EMERSON ET134 Series Integrally-Mounted Temperature Regulators Instruction Manual
- June 4, 2024
- Emerson
Table of Contents
ET134 Series Integrally-Mounted Temperature Regulators
VCIMD-16109
Instruction Manual
ET134 Series Integrally-Mounted Temperature Regulators
WARNING
Failure to follow these instructions or to properly install and maintain this
equipment could result in property damage and personal injury or death.
ET124 and ET134 Series regulators must be installed, operated, and maintained
in accordance with federal, state and local codes, rules and regulations and
Emerson Process
Management Regulator Technologies, Inc. instructions.
If the valve vents gas or a leak develops in the system, service to the unit
may be required. Failure to correct the issue could result in a hazardous
condition.
Installation, operation, and maintenance procedures performed by unqualified
personnel may result in improper adjustment and unsafe operation. Either
condition may result in equipment damage or personal injury. Only a qualified
person shall install or service the ET124 and ET134 Series regulators.
Introduction
Scope of the Manual
This manual provides instructions for the installation, troubleshooting,
maintenance, valve setting, and parts ordering for ET124 and ET134 Series
regulators. Refer to the following documents for the complete details.
- VCIMD-14980 for Types T124 and T134 temperature and pressure pilots.
- VCIMD-14961 for Type E main valve.
- VCIMD-14935 for Type E2 main valve.
Product Description
ET124 and ET134 Series are steam pressure-reducing valves and temperature regulators in a single pilot-operated valve. These regulators are a combination of a Type T124 or T134 pressure and temperature pilot and a Type E or E2 main valve. Steam pressure on the heater is modulated in proportion to temperature and load variations. Pressure control provides fast, accurate adjustment of heat transfer rate to demand requirements.
Specifications
This section lists the specifications for the ET124 and ET134 Series. Factory specifications are stamped on the nameplate fastened on the regulator at the factory.
Available Configurations
Type ET124: For heater operating pressures between 20 to 125 psi / 1.38
to 8.62 bar.
Type ET134: For heater operating pressures up to 20 psi / 1.38 bar.
Type E2T134: For heater operating pressures up to 15 psi / 1.03 bar.
Sizes
NPS 3/8, 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 5, 6, 8, 10, 12 / DN 10,
15, 20, 25, 32, 40, 50, 65, 80, 100, 125, 150, 200, 250 and 300
End Connection Styles
NPT
Maximum Operating Temperature (1)
Type T124
Cast Iron: 450°F / 232°C
Type T134
Cast Steel: 750°F / 400°C
Cast Iron: 450°F / 232°C
Maximum Inlet Pressure (1)
Type T124
Cast Iron: 250 psi / 17.2 bar
Type T134
Cast Steel: 600 psi / 41.4 bar
Cast Iron: 250 psi / 17.2 bar| Temperature Ranges (1)
20 to 120°F / -7 to 49°C
50 to 150°F / 10 to 66°C
70 to 170°F / 21 to 77°C
120 to 220°F / 49 to 104°C
150 to 300°F / 66 to 149°C
170 to 270°F / 77 to 132°C
250 to 350°F / 121 to 177°C
Main Valve Material
Body: Cast Iron and Cast Steel
Stem, Disc, Seat: 416 Stainless steel
Gasket: Graphite
Diaphragm: 301 Stainless steel
Spring: Steel
Options
Bronze or Stainless steel Thermostat
Thermostat Well
Dial Thermometer
Tubing from 5 to 20 ft / 1.5 to 6.1 m
Integral Mount
---|---
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
Intended Purpose
The ET124 and ET134 Series temperature regulators are designed to reduce steam
pressure and regulate the flow of steam to the heater to control the
temperature.
No separate reducing valve is required. The heater pressure is automatically
limited to the pressure limit spring setting. The Type ET134 has an adjustable
range between 5 to 30 psi / 0.34 to 2.07 bar. The Type ET214 has an adjustable
range between 20 to 125 psi / 1.38 to 8.62 bar. Slight variations at the
thermostat throttle the steam pressure according to the demand for heat.
Principle of Operation
The regulator is operated by its initial steam pressure.
