HITACHI RAK-AH10PCASM Remote Controller Air Conditioner Installation Guide
- May 15, 2024
- Hitachi
Table of Contents
HITACHI RAK-AH10PCASM Remote Controller Air Conditioner
Product Information
Specifications:
- Models: RAK-AH10PCASM/RAC-AH10PCASM, RAK-AH13PCASM/RAC-AH13PCASM, RAK-AH18PCASM/RAC-AH18PCASM, RAK-AH24PCASM/RAC-AH24PCASM
- Model Number: HI2022480HA
Product Usage Instructions
Safety Instructions:
Before using the air conditioner, please read through all safety instructions provided in the manual to ensure safe operation.
Preparation Before Use:
Ensure that the unit is placed in a suitable location with proper ventilation and access to power source before operation.
Installation Instructions:
Follow the detailed installation instructions provided in the manual for both indoor and outdoor unit installations, including wiring diagrams and air purging steps.
Maintenance:
Regular maintenance is essential for optimal performance. Refer to the maintenance section in the manual for instructions on how to clean and protect the unit.
Troubleshooting:
If you encounter any issues with the air conditioner, refer to the troubleshooting guide in the manual to identify and resolve common problems.
FAQs
- Q: How do I adjust the room temperature using the remote controller?
- A: To adjust the room temperature, use the setting buttons on the remote controller. Press the buttons to increase or decrease the temperature as desired.
- Q: What is the purpose of the Turbo button on the remote controller?
- A: The Turbo button is used to activate fast cooling, operating at high fan speed with a preset temperature of 16°C automatically for quick cooling.
INSTALLATION & OPERATION MANUAL
MODEL RAK-AH10PCASM/RAC-AH10PCASM RAK-AH13PCASM/RAC-AH13PCASM RAK-AH18PCASM
/RAC-AH18PCASM RAK-AH24PCASM/RAC-AH24PCASM
HI2022480HA
Remote controller operating instructions.See”remote controller instructions”.
Remote controller
Remote controller
The remote controller transmits signals to the system.
1 ON/OFF BUTTON
The appliance will be started when it is energized or will be
stopped when it is in operation, if you press this button.
1
2 MODE BUTTON
Press this button to select the operation mode.
2
MODE ON/OFF
3
FAN
TURBO
6
3 FAN BUTTON
4
TEMP
5
Used to select fan speed in sequence auto, high, medium or low. 15
4 5 ROOM TEMPERATURE
8
SETTING BUTTONS
14
Used to adjust the room temperature and the timer, also real time. 11
MUTE
LIGHT
9
SLEEP
TIMER ON
TIMER OFF
CLOCK
7 10
6 TURBO BUTTON
13
ECO IFEEL CLEAN
12
Used to start or stop the fast cooling.(Fast cooling operates at high
16
fan speed with 16Co set temp automatically).
17
7 SWING BUTTON
14 SWING BUTTON
Used to stop or start vertical adjustment
Used to stop or start Horizontal adjustment
louver swinging and set the desired up/down 15 louver swinging and set the desired left/right
airflow direction.
airflow direction.
8 SLEEP BUTTON
15 MUTE BUTTON
Used to set or cancel Sleep Mode operation.
Press it once,the MUTE function will be started.
9 LIGHT BUTTON
Press it again, the MUTE function will be shut off.
When you press this button, all the display of 17 IFEEL BUTTON
indoor unit will be closed.
Used to set IFEEL mode operation. Press it once,
10 CLOCK BUTTON
Used to set the current time.
the IFEEL function will be started. Press it again, the IFEEL function will be shut off. If the IFEEL function can’t be shut off, please try
11 12 TIMER ON/OFF BUTTON
to press this button about 5 seconds.
Used to set or cancel the timer operation.
Advice to put the remote controller in the place where the indoor unit receive signal easily.
13 ECO BUTTON
Advice to cancel the IFEEL mode so as to save
Used to set or cancel Economy Mode operation. energy when stopping the air conditioner.
16 CLEAN BUTTON
Used to set the CLEAN function.
+ 11 12 LOCK
Press them together for 3 seconds to start or stop operation .
LOCK
Indication symbols on LCD:
Cooling indicator Dry indicator Fan only indicator Heating indicator
Nanoe indicator Turbo indicator
Auto fan speed Higher fan speed High fan speed Medium fan speed Low fan speed
Lower fan speed
Mute indicator
Smart indicator Sleep indicator Economy indicator Ifeel
Lock
Airflow left and right indicator
Airflow up and down indicator
Note: Each mode and relevant function will be further specified in following pages.
Signal transmit. ON Display set timer OFF Display current time
Display temperature
1
Remote controller
Remote controller
How to Insert the Batteries
Remove the battery cover according to the arrow direction.
Insert new batteries making sure that the (+) and (-) of
1
battery are matched correctly.
Reattach the cover by sliding it back into position.
Note:
Use 2 LR03 AAA(1.5volt) batteries. Do not use rechargeable batteries.
2
Replace batteries with new ones of the same type when the display
becomes dim.
3
Storage and Tips for Using the Remote Controller The remote controller may be
stored mounted on a wall with a holder.
Note: The remote controller holder is an optional part.
How to Use
To operate the room air conditioner, aim the remote controller to the signal
receptor. The remote controller will operate the air conditioner at a distance
of up to 7m when pointing at signal receptor of indoor unit.
CAUTIONS
For appropriate signal transmission between remote controller and indoor unit,
keep the signal receiver away from the following items:
Direct sunlight or other strong lights or heat Flat panel television screen or
other electrical appliances that react to the remote controller Additionally,
the air conditioner will not operate if curtains, doors or other materials
block the signals from the remote controller to the indoor unit. If the signal
may not be transmitted properly, either move these materials or consult your
local dealer.
TEMP
2
TEMP
Signal receptor
Operation instructions
Operation modes
Selecting mode
Each time the “MODE” button is pressed, the operation mode is changed in sequence:
COOLING
DRY
FAN ONLY
HEATING AUTO
Heating mode is NOT available for cooling only air conditioner.
FAN mode
1
Each time the “FAN” button is pressed, the fan speed is changed in sequence:
Auto Higher High Medium
Low Lower
2
At “FAN ONLY” mode, only “Higher”,”High”,”Medium””Low” and “Lower” are
available. At “DRY” mode, Fan speed is set at “Auto” automatically, “FAN”
button is ineffective in this case.
Setting temperature
“” Press once to raise temperature setting by 1
“” Press once to lower temperature setting by 1
4
MODE ON/OFF
FAN
TURBO
TEMP
3
MUTE
LIGHT
SLEEP
TIMER ON
TIMER OFF
CLOCK
ECO IFEEL CLEAN
Range of available set temperature
*HEATING, COOLING
16-30
Note: Heating mode is NOT available for cooling only models.
