HILTI HUS3 6 Concrete Screw Anchor Instruction Manual

May 15, 2024
HILTI

HILTI HUS3 6 Concrete Screw Anchor

HILTI-HUS3-6-Concrete-Screw-Anchor-product

Specifications

  • Product Name: Hilti Composite Metal Deck Floor Seismic Fixing Solution
  • Anchor Systems: Hilti HUS3, HUS4, and HST3
  • Manufacturer: Hilti New Zealand Ltd
  • Contact Information: Level 1, Building B, 600 Great South Rd, Ellerslie, Auckland 1051

Product Usage Instructions

HUS4 Screw Anchor

Setting Information

  • Nominal bit diameter: 8mm or 10mm
  • Effective min. embedment: 46.4mm – 85mm
  • Nominal embedment: 54.9mm – 95mm
  • Min. hole depth: 70mm – 85mm
  • Setting tool: Hilti SIW T-A

Loads

  • Minimum concrete thickness over upper flute: 70mm
  • Minimum distance to edge of lower flute: 45mm – 47mm
  • Characteristic pullout resistance:
    • In non-cracked concrete: 15.9kN – 19.9kN
    • In cracked concrete: 11.1kN – 14.0kN
    • Seismic C1: 11.1kN – 14.0kN
  • Partial safety factor for pullout resistance: 1.5
  • Robustness factor for pullout resistance: 1.00
  • Characteristic steel resistance for shear: 17.3kN – 20.6kN
  • Steel resistance for shear, seismic C1: 14.7kN – 17.2kN
  • Partial safety factor for steel resistance for shear: 1.5

HUS3 Screw Anchor

Setting Information

  • Nominal bit diameter: 6mm
  • Effective min. embedment: 30mm – 43mm
  • Nominal embedment: 40mm
  • Min. hole depth: 43mm
  • Setting tool: SIW 22A

Loads

  • Minimum concrete thickness over upper flute: 70mm
  • Minimum distance to edge of lower flute: 45mm
  • Characteristic pullout resistance:
    • In non-cracked concrete: 7.1kN
    • In cracked concrete: 2.5kN
    • Seismic C1: NRd,p,deck,C1 kN
    • Partial safety factor for pullout resistance: gc = 1.5
    • Robustness factor for pullout resistance: ginst = 1.2
    • Characteristic steel resistance for shear: VRk,s,deck = 10.8kN
    • Steel resistance for shear, seismic C1: VRd,s,deck,C1 = 2.9kN
    • Partial safety factor for steel resistance for shear: gMs,V = 1.5

Frequently Asked Questions (FAQ)

  • Q: What is the maximum load capacity of the HUS4 Screw Anchor?
    A: The HUS4 Screw Anchor has a maximum load capacity of up to 20.6kN for steel resistance for shear.

  • Q: Can the HUS3 Screw Anchor be used in seismic applications?
    A: Yes, the HUS3 Screw Anchor is designed for seismic applications with appropriate safety factors.

  • Q: How do I determine the correct setting depth for the anchors?
    A: Refer to the setting information provided in the user manual based on the concrete thickness and other factors for proper installation.

HILTI COMPOSITE METAL DECK FLOOR SEISMIC FIXING SOLUTION
Hilti HUS3, HUS4 and HST3 ultimate performance mechanical anchor system

HUS4 Screw Anchor

Ultimate-performance screw anchor for seismic actions into ComFlor® 60, 80 and SR

**Setting Information| ****Sym.| ****Units| Nominal anchor diameter (mm)
---|---|---|---
8| 10
Nominal bit diameter| do| mm| 8| 10
Effective min. embedment| hef| mm| 46.4| 54.9| 58.6| 67.1
Nominal embedment| hnom| mm| 60| 70| 75| 85
Min. hole depth| ho| mm| 70| 80| 85| 95
Setting tool[1]| –| –| Hilti SIW T-A
Loads according to Figure 1 and 2
Minimum concrete thickness over upper flute| **
hmin,deck| mm| 70
Minimum distance to edge of lower flute| cmin,deck| mm| 45| 45| 47| 47
Characteristic pullout resistance in non- cracked concrete| NRk,p,deck,uncr| kN| 15.9| 17.5| 19.2| 19.9
Characteristic pullout resistance in cracked concrete| NRk,p,deck,cr| kN| 11.1| 12.3| 13.5| 14.0
Characteristic pullout resistance, seismic C1| ****

