimmanuacmnecelaennadngdet neenregrygeyfofiepfcfiiehcneiecignyhcoytfootfhfpethipueinnuigtn..Nit.oNmoinmailnal eefffificciieennccyy iisstteesstteeddoonnuunnititsswwitihthaappipipeelelennggththoof 5f 5mmeteretrse.s. AA mmiinniimmuumm ppiippee rruunn ooff33mmeettrreessisisrereqquuirireeddtotommininimimisiseevvibibraratitoionn&&execxecesssisviveennooisiese. .
RReeffeerrttootthheettaabblelebbeelolowwfofor rspspeecicfiificacatitoionnssoonnthtehemmaxaixmimumumlelnegntghthanadnddrdorpohpehigehigthotfopfippiinpgin. g.

Model

Maximum Length andDrop Height of Refrigerant Piping per Unit Model

Capacity (kW)

Length (m)

Mx Drop Height (m)

R32 Inverter Split Air Conditioner

<4.4 4.4 and <7

25 30

10 20

7 and<10.5

50

25

CCoonnnneeccttioionnInInstsrtuructcitoionns s- R­efRriegferirgaenrtaPnipt iPnigping

Step 1: Cut pipes

When preparing refrigerant pipes, take extra

90°

cCaroentonceuct tainodnflaIrnesthtreumcptrioopnersly.­ThRisewfirlligerant Piping

ensure efficient operation and minimise the

need for future maintenance.

Oblique Rough Warped

1. Measure the distance between the indoor anedtooucutdtoaonrduflnaits.
2. Usinegeaffipciipeentcouptteerra,tciount tahnedpmipineima ilistetlethleonger than the measured distance.
3. Make sure that the pipe is cut at a perfect 90° angle.

Warped
DO NOT DEFORM PIPE WHILE CUTTING
BTeakeextcraarecanroetftuol dnaomt atoged, admenatg, oer, dent, or ddeeffoorrmm the ppiippeewwhhileilecuctutitntign.gT.hTishmisawy ill dardavsetircsaellyyarfefedcutctehethheeahteinagtienfgficeiefnficcyieonfcy othfethueniut.nit.

Rinnai

23

PB Series Split AC IM ­ Issue 2

REFRIGERANT PIPING CONNECTION
Step 2: Remove burrs Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed. 1. Hold the pipe at a downward angle to prevent
burrs from falling into the pipe. 2. Using a reamer or deburring tool, remove all
burrs from the cut section of the pipe.
Pipe Reamer
Point down

PIPING EXTENSION BEYOND FLARE FORM

Outer Diameter of Pipe (mm)

A (mm)

Min.

Max .

Ø 6.35 Ø 9.52 Ø12.7 Ø 16 Ø 19

0.7

1.3

1.0

1.6

1.0

1.8

2.0

2.2

2.0

2.4

Flare form

A

Step 3: Flare pipe ends Proper flaring is essential to achieve an airtight seal. 1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign materials from entering the pipe. 2. Sheath the pipe with insulating material. 3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can’t put them on or change their direction after flaring.
Flare nut
Copper pipe

Pipe
6. Place flaring tool onto the form. 7. Turn the handle of the flaring tool clockwise
until the pipe is fully flared. 8. Remove the flaring tool and flare form, then
inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use excessive torque or to deform the piping in any way. You should first connect the low-pressure pipe, then the high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the minimum bending radius is 10cm.

4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the edge of the flare form in accordance with the dimensions shown in the table below.

Radius 10cm

Instructions for Connecting Piping to Indoor Unit
1. Align the center of the two pipes that you will connect.

Refrigerant piping

Rinnai

Indoor unit tubing

Flare nut Pipe

24

PB Series Split AC IM ­ Issue 2

REFRIGERANT PIPING CONNECTION

2. Tighten the flare nut as tightly as possible by hand.
3. Using a spanner, grip the nut on the unit tubing.
4. While firmly gripping the nut on the unit tubing, use a torque wrench to tighten the flare nut according to the torque values in the Torque Requirements table below. Loosen the flaring nut slightly, then tighten again.

Outer Diameter of Pipe (mm) Ø 6.35
Ø 9.52 Ø 12.7
Ø 16 Ø 19

TORQUE REQUIREMENTS

Tightening Torque (N·m) 18~20
32~39

Flare dimension(B) (mm)
8.4~8.7
13.2~13.5

49~59

16.2~16.5

57~71 67~101

19.2~19.7 23.2~23.7

Flare shape
90 °± 4 45 °±2
B
R0.4~0. 8

DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must not exceed torque requirements shown in the table above.

