AIKO MAH72Dw PV Module Solar panels
Product Specifications
- Manufacturer: Shenzhen Aiko Digital Energy Technology Co., Ltd.
- Module Types: Various models including AIKO-Axxx-MAH72Dw, AIKO-Axxx-MAH72Db, AIKO-Axxx-MAH60Dw, AIKO-Axxx-MAH54Dw, AIKO-Axxx-MAH60Db, AIKO-Axxx-MAH54Db, AIKO-Gxxx-MCH72Dw, AIKO-Gxxx-MCH54Dw
- Structure: Double glass photovoltaic modules
Applicable module models
|
Structure of modules
---|---
AIKO-Axxx-MAH72Dw
|
AIKO-Axxx-MAH72Db
|
Double glass photovoltaic
modules
AIKO-Axxx-MAH60Dw
|
AIKO-Axxx-MAH60Db
AIKO-Axxx-MAH54Dw
|
AIKO-Axxx-MAH54Db
AIKO-Gxxx-MCH72Dw
|
AIKO-Gxxx-MCH54Dw
Important Safety Information
- This installation manual provides information on the installation and safe use of photovoltaic modules (hereinafter referred to as “Modules”) from Shenzhen Aiko Digital Energy Technology Co., Ltd. (hereinafter referred to as ” Aiko “). During module installation and routine maintenance, please comply with all safety precautions and local laws and regulations specified in this manual.
- Professional skills and knowledge are required to install and maintain module systems. Only qualified personnel can install and maintain systems. Installation personnel should be familiar with the mechanical and electrical requirements of the system. Please keep this manual for future maintenance or treatment.
Overview
First of all, thank you for choosing AIKO’s products. This installation manual contains important electrical and mechanical installation information. Please understand this information before you install modules. In addition, the manual also contains some other safety information that you must be familiar with.
This installation manual does not have the meaning of any warranty, whether express or implied. There is no provision on the compensation scheme for the loss, module damage, or other expenses directly caused by or related to the installation, operation, use or maintenance of modules. If the patent right or the rights of a third party are infringed due to the use of modules, AIKO will not bear any relevant responsibilities. AIKO reserves the right to change the product manual and this installation manual without prior notice.
If the customer fails to follow the requirements listed in this manual during the installation of modules, the limited warranty provided to the customer will be invalid. At the same time, the recommendations in this manual are to improve the safety of modules during installation and have been tested and verified by practice. Please provide this manual to the owners of the photovoltaic system for reference, and inform them of all relevant safety, operation, and maintenance requirements and suggestions.
Regulation and rules
The mechanical installation and electrical installation of PV modules shall refer to corresponding regulations, including electrical law, building law and power connection requirements. These regulations vary from installation site to installation site, such as building roof installation, vehicle-mounted applications, etc. Requirements may also vary depending on the voltage and current nature (DC or AC) of the installed system. Please contact the local authority for specific terms.
General information
Module identification
Three kinds of visual labels are provided by AIKO’s modules:
- Nameplate: Product type, rated power under standard test conditions (STC), rated current, rated voltage, open circuit voltage, short circuit current under STC, certification mark, maximum system voltage and other information
- Serial number: Each module has a unique serial number. This serial number is printed on the bar code and placed in the assembly before lamination, and cannot be torn or coated after lamination. In addition, an identical serial number can be found on or next to the module nameplate.
- Current grading label(if necessary): The modules of the same gear are second-graded by rated current and marked for differentiation on the modules.
Nameplate
Bar code label
Wiring mode
The junction box of the AIKO ABC photovoltaic module is located in the middle.
Please refer to the following table for the series connection mode of various
modules.
General safety
The design of the AIKO PV module complies with IEC-61215 and IEC-61730
international standards. The application level is class A. The module can be
used for systems with DC 50V or above 240W that the public may contact. The
safety level of the module is class II and the fire protection level is class
C.
No matter whether the PV module is connected to the system or not, appropriate protective measures shall be taken when contacting the module, such as insulating tools, safety helmets, insulating gloves, safety belts, and safety insulating shoes. When you need to install, ground, wire, and clean modules, please be sure to use appropriate electrical safety protection tools.
Under the sunlight, whether the module is connected to the electrical system or not, it can generate direct current, and touching the live parts of the module (such as connectors) may cause casualties. Avoid direct contact with photovoltaic modules, which may cause electric shock or cuts.
