Borik Plus 1-3KVA Uninterruptible Power Systems Instruction Manual
- May 15, 2024
- Borik Plus
Table of Contents
- Borik Plus 1-3KVA Uninterruptible Power Systems
- Product Information
- Product Usage Instructions
- Important Safety Warning
Borik Plus 1-3KVA Uninterruptible Power Systems
Product Information
Specifications
- Product: Uninterruptible Power Systems
- Capacity: 1-3KVA
- Model Number: 4257-0552 A
Product Usage Instructions
Important Safety Warning
There are dangerous voltages and high temperatures inside the UPS. Follow all
safety instructions to avoid personnel injury or equipment damage.
Transportation
Transport the UPS system only in the original package to protect against shock
and impact.
Preparation
Ensure the UPS system is dry before installation. Allow at least two hours for
acclimation. Do not install near water, in moist environments, direct
sunlight, or heaters. Do not block ventilation holes.
Installation
Avoid connecting appliances that overload the UPS system. Place cables safely
to prevent tripping. Connect to an earthed shockproof outlet using appropriate
cables. Ensure total leakage current does not exceed 3.5mA.
Operation
Avoid disconnecting mains cable during operation to maintain protective
earthing. The UPS output may still be live when disconnected from the building
wiring outlet. Press OFF/Enter button to fully disconnect. Keep fluids and
foreign objects out of the UPS.
Maintenance, service and faults
Repairs should only be done by qualified personnel due to hazardous voltages.
Disconnect batteries before servicing to avoid electric shock.
FAQ
Q: Can I connect a laser printer to the UPS system?
A: It is not recommended to connect appliances like laser printers that
may overload the UPS system.
Q: How should I transport the UPS system?
A: Transport the UPS system only in the original package to protect it
from shock and impact.
All rights reserved.
The information in this document is subject to change without notice.
Publish statement
Thank you for purchasing this series UPS.
This series UPS is an intelligent, single phase in single phase out, high
frequency online UPS designed by our R&D team who is with years of designing
experiences on UPS. With excellent electrical performance, perfect intelligent
monitoring and network functions, smart appearance, complying with EMC and
safety standards,
The UPS meets the world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.
Contact the nearest hazardous waste disposal station when the products or
components are discarded
Important Safety Warning
Important safety instructions – Save these instructions
Please comply with all warnings and operating instructions in this manual
strictly.
Save this manual properly and read carefully the following instructions before
installing the unit. Do not operate this unit before reading through all
safety information and operating instructions carefully
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety
instructions and relative laws, otherwise it will result in personnel injury
or equipment damage. Safety instructions in this manual act as a supplementary
for the local safety instructions. Our company will not assume the liability
that caused by disobeyingsafety instructions.
Transportation
- Please transport the UPS system only in the original package to protect against shock and impact.
Preparation
-
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed.
Please allow at least two hours for the UPS system to acclimate the environment. -
Do not install the UPS system near water or in moist environments.
-
Do not install the UPS system where it would be exposed to direct sunlight or near heater.
-
Do not block ventilation holes in the UPS housing.
Installation
- Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
- Place cables in such a way that no one can step on or trip over them.
- Do not connect domestic appliances such as hair dryers to UPS output sockets.
- The UPS can be operated by any individuals with no previous experience.
- Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
- Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
- Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
- When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.
Operation
- Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
- The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
- In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
- Prevent no fluids or other foreign objects from inside of the UPS system.
Maintenance, service and faults
- The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
- Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
- Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
- Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
- Caution – risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
- Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
- emove wristwatches, rings and other metal objects
- se only tools with insulated grips and handles.
- When changing batteries, install the same number and same type of batteries.
- Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
- Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
- Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
- Do not dismantle the UPS system.
Symbols used in this guide
WARNING!
Risk of electric shock
CAUTION!
Read this information to avoid equipment damage
Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
Unpack checking
- Don’t lean the UPS when moving it out from the packaging.