InInsstrturucctitoionnssffoorrCCoonnnneeccttiinng PipientgotOo uOtudtodooroUrnUitnit

1. Unscrew the cover from the packed valve on the side of the outdoor unit.
2. Remove protective caps from ends of valves.
3. Align flared pipe end with each valve, and tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the body of the valve. Do not grip the nut that seals the service valve.

6. Loosen the flaring nut slightly, then tighten again.
7. Repeat Steps 3 to 6 for the remaining pipe.
USE SPANNER TO GRIP MAIN BODY OF VALVE
Torque from tightening the flare nut can snap off other parts of valve.

Connection

Valve cover

5. While firmly gripping the body of the valve, use a torque wrench to tighten the flare nut according to the correct torque values.

Rinnai

25

PB Series Split AC IM ­ Issue 2

AIR EVACUATION
Preparations and Precautions

Air and foreign matter in the refrigerant circuit can 8. If there is a change in system pressure, refer

cause abnormal rises in pressure, which can damage

to Gas Leak Check section for information

the air conditioner, reduce its efficiency, and cause

injury. Use a vacuum pump andem, awnhificohldcgaanudgaemtoage

evacuate the refrigerant circuit, removing any

9. 9.

non-condensable gas and moisture from the system.

on how to check for leaks. If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve).
Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by

Evacuation installation

should be and when

puenriftoisrmreeldocuapteodno. imnittihael

system.

turning the wrench in a 1/4 counterclockwise turn. Listen for gas to exit the system, then

BEFORE PERFORMING EVACUATION
Check to make sure the connective pipes between the indoor and outdoor units
are connected properly . Check to make sure all wiring is connected
properly.
EEvvaaccuuaattioionnInInsstrtruucctitoionnss

close the valve after 5 seconds. 10. Watch the Pressure Gauge for one minute
to make sure that there is no change in pressure. The Pressure Gauge should read slightly higher than atmospheric pressure. 11. Remove the charge hose from the service port.
Flare nut

1. Connect the charge hose of the manifold gauge to service port on the outdoor unit’s low pressure valve.
2. Connect another charge hose from the manifold gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed. 4. Turn on the vacuum pump to evacuate the
system. 5. Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG (-10 5Pa).

Manifold Gauge

Compound Pressure gauge gauge Manifold Gauge

-76cmHg

Low pressure valve Pressure hose /
Charge hose

High pressure valve
Charge hose Vacuum pump

Cap
valve body valve stem
12. Using hexagonal wrench, fully open both the high pressure and low pressure valves.
13. Tighten valve caps on all three valves (service port, high pressure, low pressure) by hand. You may tighten it further using a torque wrench if needed.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the stopper. Do not try to force the valve to open further.

Low pressure valve
6. Close the Low Pressure side of the manifold gauge, and turn off the vacuum pump.
7. Wait for 5 minutes, then check that there has been no change in system pressure.

Rinnai

26

PB Series Split AC IM ­ Issue 2

AIR EVACUATION

Note on Adding Refrigerant

Some ssyysstteemmssrereqquuiriereaadddititoionnalaclhcahragrignigndgedpeepnednindginognopnippeipleenlgetnhgs.thThs.eTshtaensdtarnddpairpdepleipnegtlehnvgatrhiesvaries accorddinnggttoololoccaal lreregguulaltaitoionsn.sF.or example, in one are, the standard pipe length may be 7.5m.
In ootthheerraarreeaass, ,ththeestsatnadnadradrdpipeiplenlegnthgtihs 5ism5. mTh.eTrheefrirgeefriagnetrsahnotuslhdobueldchbaergcehdarfgroemd tfhroemsetrhvieceservice port poonrthoenotuhtedoouotrduonoirt’usnloitw’s lopwrespsruersesuvraelvvea.lvTeh.e aTdhdeiatidodniatilorneafrlirgeefriagnetratnotbtoe bcheacrhgaerdgecdancabnebcealculated cuaslicnuglattheedfuoslilnogwtihnegffoollromwuinlag: formula:

ADDITIONAL REFRIGERANT PER PIPE LENGTH

Connective Pipe Length (m)