- The installation of PV modules shall comply with the laws and regulations stipulated by the relevant regions and countries where the PV modules are installed. If necessary, the construction permit and other certificates shall be obtained first.
- The installation of PV modules shall be carried out by qualified professionals who have professional skills and knowledge and are familiar with the mechanical and electrical requirements of the system. The risk of possible injury during installation, including electric shock or cuts, shall be known in advance.
The roof system can only be installed on the roof with formal and complete
structural analysis results after evaluation by construction experts.
Observe the safety rules for all installed modules. For example, wires and
cables, connectors, charging controllers, inverters, batteries, etc., only
equipment, connectors, wires, and supports matching the solar power system can
be used. If the photovoltaic system uses batteries, it shall follow the
opinions of the battery manufacturer.
- PV modules of the same size and model can be interconnected.
- Please do not artificially focus light on modules.
Electrical safety
Please strictly follow the following electrical safety provisions to avoid any
form of electrical safety accidents.
- Please do not install or operate PV modules when it is wet or windy.
- The DC voltage of photovoltaic modules may exceed 30V, and direct contact shall be avoided. It is necessary to ensure that the connecting cable is fixed on the support frame for the
installation of PV modules
- Where animals and children can reach, cables must be protected with conduits.
- Please do not artificially modify or remove any modules and labels of PV modules.
- Please do not install PV modules without safety precautions.
- Do not use any means other than connectors for electrical connection.
- The damaged PV module has the risk of electric shock and fire and should be replaced immediately.
- The installation of the PV module array must be carried out under the condition of electrical safety.
During installation, the voltage of PV modules in series shall not exceed the maximum system voltage.
- It is forbidden to plug connectors of different manufacturers and models into each other. Please do not use conventional PV modules to replace roof and wall materials.
- When there is a current or external current in the PV module, the PV module shall not be connected or disconnected.
- Please do not use corrosive chemicals to coat the surface of photovoltaic modules.
- Please do not touch the PV module when it is wet.
Operational safety
- Before the PV modules arrive at the installation site, please do not open the packaging box. Please put the packaging box in a ventilated and dry environment.
- During all handling, please ensure that the PV module will not be subject to large vibration. Improper handling and placement may cause the glass of photovoltaic modules to break or lose electrical performance, and lose the use value of photovoltaic modules.
- Handle and install PV modules with care. In any case, it is forbidden to lift the PV module by pulling the junction box or cable. Two or more people must hold the edge of the PV module with both hands.
- It is forbidden to step on, stand on, or sit on the PV module, which will damage the PV module and pose a risk of injury to people.
- It is forbidden to place any heavy object on the front and back of the PV module, and do not place the PV module on the sharp object surface.
- It is forbidden to attempt to disassemble the PV module or remove the nameplate of the PV module or the modules on the PV module.
- It is strictly prohibited to brush paint or apply any other adhesive on the surface of photovoltaic modules.
Avoid scratching the back plate and glass surface of the PV module.
- It is strictly prohibited to drill holes in the frame of PV modules, which will reduce the load resistance of the frame and lead to the corrosion of the frame, which will lead to the invalidation of the limited warranty of PV modules.
- Except for grounding, it is forbidden to scratch the anodic oxide layer on the surface of the aluminum alloy frame, which may lead to frame corrosion and affect the load resistance and long-term reliability of the frame.
- It is strictly prohibited to repair or refit PV modules by yourself.
- The surface of the touching photovoltaic module should be smooth, without sharp edges, burrs, etc
Do not dispose of electrical appliances as unsorted municipal waste, use
separate collection facilities.
Contact your local government for information regarding the collection systems
available. If electrical appliances are disposed of in landfills or dumps,
hazardous substances can leak into the groundwater and get into the food
chain, damaging your health and well-being. When replacing old appliances with
new ones, the retailer is legally obligated to take back your old appliance
for disposal at least free of charge.
Fire safety
- Please consult local laws and regulations before installing PV modules, and comply with the requirements on building fire resistance.
- When installing on the roof, the roof must be covered with a layer of fireproof materials suitable for this grade, and sufficient ventilation between the back plate and the installation surface must be ensured.
- Different roof structures and installation methods will affect the fire safety performance of buildings. Improper installation may cause fire.