- Check the appearance to see if the UPS is damaged or not during the transportation, do not switch on the UPS if any damage found. Please contact the dealer right away.
- Check the accessories according to the packing list and contact the dealer in case of missing parts.
It includes:
- UPS user’s guide
- Software Suite CD
- USB cable
- Power cord (Input and output)
- RS232 cable
Real panel view
- Output receptacles(10A)
- Battery Terminal
- SNMP intelligent slot (option)
- Network /Fax/Modem Surge Protection(option)
- RS-232 communication port
- AC input receptacle
- Input circuit breaker
- EPO(option)
- USB(option)
- Output receptacle(16A)
Installing the UPS
- Rackmount installation
The Rackmount cabinet comes with all of the hardware required for installation in a standard EIA or JIS seismic Rackmount configuration with square and round mounting holes. The rail assemblies adjust to mount in 19” racks with a distance from front to rear around 70~76 cm (27 to 30 inches) deep.
CAUTION
- The cabinet is heavy. Removing the cabinet from its carton requires a minimum of two people.
- If installing optional EBP(S), make sure to install the EBP(S) directly below the UPS so that all wiring between the cabinets is installed behind the front covers and inaccessible to users.
NOTE Mounting rails are required for each individual cabinet
To install the rail kit
-
Assemble the left and right rails to the rear rails as shown in Figure 1.Do not tighten the screws.
Adjust each rail size for the depth of your rack. -
Select the proper size in the rack for positioning the UPS (see Figure 2). The rail occupies four positions on the front and rear of the rack.
-
Tighten four M5 Umbrella Nuts in the side of rail assembly(see Figure 1).
-
Fix one rail assembly to the front of the rack with one M5×12 pan-head screw and one M5 cage nut. Using two M5 cage nuts and two M5×12 pan-head screws, to fix the rail assembly to the rear of the rack.
-
Repeat Steps 3 and 4 for the other rail assembly.
-
Tighten the four butterfly nuts in the middle of each rail assembly.
-
If installing optional cabinets, repeat Step 1 through Step 6 for each rail kit.
-
Place the UPS on a flat, stable surface with the front of the cabinet facing to you.
-
Align the mounting brackets with the screw holes on each side of the UPS and fix with the supplied M4×8 flat-head screws(see Figure 3)
-
If installing optional cabinets, repeat Step 8 and 9 for each cabinet.
-
Slide the UPS and any other optional cabinets into the rack.
-
Secure the front of the UPS to the rack using one M5×12 pan-head screws and one M5 cage nuts on each side(see Figure 4).Install the bottom screw on each side through the bottom hole of mounting bracket and the bottom hole of the rail. Repeat for any optional cabinets.
-
Continue to the following section, “Rackmount Wiring Installation.
Rackmount Wiring Installation
- Installing the UPS, including connecting the UPS internal batteries
- Connecting any Optional EBP(S)
To install the UPS
NOTE
- Do not make unauthorized changes to the ups; otherwise, damage may occur to your equipment and void your warranty.
NOTE Do not connect the ups power cord to utility until after installation is completed.
-
Remove the front cover of each UPS
Press the cover side with LCD display, hold the other side and quickly extract it, then extract the other side with display. (see Fig.5)
NOTE A ribbon cable connects the LCD control cover to the UPS. Do not pull on the cable or disconnect it.
When remove the cover, Operate as the following right Figure shows instead of the left one. (see Fig.5) CAUTION
A small amount of arcing may occur when connecting the internal batteries.
This is normal and will not harm personnel. Connect the cables quickly and firmly -
Connect the internal battery connector(see Figure 6)
Connect red to red, Press the connector tightly together to ensure a proper connection. -
If you are installing EBPS,see the following section, “Connectingthe EBP(s),”before continuing with the UPS installation.
-
Replace the UPS front cover.
To replace the cover, verify that the ribbon cable is protected and (ifEBPS are installed) the EBP cable is routed through the knockouton the bottom of the cover.
Put the front cover hooks of side with display to the cover port, put another side to the other two ports, then press it until the cover and the chassis are combined tightly. -
If you are installing power management software, connect your computer to one of the communication ports or optional connectivity card. For the communication ports, use an appropriate cable.
-
If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the ground cable (not supplied) to the groundbonding screw. See “Rear Covers”for the location ofthe ground bonding screw for each model.
-
If an emergency power-off (disconnect) switch is required by local codes, see “Remote Emergency Power-off” (REPO) to install the REPO switch before powering on the UPS.
-
Continue to “UPS Startup”.
Connecting the EBP(s)
-
To install the optional EBP(s) for a UPS
-
Remove the front cover of each EBP and UPS (see Figure 8).
It is the same with the installation of the front cover. (Refer” To install the UPS“) -
On the bottom of the UPS front cover, remove the EBP cable-knockout (see Figure 9).
-
For the bottom (or only) EBP, remove the EBP cable knockout on the top of the EBP front cover. See Figure 10 for the location of the top EBP cable knockout.
-
If you are installing more than one EBP, for each additional EBP remove the EBP cable knockout on the top and bottom of the EBP front cover. See Figure 10 for the location of the EBP cable knockouts.
CAUTION
A small amount of arcing may occur when connecting an EBP to the UPS. This is normal and will not harm personnel. Insert the EBP cable into the UPS battery connector quickly and firmly. -
Plug the EBP cable(s) into the battery connector(s) as shown in Figure 10. Up to four EBPS may be connected to the UPS. Connect black to black, Press the connector tightly together to ensure a proper connection.
To connect a second EBP, unclip the EBP connector on the first EBP and pull gently to extend the wiring to the EBP connector on the second EBP. Repeat for any additional EBPs. -
Verify that the EBP connections are tight and the adequate bend radius and strain relief exist for each cable.
-
Replace the EBP front cover.
To replace the cover, verify that the EBP cables are routed through the EBP cover knockouts, cover connects with the cover hook near the left side of the EBP cabinet. Repeat for each additional EBP.
It is the same with the installation of the front cover. (Refer to”to install the UPS”) -
Verify that all wires connected between the UPS and EBP(s) are installed behind the front covers and not accessible to users.
-
Return to Step4 to continue the UPS installation.
-
Rackmountconverted to Tower Installation
-
Rack mount-converted to Tower plasticbase installation
-
Two plastic base brackets
-
Flatten it after intercrossing
Intercross as following Figure: -
If anEBP is needed to be placed in the middle, the assembly of plastic base is similar(Figure 11 ).The difference is that two 1U plastic base extended boards are added in the middle.(as the following shows)
-
Rackmountconverted to TowerLCD Displayplasticbase installation
The installation between UPS and EBPS can be referred to Fig.14
- Install the base, then place the RT UPS on the base one by one as Fig.13 shows.
- The cover installation and cable connection of the UPS and EBPS are the same as RT.(To install the optional EBP(s) for a UPS)
UPSstartup and turn off
Startup operation
-
Turn on the UPS in line mode
NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.- Once mains power is plugged in, the UPS will charge the battery, at the moment, the LCD shows that the output voltage is 220, which means the UPS automatic ally tart the inverter. If it is expected to change to bypassmodel, you can Press “OFF” key.
- Press and hold the ON key for more than three seconds to start the UPS, then it will start the inverter.
- Once started, the UPS will perform a self-test function, LED will light and go out circularly and orderly. When the self-test finishes, it will come to line mode, the corresponding LED lights, the UPS is working in line mode.
-
Turn on the UPS by DC without mains power
- When mains power is disconnected, press and hold the ON key for more than half a second to start UPS.
- The operation of the UPS in the process of start is almost the same as that when mains power is in. After finishing the self-test, the corresponding LED lights and the UPS is working in battery mode.