NRk,p,deck,C1

| ****

kN

| ****

11.1

| ****

12.3

| ****

13.5

| ****

14.0

Partial safety factor for pullout resistance| gc| –| 1.5
Robustness factor for pullout resistance| ginst| –| 1.00
Characteristic steel resistance for shear| VRk,s,deck| kN| 17.3| 17.3| 20.6| 20.6
Characteristic steel resistance for shear, seismic C1|
VRk,s,deck,C1| kN| 14.7| 14.7| 17.2| 17.2
Partial safety factor for steel resistance for shear|
gMs,V| –| 1.5
[1] – Installation with other impact screw driver of equivalent power is possible. See ETA-20/0987 for full setting details.
Table 1 – Hilti HUS4-H, -HF, -C, -A, -AF anchors tension and shear design data for installation in the soffit of f’c = 30 MPa, normal weight concrete-filled profile deck assemblies for hammer drilled installations

All data in Table 1 applies to

  • Correct installation. See anchor box or Hilti.co.nz for details including hole cleaning and installation torque
  • No edge distance and spacing influence. Only one anchor can be used in the lower flute at a time with the min. spacing between anchors along the length of the flute to be at least 3 x hef. This datasheet does not give information for the design of fasteners in a group.
  • f’c = 30 MPa concrete. For higher compressive strengths, the tension loads may be increased by (f’c /30)0.5
  • αgap = 1.0 (no hole clearance between anchor and fixture) was used to in the formula VRd,s,deck,C1 = αgap x αeq x VRk,s,deck,C1 / gMs,V In case of connections with hole clearance according to EN 1992-4 Table 6.1, αgap = 0.5 should be used.
  • Testing in accordance with ACI 355.2 and AC 193. Evaluated in accordance with AC 193 and EAD 330232 and EOTA TR 049

For anchoring into the upper flute, either use Table 1 data below conservatively or refer to ETA-20/0867. Additionally, C2 seismic performance category is not included in ACI 355.2 and AC 193. C2 seismic performance category may be designed in the upper flute using all guidelines and parameters provided in ETA-20/0867.
ComFlor® is a registered trademark used in Australia and New Zealand under licence from Tata Steel UK Limited. © Copyright
2017 ComFlor® New Zealand. S&T Stainless Ltd.

HUS3 Screw Anchor

Ultimate-performance screw anchor for seismic actions into ComFlor® 60 and 80

**Setting Information| ****Sym.| ****Units| ****Nominal anchor diameter (mm)
---|---|---|---
6
Nominal bit diameter| do| mm| 6
Effective min. embedment| hef| mm| 30
Nominal embedment| hnom| mm| 40
Min. hole depth| ho| mm| 43
Setting tool[1]| –| –| SIW 22A
Loads according to Figure 1
Minimum concrete thickness over upper flute| hmin,deck| mm| 70
Minimum distance to edge of lower flute| cmin,deck| mm| 45
Characteristic pullout resistance in non-cracked concrete| NRk,p,deck,uncr| kN| 7.1
Characteristic pullout resistance in cracked concrete| NRk,p,deck,cr| kN| 2.5
Characteristic pullout resistance, seismic C1| NRk,p,deck,C1| kN| 2.5
Design pullout resistance, seismic C1| NRd,p,deck,C1| kN| 1.4
Partial safety factor for pullout resistance| gc| –| 1.5
Robustness factor for pullout resistance| ginst| –| 1.2
Characteristic steel resistance for shear HUS3-H, -P, -PS, -C| **
VRk,s,deck| kN| 10.8
Characteristic steel resistance for shear, seismic C1, HUS3-H, -P, -PS, -C| VRk,s,deck,C1| kN| 4.3
Design steel resistance for shear, seismic C1, HUS3-H, -P, -PS, -C| VRd,s,deck,C1| kN| 2.9
Partial safety factor for steel resistance for shear| gMs,V| –| 1.5
[1] – Installation with other impact screw driver of equivalent power is possible. See ETA-13/1038 for full setting details.
Table 2 – Hilti HUS3 anchors tension and shear design data for installation in the soffit of f’c = 30 MPa, normal weight concrete-filled profile deck assemblies for hammer drilled installations

All data in Table 2 applies to:

  • Correct installation. See anchor box or Hilti.co.nz for details including hole cleaning and installation torque
  • No edge distance and spacing influence. Only one anchor can be used in the lower flute at a time with the min. spacing between anchors along the length of the flute to be at least 3 x hef. This datasheet does not give information for the design of fasteners in a group.
  • f’c = 30 MPa concrete. For higher compressive strengths, the tension loads may be increased by (f’c /30)0.5
  • αgap = 1.0 (no hole clearance between anchor and fixture) was used to in the formula VRd,s,deck,C1 = αgap x αeq x VRk,s,deck,C1 / gMs,V In case of connections with hole clearance according to EN 1992-4 Table 6.1, αgap = 0.5 should be used.
  • Testing in accordance with ACI 355.2 and AC 193. Evaluated in accordance with AC 193 and EAD 330232 and EOTA TR 049

For anchoring into the upper flute, either use Table 1 data below conservatively or refer to ETA-13/1038. Additionally, C2 seismic performance category is not included in ACI 355.2 and AC 193. C2 seismic performance category may be designed in the upper flute using all guidelines and parameters provided in ETA-13/1038.
ComFlor® is a registered trademark used in Australia and New Zealand under licence from Tata Steel UK Limited. © Copyright 2017 ComFlor® New Zealand. S&T Stainless Ltd.