- To ensure the fire rating on the roof, the minimum distance between the PV module frame and the roof surface is 10cm.
- Please use appropriate PV module accessories such as fuse, circuit breaker, and grounding connector according to local regulations.
- Do not use PV modules if exposed flammable gases are present nearby.
Installation conditions
Installation site and working environment
- AIKO PV modules are recommended to be installed in an environment where the operating ambient temperature is -20 ° C ~ 50 ° C. The limiting operating ambient temperature of PV modules is -40 ° C ~ 85 ° C and the humidity is lower than 85%rh. AIKO PV modules apply to the operating environment below 2000m above sea level. Do not directly irradiate the artificial spotlight on the solar PV module.
- When installing solar PV modules on the roof, a safe working area must be reserved between the edge of the roof and the outer edge of the PV module array.
- When photovoltaic modules are stacked on the roof, the load of the roof shall be rechecked and the construction organization plan meeting the specification requirements shall be formulated.
- When selecting the installation position of PV modules, the position where the sun can fully shine shall be selected to avoid partial or total shielding (trees, buildings, clothes, tools, packaging materials, and other obstacles) on the surface of PV modules.
- A safety factor (1.25) regarding the open circuit voltage (Voc) and short circuit current (Isc) needs to be set, considering that the irradiance of the installation site can sometimes be higher than 1000W/m² and the temperature may be lower than 25℃.
- To make use of the power generated on the back side of the double-sided photovoltaic module, the back-side barrier should be avoided.
- Double-sided PV modules are not recommended to be installed in building attached PV systems (such as BAPVs) because the back side of the modules generates electricity by absorbing reflected light from the surface or scattered light from the surrounding environment.
- The PV module shall be installed in a well-ventilated position to ensure sufficient air circulation at the back and side of the PV module so that the heat generated during the working state of the PV module can be dissipated in time. Condensation or moisture can also be dissipated at the same time.
- When used in areas with high wind pressure and snow pressure, the support and fixed structure shall be designed in strict accordance with local design codes to ensure that the external load does not exceed the mechanical strength limit that the PV module can withstand.
- In salt spray, sulfide, and ammonia environments (coastal, factory, volcanic, and farm), corrosion may occur at the connection between modules and supports, or at the position where the grounding is connected. Corrosion-resistant materials (stainless steel or aluminum materials, etc.) must be used to contact the PV module, and the installation position shall be subject to anti-corrosion treatment.
Inclination angle selection
- The inclination angle of the PV module refers to the included angle between the PV module and the horizontal ground.
- Different projects choose different installation inclination angles according to local conditions.
- Each PV module of the same array must have the same direction and angle. Different installation directions and angles will lead to the difference in the total amount of solar radiation absorbed by photovoltaic modules, resulting in the mismatch loss of output power, thus reducing the operating efficiency of the system.
- To achieve the maximum annual power generation of PV modules, the optimal orientation and inclination of PV modules in the installed area shall be selected to ensure that even on the day with the shortest sunshine throughout the year, the sunlight can still shine on the PV modules during the period from 9:00 to 15:00. The optimal inclination design of photovoltaic array shall comprehensively consider the climatic conditions such as monthly average irradiance, direct irradiance, scattering irradiance, wind speed, etc. of the installation site for many years. The inclination of photovoltaic modules shall maximize the annual radiation received by the photovoltaic modules. The selection of angle shall also consider the influence of natural conditions, such as local wind load, snow load, avoiding ponding and ash deposition on the surface of photovoltaic modules, etc.
Mechanical installation
General requirements
Ensure that the PV module installation method and support system are firm
enough. The PV module mounting bracket must be made of corrosion-resistant and
UV-resistant materials.
The PV module must be firmly fixed to the bracket.
In areas with heavy snowfall, a higher support system shall be selected to avoid the lowest point of the PV module being covered by snow for a long time. The lowest point of the PV module shall be at a certain height to prevent the PV module from being covered by weeds and trees on the ground.
- When the PV module is installed parallel to the roof, the minimum gap between the PV module frame and the roof is 10cm.
- The minimum installation distance between two adjacent PV modules is 10mm.