Turn off operation
- Turn off the UPS in line mode
- Press and hold the OFF key for more than half a second to turn off the UPS and inverter.
- After the UPS shutdown, the LEDs go out and there is no output. If output is needed, you can set bps “ON” onthe LCD setting menu.
- Turn off the UPS by DC without mains power
- Press and hold the OFF key for more than half a second to turn off the UPS.
- When turning off the UPS, it will do self-testing firstly. The LEDs light and go out circularly and orderly until there is no display on the cover.
Configuring Battery Setings
Set the UPS for the number of EBPs installed.
To ensure maximum battery runtime, configure the UPS for the correct
number of EBPs, refer to Table 8 for the appropriate setting of battery
numbers and type. Use the up and down scroll keys to select the number of
battery strings according to your UPS configuration:
All UPS and EBP Cabinets | Number of BatteryStrings |
---|---|
UPS only (internal batteries) | 1(default) |
UPS+1EBP | 3 |
UPS+2EBPs | 5 |
UPS+3EBPs | 7 |
UPS+4EBPs | 9 |
NOTE The UPS contains one battery string; each EBP contains two batterystrings.
Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
LCD control panel introduction
- LED(fromright to left: “alarm”, “bypass”, “battery”, “inverter”);
- On-Line UPS LCD display;(3)Function keys
LED Indicator
Function Keys
Function Key | Description |
---|---|
ESC/OFF | To exit setting mode |
UP | To go to previous selection Or turn on the ups |
Down | To go to next selection |
ENTER/ON | To confirm the selection in setting mode or enter setting mode Or |
turn off the ups
LCD Display Icons
Operations
Button operation
Button | Function |
---|---|
ON /ENTER Button | Ø Turn on the UPS: Press and hold ON button for at |
least 2 seconds to turn on the UPS.
Ø Confirmcurrentsettings: When the UPS
| enters the setting mode, must press this button to confirm the settings value what you want,nest press up/down button to change settings information
Ø Out off bypass mode: when the UPS enter to bypass mode, press and hold this button it will
switch to normal mode.
---|---
OFF/ESC Button
| Ø Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS in battery mode. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
Ø Exit setting mode:Press this button to exit setting mode when in UPS setting mode,but save nothing.
UP Button
| Ø Up key: Press this button to display previous
selection in UPS setting mode.
DOWN Button
| Ø Down key: Press this button to display next selection in UPS setting mode.
Ø To confirm selection and exit setting mode:Press this button to confirm selection and exit setting mode when LCD display the
last selection in UPS setting mode.
UP + DOWN Button
| Ø Setting mode: Press and hold this button for 5
seconds to enter UPS setting mode.
Setup the UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid
using extension cords.
- For 208/220/230/240VAC models: The power cord is supplied in the UPS package.
Step 2: UPS output connection
- For socket-type outputs, simply connect devices to the outlets.
- For terminal-type input or outputs, please follow below steps for the wiring configuration:
- Remove the small cover of the terminal block
- Suggest using AWG14 or 2.1mm2 power cords for 3KVA (208/220/230/240VAC models).
- Upon completion of the wiring configuration, please check whether the wires are securely affixed.
- Put the small cover back to the rear panel.
Step 3: Communication connection
Communication port:
To allow for unattended UPS shutdown/start-up and status monitoring, connect
the communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay
card. When installing either SNMP or Relay card in the UPS, it will provide
advanced communication and monitoring options.
NOTE: USB port and RS-232 port can’t work at the same time.
Step 4: Turn on the UPS
Press the ON button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software.
LCD display
Part one: Rack display
There are 9 interfaces available in the LCD display.
UPS setting
The UPS has setting functions. This user settings can be done under any kind
of UPS working mode. The setting will take effect under certain condition.
Below table describes how to set the UPS.