Air Purging Method

< Standard pipe length Vacuum Pump

Additional Refrigerant
N/A

Standard pipe Vacuum Pump length

Liquid Side: Ø 6.35 R32:
(Pipe length ­ standard length) x 12g/m

Liquid Side: Ø 9.52 R32:
(Pipe length ­ standard length) x 24g/m

Rinnai

27

PB Series Split AC IM ­ Issue 2

ELECTRICAL AND GAS LEAK CHECKS

Before Test Run

Only perform test run after you have completed the following steps: · Electrical Safety Checks ­ Confirm that
the unit’s electrical system is safe and · operating properly · Gas Leak Checks ­ Check all flare nut
connections and confirm that the system is · not leaking · Confirm that gas and liquid (high and low
pressure) valves are fully open ·
EleeccttrriiccaallSSaafefettyyCChheeckcsks
After installation, confirm that all electrical wiring is installed in accordance with local and national regulations, and according to the Installation Manual.
BEFORE TEST RUN
Check Grounding Work
Measure grounding resistance by visual detection and with grounding resistance tester. Grounding resistance must be less than 0.1 .
DURING TEST RUN
Check for Electrical Leakage During the Test Run, use an electroprobe and multimeter to perform a comprehensive electrical leakage test.
If electrical leakage is detected, turn off the unit immediately and call a licensed electrician to find and resolve the cause of the leakage. immediately and call a licensed electrician to find

WARNING ­ RISK OF ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL CODES, AND MUST BE INSTALLED BY A LICENSED ELECTRICIAN.

Gas Leak Checks
There are two different methods to check for gas leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit. The presence of bubbles indicates a leak.
Leak Detector Method
If using leak detector, refer to the device’s operation manual for proper usage instructions.
AFTER PERFORMING GAS LEAK CHECKS After confirming that the all pipe connection points DO NOT leak, replace the valve cover on the outside unit.

Check-point of indoor unit

Check-point of outdoor unit

D

B

C

A

A: Low pressure stop valve B: High pressure stop valve C& D: Indoor unit flare nuts

Rinnai

28

PB Series Split AC IM ­ Issue 2

TEST RUN

Test Run Checks

Perform the Test Run for at least 30 minutes.

1. Connect power to the unit.
2. Press the ON/OFF button on the remote controller to turn it on.
3. Press the MODE button to scroll through the following functions, one at a time:
· COOL ­ Select lowest possible temperature · HEAT ­ Select highest possible temperature
4. Let each function run for 5 minutes, and perform the following checks:

List of Checks to Perform

PASS/FAIL

No electrical leakage

Unit is properly grounded

All electrical terminals properly covered

Indoor and outdoor units are solidly installed

All pipe connection points do not leak

Outdoor Indoor

(2):

(2):

Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function properly

Unit performs HEAT function properly

Indoor unit louvers rotate properly

Indoor unit responds to remote controller

During operation, the pressure of the refrigerant circuit will increase. This may reveal leaks that were not present during the initial leak check. Take time during the Test Run to double-check that all refrigerant pipe connection points do not have leaks. Refer to Gas Leak Check section for instructions. 5. After the Test Run is successfully completed,
and you confirm that all checks points in List of Checks to Perform have PASSED, do the following: a. Using remote control, return unit to
normal operating temperature. b. Using insulation tape, wrap the indoor
refrigerant pipe connections that was left uncovered during the indoor unit installation process.
IF AMBIENT TEMPERATURE IS BELOW 17°C
DO NOT use the remote controller to turn on the COOL function when the ambient temperature is below 17°C. In this instance, use the MANUAL CONTROL button to test the COOL function. 1. Lift the front panel of the indoor unit, and
raise it until it clicks in place. 2. The MANUAL CONTROL button is located
on the right-hand side of the unit. Press it 2 times to select the COOL function. 3. Perform Test Run as normal.
Manual control button

Rinnai

29

PB Series Split AC IM ­ Issue 2

CHECKLIST
FINAL CHECKLIST

The checklist is ONLY to be completed by an Authorised Person.
IMPORTANT

Check Item

What can happen if not checked

Is the indoor unit installed securely?

Falling, vibration, noise

Has an inspection been made to check for gas leakage? Has all thermal insulation been completed (vapour pipes, liquid pipes, indoor portions of the drain hose extension)? Is the drainage secure?
Are the electric wires installed correctly?
Is the wiring in accordance within the specifications? Are all inlets / outlets of the indoor and outdoor units free of any obstructions? Are the stop valves open?