- The maximum static test load passed by the PV module is front 3600/ back 1600 with Safety factor 1.5. The specific load depends on the installation mode of the PV module (please refer to the following). All load values mentioned in this manual are static test loads. Note: according to iec61215-2, 1.5 times of safety factor shall be considered when calculating the maximum design load; When calculating the wind load, the design maximum instantaneous gust load shall consider 3 times the safety factor.
The loads of the modules described in this manual are test loads. According to the installation requirements of IEC 61215-2, the corresponding maximum design load should be divided by at least with safety factor 1.5. The design load of the project needs to depend on the project location, climate, support structure, and relevant specifications. The support supplier and professional engineers are responsible for determining the design load, in accordance with local laws and regulations and the instructions of the structural engineer.
Mechanical installation for double glass module
The connection between AIKO double glass photovoltaic modules and the support
system can be installed by bolts and blocks. PV modules must be installed
according to the following suggestions and examples. If there are other
installation methods, please consult Shenzhen AIKO Digital Energy in advance
and obtain written consent, otherwise the warranty will be invalid.
Mounting pressure clamps
Specialized pressure clamps are used to mount modules as shown below.
- Under no circumstances should the clamp touch the glass or deform the frame. Be sure to avoid the shadowing effect from the pressure clamp.
- Be sure that pressure clamps will not fail due to deformation or corrosion while the entire module is under load. Pressure clamps > 50 mm in length and >3 mm in thickness are recommended. The overlapped distance between the pressure clamp and the module frame, D, shall be at least 7 mm but no more than 10 mm.
- When choosing clamp-mounting, please be sure to use at least four clamps on each module. Depending on the local wind and snow loads, if excessive pressure load is expected, at least six clamps should be required to ensure the module can bear the load (for more details, please contact AIKO technical personnel)
- The applied value of torque should refer to the mechanical design standard and the bolt type the customer is using, for example: M8: 16-20 N•m
Installation diagram and corresponding load
Double glass modules can be installed by clamps based on rails. Following are
the installation diagram and corresponding loads. Here, L stands for the long
side of the module, W stands for the short side of the module, black shadowing
area stands for the installation area of the middle of the clamp. Distance and
length are provided in mm; pressure is provided in Pa.
LAMP MOUNTING – LONG FRAME
Module model| Module size [mm]| Load [Pa]| Installation area D
30mm frame| 35/40mm frame
AIKO-Axxx-MAH54Dw
AIKO-Axxx-MAH54Db
| 1722×1134×30/35/40| +5400/-2400| 310≤D≤410| 350≤D≤450
1757×1134×30/35/40| +5400/-2400| 320≤D≤420| 360≤D≤460
AIKO-Gxxx-MCH54Dw| 1802×1134×30/35/40| +5400/-2400| 320≤D≤420| 360≤D≤460
AIKO-Axxx-MAH72Dw AIKO-Axxx-MAH72Db| 2278×1134×30/35/40| +5400/-2400|
430≤D≤530| 450≤D≤550
2323×1134×30/35/40| +5400/-2400| 500≤D≤550| 500≤D≤550
AIKO-Gxxx-MCH72Dw| 2382×1134×30/35/40| +5400/-2400| 500≤D≤550| 500≤D≤550
Bolts Mounting
Double glass modules can be installed by bolts based on rails. Using bolts to
fix the module on the bracket through the mounting holes at the back of the
module’s frame. Modules come standard with 4 or 8 mounting holes, matching M8
bolts, as figure below:
No | Accessories | Model | Material |
---|---|---|---|
1 | Bolt | M8*1.25 | S35C |
2 | Spring washer | 13.5*2.1 | Mn65 |
3 | Washer | 16*1.7 | Fe |
4 | Bracket | / | Q235 |
5 | Washer | 16*1.7 | Fe |
6 | Nuts | M8*1.25 | S35C |
It is important to ensure the bolts do not fail due to deformation or corrosion during the overall load of the module. AIKO recommends the thickness of the washer should ≥1.7mm and use an M8 nut and bolt, the tightening torque should be between 16-20 Am depending on the bolt grade.