The setting function is controlled by 4buttons (Up , Down, ON/Enter,OFF/ESC):
- “Up ▲+ Down▼”—goes into the setting page;
- ON/Enter — – confirm the settings option;
- Up ▲ &Down ▼— value adjustment for choosing different pages;
OFF/ESC— Exit setting mode;
After the UPS turn ON, press buttons “UP+Down” for 5seconds and then goes into
the setting interface page.
Note: Press “Down”button to confirm selection and exit setting mode when
LCD display the last selection in UPS setting mode.
Operational Status and Mode(s)
item | Content Displayed |
---|---|
2 | Standby Mode |
3 | No Output |
4 | Bypass Mode |
5 | Utility Mode |
6 | Battery Mode |
7 | Battery Self-diagnostics |
8 | Inverter is starting up |
9 | ECO Mode |
10 | EPO Mode |
11 | Maintenance Bypass Mode |
12 | Fault Mode |
13 | Generator Mode |
Alarm or Fault reference code
Event log | UPS Alarm Warning | Buzzer | LED |
---|---|---|---|
1 | Rectifier Fault | Beep continuously | Fault LED lit |
2 | Inverter fault(Including Inverter bridge |
is shorted)
| Beep continuously| Fault LED lit
9| Fan fault| Beep continuously| Fault LED lit
12| Selftest fault| Beep continuously| Fault LED lit
13| Battery Charger fault| Beep continuously| Fault LED lit
15| DC Bus over voltage| Beep continuously| Fault LED lit
16| DC Bus below voltage| Beep continuously| Fault LED lit
17| DC bus unbalance| Beep continuously| Fault LED lit
18| Soft start failed| Beep continuously| Fault LED lit
19| Rectification model
Over Temperature
| Twice per second| Fault LED lit
20| Inverter model Over Temperature| Twice per second| Fault LED lit
26| Battery over voltage| Once per second| Fault LED blinking
27| Mains Input reverse| Once per second| Fault LED blinking
28| Bypass Input reverse| Once per second| Fault LED blinking
29| Output Short-circuit| Once per second| Fault LED blinking
30| Input current limit| Once per second| Fault LED blinking
31| Bypass over current| Once per second| BPS LED blinking
32| Overload| Once per second| INV or BPS LED blinking
33| No battery| Once per second| Battery LED blinking
34| Battery under voltage| Once per second| Battery LED blinking
35| Battery low pre-warning| Once per second| Battery LED blinking
36| Over load time out| Once per 2 seconds| Fault LED blinking
37| DC component over limit.| Once per 2 seconds| INV LED blinking
39| Mains volt. Abnormal| Once per 2 seconds| Battery LED lit
40| Mains freq. abnormal| Once per 2 seconds| Battery LED lit
41| Bypass Not Available| | BPS LED blinking
42| Bypass out of tracking range| | BPS LED blinking
45| EPO Enable| Beep continuously| Fault LED lit
Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below and the Trouble Shooting Chart.
Symptom | Possible cause | Remedy |
---|---|---|
No indication and alarm even though the mains is normal. | The AC input power | |
is not connected well. | Check if input power cord firmly connected to the |
mains.
The AC input is connected to the UPS output.| Plug AC input power cord to AC
input correctly.
Alarm code is shown as“33” and battery led blinking.| The external or internal
battery is incorrectly connected.| Check if all batteries are connected well.
Alarm code is shown as “26” and battery led blinking.| Battery voltage is too
high or the charger is fault.| Contact your dealer.
Alarm code is shown as “34” and battery led blinking| Battery voltage is too
low or the charger is fault.| Contact your dealer.
Alarm code is shown as “32” and INV or BYPASS led blinking.| UPS is overload|
Remove excess loads from UPS output.
Alarm code is shown as “27&28” and FAULT led light.| Mains Input reverse&
Bypass Input reverse| Check input L/N wiring Reverse
connection
Alarm code is shown as “29” and FAULT led light.
| The UPS shut down automatically because short circuit occurs on the UPS
output.| Check output wiring and if connected devices are in short circuit
status.
