Schneider Electric XUM9A-XB Photo Electric Sensors Installation Guide
- May 15, 2024
- Schneider Electric
Table of Contents
XUM9A-XB Photo Electric Sensors
Installation Guide
XUM9A-XB Photo Electric Sensors
NPN – M8 Connector : XUM9ANXBM8
PNP – M8 Connector : XUM9APXBM8
NPN – 2 m Cable : XUM9ANXBL2
PNP – 2 m Cable : XUM9APXBL2
Polarised reflex
Package Content
(Example)
We welcome your comments about this document. You can reach us through the
customer support page on your local website.
http://qr.tesensors.com/XU0007
Scan the code to access this Instruction Sheet and all product information in
different languages or you can visit our website at:
www.tesensors.com
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Disconnect all power before servicing equipment.
- Do not connect this device to AC power.
- The power voltage must not exceed the rated range.
Failure to follow these instructions will result in death or serious injury.
WARNING
IMPROPER SETUP OR INSTALLATION
- This equipment must only be installed and serviced by qualified personnel.
- Read, understand, and follow the compliance below, before installing the XUM Photo-electric sensor.
- Do not tamper with or make alterations on the unit.
- Comply with the wiring and mounting instructions.
- Check the connections and fastening during maintenance operations.
- The proper functioning of the XUM photoelectric sensor and its operating line must be checked regularly and according to the application (for example number of operations, level of environmental pollution, etc.).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Mounting and tightening torques
CAUTION
DETERIORATION OF PROTECTION DEGREE
Do not apply excessive torque on the sensor during the installation process.
Failure to follow these instructions can result in injury or equipment damage.
LEDs and settings
Wiring diagrams
Wiring precaution
NOTICE
REDUCTION OF SERVICE LIFE
Do not pull on the sensor cable.
Failure to follow these instructions can result in equipment damage.
Dimensions
Accessories
Pre-Wired connectors (examples)
PVC cable for general use
PUR cable for severe industrial environments
M8, 4 pins Cable length| | | M8 – M12, 4 pins Jumper
length| PUR| PUR
---|---|---|---|---|---
PVC| PUR| PVC| PUR
2 m / 6.56 ft.| XZCPV0941L2| XZCP0941L2| XZCPV1041L2| XZCP1041L2| 1 m /
3.28 ft.| XZCR1509041J1| XZ CR1510041J1
5 m / 16.4 ft.| XZCPV0941L5| XZCP0941L5| XZCPV1041L5| XZCP1041L5| 2 m /
6.56 ft.| XZCR1509041J2| XZCR1510041J2
10 m / 32.8 ft.| XZCPV0941L10| XZCP0941L10| XZCPV1041L10| XZCP1041L10| | |
Sensor position adjustment
– Translate the sensor or reflector, up/down and left/right. When the setting
is optimal, the stability indicator (green) is lit.
– Check sensor operation with the object and adjust the sensor, if necessary.
Anti-interference for side by side and face to face (only for reflex model)
mounting
Output mode setting: Light-On or Dark-On (Light-On by default)
Sensor sensitivity adjustment
For accurate detection, follow the configuration below. (eg. Reflective
objects, with holes or small size to obstruct the reflection of the light
beam).
| Light-On| Dark-On
---|---|---
| 1-Connect the sensor to the power supply (see page 1 for the wire
connection & page 7 for the power voltage).
Before settings, start with the potentiometer at the minimum position
(resulting to point A).| 1-Connect the sensor to the power supply (see page 1
for the wire connection & page 7 for the power voltage).
Before settings, start with the potentiometer at the minimum position
(resulting to point A).
| 2-Put the reflector in front of the sensor. Turn the potentiometer clockwise
until the output led (yellow) switches on: the reflector is detected
(resulting to point B). Continue to turn the potentiometer clockwise until the
stability led (green) switches on (resulting to point C).| 2-Put the reflector
in front of the sensor. Turn the potentiometer clockwise until the output led
(yellow) switches off: the reflector is detected (resulting to point B).
Continue to turn the potentiometer clockwise until the stability led (green)
switches on (resulting to point C).
| 3-Put the object between the sensor and the reflector. Make sure the output
led (yellow) switches off and the stability led (green) is on. This ensures a
good stability of detection.
The Sensor is set and ready to detect.| 3-Put the object between the sensor
and the reflector. Make sure the output led (yellow) switches on & the
stability led (green) is on. This ensures a good stability of detection.
The Sensor is set and ready to detect.
Detection curves
Characteristics
Certification | CE – UKCA – cULus |
---|
Sensing Range (using a 50 mm x 50 mm reflector XUZC50)
Excess gain = 1: Maximum sensing distance| 8 m – excess gain = 1 6,7 m –
excess gain = 2
Color of detection light beam| Red
Blind zone| 50 mm using a 50 mm x 50 mm reflector XUZC50 (for the reflector –
no blind zone for objects)
Sensing distance setting| Potentiometer 1 turn (~ 240 degrees)
Light-On/Dark-On selection| Switch (~ 120 degrees)
Output type| One open collector output, PNP or NPN
ON Voltage drop| 2 V max. (30 Vdc 100 mA) / 1,2 V max. (30 Vdc 10mA)
Current consumption| < 20 mA max.
Switching capacity| 100 mA
Response time| 0,5 ms max.
Recovery time| 0,5 ms max.
Switching frequency| 1000 Hz
Electrostatic discharge immunity| 4 kV (Contact), 8 kV (Air) conforming to IEC
61000-4-2
Electromagnetic field immunity| 10 V/m conforming to IEC 61000-4-3
Fast transients immunity| Burst 5 kHz – 2 kV conforming to IEC 61000-4-4
Conducted disturbances immunity| 10 V conforming to IEC 61000-4-6
Emissivity Radiated disturbances| Class A conforming to EN 55011 / CISPR 11
Power Voltage| Rated operational voltage: 12…24 Vdc Ripple p-p 10% maximum
Operating range: 10…30 Vdc (including ripple)
Product protection| Power supply : Reverse polarity protection Output: Short
circuit protection
Reverse polarity protection
Light Immunity| Operating atmosphere; Sunlight 40 kLx max. Incandescent light
10 kLx max. (at the receiver surface)
Ambient Temperature| Operating : – 30…+55 °C (-22…+131 °F),
Storage : – 40…+70 °C (-40…+158 °F)
Ambient Humidity| Operating : 35…95% RH, Storage : 35…95% RH
Degree of protection| IP65, IP67 conforming to IEC 60529
Vibration resistance| Frequency range: 10 Hz to 500 Hz Acceleration: 9 gn
Shock resistance| Peak acceleration: 100 gn
Duration of the pulse: 11 ms
Material| Housing: PBT, Lens: PMMA, Operation cover: PC, Adjustment
potentiometer: PBT
Manufacturer :
Schneider Electric Industries SAS
35 rue Joseph Monier
92500 Rueil Malmaison
France
UK Representative :
Schneider Electric Limited
Stafford Park 5
Telford, TF3 3BL
United Kingdom
NNZ98172_01
www.tesensors.com