Bolts Mounting diagram and corresponding load
Double glass modules bolt mounting diagram and corresponding loads as below
diagram
AIKO-Axxx-MAH54Dw
AIKO-Axxx-MAH54Db
| 1722×1134| 30/35/40|
+5400/-2400
|
+2400/-2400
---|---|---|---|---
1757×1134| 30/35/40
AIKO-Gxxx-MCH54Dw| 1802×1134| 30/35/40
AIKO-Axxx-MAH72Dw AIKO-Axxx-MAH72Db| 2278×1134| 30/35/40|
/
|
+5400/-2400
2323×1134| 30/35/40
AIKO-Gxxx-MCH72Dw| 2382×1134| 30/35/40
Table 4: Double glass modules bolt mounting diagram and corresponding
loads, longitudinal (E)
Note: The above data is based on the static load requirements of the
IEC61215 standard
Electrical installation
Electrical performance
Please see the PV module product specifications for the electrical performance
parameters of PV modules of AIKO digital energy. There is ± 3% tolerance
between the nominal values of the electrical performance parameters of
photovoltaic modules such as Isc, Voc, and Pmax at the standard test
conditions and bifacial nameplate irradiance. Standard test conditions (STC)
for photovoltaic modules: irradiance 1000w/m2, cell temperature 25 ℃, air
quality AM1.5. The bifacial nameplate irradiance is 1,000 W/m2 on the module
front and 135 W/m2 on the module rear.
- The maximum system voltage of AIKO digital energy photovoltaic modules is 1500V
- When the PV modules are connected in a series, the final voltage is the sum of the single PV modules.
- When the PV modules are connected in parallel, the final current is the sum of the single PV modules, as shown in the figure below. Photovoltaic modules of different electrical performance models cannot be connected in a string.
- When the PV modules are connected in a series, the final voltage is the sum of the single PV modules.
- When the PV modules are connected in parallel, the final current is the sum of the single PV modules, as shown in the figure below. Photovoltaic modules of different electrical performance models cannot be connected in a string.
- If there is a reverse current exceeding the maximum fuse current of the PV module passing through the PV module, an overcurrent protector of the same specification must be used to protect the PV module. If the number of parallel connections is greater than two strings, each string of PV module must have an overcurrent protector, as shown in the above figure.
- The voltage of the string shall not be higher than the maximum voltage that the system can withstand and the maximum input voltage of the inverter and other electrical equipment installed in the system. To ensure this, the open circuit voltage of the array needs to be calculated at the lowest expected ambient temperature at that location. The following formula can be used for the calculation.
Cables and wiring
The protection grade of the junction box of the PV module is IP68, which is
composed of a connected cable and connector with an IP68 protection grade. The
PV module has a dedicated PV output cable with a positive pole and a negative
pole connected to the inside of the junction box, and the other end is
connected with a plug-and-play connector. The two PV modules can be connected
in series by connecting the positive connector of the PV module with the
negative connector of the adjacent PV module.
According to the electrical design and construction specifications,
regulations, and corresponding regulatory requirements of the installation
site, special solar cables and appropriate connector models shall be used to
ensure good electrical and mechanical properties of the cables.
The solar PV module of AIKO adopts special PV cables with a cross-sectional area of 4mm2 or more and UV protection. All other cables used to connect the DC system shall have similar (or higher) specifications. AIKO recommends that all cables should be laid in appropriate pipelines or trunking and away from places prone to ponding. For field wiring, PV special copper core cable with a minimum temperature resistance of 90 °C, light resistance, and a cross-section of not less than 4mm2 shall be used as the PV connecting wire.
Connector
Please ensure that the connector is dry and clean. Confirm that the connector
nut is tightened before wiring.
Do not connect when the connector is wet or in other abnormal conditions. The
premise that the connector meets the IP68 protection grade is that the
positive and negative poles are fully inserted, so the PV modules need to be
connected as soon as possible after installation or appropriate measures
should be taken to avoid water vapor and dust infiltration inside the
connector.
- Avoid direct sunlight and immersion in water. Avoid direct contact between the connector and the ground or roof.
- Please ensure that all electrical connections are secure. Incorrect connections may cause arc and electric shock risks. It is forbidden to plug connectors of different models into each other.
Grounding
In the design of PV modules, an anodized corrosion-resistant aluminum alloy frame is used as a rigid support. To use it safely and avoid lightning and electrostatic damage to PV modules, the PV module frame must be grounded. When grounding, the grounding device must be in full contact with the interior of the aluminum alloy to penetrate the oxide film on the frame surface.
The grounding hardware includes a grounding screw, flat washer, puncture
gasket, and grounding wire.
Except for the grounding wire, other related hardware shall be made of
stainless steel. The grounding conductor or grounding wire adopts copper core
wire, and the grounding conductor must be connected to the earth through a
suitable grounding electrode. The third-party grounding device that meets the
requirements of the installation ground electrical equipment specification can
be used for the grounding of AIKO digital energy photovoltaic modules. The
grounding device shall be installed and operated by the operation manual
specified by the manufacturer.
The following are the recommended grounding methods
On side C of the PV module frame, there is Ф 4.2mm grounding holes, use
separate grounding wires and relevant accessories to connect the aluminum
alloy frame of the solar photovoltaic module and connect the grounding wire to
the earth. It is recommended to use an m4x12mm grounding bolt and M4 nut, star
washer, and flat washer.
The recommended torque value of the grounding bolt is 3~7n · m, and the
grounding wire adopts a 4mm2 copper core wire.
Unused PV module mounting holes on the frame can also be used for grounding.
PV module maintenance
The PV modules must be regularly inspected and maintained, especially within
the warranty period, which is the responsibility of the user. And notify AIKO’
customer service personnel as soon as possible in case of any damage or other
significant abnormalities of PV modules.
Clean
The power output of photovoltaic modules is related to the incident light
intensity. Dust accumulation or other obstructions will reduce the power
output of photovoltaic modules. The dirt on the PV module shall be cleaned in
time.
As for cleaning frequency, it depends on the accumulation rate of dirt. If the
PV module has enough inclination angle, the rainwater will clean the surface
of the PV module, which can reduce the cleaning frequency.
It is recommended to use a sponge moistened with clean water to wipe the glass
surface of photovoltaic modules. It is strictly prohibited to use cleaning
agents containing acid or alkali to clean PV modules. It is forbidden to use a
brush and other tools with a rough surface for cleaning.
It is recommended to clean PV modules in the early morning or evening when the
light is weak and the temperature of PV modules is relatively low.
Visual inspection
- Visually inspect the PV module for appearance defects, such as:
- Whether the photovoltaic module glass is broken;
- Whether the photovoltaic module backplane is cracked or otherwise abnormal;
- Whether the junction box is damaged and whether the cable is damaged;
- Whether the PV module is covered by foreign matters and shadows;
- Check whether the bolts fixing PV module and bracket are loose or rusted, and adjust or replace them in time;
- Check whether the PV module is well grounded.
Connector and cable inspection
- It is recommended to carry out preventive inspections once every six months, such as:
- Check the tightness of the connector and the firmness of the cable;
- Check the junction box sealant for cracks.
Revision version and date
- Rev 1.0, issued in May 2023;
- Rev 1.1, revised in Sep 2023;
- Rev 1.2, revised in Nov 2023.
Appendix: Electrical performance parameters of modules
Type of module
|
Maximum power (Pmax)
[W]|
Open- circuit voltage (Voc) [V]
|
Operating voltage at the maximum power
(Vmp) [V]
|
Short- circuit current (Isc) [A]
| Operating current at the maximum power
(Imp) [A]
|
Fuse current (A)
|
Maximum system voltage (Vsys) [V]
---|---|---|---|---|---|---|---
Under STC
AIKO-Axxx-MAH72Dw
| 585| 53.84| 13.90| 44.50| 13.15| 25| 1500
590| 53.94| 13.98| 44.60| 13.23| 25| 1500
595| 54.04| 14.06| 44.70| 13.32| 25| 1500
600| 54.14| 14.14| 44.80| 13.40| 25| 1500
605| 54.24| 14.22| 44.90| 13.48| 25| 1500
610| 54.34| 14.30| 45.00| 13.56| 25| 1500
615| 54.44| 14.38| 45.10| 13.64| 25| 1500
620| 54.57| 14.46| 45.20| 13.72| 25| 1500
625| 54.70| 14.54| 45.30| 13.80| 25| 1500
AIKO-Axxx-MAH72Db
| 585| 54.04| 13.85| 44.70| 13.09| 25| 1500
590| 54.14| 13.93| 44.80| 13.17| 25| 1500
595| 54.24| 14.01| 44.90| 13.26| 25| 1500
600| 54.34| 14.09| 45.00| 13.34| 25| 1500
605| 54.44| 14.17| 45.10| 13.42| 25| 1500
610| 54.57| 14.25| 45.20| 13.50| 25| 1500
615| 54.70| 14.33| 45.30| 13.58| 25| 1500
620| 54.83| 14.41| 45.40| 13.66| 25| 1500
AIKO-Gxxx-MCH72Dw
| 610| 53.70| 14.60| 44.51| 13.71| 30| 1500
615| 53.80| 14.66| 44.61| 13.79| 30| 1500
620| 53.90| 14.72| 44.71| 13.87| 30| 1500
625| 54.00| 14.78| 44.81| 13.95| 30| 1500
630| 54.10| 14.84| 44.91| 14.03| 30| 1500
635| 54.20| 14.90| 45.01| 14.11| 30| 1500
640| 54.30| 14.96| 45.11| 14.19| 30| 1500
645| 54.40| 15.02| 45.21| 14.27| 30| 1500
650| 54.50| 15.08| 45.31| 14.35| 30| 1500
AIKO-Axxx-MAH60Dw
| 490| 44.92| 13.96| 37.13| 13.20| 25| 1500
495| 45.02| 14.05| 37.23| 13.30| 25| 1500
500| 45.12| 14.14| 37.33| 13.40| 25| 1500
505| 45.22| 14.23| 37.43| 13.50| 25| 1500
510| 45.32| 14.32| 37.53| 13.59| 25| 1500
| 515| 45.42| 14.41| 37.63| 13.69| 25| 1500
---|---|---|---|---|---|---|---
520| 45.52| 14.50| 37.73| 13.79| 25| 1500
AIKO-Axxx-MAH60Db
| 490| 45.12| 13.88| 37.33| 13.13| 25| 1500
495| 45.22| 13.97| 37.43| 13.23| 25| 1500
500| 45.32| 14.06| 37.53| 13.33| 25| 1500
505| 45.45| 14.15| 37.63| 13.43| 25| 1500
510| 45.58| 14.24| 37.73| 13.52| 25| 1500
515| 45.71| 14.33| 37.83| 13.62| 25| 1500
AIKO-Axxx-MAH54Dw
| 440| 40.41| 13.94| 33.40| 13.18| 25| 1500
445| 40.51| 14.04| 33.50| 13.29| 25| 1500
450| 40.61| 14.14| 33.60| 13.40| 25| 1500
455| 40.71| 14.24| 33.70| 13.51| 25| 1500
460| 40.81| 14.34| 33.80| 13.62| 25| 1500
465| 40.93| 14.44| 33.90| 13.72| 25| 1500
AIKO-Axxx-MAH54Db
| 440| 40.61| 13.85| 33.60| 13.10| 25| 1500
445| 40.71| 13.95| 33.70| 13.21| 25| 1500
450| 40.81| 14.05| 33.80| 13.32| 25| 1500
455| 40.93| 14.15| 33.90| 13.43| 25| 1500
460| 41.06| 14.25| 34.00| 13.54| 25| 1500
465| 41.19| 14.35| 34.10| 13.64| 25| 1500
AIKO-Gxxx-MCH54Dw
| 460| 40.27| 14.69| 33.44| 13.76| 30| 1500
465| 40.37| 14.75| 33.54| 13.87| 30| 1500
470| 40.50| 14.82| 33.64| 13.98| 30| 1500
475| 40.63| 14.89| 33.74| 14.09| 30| 1500
480| 40.76| 14.96| 33.84| 14.19| 30| 1500
485| 40.89| 15.03| 33.94| 14.30| 30| 1500
Under BNPI
AIKO-Axxx-MAH72Dw