Alarm code is shown as “9” and FAULT led light.| Fan fault.| Contact your
dealer.
Alarm code is shown as “01,02, 15,16,17,18”| A UPS internal fault has
occurred.| Contact your dealer.
Battery backup time is shorter than nominal value| Batteries are not fully
charged| Charge the batteries for at least 5 hours and then check capacity. If
the problem still persists, consult your dealer.
Batteries defect| Contact your dealer to replace the battery.
Trouble Shooting Chart
Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright
in a cool, dry location. During storage, recharge the battery in accordance
with the following table:
Storage Temperature | Recharge Frequency | Charging Duration |
---|---|---|
-25°C – 40°C | Every 3 months | 1-2 hours |
40°C – 45°C | Every 2 months | 1-2 hours |
Options
SNMP card: internal SNMP(options)
- Loosen the 2 torque screws (on each side of the card).
- Carefully insert the SNMP card and lock the screws
The slot called SNMP supports the MEG Atecpro to col. We advise that the
NetAgentlI-3 port is also a tool to remotely monitor and manage any UPS system
NetAgentlI-3Ports supports the Modem Dial-in(PPP) function to enable there
mote control via the internet when the network is unavailable.
In addition to the features of a standard NetAgentMini, NetAgentll has the
option to add NetFeelerLitetodetect
temperature, humidity, smoke and security sensors.Thus,makingNetAgentlI a
versatile management tool.NetAgentll also supports multiple languages and is
setup for web- based auto language detection.
Relaycard(options)
Mini dry contact card is used for providing the inter face for UPS peripheral
monitoring. The contact signals can reflect UPS running status.The card is
connected to peripheral monitoring devices via a terminal board to facilitate
the effective monitoring of the real-time status of UPS and timely feedback
the status to monitor abnormal situations occurs(such as UPS failure, mains
interruption, UPS by pass and ect.). It is installed in thein telligent slot
of the UPS.
There lay card includes output ports and one input port.Please refer to the
following table for detail.
Pins definition of connecting terminal on the board
Emergency Power-off (EPO) (options)
EPO is used to shut down the UPS from a distance. This feature can be used for
shutting down the load and the UPS by thermal relay, for instance in the event
of room overtemperature. When EPO is activated, the UPS shuts down the output
and all its power converters immediately. The UPS remains on to alarm the
fault.
NOTE Depending on user configuration, the pins must be shorted or opened to
keep the UPS running. To restart the UPS, reconnect (re-open) the EPO
connector pins and turn on the UPS manually. Maximum resistance in the shorted
loop is 10 ohm.
Always test the EPO function before applying your critical load to avoid
accidental load loss.Leave the EPO connector installed onto the EPO port of
the UPS even if the EPO function is not needed.
Load Segments(options)
Load segments are sets of receptacles that can be controlled by power
management software or through the display, providing an orderly shutdown and
startup of your equipment. For example, during a power outage, you can keep
critical equipment running while you turn off other equipment. This feature
allows you to save battery power. Each UPS has two load segments:
- Load Segment 1: The power-shedding battery voltage of this segment can be set by LCD.
- Load Segment 1: The power-shedding battery end of discharge(EOD).
Specification
MODEL| 1KVA(S)| 1KVA(H)| 1.5KVA (S)| 1.5KVA(H)|
2KVA(S)| 2KVA(H)| 3KVA(S)| 3KVA(H)
---|---|---|---|---|---|---|---|---
PHASE| Single phase with ground
Capacity (VA/Watts)| 1000VA/ /1000W| 1500VA/ 1500W| 2000VA / 2000W| 3000VA
/3000W
INPUT
Nominal voltage| 208/220/230/240VAC
Operating voltage range (Ambient Temp.
