legrand LERAK136-FRENIT EV Charging Station Mounting Kit Instruction Manual
- June 2, 2024
- Legrand
Table of Contents
Green’up One
0 570 18
Installation Manual
Introduction
- The mounting kit is designed for the EV charging stations 0 570 10, . … .., 0 570 17.
- The pedestal is double-sided, so you can install one or two charging stations to it.
Safety instructions
Electrically skilled person
- The installation must only be done by a qualified professional.
- Read this Installation Manual carefully before you start the installation work.
- Obey the instructions in this Installation Manual, and make sure that the installation complies with national safety regulations, installation methods and restrictions.
- The information provided in this Installation Manual in no way exempts the installer or user from responsibility to obey all applicable safety regulations.
- This Installation Manual is a part of the product and must be stored in a safe location so that it is available for future installation and service.
WARNING
Danger of electric shock! Risk of fire!
- Improper installation can cause personal injury and property damage.
- Do not switch on the power supply before the installation work is completed.
Description of symbols
**| WARNING – Indicates a hazard with a medium level of risk which, if
not avoided, could result in death or serious injury or considerable damage to
the equipment.
---|---
**| Electrically skilled person
****| Environmental instructions
Delivery content
- Pedestal
- Mounting accessories
- Installation Manual
4.1. Pedestal
- The pedestal is applicable for mounting on ground or floor.
- Inside the pedestal is a metal conduit Ø 60mm for electrical cable routing and a compartment for possible electrical connections.
Attach the bottom plate to the pedestal:
- Remove the pre-installed fastening screws 4 pcs from the pedestal.
- Attach the bottom plate to the pedestal with the screws you removed.
4.2. Mounting accessories
Item | Description and use | Quantity |
---|---|---|
Screw M5x20 | ||
•Attach the charging station to the pedestal | 2 | |
Screw M5x10 | ||
•Fasten the pedestal to a pole (e.g. car heating pole) | 4 | |
Branching connector max. 4 connections | ||
•Branch LI, L2., L3 and N | 4 | |
Branching connector max. 6 connections | ||
•Branch PE | 1 | |
Cover plug for M32 opening | ||
•Close the cable entry at the bottom of the charging station | I | |
Membrane entry grommet for 16mm hole | ||
•For ethernet cable when installing two charging sta- Lions | 1 | |
Grommet M16 for cable 0 5-9mm | ||
•For ethernet cable | 2 |
| Grommet M32 for cable 0 15-20mm
•For supply cable| 2
| Cover cap for MS screw head
•Cover fastening screws inside the charging station| 4
Mounting instructions
5.1. Before installation
Remove the pedestal from its package. Do not scratch the surface of the item
after removal from the package.
When selecting installation site, take into account the following:
- You need accessories applicable for the mounting site and method.
- The charging station is applicable for indoor and outdoor use.
- To make sure the optimal charging performance, the charging station should not be exposed to direct sunlight.
- The minimum space necessary for operating and maintenance.
Obey always
national regulations and site requirements
5.2. Cable entries
Open cable entries on the rear of the charging station to route electrical
cables to the charging station.
Disassemble the charger Prepare the charger for mounting
5.3. Disassemble the pedestal
Installation steps
Keep the removed parts.
All the removed parts are necessary when you assemble the pedestal. 5.4.
Attach the charging station to the pedestal
Installation steps
Installation instructions
- A separate connection cable is necessary for the installation. Make sure that the connection cable complies with the system dimensioning.
- Use the included connectors for installation.
- Alternatively you can route the supply cable directly to the charging station.
- If the charging station will be connected to the internet, first connect the Ethernet cable to the RJ45 connector and then the supply conductors to the power terminals.
6.1. Connection cable
* The length is
for the longest conductor. Cut the other conductors to applicable lengths.
Leave the ground conductor long enough so that if a fault occurs it is the
last one that comes loose.
For more detailed wiring instructions please see the charging station’s
Installation Manual.
6.2. Wiring example
The installation of two 1-phase charging stations to the pedestal
Tightening torque: 10 Nm The
installation of two 3-phase charging stations to the pedestal**
Tightening torque: 10 Nm
Mounting on concrete casting
Items needed:
Pedestal…………………..1 pcs
Anchor bolts M12 (not included) ………………4 pcs
Washers (not included)
Nuts (not included)
Make sure that the materials used for the concrete casting and the
installation procedures obey local building regulations and safety standards.
- Dig a trench for cable conduits and an excavation pit for the concrete foundation. The pit floor should be compacted and level.
- Put cable and possible drain pipes in place.
- Fill the pit with concrete.
- Let the concrete cure. Make sure that the surface stays level during the process.
Installation steps
- Make sure that the concrete surface is compacted and level.
- Drill a hole in the concrete for the anchor bolts. For more in- formation, please see the anchor bolt instructions.
- Put the anchor bolts in place.
- Pull the electrical cables approx. 1600 mm measured from the concrete surface.
- Attach the pedestal on the anchor bolts with washers and nuts.
- Pull the electrical cables through the metal conduit in the pole.
- Attach the charging station to the pedestal. See instruc- tions on page 27.
Dimension drawings
Technical information
Electrical connections | Mounting Kit |
---|---|
Nominal supply voltage | 1-ph, 230 VAC / 3-ph, 400VAC |
Nominal frequency | AC 50 Hz |
Supply connection to included connectors | Cu 2,5 mm² – 16 mm² Tightening |
torque: 10Nm
Connection cable| Cu 2,5 mm² – 6 mm² Ø 10 – 20 mm Stranded or solid conductors
Supply connection to charging station| See the charging station’s technical
specifications
Design and Mechanics| Pedestal
---|---
Material| Aluminium
Color| Silver
Mounting| Ground / Floor
Weight| approx. 8,8 kg
Ingress protection rating| IP23
Impact resistance rating| IK10
Tested according to IEC 61439-07 medium resistance
Disposal
**** Do not dispose of electrical and electronic devices including their accessories with the household waste.
- When the charging station is at the end of its life cycle, it must be disposed of properly according to local recycling guidelines.
- The cardboard packing of the charging station can be recycled.
- Dispose of the plastic wrap with the household waste or according to local recycling guidelines.
Installation / Commissioning checklist
Introduction
Examine the mechanical and electrical installation in accordance with this
checklist to make sure that the charging station is properly installed.
Checking the Installation
Examine the visual, mechanical and electrical installation when the
charging station is un-powered.
CATEGORY | X | ITEM |
---|---|---|
Overall look | You have received the ordered material. | |
You do not see any scratches or damages. | ||
Mechanical installation | The charging station is fixed properly on the |
installation site.
Electrical installation| | Charging station’s power supply capacity meets the
electrical planning (cable size, protective devices…).
Review the local electrical design plan.
| The PE-cable screw is tight.
| The power supply conductors (L1, L2, L3, N and PE) are properly connected.
| The insulation of the power supply cable and the conductors (L1,1_2, L3, N
and PE) is intact.
| TN /TT network:
•The voltage between PE and N is less than 10 V.
IT network:
•The voltage between LI and N is 230 V.
•The voltage between Ll and PE is 130 V.
| The PE conductor resistance is less than 3 O.
| Test the functionality of the protective device.
Legrand reserves at any time the right to modify the contents of this booklet and to communicate, in any form and modality, the changes brought to the same.
LEGRAND
Pro and Consumer Service
BP 30076 – 87002
LIMOGES CEDEX FRANCE
www.legrand.com
Documents / Resources
|
legrand LERAK136-FRENIT EV Charging Station Mounting
Kit
[pdf] Instruction Manual
LERAK136-FRENIT-20230502, LERAK136-FRENIT EV Charging Station Mounting Kit,
LERAK136-FRENIT, EV Charging Station Mounting Kit, Charging Station Mounting
Kit, Station Mounting Kit, Mounting Kit, Kit
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>