No cooling or heating
Condensation
Water leakage No cooling or heating, may cause electrical shock or electrical fire. Operation failure, electrical fire No cooling or heating
No cooling or heating

Are the pipes designed for use with R32?

Pipe or pipe connection leakage

Has a leak test been carried out for the pipe connections?

Pipe connection leakage

Has air purging been carried out?

No cooling or heating

Has the appliance been tested for correct operation?

No cooling or heating

Is the end user fully aware of the operating procedure?

Incorrect operation

Ifyouhaveanswerednotoanyoftheabove,youmustcheckandcorrectbeforeappliancehand- overtocustomer.

Rinnai

30

PB Series Split AC IM ­ Issue 2

SPECIFICATIONS

RINNAI-PBSeriesHi-WallSplitSystem Nominal Capacity

HSNRP26B

kW

2.65

HSNRP35B 3.55

Power Supply to Outdoor Unit

V – Ph – Hz 220~240 – 1 – 50

Recommended Circuit Breaker

A

16

16

Connectivity

Wi-Fi Enabled

Demand Response Enabling Device

DRED Enabled

Cooling

Rated Capacity

kW

2.65

3.5

Capacity Range

1.00-3.50

1.50-4.90

Rated Power Input

W

530

790

Rated Current (Range)

A

2.5

3.8

AEER

W/W

4.98

4.42

TCSPF (Hot & Humid / Mixed / Cold)

8.02 / 7.497 / 7.887

7.00 / 6.76 / 7.07

Star Rating (Hot & Humid / Mixed / Cold)

6.5 / 5.5 / 6.0 STAR

5.0 / 5.0 / 5.5 STAR

Heating

Rated Capacity

kW

2.7

3.8

Capacity Range

1.40-4.00

1.80-5.10

Rated Power Input

W

510

830

Rated Current (Range)

A

2.5

5

ACOP

W/W

5.273

4.564

HSPF (Hot & Humid / Mixed / Cold)

5.79 /5.35 / 4.96

6.23 / 5.22 / 4.50

Star Rating (Hot & Humid / Mixed / Cold)

4.0 / 3.5 / 3.0 STAR

4.5 / 3.5 / 3 STAR

Maximum Input Power (Cooling / Heating)

W

2300

2300

Maximum Input Current (Cooling / Heating)

A

10.5

10.5

Suitable Area Coverage (up to 2.6m insulated ceiling) Indoor Unit Model No.

11-17

HINRP26MB

16-23 HINRP35MB

Air Flow (Turbo / Hi / Med / Lo / Min)

L/s

175 / 139 / 100 / 83 / 56

183 / 147 / 106 / 86 / 58

Moisture Removal

L/h

1.00

1.20

Air Flow (Turbo / Hi / Med / Lo / Min)

m3/h

630 / 500 / 360 / 300 / 200

660 / 530 / 380 / 310 / 210

Sound Pressure Level @ 1m (Turbo / Hi / Med / Lo / Min)

dB(A)

46.4 / 39 / 32.5 / 30 / 24.5

46.7 / 39 / 32.5 / 30 / 24.5

Air Swing Louvres Type

4-way swing

Dimensions

Dimension (W x H x D)

mm

802 x 200 x 295

802 x 200 x 295

Packing (W x H x D)

965 × 370 × 282

1010 x 385 x 307

Net / Gross Weight

kg

8.5 / 11.1

8.5 / 11.1

Operating Range

Cooling

°C

16 ~ 32

16 ~ 32

Heating

0 ~ 30

0 ~ 30

Outdoor Unit Model No.

HONRP26B

HONRP35B

Sound Power Level Sound Pressure Level @ 1m

dB(A)

57.8

58.5

55.5

55.5

Dimensions

Dimension (W x H x D) Packing (W x H x D)

mm

805 x 330 x 554

915 x 370 x 615

805 x 330 x 554 915 x 370 x 615

Refrigerant

Net / Gross Weight Charged Volume

kg

32.2 / 34.9

kg

0.9

32.2 / 34.9 0.9

Pipe Size: Liquid / Gas

mm

6.35mm / 9.52mm

6.35mm / 9.52mm

Maximum Pipe Length

m

25

25

Chargeless Length

10

10

Extra Charge for Lengths >10m

g/m

12

12

Maximum Vertical Separation

m

10

10

Ambient Temperature Limits

Cooling Heating

°C

0 ~ 52

-15~24

0 ~ 52 -15~24

Capacities tested in accordance with AS/NZS 3823.2, with 5m interconnecting pipe length. With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.

