Honeywell 6860 Remote Annunciator Installation Guide
- May 15, 2024
- Honeywell
Table of Contents
6860
Remote Annunciator
Product Installation Document
Description
The 6860 is an optional 4×40 remote annunciator that can be surface or flush- mounted.
1.1 Compatibility
The 6860 is compatible with the Silent Knight Series FACPs. For more
information, refer to the FACP Manual.
1.2 Specifications
Operating Voltage: | 24VDC |
---|---|
Current | Standby Current: |
Alarm Current: | 53mA |
Operating Temperature: | 32° to 120° F (0° to 49° C) |
Dimensions | Flush Mount: |
12.25” W x 11.5” H x 0.875” D
(31.1 cm W x 29.2 cm H x 2.2 cm D)
Backbox: 9.25” W x 8.375”H
(23.5cm W x 21.27cm H)
Surface Mount:| Including trim ring:
12.25” W x 11.5” H x 3.0” D
(31.1 cm W x 29.2 cm H x 7.6 cm D)
Table 1 Specifications
Installation
- Ensure power is turned off at the panel.
- Mount the 6860 in the desired location. See Section 2.1.
- Connect the 6860 to the panel. See Figure 5.
- Use the DIP switches on the back of the 6860 to assign an ID number. Refer to the FACP manual.
- The 6860 module must be added to the system through FACP programming. JumpStart can be used to automatically add the module or it may be added manually. Refer to the FACP Manual for more information.
2.1 Mounting
2.1.1 Flush Mounting
Follow these steps to flush mount the 6860.
- The backbox dimensions are 9.25” W x 8.375” H. The minimum depth required is 2″. Mount the backbox using the mounting holes shown below.
- Remove knockouts as needed for wires. There are 10 knockouts available, two on each side and two in the back of the cabinet.
- Wire the annunciator board to the main control panel as shown in Figure 5.
- Attach the annunciator and door assembly to back box as shown below using the supplied screws.
2.1.2 Surface Mounting
The RA-100TR Red Trim Ring kit is available for use when surface mounting the
6860.
- Remove the desired knockout.
- Mark and pre-drill hole in the wall for the center top keyhole mounting bolt. Refer to Figure 2 for mounting hole locations.
- Install center top fastener in the wall with the screw head protruding.
- Place backbox over the top screw, level and secure.
- Mark and drill the left and right upper and lower mounting holes.
- Install remaining fasteners and tighten.
- Run wires to the control panel. Refer to Figure 5.
- Place the trim ring over the back box as shown below.
- Attach the door assembly to the backbox using the screws provided. Refer to Figure 3.
Wiring Connections
Wire the 6860 to the FACP as shown in below. ~~~~
~~~~Figure 5 SBUS Connections
Setting the DIP Switches
4.1 Address Setting
Each SBUS device requires a unique address. DIP switches 1-6 on S1 are used to
set the address. This address will be displayed on the LCD display as the
Station ID number.
The maximum number of devices that can be connected to the SBUS communication
circuit depends on the limitations of the FACP. Refer to the FACP manual for
more information. SBUS device addresses do not need to be sequential and can
be set to any number between 01 and 63.
Note that 00 is not a valid address.
4.2 Communication Protocol
DIP switch 7 is used to determine the communication protocol of the 6860. Set
DIP switch 7 to ON for SBUS protocol. This switch must stay in the ON position
for proper functionality. 4.3 End-of-Line Resistor
The end-of-line termination resistor must be enabled at S1 DIP switch 8 on the
last device on the communication circuit. All other annunciators should have
these switches set to disable.
Honeywell Silent Knight
12 Clintonville Road Northford, CT 06472-1610
203.484.7161
www.silentknight.com
LS10174-001SK-E | C | 06-22
©2022 Honeywell International Inc.
Documents / Resources
|
Honeywell 6860 Remote
Annunciator
[pdf] Installation Guide
6860, 6860 Remote Annunciator, Remote Annunciator, Annunciator
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>