Note: Press and hold ”
” button and ” TEMP ” button
together for 3 seconds will alternate the temperature display
between the and °F scale.
Turning on
Press ON/OFF button, when the appliance receives the signal, the RUN indicator of the indoor unit lights up.
SWING, SMART, TIMER ON, TIMER OFF, CLOCK, SLEEP and SUPER operation modes will
be specified in the following pages.
Changing modes during operation, sometimes the unit does not response at once.
Wait 3 minutes. During heating operation, air flow is not discharged at the
beginning. After 25 minutes, the air flow will be discharged until temperature
of indoor heat exchanger rises. Wait 3 minutes before restarting the
appliance.
3
Operation instructions
Airflow direction control
Airflow direction control
Vertical airflow(Horizontal airflow) is automatically adjusted to a certain angle in accordance with the operation mode after turning on the unit.
Operation mode Direction of airflow
COOLING, DRY
*HEATING, FAN ONLY
horizontal downward
The direction of airflow can be also adjusted to your own
5 requirement by pressing the
“SWING” button of the remote controller.
*Heating mode is only available for heat pump models.
MODE ON/OFF
FAN
TURBO
TEMP
MUTE
LIGHT
SLEEP
TIMER ON
TIMER OFF
CLOCK
ECO IFEEL CLEAN
Vertical airflow control (with the remote controller)
Using remote controller to set various angles of flow or specific angle as you like.
Swinging airflow
Pressing
button once, the vertical adjustment louver
will swing up and down automatically.
Desired direction airflow
Pressing the
button again when the louvers swing
to a suitable angle as desired.
Horizontal airflow control (with the remote controller)
Using remote controller to set various angles of flow or specific angle as you
like.
Swinging airflow
Pressing button once, the horizontal adjustment louver will swing left and
right automatically.
Desired direction airflow
Pressing the button again when the louvers swing to a suitable angle as
desired.
NOTE:This function is to keep global format standardization and for this model
isn’t available. You can adjust the horizontal airflow by yourself
Do not turn the vertical adjustment louvers manually, otherwise malfunction
may occur. If that happens, turn off the unit first and cut off the power
supply, then restore power supply again. It is better not to let the vertical
adjustment louver tilt downward for a long time at COOLING or DRY mode to
prevent condensed water from dripping.
4
Operation instructions
CLOCK button
You can adjust the real time by pressing CLOCK button, then using “” and “”
buttons to get the correct time, press CLOCK button again the real time is
set.
Timer mode
It is convenient to set the timer on with TIMER ON button when you go out in
the morning to achieve a comfortable room temperature at the time you get
home. You can also set timer off at night to enjoy a good sleep.
How to set TIMER ON TIMER ON button can be used to set the timer programming
as wished in order to switch on the appliance at your desired time. i) Press
TIMER ON button, “ON 12:00” flashes on the LCD, then you can press the “” or
“” buttons to select your desired time for appliance on.
Increase
Decrease Press the “” or “” button once to increase or decrease the time
setting by 1 minute. Press the “” or “” button 2 seconds to increase or
decrease the time setting by 10
minutes. Press the “” or “” button for a longer time to increase or decrease
the time by 1 hour.
Note: If you don’t set the time in 10 seconds after you press TIMER ON button,
the remote controller will exit the TIMER ON mode automatically.
ii) When your desired time displayed on LCD, press the TIMER ON button and
confirm it.
“ON” stops flashing. The TIMER indicator on the indoor unit lights up.
iii) After the set timer displayed for 5 seconds the clock will be displayed
on the LCD of the remote controller instead of set timer.
How to cancel TIMER ON Press the TIMER ON button again, the indicator
disappears, the TIMER ON mode has been canceled.
Note: It is similar to set TIMER OFF, you can make the appliance switch off
automatically at your desired time.
5
Operation instructions
SLEEP mode
SLEEP mode
SLEEP mode can be set in COOLING, HEATING or DRYING operation mode. This
function gives you a more comfortable environment for sleep. In SLEEP mode,
The appliance will stop operation automatically after operating for 8 hours.
Fan speed is automatically set at low speed. Set temperature will rise by 1
at mostif the appliance operates in cooling mode for 1 hour constantly, then
keeps steady. Set temperature will decrease by 3 at most if the appliance
operates in heating mode for 3 hours constantly, then keeps steady.
For some models, such as G1Q series
Set temperature will rise by 2 at mostif the appliance operates in cooling mode for 2 hour constantly, then keeps steady. Set temperature will decrease by 2 at most if the appliance operates in heating mode for 2 hours constantly, then keeps steady.
*Note: In cooling mode, if room temperature is 26or above, set temperature will not change.
Note: Heating is NOT available for cooling only air conditioner. Note: Press
TURBO ,ON/OFF,FAN, MODE,ECO or SLEEP button cancel SLEEP mode.
TURBO mode
TURBO mode
TURBO mode is used to start or stop fast cooling when the unit is on. TURBO
mode can be set when the appliance is in operation or energized. In TURBO
mode, you can set airflow direction or timer.
How to set TURBO mode?
Press TURBO button at the cooling,fan only or dry mode.
Result :
At high fan speed ,the set temperature
automatically to 16.
Press TURBO button at the heating mode .
Result :
At AUTO fan speed ,the set temperature
automatically to 30.
How to cancel TURBO mode?
Press TURBO , MODE, FAN, ON/OFF,SLEEP,TURBO or MUTE button.
Result :
The display return to the original mode.. Escape from TURBO mode.
Cancel
6
Operation instructions
LOCK function
LOCK function
Press TIME ON and TIME OFF buttons together for 3 seconds to start LOCK function.
The icon will appears on the the LCD
Press TIME ON and TIME OFF buttons together for 3 seconds again to stop LOCK function.
The icon will disappeared from the the LCD
CLEAN
1
2
Press together
for 3 seconds
MUTE mode
MUTE mode
In this mode, the air conditioner will work with low noise performance.
In this mode, you can start the SLEEP mode at the same time.
Note:
PRESS
-
MUTE button is only available in COOLING, HEATING and FAN ONLY mode.
-
Press MODE, FAN SPEED, SMART or SUPER button to cancel MUTE mode.
ECO mode
ECO mode
In this mode, the air conditioner will bring you energy saving performance by lower running currency.
Note: ECONOMY button is ineffective in SMART and SUPER mode. SMART and SUPER buttons are not available in ECONOMY mode.
- Press ON/OFF, MODE, TEMP ±, FAN SPEED, SLEEP, QUIET or ECONOMY button to cancel ECONOMY mode.
PRESS
CLEAN
IFEEL function
IFEEL function
The temperature sensor built in remote controller is activated.It can sense its surrounding temperature,
and transmit the signal back the unit,the unit can adjust the temperature so as to provide maximum
comfort.