The main valve is normally closed, being held so by initial pressure on the
disk and by an internal main spring. The pilot is opened by compressing the
pressure limit spring.
When steam is turned on, it flows to the pilot up through the top flange. See
Figure 2. At the No. 8B tee between the valve and the pilot the flow divides,
one branch being connected to bleed port No. 211, the other to restriction
elbow No. 211, the other to restriction elbow No. 5A and the underside of the
main valve diaphragm. Bleedport No. 211 restricts the flow, builds pressure
under the diaphragm, and opens the main valve. Restriction No. 5A steadies the
operation
of the regulator. Steam
flowing to the heater creates a rising delivery pressure which feeds back
through the control pipe to the underside of the pilot diaphragm. As the
pressure on this diaphragm approaches a balance with the thrust of the
pressure limit spring, the pilot throttles. This, in turn, allows the main
valve to assume a position where just enough steam flows to maintain the set
maximum delivery pressure.
As the temperature of the heated medium rises, vapor pressure is generated in
the thermostat bulb and transmitted to the pilot temperature diaphragm. When
the vapor pressure becomes sufficient to over-balance the combined thrust of
the temperature adjusting and pressure limit springs, the regulator throttles
to maintain the set temperature.
Installation
**WARNING**
Personal injury or system damage may result if this regulator is installed,
without appropriate overpressure protection, where service conditions could
exceed the limits given in
the Specifications section and/or regulator nameplate.
Additionally, physical damage to the regulator may result in personal injury
or property damage due to escaping of accumulated gas. To avoid such injury
and damage, install the regulator in a safe location.
Under enclosed conditions or indoors, escaping gas may accumulate and be an
explosion hazard. In this case, the vent should be piped outdoors.
Planning the Installation
-
Locate the regulator in a horizontal pipe.
-
Prevent water hammer and erratic operation by providing a trap ahead of the regulator.
-
Avoid damaging the effects of scale and dirt in pipe lines by using a strainer to protect the regulator.
-
Provide a three-valve by-pass to facilitate inspection of the regulator without interrupting service.
-
Thermostat position:
a. The preferred thermostat position is horizontal.
b. When vertical or slanting, the tip of the bulb must point downward.
c. Locate the thermostat as close to the heater outlet as practical.
d. Expose the entire length of the bulb to the active flow leaving the heater. -
If the pressure rating of the heater or the connected equipment is less than the initial stream pressure, provide a safety valve.
-
Hot water and similar liquid systems require a relief valve to prevent dangerous overpressure due to expansion.
-
Instantaneous Heaters – When operated on intermittent demand, as in domestic water heating, require the following conditions for best temperature regulation.
a. Constant forced recirculation of fluid through the heater.
b. Omission of thermostat well to reduce temperature lag. The use of a thermostat compatible with the heated medium is preferred over the use of a standard thermostat installed in a well, which is compatible with the heated medium. When the use of a well is unavoidable, an appropriate heat transfer medium should be
installed between the well and the thermostat.
Main Valve
- Flush the piping system thoroughly to clear it of welding beads, scale, sand, etc.
- Mount the main valve with the diaphragm chamber down and the arrow on the body pointing in the direction of the flow.
Pilot
-
Remove the protecting cover from the top flange of the valve and flange of the pilot. Mount the pilot to the valve as shown in Figure 3.
-
Screw No. 4A bleed port fitting into the 1/8 in. / 3.18 mm pipe tap on the outlet side of the main valve body. Note that the bleed orifice in this fitting is vital to the operation of the regulator.
-
Screw No. 4B coupling into 1/8 in. / 3.18 mm pipe tap in the pilot.
-
Screw No. 5A elbow containing the restriction orifice into the 1/8 in. / 3.18 mm pipe tap on the underside of the main valve diaphragm chamber.
Type E2 main valves use a No. 5B elbow without an orifice. -
Connect the tubing bends as illustrated in Figure 3 for Type E and E2 main valves.
Control Pipe
- Use 1/4 in. / 6.35 mm pipe for this line which connects the pilot pressure diaphragm chamber to the desired point of pressure control. See Figure 3.