<40℃)
| Low line transfer| 176Vac±5% @100%-50% load;
110Vac±5% @50%-0% load;
Low line comeback| 186Vac±5% @100%-50% load;
120Vac±5% @50%-0% load;;
High line transfer| 264Vac±5% @100%-50% load;
300Vac±5% @50%-0% load;
High line comeback| 254Vac±5% @100%-50% load;
290Vac±5% @50%-0% load;
Operating frequency
range**
| 40-70Hz
Power factor| 0.99@100% load(Nominal Input Voltage)
Bypass voltage range
| Bypass high voltage point
230-264 : setting the high voltage point in LCD from 230Vac to 264Vac. (Default: 264Vac)
Bypass low voltage point
176-220 : setting the low voltage point in LCD from 176Vac to 220Vac. (Default: 176Vac)
Generator input| Support
OUTPUT
Output voltage*| 208/220/230/240Vac
Power factor| 1.0
Voltage regulation| ±1%
Frequency
| ****
Line Mode (synchroni zed range)
| ****
46-54Hz or 56-64Hz
Bat. Mode| (50/60±0.1)Hz
Crest factor| 3:1
Harmonic distortion (THDv)| ≤3% THDwith linear load
≤5% THD with non linear load
Waveform| Pure Sinewave
Transfer time
| AC mode
<->Batt. mode
| Zero
Inverter
<->
bypass
| 4ms(Typical)
Efficiency| 90%(AC mode)
85%(DC mode)
| 91%(AC mode)
86%(DC mode)
| 92%(AC mode)
86%(DC mode)
| 92%(AC mode)
87%(DC mode)
BATTERY
Battery Type
| ****
12V9AH
| depends on the capacity of external
batteries
| ****
12V9AH
| depends on the capacity of external
batteries
| ****
12V9AH
| depends on the capacity of external
batteries
| ****
12V9AH
| depends on the capacity of external
batteries
Numbers| 2| 2| 3| 3| 3| 4| 4| 8| 6| 6| 8
Backup time| Long run unit depends on the capacity of external batteries
---|---
Typical recharge
time(standard modle)
| 4 hours recover to 90% capacity (Typical)
Charging voltage| ****
27.4 ±1%
| ****
41.0 ±1%
| ****
54.7±1%
| ****
82.1 ±1%
| 109.
4±1
%
Charge current| 1/2A| 6/12A| 1/2A| 6/12A| 1/2A| 6/12A| 1/2A| 6/12A
SYSTEM FEATURES
Overload
| Line Mode| 105%~125%: UPS transfer to bypass after 1minute when the utility is normal 125%~130%: UPS transfer to bypass after 30 seconds when the utility is normal
130%: UPS transfer to bypass immediately when the utility is normal
Batt. Mode| 105%~125%: UPS after 1minute shut down; 125%~130%: UPS after 10 seconds shut down;
130%: UPS immediately shut down;
Short Circuit| Hold Whole System
Overheat| Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage| Alarm and Switch off
EPO (optional)| Shut down UPS immediately
Audible & Visual alarms| Line Failure, Battery Low, Overload, System Fault
Comunication interface| USB(or RS232), SNMPcard(optional), Relay card
(optional)
ENVIRONMENTAL
Operating temperature| 0℃~40℃
Storage temperature| -25℃~55℃
Humidity range| 20-90 % RH @ 0- 40°C (non-condensing)
Altitude| < 1500m
Noise level| Less than 55dBA at 1 Meter
PHYSICAL
Dimension W×D×H (mm)| ****
44032586.5
| ****
440460
86.5
| ****
440600
86.5
| ****
440460
86.5
| ****
44060086.5
Net Weight (kg)| 11.3| 5.6| 16.5| 8.1| 19.5| 8.5| 26.2| 8.8
STANDARDS
Safety| IEC/EN62040-1,IEC/EN60950-1
EMC| IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
- Derate to 80% of capacity when the output voltage is adjusted to 208VAC
- Derate to 75% of capacity when the Input voltage frequency out of range(50/60±4Hz)
- Product specifications are subject to change without further notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>