Note: Advice to put the remote controller in the place where the indoor unit receive signal easily. Advice to cancel the IFEEL mode so as to save energy when stopping the air conditioner.
CLEAN
PRESS
CLEAN function
LOCK function
When the air conditioner is in standby, and the mode of remote controller is in Cooling or Dry, Press CLEAN button to start Clean mode,then the indicator ” ” will display on LCD. .
Clean mode is ineffective in TURBO mode.
Press ON/OFF or MODE button can exit the Clean mode, then the
ECO
IFEEL CLEAN
indicator ” ” will disappear.
After the clean process finish, the air conditioner will return to Cooling or Dry as preset,
PRESS
while the indicator” ” on remote controller will display for about 10 mins.
7
Safety instructions
16. The batteries in remote controller must be recycled or disposed of properly. Disposal of Scrap
1. To guarantee the unit work normally, please read the manual carefully before installation, and try to install strictly according to this manual. 2. Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner. 3. Properly ground the air conditioner into the earth. 4. Check the connecting cables and pipes carefully, make sure they are correct and firm before connecting the power of the air conditioner. 5. There must be an air-break switch. 6. After installing, the consumer must operate the air conditioner correctly according to this manual, keep a suitable storage for maintenance and moving of the air conditioner in the future. 7. Fuse of indoor unit:T3.15A 250VAC or T5A 250VAC. Please refer to the screen printing on the circuit board for the actual parameters, which must be consistent with the parameters on the screen printing. 8. For 5K~13K models, fuse of outdoor unit:T15A 250VAC or T 20A 250VAC. Please refer to the screen printing on the circuit board for the actual parameters, which must beconsistent with the parameters on the screen printing 9. For 14K~18K models, fuse of outdoor unit: T 20A 250VAC. 10. For 21K~36K models, fuse of outdoor unit: T 30A 250VAC.
Batteries — Please discard the batteries as sorted municipal waste at the accessible collection point. 17. If the appliance is fixed wiring, the appliance must be fitted with means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection under over voltage category III conditions, and these means must be incorporated in the fixed wiring in accordance with the wiring rules. 18. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. 19.The appliance shall be installed in accordance with national wiring regulations. 20. Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. 21. The appliance shall not be installed in the laundry 22.Regarding to installation, please refer to section “Installation instructions”. 23. Regarding to maintenance, please refer to section “Maintenance”. 24. For models using R32 refrigerant, piping connection should be conducted on outdoor side.
11. The installation instructions for appliances that are Preparation before
use
intended to be permanently connected to fixed wiring,
and have a leakage current that may exceed 10 mA, shall state that the installation of a residual current
Note
device (RCD) having a rated residual operating current not exceeding 30 mA is advisable
1. When charging refrigerant into the system, make sure to charge in liquid state,if therefrigerant of the
12. Warning: Risk of electric shock can cause injury or appliance is R32.Otherwise, chemical composition
death: Disconnect all remote electric power supplies of refrigerant (R32) inside the system may change
before servicing.
and thus affect performance of the air conditioner
13. The maximum length of the connecting pipe
2. According to the character of refrigerant (R32,the
between the indoor unit and outdoor unit should be less than 5 meters. It will affect the efficiency of the
value of GWP is 675), the pressure of the tube is very high, so be sure to be careful when you install
air conditioner if the distance longer than that length and repair the appliance.
14. This appliance is not intended for use by person 3. If the supply cord is damaged, it must be replaced (including children) with reduced physical, sensory or by the manufacturer, its service agent or similarly
mental capabilities, or lack of experience and
qualified persons in order to avoid a hazard.
knowledge, unless they have been given supervision 4. Installation of this product must be done by
or instruction concerning use of the appliance by a
experienced service technicians professional
person responsible for their safety.Children should be installers only in accordance with this manual.
supervised to ensure that they do not play with the appliance.Cleaning and user maintenance shall not
5. The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the
be made by childrenwithout supervision
copper tube.
15. This appliance can be used by children aged from 8 years and above and personswith reduced physical,
Preset
sensory or mental capabilities or lack of experience
Before using the air conditioner, be sure to check
and knowledge if they have been given supervision or and preset the following.
instruction concerning use of the appliance in a safe 1.Remote Control presetting
way and understand the hazards involved. Children Each time after the remote control is replaced with
shall not play with the appliance. Cleaning and user new batteries or is energized, remote control auto
maintenance shall not be made by children without
presettingheat pump.If the air conditioner you
supervision.
purchased is a Cooling Only one, heat pump remote
controller can also be used.
8
2. Back-light function of Remote Control(optional)
Hold down any button on remote control to activate
ON
the back light. It automatically shuts off 10 seconds
OFF
later. Note: Back-light is an optional function. 3. Auto Restart Presetting
The air conditioner has an Auto-Restart function.
Safeguarding the environment
Do not use the power
supply circuit breaker or pull off the plug to turn it off during operation. This may cause a fire due to
Do not touch the operation buttons when your hands are wet.
spark, etc. ON OFF
Do not put any objects on the outdoor unit.
This appliance is made of recyclable or re-usable material. Scrapping must be carried out in
SMART
TEMP.
MODE
SUPER
TEMP.
FAN SPEED
FEEL
SLEEP
CLOCK
TIMER ON
TIMER OFF
QUIET
DIMMER
ECONOMY
compliance with local waste disposal regulations. Before scrapping it, make sure to cut off the mains cord so that the appliance cannot be re-used. For more detailed information on handling and recycling this product, contact your local authorities who deal with the separate collection of rubbish or the shop where you bought the
It is the user’s responsibility to make the appliance be grounded according to local codes or ordinances by a licenced
Turn off the
Do not knit, pull or
applianceby remote press the power supply
control firstly before cord, lest the power
cutting off power supply cord be broken.
supply if malfunction An electric shock or fire
occurs.
is probably caused by
technician.
a broken power supply
cord.
appliance. SCRAPPING OF APPLIANCE
Safety precautions
This appliance is marked according
to the European Directive 2012/19/EC,
Precautions for using R32 refrigerant
Waste Electrical and Electronic Equipment (WEEE). This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal,recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.
The basic installation work procedures are the same as the conventional
refrigerant(R22 or R410A). However, pay attention to the following points:
1.Transport of equipment containing flammable refrigerants
Compliance with the transport regulations 2.Marking of equipment using signs
Compliance with local regulations 3.Disposal of equipment using flammable
refrigerants
Compliance with national regulations 4.Storage of equipment/appliances
The storage of equipment should be in
Safety precautions
accordance with the manufacturer’s instructions.
Symbols in this Use and Care Manual are
interpreted as shown below.