- On instantaneous heaters with steam in the shell, tap the control pipe into the shell. Otherwise, enter the delivery steam pipe at the point of entry to the heater. (See Figure 2)
- Pitch the control pipe away from the pilot and avoid water pockets.
Insulation
Insulation may be applied to the upper portion (globe and flanges) of the main
valve. Do not insulate the diaphragm chamber or any part of the pilot. See
Figure 3.
Starting Up and Setting Controlled Temperature
Best temperature control will result when the delivery pressure setting is the lowest steam pressure capable of sustaining the desired temperature at maximum load. The following adjustments should be made under full load conditions or as near such as possible:
-
Close by-pass. Open 1/4 in. / 6.35 mm control pipe valve and turn up temperature adjusting wheel, until 1/2 in. / 12.7 mm of thread is exposed.
Back off the pressure-adjusting screw to remove all compression from the pressure limit spring. (See Figure 3)
-
Crack open outlet stop valve. Crack open the inlet stop valve, blow down the strainer, then slowly open the inlet valve, wide open.
-
Turn up the pressure adjustment slowly. When steam begins to flow, open the outlet stop valve gradually.
-
Continue delivery pressure adjustment until heater output temperature is 5°F / -15°C above that required. (If the temperature adjustment of paragraph 1 limits this operation, set the adjusting wheel a little higher.)
-
Lower the temperature adjusting wheel until the desired operating temperature is reached.
-
If the adjustment is made at a partial load, the temperature will sag under heavy loads. When maximum load occurs, increase the pressure setting just sufficient to restore the temperature to normal.
Maintenance
WARNING
To avoid personal injury or property damage from the sudden release of pressure, isolate the regulator from the pressure system and release all pressure from the pilot and main valve before performing maintenance operations.
Complete dismantling at regular intervals for inspection and repair is not recommended. Under normal conditions, if kept relatively free of dirt, a regulator will function year after year with minimum maintenance attention. These service points are suggested:
-
After the first few days and thereafter twice a year, inspect for dirt collected at:
a. Bleedport orifice – screwed into the downstream side of the main valve.
b. Restriction orifice – screwed into the underside of the main valve Types E and E5. Type E2 main valve has an open elbow without an orifice. -
After the first few days of operation and thereafter twice a year, inspect all flanges and screwed joints for leakage. Tighten all bolts. Never allow a leak to persist.
-
Do not, under any circumstances, loosen the bolts on the temperature diaphragm chamber or attempt to dismantle the thermostat element. The system is filled with a volatile fluid which if lost, will render the pilot inoperative. A damaged element, however, can easily be changed in the field by following the directions in Form SIOI12B.
Troubleshooting
Failure to Open
-
The setting of adjusting springs may have been tampered with.
-
Initial pressure may be down due to a partially-closed supply valve, clogged strainer, or other obstruction.
-
Bleedport may have been omitted and an open coupling is substituted.
-
The orifice in the No. 5A restriction may be plugged.
-
The control pipe on the pilot may be plugged in. Most likely, points of obstruction are at the shutoff valve and entrance to the delivery main valve.
-
Make sure the heater is properly trapped and free of condensation.
-
Pilot or main valve diaphragms may be broken.
Check for leakage around the stem between the lever and the diaphragm on the pilot. Check the main valve with air pressure in the diaphragm chamber before dismantling. -
A leak in the thermostat bulb may allow heated fluid pressure, if sufficiently high, to back up into the thermal system to hold the pilot closed.
Failure to Close, Overheating
-
The setting of adjusting springs may have been tampered with.
-
By-pass may be leaking.
-
The thermostat is located too far from the instantaneous heater outlet.
-
The thermostat may be kinked, broken, or have lost its fill. Alternately warm and cool the bulb at least 10°F / -12°C above and below its setpoint. If the thermostat is operative, the stem between the lever and the pressure diaphragm will become loose and snug as the temperature stem on opposite ends of the lever moves up and down.
