**Honeywell MPA2C3 MPA Series Access Control Panel User Guide
**
This guide describes the basic setup, wiring, and configuration steps for getting started with a MPA access control panel.
Setup Process
Step 1. Download the Device Utility App
Step 2. Preparing to Start up
Step 3. Connecting Devices
Step 4. Powering up
Step 5a. Connecting to MAXPRO Cloud
Step 5b. Setup Computer for Web Mode Connection
Step 5c. Connecting to the Panel in Web Mode
Step 5d. Connecting to WIN-PAK
Digital Manuals and manuals in other languages
Honeywell provides this manual in English and other languages on the following
link:
Get Online Documents Here
The same links can be found on the product by scanning this QR code.
Note: UL certificate does not contain model MPA2MPSE/MPA4MPSE.
Download the Device Utility App
Note: Mobile device must have iOS 13 or Android 6 or higher.
Download the application from the App Store, or Play Store. Scan this QR code for the application in the App Store.
Get Device Utility App Here
Scan this QR code for the application in the Play Store.
Get Device Utility App Here
Preparing to Start up
- Check DIP Switches SW1 default status. (Set Bit 3 and Bit 9 to ‘ON’.). For Default IP, set Bit 4 to ON. (see step 5)
- a. Check/Connect the power 10 -19 VDC and battery 12 VDC, 7Ah-12 Ah, OR b. Connect the power POE+.
Note: Do not connect a backup battery when using PoE+.
- Select/Check the host connection IP(Ethernet) Or USB.
- Check the output jumper configuration.(12 VDC/Ext .V; NO/ NC) .
Connecting Devices
- Check host Ethernet (RJ45) or Type-C USB connection.
- Check/Connect the reader connections (OSDP/Wiegand) by RJ45, or MPA2RJ (RJ45 to 8 terminal block converter).
- Check/Connect)the MPA2S5 cable to input/output devices (door status/door contact connection)(Push-in Terminal block or RJ45).
Readers | Conductors | Gauge | Distance |
---|---|---|---|
Wiegand | __ 6-8 | 18 AWG Shield 20 AWG Shield CAT6 CAT6a CAT7 | 350 ft. |
(90m)190 ft.(55m)<120 ft.(35)
OSDP| 4| 24 AWGCAT6 CAT6a CAT7| Single reader 75 ft. (20 m)
Inputs| Twisted pair| 18 AWG Shield 30Ohm| 2000ft.(610m)
Output| Twisted Pair| 18 AWG Shielded| 2000ft.(610m)
Powering up
- Power up the panel (10-19 VDC PSU, or PoE+)
- a. Check Mains LED for PSU (Green ON), or b. Check PoE+ LED for PoE+ (Blue ON).
Note: Battery LED (Red ON) indicates the panel is powered by battery.
- Check Running LED
- Blinking green for 2-door panel.
- Blinking orange for 4-door licensed panel.
- Test credentials and readers (OSDP / Wiegand).
Power Requirements
MPA2 Reader Door Configuration
| Specification| MPA2C3 or MPA2C3-4
---|---|---
Outputs| Number of outputs| 4 SPST Door relays (Jumper- Selectable NO or NC
Contacts) per door rated 3A @30VDC; 4 SPST Aux
relays NO Contacts rated 3A @30VDC (NC selectable in software)
Door Relay Power Source| Selectable:12 VDC(max 750mA per 2 door
outputs) internal power source, or external power source, max 3A @30VDC per
output
Inputs| Number of Inputs| 8(+4) Configurable four-state supervised Input
points (factory Default Settings are: Status, REX, Reader Tamper A, Reader
Tamper B, Power Fail, General Inputs)
Panel Tamper (4X)| Panel Door, Off-Wall, internal back tamper and External
Tamper
Metal cabinet Mains power input| Mains Inputs| 100 to 240 VAC, 1.1A, 50/60Hz
Socket or Hardware AC Inputs (IEC/UL)| MPA2MPSU or MPA4MPSU only
Power Inputs| Control Board Power Inputs| 13.8VDC ~3.3A from Included Power
Supply Note: It is forbidden changing the PSU by user
Power Output (internal panel power)| Power for locks/Strikes/ Reader(s)/
Inputs Devices| 750mA per 2 doors for locks/strikes, 500mA per 2 reader ports
3A @ 12VDC total available power for all devices(internal PSU).
Hard Default Procedure
To hard default the MPA2 series panels to factory default:
Note:
- Note down the existing settings on DIP Switch SW1.
- When the panel is powered up, turn all DIP switches to the OFF position.
- Power down, then power the panel back up.
- Wait for the panel to completely restart. The RUN LED should blink fast.
- Set the DIP switches (SW1) back to their original positions.
- Power down, then power the panel back up.
- The RUN LED should blink at a normal pace.
The panel is now reset to the original factory default values.
Note: When using the DIP switches to reset a panel to the original factory default values, the Event History is lost, and any customized databases are removed; the panel is reset with the original factory default database. This does not affect the Ethernet IP address.
Connecting to MAXPRO Cloud
The MPA2C3, or MPA2C3-4 panel is configured Plug & Play out of the box for MAXPRO Cloud connectivity (DHCP Server Required).
Configuration is not required in local web mode all settings are configured within the MAXPRO Cloud web user interface.
To use this panel on cloud requires a MAXPRO Cloud account.
- Login to your MAXPRO Cloud account at: mymaxprocloud.com
- Create and / or navigate to the Customer Account
- Create and / or navigate to a Site
- Click on ADD CONTROLLER button
- Choose “MPA2”, OR “MPA4”, select “MPA2MPS(U/E)” OR “MPA4MPS(U/E)”
- Type in the panel’s MAC ID, click **ADD CONTROLLER
**
Setup Computer for Web Mode Connection
Use the Device Utility App to set up the panel for Web mode operation.
Note: These steps are for computers with windows 10 operating system, or
higher. The steps for other operating system might be slightly different.
Note: When connecting to USB, USB driver is required. Navigate to the
Technical Support Self- Service/Download Center.
https://myhoneywellbuildingsuniversity.com/training/support/
- Click Start > Control Panel.
- Click Network and Sharing center.
- Click change adapter settings.
- Identify your local Ethernet connection(Local Area Connections) and double-click on the link.
- Click Properties.
- Highlight the Internet Protocol (TCP/IPv4).
- Click properties. View your system current IP address.
- Use the following IP address.
- Enter: 192.168.1.10* in the IP address field when connecting to Eth1/PoE+ – HOST .
- Enter: 192.168.2.10* in the IP address field when connecting to USB 2 – WEB MODE.
- Enter: 255.255.255.0 In the Subnet Mask field.
- Click OK; OK;Close.
Note: *IP address 192.168.1.10 only valid if default panel address is in use.
Connecting to the Panel in Web Mode
-
Launch the Google Chrome™ Browser.
-
Enter the panel’s IP address in the address box.
Connection Type:- Eth 1 / PoE+- HOST: Default IP DIP Switch SW1, Bit 4 (ON) https://192.168.1.150
- USB 2 – WEB MODE (Fixed): https://192.168.2.150
-
Default Login.
- Username: admin
- Password: admin
-
Navigate to “Host” and select WEB.
-
To set the IP, navigate to Settings tab and configure a static IP Address, Subnet Mask and Default Gateway
Connecting to WIN-PAK
Use the Device Utility App to set up the panel for WIN-PAK operation.
In WIN-PAK.
-
Add panel as MPA-2-R3 or MPA-4-R3 in Device Map.
In the MPA2C3 / MPA2C3-4 Panel. -
For easy connection, Use DIP Switch SW1, Bit 4 (ON) for default IP address.
-
Log into Panel’s Web interface.
-
Click Main Menu Icon.
-
Select Panel Configuration and Host / Loop Communications.
-
If not configured, select WIN-PAK and IP properties and Click Save.
-
Follow the TLS Encryption procedure from WIN-PAK manual.
-
Upload the TLS encryption file to the panel.
-
Switch DIP Switch SW1, Bit4 to OFF position.
Honeywell Omni Smart OSDP Configuration
Set the following in the reader tool.
- Create a template selecting reader type as: HID Reader.
- Profile: Standard profile
- In credentials: Enable all credential type
- Keys: No need to select anything.
- Configure Reader settings:
- BLE Settings: Default settings
- Communication protocol:
- Enable OSDP
- Spec Compliance V1
- Address 1, 2, 3, or 4
- Baud rate: 9600
Add the above to template (using the menu).
- Keypad Settings: Input Format: BCD -4 BIT, facility Code:0, Backlight LED Color: RED (default).
MPA2C3- Two Door OSDP Configuration
Configuration| Types| Reader| Reader/IU (Connector)|
OSDP Reader Address| Wiegand
---|---|---|---|---|---
Door 1| 1 Direction| Reader A| Reader 1 IN| 1| No Hold line required, but can
be connected
2 Direction| Reader B| Reader 1 OUT| 2
Door 2| 1 Direction| Reader A| Reader 2 IN| 1
2 Direction| Reader B| Reader 2 OUT| 2
Note: For OSDP reader addressing, the addressing tool in the panel can be used. Connect the readers one by one and assign the address to the reader.
Required OSDP Reader settings
- AES Encryption: ON (OSDP V2)
- Encryption keys: Default
- Address: 1, 2, 3 or 4
- Baud rate: 9600
Note: For OSDP reader addressing, the addressing tool in the panel can be used. Connect the readers one by one and assign the address to the reader.
MPA2C3-4 Four Door Configuration
Technical Support
Hours of Operation | Monday through Friday, 9:00 am – 7:00 pm EST
USA +1 800 323 4576 # Option 2
Technical Support, Option 2 (Access Control)
EMEA
Hours of Operation | Monday through Friday, 9:00 AM – 6:00 PM CET
Phone Support
EMEA ITALY +390399301301
UK +441344238266
SPAIN +34911238038
FRANCE +33366880142
THE NETHERLANDS +31108080688
E-mail Support
USA https://myhoneywellbuildingsuniversity.com/training/support
EMEA ITALY
hsgittechsupport@honeywell.com
UK
hsguktechsupport@honeywell.com
SPAIN
hsgestechsupport@honeywell.com
FRANCE
hsgfrtechsupport@honeywell.com
THE NETHERLANDS
hsgnltechsupport@honeywell.com
Web Support
Technical Assistance & Schedule Support:
https://buildings.honeywell.com
Mywebtech Customer Support:
https://myhoneywellbuildingsuniversity.com/training/support
Online Training: https://myhoneywellbuildingsuniversity.com
https://buildings.honeywell.com/
Honeywell Building Technologies
715 Peachstreet ST.NE
Atlanta, GA30308
USA
Honeywell Comercial Security
Carlton Park, BUilding 5
King Edward Avenue
Narborough,Leicester
LE193Q United Kingdom
Document 800-26607-02_Rev-A – December 2022 © 2023 Honeywell International. All rights reserved.
References
- Building Automation
- Building Automation
- myhoneywellbuildingsuniversity.com
- Login - Learning Management Portal1
- Login - Learning Management Portal1
- Honeywell Device Utility on the App Store
- Honeywell Device Utility - Apps on Google Play