Be sure not to do.
Grounding is essential.
Pay attention to such a situation.
5.Storage of packed (unsold) equipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge.
Warning: Incorrect handling could cause a
The maximum number of pieces of equipment
serious hazard, such as death, serious injury, etc. permitted to be stored together will be
determined by local regulations.
Use correct power
supply inaccordance
with the rating plate
requirement. Otherwise, serious faults or hazard may occur or a fire maybe break out.
It is harmful to your health if the cool air reaches you for a long time. It is advisable to let the air flow be
Never insert a stick or similar obstacle to the unit. Since the fan rotates at high speed,
6.Information on servicing 6-1 Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For
repair to the refrigerating
ON OFF
Keep the power supply circuit
deflected to all the this may cause an injury. room.
system, the following precautions shall be complied with prior to conducting work on the system.
breaker or plug from
dirt. Connect the
power supply cord to
Do not repair the
it firmly and correctly,
appliance by yourself.
lest an electric shock Prevent the air flow If this is done
or a fire break out from reachingthe gas incorrectly, it may cause
due to insufficient burners and stove. an electric shock, etc.
6-2 Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of flammable gas or vapour being present while the work is being performed.
contact.
9
6-3 General work area All maintenance staff and others working in the local
area shall be instructed on the nature of work being carried out. Work in
confined spaces shall be avoided. The area around the workspace shall be
sectioned off. Ensure that the conditions within the area have been made safe
by control of flammable material.
6-4 Checking for presence of refrigerant The area shall be checked with an
appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. Ensure that the leak
detection equipment being used is suitable for use with flammable
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
6-5 Presence of fire extinguisher If any hot work is to be conducted on the
refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
6-6 No ignition sources No person carrying out work in relation to a
refrigeration system which involves exposing any pipe work that contains or
has contained flammable refrigerant shall use any sources of ignition in such
a manner that it may lead to the risk of fire or explosion All possible
ignition sources, including cigarette smoking, should be kept sufficiently far
away from the site of installation, repairing, removing and disposal, during
which flammable refrigerant can possibly be released to the surrounding space.
Prior to work taking place, the area around the equipment is to be surveyed to
make sure that there are no flammable hazards or ignition risks. “No Smoking”
signs shall be displayed.
6-7 Ventilated area Ensure that the area is in the open or that it is
adequately ventilated before breaking into the system or conducting any hot
work. A degree of ventilation shall continue during the period that the work
is carried out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere
6-8 Checks to the refrigeration equipment Where electrical components are
being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer’s maintenance and service
guidelines shall be followed. If in doubt consult the manufacturer’s technical
department for assistance.
The following checks shall be applied to installations using flammable
refrigerants:
The charge size is in accordance with the room size within which the
refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not
obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit
shall be checked for the presence of refrigerant;
Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
6-9 Checks to electrical devices Repair and maintenance to electrical
components shall include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety, then no electrical
supply shall be connected to the circuit until it is satisfactorily dealt
with. If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used. This shall
be reported to the owner of the equipment so all parties are advised. Initial
safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking;
That there no live electrical components and wiring are exposed while
charging, recovering or purging the system;
That there is continuity of earth bonding 7. Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc. If it is absolutely necessary to have an electrical supply
to equipment during servicing, then a permanently operating form of leak
detection shall be located at the most critical point to warn of a potentially
hazardous situation. Particular attention shall be paid to the following to
ensure that by working on electrical components, the casing is not altered in
such a way that the level of protection is affected.
10
This shall include damage to cables,
Leak detection fluids are suitable for use with
excessive number of connections, terminals
most refrigerants but the use of detergents
not made to original specification, damage to
containing chlorine shall be avoided as the
seals, incorrect fitting of glands, etc.
chlorine may react with the refrigerant and
Ensure that apparatus is mounted securely.
corrode the copper pipe-work.
Ensure that seals or sealing materials have not If a leak is suspected, all naked flames shall
degraded such that they no longer serve the
be removed/ extinguished.
purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications. NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do
If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the system remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both
before and
not have to be isolated prior to working on them.
during the brazing process.
8.Repair to intrinsically safe components Do not apply any permanent inductive or
12.Removal and evacuation When breaking into the refrigerant circuit to
capacitance loads to the circuit without
make repairs or for any other purpose
ensuring that this will not exceed the permissible voltage and current permitted for
conventional procedures shall be used. However, it is important that best practice is
the equipment in use.
followed since flammability is a consideration.
Intrinsically safe components are the only
The following procedure shall be adhered to:
types that can be worked on while live in the
Remove refrigerant;
presence of a flammable atmosphere. The test Purge the circuit with inert gas;
apparatus shall be at the correct rating.
Evacuate;
Replace components only with parts specified
Purge again with inert gas;
by the manufacturer. Other parts may result in the ignition of refrigerant in
the atmosphere from a leak. 9.Cabling Check that cabling will not be subject
to wear, corrosion, excessive pressure, vibration, sharp edges or any other
adverse environmental effects. The check shall also take into account the
effects of aging or continual vibration from sources such as compressors or
fans 10.Detection of flammable refrigerants Under no circumstances shall
potential sources of ignition be used in the searching for or detection of
refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used 11.Leak detection methods The following leak detection
methods are deemed acceptable for systems containing flammable refrigerants:
Electronic leak detectors shall be used to
Open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe- work are to take place. Ensure that the outlet for the vacuum pump is
detect flammable refrigerants, but the sensitivity may not be adequate, or may need
not close to any ignition sources and there is ventilation available.
re-calibration. (Detection equipment shall be 13.Charging procedures
calibrated in a refrigerant-free area.)
In addition to conventional charging
Ensure that the detector is not a potential
procedures, the following requirements shall
source of ignition and is suitable for the
be followed:
refrigerant used.
Ensure that contamination of different
Leak detection equipment shall be set at a
refrigerants does not occur when using
percentage of the LFL of the refrigerant and
charging equipment.
shall be calibrated to the refrigerant employed Hoses or lines shall be as short as possible to
and the appropriate percentage of gas (25 % maximum) is confirmed.
11
minimise the amount of refrigerant contained in them.
Cylinders shall be kept upright.
15.Labelling
Ensure that the refrigeration system is earthed Equipment shall be labelled stating that it has
prior to charging the system with refrigerant.
been de-commissioned and emptied of
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system.
refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contain flammable refrigerant.
Prior to recharging the system it shall be
16.Recovery
pressure tested with OFN. The system shall be leak tested on completion
When removing refrigerant from a system, either for servicing or decommissioning, it is
of charging but prior to commissioning.
recommended good practice that all
A follow up leak test shall be carried out prior to leaving the site.
refrigerants are removed safely. When transferring refrigerant into cylinders,
14.Decommissioning
ensure that only appropriate refrigerant
Before carrying out this procedure, it is essential that the technician is completely
recovery cylinders are employed. Ensure that the correct number of cylinders
familiar with the equipment and all its detail.
for holding the total system charge is available
It is recommended good practice that all refrigerants are recovered safely.
All cylinders to be used are designated for the recovered refrigerant and labelled for that
Prior to the task being carried out, an oil and
refrigerant (i.e. special cylinders for the
refrigerant sample shall be taken in case analysis is required prior to re-use of
recovery of refrigerant). Cylinders shall be complete with pressure
reclaimed refrigerant. It is essential that
relief valve and associated shut-off valves in
electrical power is available before the task is commenced.
good working order. Empty recovery cylinders are evacuated and,
a) Become familiar with the equipment and its
if possible, cooled before recovery occurs.
operation. b) Isolate system electrically.
The recovery equipment shall be in good working order with a set of instructions
c) Before attempting the procedure ensure
concerning the equipment that is at hand and
that:
shall be suitable for the recovery of
Mechanical handling equipment is available, flammable refrigerants.
if required, for handling refrigerant cylinders; In addition, a set of calibrated weighing scales
All personal protective equipment is available shall be available and in good working order.
and being used correctly;
Hoses shall be complete with leak-free
The recovery process is supervised at all
disconnect couplings and in good condition.
times by a competent person;
Before using the recovery machine, check
Recovery equipment and cylinders conform to the appropriate standards. d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with manufacturer’s instructions. h) Do not overfill cylinders. (No more than 80 % volume liquid charge). I ) Do not exceed the maximum working pressure of the cylinder, even temporarily. j ) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are
that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers.
closed off.
k) Recovered refrigerant shall not be charged
into another refrigeration system unless it
has been cleaned and checked.
12
Only electric heating to the compressor body
Mechanical connectors used indoors shall
shall be employed to accelerate this process.
comply with ISO 14903. When mechanical
When oil is drained from a system, it shall be
connectors are reused indoors, sealing parts
carried out safely.
shall be renewed. When flared joints are
When moving or relocating the air conditioner,
reused indoors, the flare part shall be
consult experienced service technicians for
re-fabricated.
disconnection and reinstallation of the unit
The installation of pipe-work shall be kept to
Do not place any other electrical products or
a minimum.
household belongings under indoor unit or
Mechanical connections shall be accessible
outdoor unit. Condensation dripping from the
for maintenance purposes.
unit might get them wet, and may cause
Explanation of symbols displayed on the indoor
damage or malfunction of your property.
unit or outdoor unit.
Do not use means to accelerate the defrosting
process or to clean, other than those recommended by the manufacturer.
The appliance shall be stored in a room
without continuously operating ignition
sources(for example, open flames, an
operating gas appliance or an operating electric heater). Do not pierce or
burn.
Be aware that refrigerants may not contain an odor.
This symbol shows that this appliance uses
WA R N I N G
[symbol ISO 7010-W021
a If
flammable refrigerant. the refrigerant is leaked
and
exposed
to
(2011-05)] an external ignition source, there is a risk
Caution, risk of fire
of fire
WA R N I N G
Waring;low burning velocity material
A2L symbol
This symbol shows that this appliance uses a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire
[symbol ISO This symbol shows that the operation 7000-0790 manual should be
read carefully.
CAUTION (2004-01)]
This symbol shows that a service [symbol ISO personnel should be handling this CAUTION 7000-1659 equipment with reference to the (2004-01)] installation manual.
To keep ventilation openings clear of obstruction. The appliance shall be stored in a
CAUTION
[symbol ISO 1641-0790
This symbol shows that information is available such as the operating manual
or
(2004-01)] installation manual.
Installation instructions well-ventilated area where the room size
corresponds to the room area as specified for
operation. The appliance shall be stored in a room
Installation diagram
without continuously operating open flames (for example an operating gas appliance) and ignition sources (for example
Distance from wall should be over 50mm
Distance from ceiling should be over 200 mm
an operating electric heater).
Any person who is involved with working on or
breaking into a refrigerant circuit should hold
a current valid certificate from an industryaccredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an
Distance from the obstacle should be over 3000mm.
Distance from floor should be over 2500mm.
Distance from the wall should be over 50mm
industry recognised assessment specification. Servicing shall only be performed as
Distance from the obstacle should be
recommended by the equipment manufacturer.
over 500mm.
Maintenance and repair requiring the
assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. Do not use means to accelerate the defrosting
Air intake distance from the wall should be over 250mm
Air intake distance from the wal should be over 250mml
process or to clean, other than those
recommended by the manufacturer. Appliance shall be installed, operated and stored in a room with a floor arealarger than 10 m2. The installation of pipe- work shall be kept to a a room with a floor area largerthan 10 m2.
shaoiruoldutbleet odvisetra5n0ce0mfrmom the wall
over 250mm
The pipe-work shall be complianced with national gas regulations. The maximum refrigerant charge amount is
Above figure is only a simple presentation of the unit, it may not match the external appearance of the unit you purchased.
2.5 kg.The specific refrigerant charge is
Installation must be performed in accordance with
based on the nameplate of the outdoor unit
the national wiring standards by authorized personnel only.
13
Select the installation locations
Indoor unit installation
Location for Installing Indoor Unit
Where
there
is
no
obstacle
near Indoor
unit Pipe
length
the air outlet andair can be easily blown to every corner.
is 15 meters Max.
Height should be less than 5m
2. Where piping and wall hole can be easily arranged. 3. Keep the required space from
the unit to the ceiling and wall
according to the installation diagram on previous page.
4. Where the air filter can be easily removed.
Outdoor unit
5. Keep the unit and remote controller 1m or more
apart from television, radio etc.
6. Keep as far as possible from fluorescent lamps.
7. Do not put anything near the air inlet to obstruct it from air absorption. 8. Install on a wall that is strong enough to bear the
weight of the unit. 9. Install in a place that will not increase operation noise and vibration.
10. Keep away from direct sunlight and heating
sources. Do not place flammable materials or combustion apparatuses on top of the unit.
Location for Installing Outdoor Unit
1. Installing the Mounting Plate Decide an installing location for the mounting plate according to the indoor unit location and pipe direction. Keep the mounting plate horizontally with a horizontal ruler or level. Drill holes of 32mm in depth on the wall for fixing the plate. Insert the plastic plugs to the hole, fix the mounting plate with tapping screws. Inspect if the mounting plate is well fixed. Then drill a hole for pipe.
Tapping screw
Mounting plate
Note: The shape of your mounting plate may be different from the one above,
but the installation method is similar.
Note: As the above figure shown, the six holes matched with tapping screw on
the mounting plate must be used to fix the mounting plate, the others are
prepared.
Height should be less than 5m
Indoor Outdoor
1. Where it is convenient to install and well ventilated.
2. Avoid installing it where flammable gas Outdoor unit could leak.
3. Keep the required distance apart from the wall.
Pipe length is 15 meters Max.
The pipe length between indoor and
2. Drill a Hole for Pipe
Decide the position of hole for pipe according to the location of mounting
plate. Drill a hole on the wall about 50mm. The hole
Wall hole sleeve ( hard polythene tube
prepared by user)
5mm (tilt downward)
outdoor unit should be not more than
should tilt a littledownward toward outside.
5 meters in factory default status, but it can go up to maximum 15 meters with
Install a sleeve through the wall hole to keep the wall tidy and clean.
additional refrigerant charge.
3. Indoor Unit Pipe Installation
6. Keep the outdoor unit away
Put the pipes (liquid and gas pipe) and cables
from greasy dirt, vulcanization
through the wall hole from outside or put them
gas exit.
7. Avoid installing it by the
Indoor unit
roadside where there is a risk
of muddy water.
8. A fixed base where it is not subject to increased
operation noise.
through from inside after indoor pipe and cables connection complete so as to connect to outdoor unit. Decide whether saw the unloading piece off in accordance with the pipe direction.(as shown below) Pipe direction
9. Where there is not any blockage of the air outlet.
Trough
10. Avoid installing under direct sunlight, in an aisle
Knock-down panel
4
or sideway, or near heat sources and ventilation fans.
1
3
Keep away from flammable materials, thick oil fog,
and wet or uneven places.
Model
Max. allowed pipe
Limit of pipe Limit of Elevation Required amount of
length without additional length (m) Difference H (m) additional refrigerant
refrigerant (m)
(g/m)
5K~18K
5
15
5
20
21K~25K
5
15
5
30
28K~36K
5
15
5
40
If the height or pipe length is out of the scope of the
table, please consult the dealer.
Cut off the Knock-down panel
2
along the trough using needle
Note: When installing the pipe at the directions 1,2 or 4, saw
nose pliers or other suitable the corresponding unloading
tool.
piece off the indoor unit base.
After connecting pipe as required, install the drain
hose. Then connect the power cords. After
connecting, wrap the pipes, cords and drain hose
together with thermal insulation materials.
14
Pipe Joints Thermal Insulation: Wrap the pipes joints with thermal insulation materials and then wrap with a vinyl tape.
wrapped with vinyl type
Thermal insulation
Pipes Thermal Insulation:
a. Place the drain hose under the pipes. b. Insulation material uses polythene Thermal insulation tube Notfeo:aDmraionvheors6emismpreinpathreidckbnyeussse.r.(juPsotwaesrcLchaoerrgdmeaptiicp)e
Drain pipe should point downward
for easy drain flow. Do not arrange
the drain pipe twisted, sticking out
or wave around, do not immerse
Small
the end of it in water.
Drain hose
pipe
(prepared by user)
If an extension drain hose is connected to the drain
pipe, make sure to thermal insulated when passing
along the indoor unit.
When the pipes is directed to the right, pipes, power Cord and drain pipe should be thermal insulated and fixed onto the back of the unit with a pipe fixer.
Insert here
large pipe
drain small hose pipe
large pipe
drain small hose pipe
Base
Pipe fixer Base
Pipe fixer Base
Hook here
A. Insert the pipe fixer to the slot. B. Press to hook the pipe fixer onto the base.
Piping Connection:
a.Before unscrewing the big and the small sealing caps, press the small
sealing cap with the finger until the exhaust noise stops, and then loosen the
finger.
b.Connect indoor unit pipes with two wrenches. Pay special attention to the
allowed torque as shown below to prevent the pipes, connectorsand flare nuts
from being deformed and damaged.
c. Pre-tighten them with fingers at first, then use the wrenches.
For ON-OFF appliance
Model
5~12K,13~18K,21~24K
Pipe size Liquid Side (6mm or 1/4 inch)
Torque Nut width Min.thickness
15~20N·m 17mm
0.5mm
18K#,22,24K#,28,30,36K 5~10K,12K 12K#,14,15,18K 18K#,22,24,28,30,36K 36K#
Liquid Side (9.53mm or 3/8 inch) 30~35N·m Gas Side (9.53mm or 3/8 inch) 30~35N·m Gas Side (12mm or 1/2 inch) 50~55N·m Gas Side (16mm or 5/8 inch) 60~65N·m Gas Side (19mm or 3/4 inch) 70~75N·m
22mm 22mm 24mm 27mm 32mm
0.6mm 0.6mm 0.6mm 0.6mm 1.0mm
Note: The unit of 12K#,18K#,24K#,36K# is bigger than the unit of 12K,18K,24K,36K.
4. Connecting of the Cable
Indoor Unit
Connect the power cord to the indoor unit by connecting the wires to the
terminals on the control board individuallyin accordance with the outdoor unit
connection.
Note: For some models, it is necessary to remove the cabinet to connect to the
indoor unit terminal.
Outdoor Unit
- Remove the access door from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as follows.
- Secure the power cord onto the control board w. ith cable clamp.
- Reinstall the access door to the original position with the screw.
- Use a recognized circuit breaker for 24K model between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.
Front panel Terminal (inside)
Indoor unit
Cabinet Chassis
Access door Terminal(inside)
If you don’t hear the exhaust noise, please contact with the merchant.
Outdoor unit
The figures in this manual are based on the external
For Inverter appliance
Model
Pipe size
Torque Nut width Min.thickness
view of a standard model. Consequently, the shape may differ from that of the air conditioner you have
5k~12K,13k~18K,21~24K Liquid Side (6mm or 1/4 inch) 15~20N·m 17mm
0.5mm
selected.
18K#, 21K~36K 5K~13K 12K#, 13K~18K 18K#, 21K~36K 36K#
Liquid Side (9.53mm or 3/8 inch) 30~35N·m Gas Side (9.53mm or 3/8 inch) 30~35N·m Gas Side (12mm or 1/2 inch) 50~55N·m Gas Side (16mm or 5/8 inch) 60~65N·m Gas Side (19mm or 3/4 inch) 70~75N·m
22mm 22mm 24mm 27mm 32mm
0.6mm 0.6mm 0.6mm 0.6mm 1.0mm
Note: The unit of 12K#,18K# and 36K# is bigger than the unit of 12K,
Caution:
1. Never fail to have an individual power circuit specifically for the air
conditioner. As for the method of wiring, refer to the circuit diagram posted
on the inside of the access door. 2. Comfirm that the cable thickness is as
specified in the power source specification.
18K and 36K.
3. Check the wires and make sure that they are all tightly
fastened after cable connection.