HST3 Expansion Anchor
Ultimate-performance expansion anchor for seismic actions into ComFlor® 60 and 80

**Setting Information| ****Sym.| ****Units| Nominal anchor diameter (mm)
---|---|---|---
8| 10| 12| 16
Nominal bit diameter| do| mm| 8| 10| 12| 16
Effective min. embedment| hef| mm| 47| 60| 70| 85
Nominal embedment| hnom| mm| 54| 68| 80| 98
Min. hole depth| ho| mm| 59| 73| 88| 106
Installation torque| Tinst| Nm| 20| 45| 60| 110
Methods for application of torque moment| –| –| Machine torquing using a Hilti SIW 6AT-A22 impact wrench with SI-AT- A22 adaptive torque module or manual torquing using a torque wrench
Loads according to Figure 3
Minimum concrete thickness over upper flute| hmin,deck| mm| 70
Minimum distance to edge of lower flute| cmin,deck| mm| 43| 45| 47| 50
Characteristic pullout resistance in non-cracked concrete| **

NRk,p,deck,uncr

| ****

kN

| ****

11.9

| ****

18.6

| ****

20.6

| ****

29.2

Characteristic pullout resistance in cracked concrete| ****

NRk,p,deck,cr

| ****

kN

| ****

8.0

| ****

12.7

| ****

16.5

| ****

20.4

Chacteristic pullout resistance, seismic C1| NRk,p,deck,C1| kN| 8.0| 12.7| 16.5| 20.4
Partial safety factor for pullout resistance| gc| –| 1.5
Robustness factor for pullout resistance| ginst| –| 1.0
Characteristic steel resistance for shear| VRk,s,deck| kN| 15.0| 24.2| 21.4| 26.0
Characteristic steel resistance for shear, seismic C1| ****

VRk,s,deck,C1

| ****

kN

| ****

13.6

| ****

21.9

| ****

19.4

| ****

22.9

Design steel resistance for shear, seismic C1| VRd,s,deck,C1| kN| 9.0| 14.6| 13.0| 15.3
Partial safety factor for steel resistance for shear| gMs,V| –| **** 1.25

Table 3 – Hilti HST3 anchors tension and shear design data for installation in the soffit of f’c = 30 MPa, normal weight concrete-filled profile deck assemblies for hammer drilled installations

All data in Table 3 applies to

  • Correct installation. See anchor box or Hilti.co.nz for details including hole cleaning and installation torque
  • No edge distance and spacing influence. Only one anchor can be used in the lower flute at a time with the min. spacing between anchors along the length of the flute to be at least 3 x hef. This datasheet does not give information for the design of fasteners in a group.
  • f’c = 30 MPa concrete. For higher compressive strengths, the tension loads may be increased by (f’c /30)0.5
  • αgap = 1.0 (no hole clearance between anchor and fixture) was used to in the formula VRd,s,deck,C1 = αgap x αeq x VRk,s,deck,C1 / gMs,V In case of connections with hole clearance according to EN 1992-4 Table 6.1, αgap = 0.5 should be used
  • Testing in accordance with ACI 355.2 and AC 193. Evaluated in accordance with AC 193 and EAD 330232 and EOTA TR 049

For anchoring into the upper flute, either use Table 2 data below conservatively or refer to ETA-98/0001. Additionally, C2 seismic performance category is not included in ACI 355.2 and AC 193. C2 seismic performance category may be designed in the upper flute using all guidelines and parameters provided in ETA-98/0001.
ComFlor® is a registered trademark used in Australia and New Zealand under licence from Tata Steel UK Limited. © Copyright 2017 ComFlor® New Zealand. S&T Stainless Ltd.

Figures for performance data

HUS3 and HUS4 Ultimate screw anchors

HILTI-HUS3-6-Concrete-Screw-Anchor- \(1\)

Figure 1 – Hilti HUS4/HUS3 in the soffit of concrete filled open trough profile steel deck assemblies

HUS4 Ultimate screw anchor

HILTI-HUS3-6-Concrete-Screw-Anchor- \(2\)

Figure 2 – Hilti HUS4 in the soffit of concrete filled re-entrant profile steel deck assemblies

HST3 Ultimate expansion anchor

HILTI-HUS3-6-Concrete-Screw-Anchor- \(3\)

Figure 3 – Hilti HST3 in the soffit of concrete filled open trough profile steel deck assemblies

Updated: Jan-24

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>