-
A lift of condensate to a hot well may require more pressure in the heater than the heated medium.
a. Arrange the drainage of the heater by gravity or install a pump to lift condensate. -
Main valve or pilot may be held open by foreign matters to determine which valve leaks:
a. Close the inlet stop valve and 1/4 in. / 6.35 mm control valve.
b. Remove the bleed port bend so the pilot will exhaust into the atmosphere.
c. Remove all compression from the pressure-adjusting spring.
i. If steam issues from the end of the bleed port bend on the pilot, there is an obstruction between its seat and disk.
ii. Steam blowing back from the bleed port on the downstream side of the valve indicates that the main valve disk is held open by a foreign matter.
iii. Leakage of wither valve requires dismantling. See dismantling and valve grinding for the method.
Erratic Temperature Control
-
The thermostat was installed too far from the heater outlet.
-
Improper trapping or erratic discharge of trap.
-
Lift of condensate to a hot well may require more pressure than that called for by the medium flowing through the heater.
a. Arrange to drain condensate by gravity or lift it with a pump. -
A sticky check valve in the return line.
-
Poor circulation through the heater.
a. Constant circulation should be employed. -
The valve is too large for the heater or the heater is too
large for the load. -
The valve is installed too far from the heater.
Dismantling
Main Valve
- Remove the pilot and its connection to the main valve.
- Remove the top flange of the valve.
- Connect a source of air (water, steam) pressure which can be adjusted by hand to the underside of the diaphragm as shown in Figure 4.
- Apply 50 to 60 psi / 3.45 to 4.14 bar to Type E, and 10 psi / 0.69 bar to Types E2 and E5 to jack the valve wide open. The friction of the pressure plate against the stops in the base will prevent the stem (key 11) from turning while removing the stem nuts.
Pilot
Note
If possible, remove the bulb of the thermostat from the tank or pipeline.
This will make disassembling easier and permit the omission of step 1. If it
is not possible to remove the bulb of the thermostat, proceed with step 1.
- Loosen the set screw in the cowl bracket just below the barrel nut and unscrew the pressure pilot from the barrel.
- Release the compression on the pressure-adjusting spring and remove the spring.
- Remove the flange bolts at the small flange where the pilot connects to the valve, and remove the pilot.
- Take the pilot body apart at the diaphragm joint.
- Hold the pusher plate on the upper end of the pilot body to turn off the stem nuts.
Grinding the Main Valve or Pilot Disk
- Use extremely fine (400 grit) compound with light pressure to avoid the tearing of metal.
- Clean all parts with solvent before reassembling.
Parts Ordering
When corresponding with your local Sales Office about this equipment, always
reference the equipment regulator size, service, and serial number.
When ordering replacement parts, reference the key number of each needed part
as found in the following parts list and indicate the part number.
Parts List
Type E Main Valve
See Instruction Manual VCIMD-14961-EN
Type E2 Main Valve
See Instruction Manual VCIMD-14935-EN
T124 and T134 Series Pilot
See Instruction Manual VCIMD-14980-EN
Emerson Automation Solutions
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574| Asia Pacific
Singapore 128461, Singapore
T +65 6777 8211
---|---
Europe
Bologna 40013, Italy
T +39 051 419 0611| The Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100
VCIMD-16109 © 2021 Emerson Electric Co. All rights reserved. 11/21 Spence is a
mark owned by one of the companies in the Emerson Automation Solutions
business unit of Emerson Electric Co. The Emerson logo is a trademark and
service mark of Emerson Electric Co. All other marks are the property of their
prospective owners.
The contents of this publication are presented for informational purposes
only, and while every effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied, regarding
the products or services described herein or their use or applicability. All
sales are governed by our terms and conditions, which are available upon
request. We reserve the right to modify or improve the designs or
specifications of such products at any time without notice.
Emerson Electric Co. does not assume responsibility for the selection, use, or
maintenance of any product. Responsibility for the proper selection, use, and
maintenance of any Emerson Electric Co. product remains solely with the
purchaser.
SIOI85B
Documents / Resources
|
EMERSON ET134 Series Integrally-Mounted Temperature
Regulators
[pdf] Instruction Manual
ET124, ET134 Series, ET134 Series Integrally-Mounted Temperature Regulators,
ET134 Series, Integrally-Mounted Temperature Regulators, Temperature
Regulators, Regulators
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>