| 615| 53.93| 14.52| 44.60| 13.79| 25| 1500
620| 54.03| 14.60| 44.70| 13.88| 25| 1500
625| 54.13| 14.68| 44.80| 13.96| 25| 1500
630| 54.23| 14.76| 44.90| 14.04| 25| 1500
635| 54.33| 14.84| 45.00| 14.12| 25| 1500
640| 54.43| 14.92| 45.10| 14.20| 25| 1500
645| 54.53| 15.00| 45.20| 14.28| 25| 1500
650| 54.63| 15.08| 45.30| 14.35| 25| 1500
655| 54.73| 15.16| 45.40| 14.43| 25| 1500
AIKO-Axxx-MAH72Db
| 615| 54.13| 14.46| 44.80| 13.73| 25| 1500
620| 54.23| 14.54| 44.90| 13.81| 25| 1500
625| 54.33| 14.62| 45.00| 13.89| 25| 1500
| 630| 54.43| 14.70| 45.10| 13.97| 25| 1500
---|---|---|---|---|---|---|---
635| 54.53| 14.78| 45.20| 14.05| 25| 1500
640| 54.63| 14.86| 45.30| 14.13| 25| 1500
645| 54.73| 14.94| 45.40| 14.21| 25| 1500
650| 54.83| 15.02| 45.50| 14.29| 25| 1500
AIKO-Gxxx-MCH72Dw
| 665| 53.74| 15.73| 44.55| 14.93| 30| 1500
670| 53.84| 15.81| 44.65| 15.01| 30| 1500
675| 53.94| 15.89| 44.75| 15.09| 30| 1500
680| 54.04| 15.97| 44.85| 15.17| 30| 1500
685| 54.14| 16.05| 44.95| 15.24| 30| 1500
690| 54.24| 16.13| 45.05| 15.32| 30| 1500
695| 54.34| 16.21| 45.15| 15.40| 30| 1500
700| 54.44| 16.29| 45.25| 15.47| 30| 1500
705| 54.54| 16.37| 45.35| 15.55| 30| 1500
AIKO-Axxx-MAH60Dw
| 515| 44.99| 14.58| 37.21| 13.85| 25| 1500
520| 45.09| 14.67| 37.31| 13.94| 25| 1500
525| 45.19| 14.76| 37.41| 14.04| 25| 1500
530| 45.29| 14.85| 37.51| 14.13| 25| 1500
535| 45.39| 14.94| 37.61| 14.23| 25| 1500
540| 45.49| 15.03| 37.71| 14.32| 25| 1500
545| 45.59| 15.12| 37.81| 14.42| 25| 1500
AIKO-Axxx-MAH60Db
| 515| 45.19| 14.50| 37.41| 13.77| 25| 1500
520| 45.29| 14.59| 37.51| 13.87| 25| 1500
525| 45.39| 14.68| 37.61| 13.96| 25| 1500
530| 45.49| 14.77| 37.71| 14.06| 25| 1500
535| 45.59| 14.86| 37.81| 14.15| 25| 1500
540| 45.69| 14.95| 37.91| 14.25| 25| 1500
AIKO-Axxx-MAH54Dw
| 460| 40.42| 14.53| 33.43| 13.77| 25| 1500
465| 40.52| 14.63| 33.53| 13.87| 25| 1500
470| 40.62| 14.73| 33.63| 13.98| 25| 1500
475| 40.72| 14.83| 33.73| 14.09| 25| 1500
480| 40.82| 14.93| 33.83| 14.20| 25| 1500
485| 40.92| 15.03| 33.93| 14.30| 25| 1500
AIKO-Axxx-MAH54Db
| 460| 40.62| 14.43| 33.63| 13.69| 25| 1500
465| 40.72| 14.53| 33.73| 13.79| 25| 1500
470| 40.82| 14.63| 33.83| 13.90| 25| 1500
475| 40.92| 14.73| 33.93| 14.01| 25| 1500
480| 41.02| 14.83| 34.03| 14.11| 25| 1500
485| 41.12| 14.93| 34.13| 14.22| 25| 1500
AIKO-Gxxx-MCH54Dw
| 500| 40.33| 15.76| 33.45| 14.96| 30| 1500
---|---|---|---|---|---|---|---
505| 40.43| 15.86| 33.55| 15.06| 30| 1500
510| 40.53| 15.96| 33.65| 15.17| 30| 1500
515| 40.63| 16.06| 33.75| 15.27| 30| 1500
520| 40.73| 16.16| 33.85| 15.37| 30| 1500
525| 40.83| 16.26| 33.95| 15.47| 30| 1500
QR SCAN
- Aiko Digital Energy Technology reserves the right to change this manual without prior notice.
- Please log on to the official website of AIKO Digital Power for the latest version of the installation manual, URL: http://www.aikosolar.com.
FAQ
Frequently Asked Questions
- Q: Where can I find the latest version of the installation manual?
- A: The latest version of the installation manual can be accessed on the official website of AIKO Digital Power at URL http://www.aikosolar.com.