Note: Piping connection should be conducted on outdoor 4. Be sure to install an earth leakage circuit breaker in wet or
side !
15 moist areas.
Cable Specifications for Inverter appliance
Capacity (Btu/h) 5K~13K 5K~13K 14K~18K 14K~18K
21K~36K 21K~30K 21K~24K
Power cord
Type
Normal cross – sectional area
Power connecting cord
Type
Normal cross – sectional area
H07RN-F H07RN-F H05VV-F IS:694
0.75~1.5mm2X3 0.75~1.5mm2X3 0.75~1.5mm2X3 0.75~1.5mm2X3
H05RN-F H07RN-F H07RN-F IS:9968
0.75mm2X4 0.75~1.5mm2X5 0.75~1.5mm2X4 0.75~1.5mm2X4
H07RN-F 1.5mm2X3
H07RN-F 1.5mm2X3 H05VV-F 1.5/2.5mm2X3
H05RN-F H07RN-F H07RN-F
0.75mm2X4
1.5mm2X5 1.5/2.5mm2X4
IS:694 1.5/2.5mm2X3 IS:9968 1.5/2.5mm2X4
H07RN-F 2.5mm2X3
H05RN-F 0.75mm2X4
H07RN-F H07RN-F H05VV-F
2.5mm2X3 2.5mm2X3 2.5mm2X3
H07RN-F H07RN-F H07RN-F
1.0mm2X4 2.5mm2X5 2.5mm2X4
IS:694
2.5mm2X3
IS:9968
2.5mm2X4
H05VV-F 1.5mm2X3
H07RN-F 1.5mm2X4
NOTE: 1.K* means the power supply of this model comes from indoor unit. 2.K*
indicates indoor power supply unit model with power line and
plug. 3.For 14K~18K* models under Tropical(T3) Climate condition, the
normal cross-sectionl area of Power cord and Power connecting cord is
2.5mm2×4. Attention:
The plug must be accessible even after the installation of the appliance in
case there is a need to disconnect it. If not possible, connect appliance to a
double-pole switching device with contact separation of at least 3 mm placed
in an accessible position even after installation.
Cable Specifications for ON-OFF appliance
Capacity (Btu/h)
5K~13K 14K~24K 18K~30K
18K~30K 24K~36K 24K~36K
Power cord
Type
Normal cross – sectional area
Power connecting cord
Type
Normal cross – sectional area
Power connecting cord1
Type
Normal cross – sectional area
Main power supply
H05VV-F
0.75~1.5mm2X3
H07RN-F H05RN-F
1.5mm2X3 0.75~1.0mm2X3
H05RN-F
0.75mm2X2 (Heat-pump)
To indoor
H05VV-F 1.5~2.5mm2X3 H07RN-F
1.5~2.5mm2X3
H05RN-F
0.75mm2X2 (Heat-pump)
To indoor
H05VV-F
H07RN-F H07RN-F H07RN-F
1.5~2.5mm2X3
2.5mm2X3 2.5~4.0mm2X3
1.5mm2X5
H07RN-F
H05RN-F H07RN-F H05RN-F H07RN-F
H05RN-F
1.5~2.5mm2X4 H05RN-F
1.0mm2X3 1.0mm2X4Cooling only H05RN-F
0.75mm2X4 H05RN-F 1.0mm2X4 0.75mm2X4 H05RN-F
0.75mm2X2 To indoor (Heat-pump&Optional)
0.75mm2X3 (Heat-pump)
To outdoor
0.75mm2X2 (Heat-pump&Optional) To outdoor
0.75mm2X2 (Heat-pump)
To outdoor
NOTE:
The cord may be different from the list above. It may be used as the next
list. And it can be larger.0-6A, use 0.75mm 2 or 18AWG. 0-10A, use 1mm2 or
16AWG. 0-16A, use 1.5mm 2 or 14AWG 0-20A, use 2.5mm2 or 14AWG. 0-25A, use
2.5mm 2or 12AWG. 0-32A, use 4mm 2
Wiring diagram
Outdoor unit installation
1. Install Drain Port and Drain Hose (for heat-pump
model only)
The condensate drains
Rubber pad (optional) Place under the leg pedestal
from the outdoor unit when
the unit operates in heating
mode. In order not to
disturb your neighbor and
Washer
protect the environment, install
Drain port Drain hose
a drain port and a drain hose to direct (prepared by user)
the condensate water. Just install the drain port and
rubber washer to the chassis of the outdoor unit,
then connect a drain hose to the port as the right
figure demonstrates.
2. Install and Fix Outdoor Unit Fix with bolts and nuts tightly on a flat and
strong floor. If installed on the wall or roof, make sure to fix the supporter
well to prevent it from shaking due to serious vibration or strong wind. 3.
Outdoor Unit Piping Connection
Remove the valve caps from the 2-way and 3-way valve. Connect the pipes to the
2-way and 3-way valves separately according to the required torque.
4. Outdoor Unit Cable Connection (see previous page)
Air purging
The air which contains moisture remaining in the refrigeration cycle may cause
a malfunction on the compressor. After connecting the indoor and outdoor
units, release air and moisture from the refrigerant cycle using a vacuum
pump, as shown below.
Note: To protect the environment, be sure not to discharge the refrigerant to
the air directly.
Warning: Before obtaining access to terminals, all supply circuits must be disconnected. Make sure that the color of the wires in the outdoor unit and terminal No. are the same as those of the indoor unit, the details please refer to the wiring diagram which is near the terminal inside the unit.
Vacuum pump
indoor unit
Refrigerant flow direction
2-way valve
3-way valve diagram
3-way valve
connect to indoor unit
(6) Open 1/4 turn
Service port
(2) Turn (8) Tighten
(7) Turn to fully open the valve
(1) Turn
(7) Turn to fully open the valve valve cap
(1) Turn (8) Tighten
Valve cap
(8) Tighten
Connect to outdoor unit
open position spindle
needle
Valve core
service port cap
16
How to Purge Air Tubes:
(1) Unscrew and remove caps from 2 and 3-way valves. (2) Unscrew and remove
cap from service valve. (3) Connect vacuum pump flexible hose to the service
valve. (4) Start vacuum pump for 10-15 minutes until reaching a vacuum of
100Pa absolutes. (5) With vacuum pump still running close the low .pressure
knob on vacuum pump manifold. Then stop the vacuum pump. (6) Open 2-way valve
,1/4 turn, then close it after 10 seconds. Check tightness of all joints using
liquid soap or an electronic leak detector (7) Turn 2 and 3-way valves stem to
fully open the valves. Disconnect the flexible vacuum pump hose. (8) Replace
and tighten all valve caps.
Maintenance
Front panel maintenance
Cut off the power supply
a
Turn off the appliance first before disconnecting from power supply.
Grasp position “a”
and pull outward to
remove the front panel.
a
Wipe with a soft and dry cloth.
Use soft moisture cloth to clean if the front panel is very dirty;
Never use volatile
Use a dry and substance such as gasoline soft cloth to or polishing powder to
clean
clean it. the appliance.
Protection
Operating condition
Operating temperature for Inverter appliance
Temperature Cooling operation Heating operation Drying operation
Indoor max temperature min
32 21
27 7
32 18
Outdoor max temperature min
note note
24 -15
43 21
NOTE: Optimum performance will be achieved within these operating temperature. If air conditioner is used outside of the above conditions, the protective device may trip and stop the appliance. Normally,the outdoor max temperature is 43,but some models will be achieved 46,48,or 50.For Tropical (T3) Climate condition models, the outdoor max temperature is 55 .
For some models, can keep cooling at -15 outdoor ambient via unique design. Normally, optimum cooling performance will be achieved above 21 . Please consult the merchant to get more information.
For some models, can keep heating at -15 outdoor
ambient , some models heat at -20 outdoor ambient, even heat at lower outdoor
ambient The temperature of some products is allowed beyond the range. In
specific situation, please consult the merchant.
When relative humidity is above 80%, if the air conditioner runs in COOLING or
DRY mode with door or window
opened for a long time, dew may drip down from the outlet.
Operating temperature for ON-OFF appliance
The protective device maybe trip and stop the appliance in the cases listed
below
Never sprinkle water onto the indoor unit
Reinstall and shut the
front panel.
Reinstall and shut the front panel by
pressing position “b” downward.
b
b
Dangerous! Electric shock!
Air filter maintenance
Stop the appliance, cut off
Clean and reinstall the
the power supply and remove air filter.
the air filter.
If the dirt is conspicuous, wash it with a solution of
detergent in lukewarm
water.After cleaning,
dry well in shade.
1
23
1.Open the front panel. 2.Press the handle of the filter gently from the
front. 3.Grasp the handle and slide out the filter.
Close the front panel again It is necessary to clean the air filter
after using it for about 100 hours.
Clean the air filter every two weeks if the air conditioner operates in an
extremely dusty environment.
Outdoor air temperature is over 24oC HEATING Outdoor air temperature is below
-7oC
Room temperature is over 27oC
note COOLING
Room temperature is below 21oC DRY Room temperature is below 18oC
NOTE: Normally,the outdoor max temperature is 43,but some models will be
achieved 46,48,or 50.For Tropical (T3) Climate condition models, the outdoor
max temperature is 55 . The temperature of some products is allowed beyond the
range. In specific situation, please consult the merchant. If the air
conditioner runs in COOLING or DRY mode withdoor or window opened for a long
time when relative humidity is above 80%,dew may drip down from the outlet.
Noise pollution
Install the air conditioner at a place that can bear its weight in order to
operate more quietly. Install the outdoor unit at a place where the air
discharged and the operation noise would not annoy your neighbors. Do not
place any obstacles in front of the air outlet of the outdoor unit lest it
increases the noise level.
17
Features of protector
1. The protective device will work at following cases. Restarting the unit at
once after operation stops or changing mode during operation, you need to wait
for 3 minutes. Connect to power supply and turn on the unit at once, it may
start 20 seconds later.
2. If all operation has stopped, press ON/OFF button again to restart, Timer
should be set again if it has been canceled.
Features of HEATING mode
Preheat
At the beginning of the HEATING operation, the airflow from the indoor unit is
discharged 2-5 minutes later.
Defrost
In HEATING operation the appliance will defrost (de-ice) automatically to
raise efficiency. This procedure usually lasts 2-10 minutes. During
defrosting, fans stop operation. After defrosting completes, it returns to
HEATING mode automatically. Note: Heating is NOT available for cooling only
air conditioner models.
Troubleshooting
The following cases may not always be a malfunction, please check it before asking for service.
Trouble
Does not run
No cooling or heating air
Analysis
1. If the protector trip or fuse is blown. 2. Please wait for 3 minutes and
start again, protector device may be preventing unit to work. 3. If batteries
in the remote controller exhausted. 4. If the plug is not properly plugged.
1. Is the air filter dirty 2. Are the intakes and outlets of the air
conditioner blocked 3. Is the temperature set properly
Ineffective control
Does not operate immediately
If strong interference(from excessive static electricity discharge, power
supply voltage abnormality)presents, operation will be abnormal. At this time,
disconnect from the power supply and connect back 2-3 seconds later.
Changing mode during operation, 3 minutes will delay.
Trouble
Analysis
A sound of flowing water Caused by the flow of refrigerant in the
air conditioner, not a trouble.
Defrosting sound in heating mode.
Cracking sound is heard The sound may be generated by the expansion or contraction of the front panel due to change of temperature.
Spray mist from the outlet Mist appears when the room air becomes very cold
because of cool air discharged from indoor unit during COOLING or DRY
operation mode.
The compressor indicator The unit is shifting from heating mode (red) lights
on constantly, to defrost.The indicator will lights off and indoor fan stops.
within ten minutes andreturns to
heating mode.
Display introduction
NO
Display
Introduction
1
2
3 4 5 6 7 8 9 10 11 12 13
14 AI
Example:
Temperature indicator Display set temperature. It shows FC after 200 hours of
usage as reminder to clean the filter.After filter cleaning press the filter
reset button located on the indoor unit behind the front panel in order to
reset the display.(optional)
Running indicator It lights up when the AC is running. It flashes during
defrosting.
Timer indicator
It lights up during set time.
Sleep indicator It lights up in sleep mode Compressor indicator It lights up
when the compressor is on
Mode indicator Heating displays orange,others display white
Fan speed indicator
Signal Receptor
Smart WIFI indicator It lights up during WIFI is on
NANOE indicator It lights up in NANOE mode.
FAN ONLY mode indicator It lights up in FAN ONLY mode
Airflow Follow You/Airflow Avoid You indicator Humidity indicator It lights up
in humidity mode. Artificial Intelligence Smart Running Indicator It lights up
in AI mode
1
2 3 45
8
8
1
don’t run
Peculiar odor
This odor may come from another source such as furniture, cigarette etc, which issucked in the unit and blows out with the air.
3
2
4
The symbols may be different from these models, but the functions are similar.
18
Emergency button A
A
Pressing this button can let the AC run or stop.
The symbol may be different from your model, but the button is similar.
19
Specifications in this document are subject to change without notice, in order
that Hitachi-Johnson Controls Air Conditioning, Inc. may bring the latest
innovations to their customers.
Hitachi-Johnson Controls Air Conditioning, Inc.
© 2022 Hitachi- Johnson Controls Air Conditioning, Inc.
2022.05 Version.A Printed in China