Rinnai

31

PB Series Split AC IM ­ Issue 2

SPECIFICATIONS

RINNAI-PBSeriesHi-WallSplitSystem Nominal Capacity

HSNRP50B

kW

5

HSNRP60B 6

Power Supply to Outdoor Unit

V – Ph – Hz

Recommended Circuit Breaker

A

20

20

Connectivity

Wi-Fi Enabled

Demand Response Enabling Device

DRED Enabled

Cooling

Rated Capacity

kW

5.0

6.0

Capacity Range

2.10-7.20

2.10-7.20

Rated Power Input

W

1280

1750

Rated Current (Range)

A

5.8

8.0

AEER

W/W

3.90

3.42

TCSPF (Hot & Humid / Mixed / Cold)

6.19 / 5.83 / 6.17

5.86 / 5.61 / 5.99

Star Rating (Hot & Humid / Mixed / Cold)

4.5 / 4.0 / 4.5 STAR

4.0 / 4.0 / 4.0 STAR

Heating

Rated Capacity

kW

5.4

6.5

Capacity Range

2.50-7.80

2.50-7.80

Rated Power Input

W

1340

1686

Rated Current (Range)

A

6

8.2

ACOP

W/W

4.019

3.847

HSPF (Hot & Humid / Mixed / Cold)

4.89 / 4.31 / 3.71

5.31 / 4.29 / 3.52

Star Rating (Hot & Humid / Mixed / Cold)

3.0 / 2.5 / 2.0 STAR

3.5/ 2.5 / 1.5 STAR

Maximum Input Power (Cooling / Heating)

W

3600

3600

Maximum Input Current (Cooling / Heating)

A

15.5

15.5

Suitable Area Coverage (up to 2.6m insulated ceiling) Indoor Unit Model No.

23-33

HINRP50MB

27-40 HINRP60MB

Air Flow (Turbo / Hi / Med / Lo / Min)

L/s

264 / 222 / 167 / 139 / 89

264 / 222 / 167 / 139 / 89

Moisture Removal

L/h

1.80

2.10

Air Flow (Turbo / Hi / Med / Lo / Min)

m3/h

950 / 800 / 600 / 500 / 322

950 / 800 / 600 / 500 / 322

Sound Pressure Level @ 1m (Turbo / Hi / Med / Lo / Min)

dB(A)

47.1 / 44.5 / 38 / 34.5 / 28

47.1 / 44.5 / 38 / 34.5 / 28

Air Swing Louvres Type

4-way swing

Dimensions

Dimension (W x H x D)

mm

971 x 228 x 321

971 x 228 x 321

Packing (W x H x D)

1067 x 385 x 312

1205 x 400 x 317

Net / Gross Weight

kg

11.1 / 14.4

11.1 / 14.4

Operating Range

Cooling

°C

Heating

Outdoor Unit Model No.

HONRP50B

HONRP60B

Sound Power Level

dB(A)

65.2

65.2

Sound Pressure Level @ 1m

59.5

59.5

Dimensions

Dimension (W x H x D)

mm

890 x 342 x 673

890 x 342 x 673

Packing (W x H x D)

995 x 398 x 740

995 x 398 x 740

Net / Gross Weight

kg

38.3 / 41.4

38.3 / 41.4

Refrigerant

Charged Volume

kg

1.26

1.26

Pipe Size: Liquid / Gas

mm

6.35mm / 12.7mm

6.35mm / 12.7mm

Maximum Pipe Length

m

30

30

Chargeless Length

10

10

Extra Charge for Lengths >10m

g/m

12

12

Maximum Vertical Separation

m

20

20

Ambient Temperature Limits

Cooling Heating

°C

0 ~ 50

-15 ~ 24

0 ~ 50 -15 ~ 24

Capacities tested in accordance with AS/NZS 3823.2, with 5m interconnecting pipe length. With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.

Rinnai

32

PB Series Split AC IM ­ Issue 2

SPECIFICATIONS

RINNAI-PBSeriesHi-WallSplitSystem Nominal Capacity

HSNRP70B

kW

7

HSNRP80B 8

Power Supply to Outdoor Unit

V – Ph – Hz

Recommended Circuit Breaker

A

25

25

Connectivity

Wi-Fi Enabled

Demand Response Enabling Device

DRED Enabled

Cooling

Rated Capacity

kW

7.15

7.8

Capacity Range

3.20-8.0

3.20-8.0

Rated Power Input

W

1920

2200

Rated Current (Range)

A

10.5

10.5

AEER

W/W

3.53

3.39

TCSPF (Hot & Humid / Mixed / Cold)

5.36 / 5.14 / 5.37

5.38 / 5.21 / 5.48

Star Rating (Hot & Humid / Mixed / Cold)

3.5 /3.5 / 3.5

3.5 / 3.5 / 3.5

Heating

Rated Capacity

kW

7.8

8.3

Capacity Range

2.20-8.8

2.20-8.8

Rated Power Input

W

1990

2280

Rated Current (Range)

A

10.8

10.8

ACOP

W/W

3.734

3.611

HSPF (Hot & Humid / Mixed / Cold)

Star Rating (Hot & Humid / Mixed / Cold)

4.97 / 4.32 / 3.82 3.0 / 2.5 / 2.0

4.96 / 4.20 / 3.66 3.0 / 2.5 / 2.0

Maximum Input Power (Cooling / Heating)

W

4050

4050

Maximum Input Current (Cooling / Heating)

A

17.5

17.5

Suitable Area Coverage (up to 2.6m insulated ceiling)

32-47

32-47

Indoor Unit Model No.

HINRP70MB

HINRP80B

Air Flow (Turbo / Hi / Med / Lo / Min)

L/s

382 / 303 / 250 / 229 / 147

382 / 303 / 250 / 229 / 147

Moisture Removal Air Flow (Turbo / Hi / Med / Lo / Min)

L/h

2.40

3.00

m3/h

1375 / 1090 / 900 / 825 / 530 1375 / 1090 / 900 / 825 / 530

Sound Pressure Level @ 1m (Turbo / Hi / Med / Lo / Min)

dB(A)

57.645 / 45 / 39 / 33.5 / 29.5 57.645 / 45 / 39 / 33.5 / 29.5

Air Swing Louvres Type

4-way swing

Dimensions

Dimension (W x H x D)

mm

1082 x 234 x 337

1082 x 234 x 337

Packing (W x H x D) Net / Gross Weight

1155 x 415 x 315

kg

13.5 / 17.1

1155 x 415 x 315 13.5 / 17.1

Operating Range

Cooling

°C

Heating

Outdoor Unit Model No.

HONRP70B

HONRP80B

Sound Power Level

dB(A)

65

66.5

Sound Pressure Level @ 1m

61

61

Dimensions

Dimension (W x H x D) Packing (W x H x D)

mm

890 x 342 x 673

995 x 398 x 740

890 x 342 x 673 995 x 398 x 740

Refrigerant

Net / Gross Weight Charged Volume

kg

42.4 / 46.7

kg

1.4

42.4 / 46.7 1.4

Pipe Size: Liquid / Gas

mm

6.35mm / 15.9mm

6.35mm / 15.9mm

Maximum Pipe Length

m

50

50

Chargeless Length

10

10

Extra Charge for Lengths >10m

g/m

12

12

Maximum Vertical Separation

m

25

25

Ambient Temperature Limits

Cooling Heating

°C

-15 ~ 50

-15 ~ 24

-15 ~ 50 -15 ~ 4

Capacities tested in accordance with AS/NZS 3823.2, with 5m interconnecting pipe length. With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.

Rinnai

33

PB Series Split AC IM ­ Issue 2

NOTES

Rinnai

34

PB Series Split AC IM ­ Issue 2

NOTES

Rinnai

35

PB Series Split AC IM ­ Issue 2

CONTACTS

innai Australia Pty Ltd

ABN 74 005 138 769 | AU45204

100 Atlantic Drive, Keysborough, Victoria 3173 P.O. Box 460, Braeside, Victoria 3195 Tel: (03) 9271 6625 Fax: (03) 9271 6622

National Help Line Tel: 1300 555 545* Fax: 1300 555 655 Monday to Friday, 8.00 am to 5.00 pm EST.

*Cost of a local call may be higher from a mobile phone. (National calls from public phones in Australia are free.)

For further information visit www.rinnai.com.au or email enquiry@rinnai.com.au

innai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your innai appliance. If your appliance requires service, please call our National Help Line. Rinnai recommends that this appliance be serviced once a year.

With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.

Rinnai

36

PB Series Split AC ­ IM ­ Issue 2 ­ March 2024

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals