ELK PRODUCTS ELK-P1224 Power Supply Battery Charger Kit Installation Guide
- June 2, 2024
- ELK PRODUCTS
Table of Contents
Installation and Setup Guide
ELK-P1224
ELK-P1224
Power Supply /
Battery Charger Kit
APPLICATION
The ELK-P1224 Power Supply/Battery Charger Kit is a plug-in14VDC Power Supply (ELK-P1426) combined with an intelligent Charger Board (ELK-P1224CB). It can supply up to 2.4 Amps of current at 12VDC (nominal). The charger board features a Low Battery Supervision output, Low Battery Cutoff, as well as a Manual On/ Off switch. The Power Supply features built-in overload reset and screw terminals for connections.
FEATURES
- Auto-Resetting Overload Protection
- Built-In Battery Charging Circuit
- Low Battery Trouble Output
- Low Battery Deep Discharge Cutoff Protection
- Master Power Switch
- Lifetime Limited Warranty
SPECIFICATIONS
ELK-P1426
Plug-in power supply with receptacle mounting bracket
- Input Voltage Range: 100 – 240 Volts AC, 50/60Hz
- Input Current: 0.8 Amps AC
- Output Voltage Range: 13.8 to 14 Volts DC.
- Continuous Output Current: 2.6 Amps DC
- Complies with UL 60950
- Compliant with Energy Star EISA Level V
- RoHS compliant (RoHS2-2011/65/EU)
- Size w/ mounting bracket: 3.07″ x 2.83″ x 1.5″ (78 x 72 x 38 mm)
- AC input plug style: NEMA 1-15P (non-polarized)
- Positive and Negative screw terminals on DC output
ELK-P1224CB
- Power Supply Input: 14 Volts DC provided by ELK-P1426
- Continuous Output Current: 2.4 Amps. **
- Low Battery Trouble: 11 Volts. (nominal)
- Low Battery Cutoff: 9 Volts. (nominal)
- PC Board Size: 2.25″ X 2.5″ (57.15mm X 63.5mm )
- Standby Battery Charging Capacity: 1 to 12 Ah, Sealed Lead Acid
- Battery Wire Length: 16″ with F1-Faston No. 187 Receptacles
- Master Power Switch turns On/Off the DC Input and Battery
- Operating Temp: 32° to +120° degrees F
- Humidity: 95% RH (max.), non-condensing
** Higher output current (up to 2.5 Amps) may be drawn for a short time provided a fully charged battery is connected.
Features or Specifications subject to change without notice.
AVAILABLE PART NUMBERS/CONTENTS
ELK-P1224 Power Supply/Charger Kit (pictured above)
ELK-P1426 Plug-in Power Supply
ELK-P1224CB Circuit Board
ELK-P1426 Plug-in Power Supply ONLY, 14VDC @ 2.6A
OPERATION
Master Power Switch
This switch allows users to turn On or Off all power from the DC Output
terminals for servicing.
Battery Supervision
If DC power from the ELK-P1426 is lost (i.e. AC power outage), the battery
should continue to supply power to the ELK-P1224CB DC Output terminals. The
battery’s voltage is then monitored and if the voltage drops to 11 volts, then
the –SUP low battery supervision output will turn ON (pull to ground)
indicating a Low Battery condition.
The -SUP output can be connected to an LED, 12 Volts DC Sounder, or a zone on
a Security Control to report a low battery condition.
Note: The –SUP output will only work until Low Battery Cutoff activates,
(see below) at which time -SUP becomes inactive since all power to the P1224CB
board will be completely shutoff.
Low Battery Cutoff
If DC power from the ELK-P1426 continues to be lost for an extended period,
the battery should continue to supply power to the ELK-P1224CB DC Output
terminals. The battery’s voltage is monitored during this time and if the
voltage drops to 9 volts, then the battery will be Cutoff (disconnected) from
the DC Output terminals. This helps to prevent “deep discharging” of the
battery.
Hookup
-
Observe correct polarity on all connections.
-
The ELK-P1224CB circuit board can be mounted directly on top of a battery. Connect the two battery wires to the battery terminals. Red wire to positive, Black wire to negative.
-
Connect ONLY the ELK-P1426 Power Pack to the DC Input terminals. DO NOT CONNECT an AC TRANSFORMER.
Two-conductor jacketed cable having Red and Black color coded wires are recommended, minimum 18 AWG. Maintain polarity if using non-color coded Zip cord. The consequences of using too small of a wire gauge, or extending the wire length beyond the recommended lengths may harm the ability to properly charge the battery, especially at full DC Output Load.
If using 18AWG – Do NOT exceed a distance of 10 feet.
If using 16AWG – Do NOT exceed a distance of 15 feet.
If using 14AWG – Do NOT exceed a distance of 25 feet. -
Plug the ELK-P1426 into a constant 120VAC source.
-
Connect the DC Output to the desired load.
-
Turn on Master Power Switch.
Printed in USA L707 2/6/2023
800-797-9355
www.elkproducts.com
email: info@elkproducts.com
PO Box 100 • Hildebran, NC 28637 • USA
For the latest downloadable version of this manual, visit our website:
http://www.elkproducts.com
ELK-P1224 Installation Manual
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>