Honeywell ECS-50WBU Backup Amplifier Installation Guide

May 15, 2024
Honeywell

Honeywell ECS-50WBU Backup Amplifier

Honeywell-ECS-50WBU-Backup-Amplifier-PRODUCT

Product Information

Specifications

  • Product Name: Farenhyt Series ECS-50WBU Backup Amplifier
  • Compatibility: Designed for use with ECS-DUAL50W in the 100-watt-with-backup mode for single and dual-channel setups

Product Usage Instructions

Installation and Wiring

  1. Remove AC power from the ECS-DUAL50W.
  2. Disconnect backup batteries from the ECS-DUAL50W.
  3. Connect one end of the supplied wiring harness (P/N 50116775-001) from the connector labeled “Backup Amplifier” on the ECS-DUAL50W to the connector on the ECS-50WBU.
  4. Mount the ECS-50WBU to the standoffs using the 4 supplied screws.
  5. Restore AC Power.
  6. Reconnect backup batteries.

Note: Follow the provided figure for correct installation and wiring details.

FAQ

Q: Can the ECS-50WBU be used with other amplifier models?

  • A: The ECS-50WBU is specifically designed for use with the ECS-DUAL50W in the specified mode and may not be compatible with other amplifier models.

Q: What is the purpose of the backup capability provided by the ECS- 50WBU?

  • A: The backup capability ensures continued operation in case of power outages or failures, maintaining uninterrupted functionality for critical systems.

Description

The ECS-50WBU provides backup capability when operating the ECS-DUAL50W in the 100-watt-with-backup mode for both single and dual-channel setups.

Compatibility

  • The ECS-50WBU is compatible with the following Honeywell Farenhyt Series Fire Alarm Control Panels (FACPs).
  • For more information, refer to the FACP Installation Manual or the ECS Series Manual (PN 151455).
  • IFP-2100ECS
  • IFP-300ECS
  • IFP-2000ECS
  • IFP-1000ECS
  • IFP-100ECS

Installation and Wiring

The ECS-50WBU mounts on top of the ECS-DUAL50W board on the standoffs provided.

  1. Remove AC power from the ECS-DUAL50W.
  2. Disconnect backup batteries from the ECS-DUAL50W.
  3. Connect one end of the supplied wiring harness (P/N 50116775-001) from the connector labeled, “Backup Amplifier” on the ECS-DUAL50W to the connector on the ECS-50WBU as shown in Figure 1.
  4. Mount the ECS-50WBU to the standoffs using the 4 supplied screws as shown in Figure 1.
  5. Restore AC Power.
  6. Reconnect backup batteries.

Document LS10059-001SK-E:C 12/14/2021 ECN: 151770

Documents / Resources

| Honeywell ECS-50WBU Backup Amplifier [pdf] Installation Guide
ECS-50WBU, ECS-50WBU Backup Amplifier, Backup Amplifier, Amplifier
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals