thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide

June 17, 2024
thermokon

thermokon JOY SR 5DO Electronic Fancoil Thermostat

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
PRODUCT

Specifications

  • Model: JOY SR 5DO | EC AO2DO | EC 3AO RS485 Modbus
  • Type: Electronic Fancoil Thermostat
  • Version: From Version 2.6.x

Product Usage Instructions

Software and Firmware Update

To update the software or firmware of the device:

  1. Remove the upper part of the device.
  2. Insert a MicroSD card with the valid update file.
  3. Place the upper part back on the lower part.
  4. The update process will start, indicated by flashing ring illumination.
  5. After completion, the device will restart, and the new application will be active.
  6. Remember to remove the MicroSD card after the update is complete.

Device Configuration

To configure the device:

  1. Remove the upper part of the device.
  2. Insert a MicroSD card with the device configuration file.
  3. Place the upper part back on the lower part.
  4. The device will recognize the configuration file and be ready for operation.
  5. Remove the MicroSD card after the configuration is complete.

Enocean Configuration

To configure Enocean settings:

  1. Follow similar steps as device configuration but use an Enocean configuration file.
  2. The device will restart after the configuration is complete.
  3. The device will be ready for operation after the restart.

Save Enocean Configuration

To save Enocean configuration

  1. Remove the upper part, insert an empty MicroSD card, and place the upper part back on the lower part.
  2. The configuration file will be saved on the MicroSD card.
  3. Remember to remove the MicroSD card after saving the configuration file.

Note: It’s important to manually trigger teach-in telegram for EasySens receivers (SAB valve actuators or actuators, SRC/STC-x).
Note: Software updates are only possible within the same version main numbers.

APPLICATION

JOY SR Fancoil 5DO RS485 Modbus (85..260 V ~)
Modern design, flush mounting fan coil room thermostat. Used for individual control of temperature in commercial and residential buildings. It is
tailored for two-pipe and four-pipe fan coil units with two-wire electric valves. The device combines a modern design with a 2,5” LCD and a touch- sensitive surface, 3-time program options each with 4 time period options.

JOY SR Fancoil EC AO2DO RS485 Modbus (85..260 V ~)
Modern fan coil room thermostat to control fan coil units with EC fans. It is suitable for 2- and 4-pipe systems. It has 2 relays and 1 analog output 0-10V (heating valve, cooling valve, and EC fan). The device combines a modern design with a 2,5” LCD and a touch-sensitive surface, 3-time program options each with 4 time period options.

JOY SR Fancoil EC 3AO RS485 Modbus (24 V ~/=)
Modern design, flush mounting fan coil room thermostat. Used for individual control of temperature in commercial, industrial, and residential buildings. It is tailored for two-pipe and four-pipe fan coil units with two-wire electric valves or controlling a 6-way valve. The device combines a modern design with a 2,5” LCD and a touch-sensitive surface, 3-time program options each with 4 time period options.

SECURITY ADVICE – CAUTION

The installation and assembly of electrical equipment should only be performed by authorized personnel. The product should only be used for the intended application. Unauthorized modifications are prohibited! The product must not be used in relation to any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals, or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.

CAUTION: Risk of electric shock due to live components within the enclosure, especially devices with mains voltage supply (usually between 90..265 V).

Please comply with

  • Local laws, health & safety regulations, technical standards and regulations
  • Condition of the device at the time of installation, to ensure safe installation
  • This data sheet and installation manual

PRODUCT TESTING AND CERTIFICATION

Declaration of conformity
The declaration of conformity of the products can be found on our website https://www.thermokon.de/

NOTES ON DISPOSAL
As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as part of a building or a structure at a pre- defined and dedicated location, hence the Waste Electrical and Electronic Act (WEEE) is not applicable. However, most of the products may contain valuable materials that should be recycled and not disposed of as domestic waste. Please note the relevant regulations for local disposal.

MOUNTING ADVISE ROOM SENSORS

The Accuracy of the room sensors is influenced by the technical specifications as well as the positioning and the installation type.

During Assembly

  • Seal the mounting box (if present).
  • Installation type, air draught, heat source, radiation heat or direct sunlight can affect the measurement.
  • Building material-specific properties of the installation place (brick-, concrete-, partition wall, cavity wall, …) can affect the measurement. (e.g.: Concrete accepts room temperature variation slower than cavity walls)

Assembly not recommendet in…

  • Air draught (e.g.: close to windows/doors/fans…)
  • Near heating sources,
  • Direct sunlight
  • Niches / between furniture / …

MOUNTING ADVICES

Plasterboard boxes shall be covered by wallpaper or paint to avoid the plasterboard box’s front rim being partially visible underneath JOY. Maybe consider using white plasterboard boxes (i.e. Kaiser 9063-77)

APPLICATION NOTICE

Software| Software Description on https://www.thermokon.de/
---|---
MicroSD- Card| Storage medium to be used for update, upgrade or configuration, parameterization receive channels.

– Formatting in FAT file system required

– NTFS and exFAT file systems are not supported!

– Read in/out Enocean configuration

Bootloader| A MicroSD card bootloader for applications (update, upgrade) or configurations is integrated in the device.

Active bootloader = ring illumination flashes (1 sec. cycle), the display is not activated.

Firmware Update| – Remove the upper part, insert the MicroSD card with the valid update file, and place the upper part on the lower part.

– Valid update file is recognized and the update process is started (ring illumination flashes at 300ms intervals).

– New application is started after update (approx. 20-30 sec.).

– Remove the upper part to remove the MicroSD card from the device!

Device Configuration| – Remove the upper part, insert the MicroSD card with a device configuration file, and place the upper part on the lower part.

– Configuration file is recognized and the device is configured

– Device ready for operation

– Remove the upper part, remove the MicroSD card from the device, and place the upper part on the lower part.

|

Note: The parameters for the display, the setpoints and the controller can only be changed via the configuration software.

Enocean Configuration| – Remove the upper part, insert the MicroSD card with the Enocean configuration file, and place the upper part on the lower part.

– Configuration file is recognized and the device is configured

– Device restarts after update.

– Device ready for operation

– Remove the upper part, remove the MicroSD card from the device, and place the upper part on the lower part.

Save Enocean Configuration on MicroSD-Card| – Remove the upper part, insert an empty microSD card, and place the upper part on the lower part.

– Device starts

– Configuration file is saved on a MicroSD card

– Remove the upper part, remove the MicroSD card from the device, and place the upper part on the lower part.

UPDATE FUNCTION ADVICE

thermokon-JAOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-1

TECHNICAL DATA

Measuring values temperature, humidity (optional)
Network technology RS485 Modbus RTU, Fail-safe Biasing required
Radio technology EnOcean (IEC 14543-3-10), transmission power <10 mW
Measuring range temp. 0..+50 °C
Accuracy temperature ±1 K (typ. at 21 °C)

Measuring range humidity

(optional)

| 0..100% rH non-condensing
Accuracy humidity (optional)| ±2% between 10..90% rH (typ. at 21 °C)
Control function| setpoint adjustment 0..+50 °C, fan stages
Display| LCD 2,5“, 240×160 px, white backlighting
Functions| integrated PI-controller, 2nd control loop: 2-point controller, MSG server for 2nd control loop via radio
Enclosure| PC and glass, optional black or white
Protection| IP30 according to EN 60529
Connection electrical| Terminal 1..8

terminal block max. 1,5 mm²

| Terminal 9..12

terminal block max. 1.0 mm²

Ambient condition| 0..+50 °C, max. 85% rH non-condensing
Weight| 195 g
Mounting| flush mounted with standard EU box (Ø=60 mm)
Notes| there are 20 EnOcean transmit / receive channels available for various functions
» Joy Fancoil 5DO|
Output switch contact| 3x normally open contacts (fan speed), 240 V, load max. 3 A| 2x normally open contacts (heating/cooling), 240 V, load max. 500 mA
Power supply| 85..260 V ~
Power consumption| max. 3 VA (260 V ~)
Inputs| DI1

input for NTC 10 K or floating contact

| DI2

digital input for non-floating contact

» JOY Fancoil EC AO2DO|
Output voltage| 1x 0..10 V, max. load 5 mA, EC FAN control
Output switch contact| 2x normally open contacts (heating/cooling), 240 V max. load 500 mA
Power supply| 85..260 V ~
Power consumption| max. 3 VA (260 V ~)
Inputs| DI1 DI2

input for NTC 10 K or floating contact                             digital input for non-floating contact

» JOY Fancoil 3AO|
Ausgang Spannung| 3x 0..10 V, max. Last 5 mA, Ansteuerung EC Lüfter, Heizen & Kühlen oder Ansteuerung 6-Wege-Ventil (konfigurierbar via Software)
Spannungsversorgung| 24 V = (±10%) oder 24 V ~ (±10%) SELV
Leistungsaufnahme| max. 2,5 W (24 V =)
Eingänge| DI 1

1 Eingang für NTC10k oder potentialfreien Kontakt

| Di 2

Eingang digital, für potentialfreien Kontakt

Power supply
When several BUS devices are supplied by one 24 V AC voltage supply, it is to be ensured that all “positive” operating voltage input terminals (+) of the field devices are connected with each other and all “negative” operating voltage input terminals (-) (=reference potential) are connected together (in- phase connection of field devices).
In case of reversed polarity at one field device, a supply voltage short- circuit would be caused by that device. The consequential short-circuit current flowing through this field my cause damage to it.

Therefore, pay attention to correct wiring.

CONFIGURATION VIA UCONFIG | MICROSD-CARD OR MODBUS

Configuration software
config | Windows 10 is required to use the config configuration software
The JOY room thermostat can be parameterized using the uConfig configuration software. An SD card is used to transfer the created configuration file to the device. For BUS devices, a live configuration can also be performed via the BUS interface.
The online installer for the configuration software can be found in our download center. The installer retrieves all necessary files and plug-ins from our web server. In this version, an update function is integrated in the software.

CONNECTION PLAN

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-4

Note: Parallel connection of the potential-loaded inputs is not permitted!
If the operating mode (change-over DI) of several devices is to be switched together by one contact, the potential-free 230V input must be used (DI2, only possible with the 230V version). It must be ensured that the same phase is used for jointly switched devices.

FUNCTION DESCRIPTION

FUNCTION DESCRIPTION – CONTROLLER/FAN STAGES

JOY Fancoil 5DO (85..260 V ~)| JOY Fancoil EC AO2DO (85..260 V ~)| JOY Fancoil EC 3AO (24 V ~/=)
---|---|---
PI controller (PWM) & 2-point/3-point controller

(configurable)

| PI controller (PWM) & 2-point/3-point controller

(configurable)

| ****

PI controller (0..10 V)

Fan stages (all types)
In automatic mode, the fan speed is linked to the controller. The assignment of the fan stage to the control (heating/cooling, only heating, only cooling) is freely selectable. To ensure that the fan motor starts reliably, a period can be configured in which the fan starts with maximal value. Using one or more time channels, the fan control has to be set per time channel and period. Via the touch surface, the user has the option to override the settings of the device every time. When the next time the channel starts, the fan speed is set to the configured value. The fan is set to automatic mode when the user changes the occupancy state (occupied↔unoccupied).

Heating/ cooling with PI-controller (PWM) (only 5DO and EC AO2DO)
The time response of the PI control loop depends on the control parameters xp for the proportional area and tn for the reset time of the integral range. In case of an error, the P portion immediately changes the position value proportionally to the error variable, while the integral portion takes effect after a certain time.

The resulting actuating variable is output as a pulse-width-modulated signal directly to the outputs.
Heating/ cooling with 2-point-/ 3-point-controller (only 5DO and EC AO2DO)
In the case of temperature control, the 2-point controller only knows the switching states heating ON and heating OFF. The 3-point controller also knows the switching state of cooling. Two – and three-point controllers work with a hysteresis.

Heating/ cooling with PI-controller (0..10 V) (only EC 3AO)
The time response of the PI control loop depends on the control parameters xp for the proportional area and tn for the reset time of the integral range. In case of an error variable, the P portion immediately changes the position value proportionally to the error variable, while the integral portion takes effect after a certain time.

The resulting manipulated variable is output as an analogue 0..10 V signal directly to the outputs.
EC Fan automatic mode with PI-controller (only EC 3AO and EC AO2DO) (for EC AO2DO with two-point/three-point controller, the temperature range for controlling the 0..10 V EC fan is parameterized separately)

The 0..10 V (0..100%) control of the fan is proportional to the calculated manipulated variable of the PI controller.
i.E.: Calculated actuating variable 65% → Fan control with 6,5 V Calculated actuating variable 22% → Fan control with 2,2 V

EC Fan manual with PI-controller (only EC 3AO and EC AO2DO)
Up to 5 steps (steps) can be set using the configuration software. The set number of steps is divided linearly to the manipulated variable of 0..100%.
i.E.: Max. steps (stages) = 5
Stage 1 = 20% | Stage 2 = 40% | Stage 3 = 60% | Stage 4 = 80% | Stage 5 = 100%

DISPLAY

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-6

FUNCTION DESCRIPTION – BUTTONS

On the touch surface, there are adjustment options for setpoint and fan speed regulation.
While pressing these buttons, the white ring-LED of the Power-button lights up for visual feedback.

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-7

3 seconds without any interaction, the display returns back to main screen.

Standby mode (not compatible with Keycard-switch function)
In standby mode the display and all outputs are switched off (controller deactivated). The frost and heat protection monitoring remains active. The Modbus registers can still be read out (e.g. room temperature).

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-8

DIAGNOSTICS MENU
To access the diagnostics menu, select the header in the startscreen of the parameter menu, and press the ENTER key. Here you will find various information, such as device type, software version, state of the inputs and outputs and controller state (current manipulated variable).

PARAMETER MENU – MODBUS INTERFACE
The configuration menu is activated by simultaneously pressing the buttons “up” (A) and “down” (C) for at least 5 seconds.
The menu is enabled during the first 60 minutes after switching on the supply voltage as long as the device is not actively involved in Modbus communication. As soon as the device receives a valid request addressed to the device from a DDC, access to the menu is blocked. Without valid communication, access is blocked after 60 minutes!

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-9

CONFIGURATION

Parameter menu

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-10

MENU → TIME CHANNELS
Up to 3 time channels with 4 time periods each can be parameterized. The time channels are prioritized, channel 3 has the highest priority.

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-11

Time Channel
Period within one-week configuration ◄- / +► via button left / right 4 periods

Periods

  • Start – configuration start setpoint (24h format)
  • Fan – selection fan stage (depends on type)
  • Temperatur – setpoint (in °C or °F depends on configuration)
  • ECO mode – In ECO mode, the dead zone between heating and cooling is automatically set to the ECO dead zone configured in the “General Settings” menu (default: 10 K).

MENU → TIME/DATE
In the Time/ Date menu, the time, date, and display format can be configured.

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-13

MENU → SENSOR SETTINGS
Offset correction settings for internal and external sensor value. Value display of internal and external temperature sensors

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-14

Unit – Setting the temperature unit in celsius / Fahrenheit.

MENU → COMMON SETTINGS

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-15

  • Common device settings:
    • Brightness
    • Valve protection
    • ECO deadband
  • Fanstages
    • Language
    • Factory setting (reset)
  • Brightness
    • Configuration of the LCD brightness/ LED ring brightness during button operation/ usage.
  • Valve protection
    • A valve protection function actuates the heating and cooling valves regularly to prevent locking during non-usage times.
    • The function is executed on Fridays at 11.00 (heating valve) and 11.15 (cooling valve). The corresponding valve is triggered for 5 minutes, if not activated during the last 96 hours.
  • ECO deadband
    • The dead band can be adjusted (default 10.0 K)
    • further information in the software specification file
  • Factory setting
    • By selecting “Factory setting”, the room thermostat will be reset and restore the device to factory default settings.

MENU → ENOCEAN LIST
In this list, all channels with the taught-in sensors or actuators are displayed.

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-16

MENU → ENOCENAN CONFIGURATION
In this menu item, the radio channels can be configured and individual information can be called up.

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-17

In the footer, various menu items can be selected with the LEFT / RIGHT keys and the corresponding menu item is selected with the ENTER key. SAB valve actuators are learned in with the function

INFO: Access to the menu can be protected with a password via Modbus. The login remains unlocked in the EnOcean menu until 10 minutes after the last key press. Default password: 2030

More detailed information for the configuration of the EnOcean channels can be found in the specification.
There are 20 channels available that can be assigned different functions. A channel can be configured as a receive channel, as a send channel or as a message server (SAB communication).

6 channels can be configured with the SAB valve actuator, one of these can be set with the bath function. For the SAB with the bath function, an additional setpoint offset can be set. If SAB valve actuators are learned in, the analog outputs to the internal controller remain active and can also be used.

FUNCTIONAL OVERVIEW SAB

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-18

The profiles used are divided into functional groups:

SRW/SRG| Window contact and window handle. Both have an influence on the window contact function and are linked to the digital inputs or the Modbus default. Up to five sensors can be learned-in.
---|---
VFG| Sensor for chngeover control. Only one changeover sensor can be learned in.
EXT/WRF| Receiving channel: Temperature preset by an external room temperature sensor. Overrides the internal temperature sensor. Max. one sensor can be learned in. An EnOcean room operating unit is displayed on the send channel.
OCC| Up to 3 motion sensors can be learned in and affect the occupancy function. The last changed value (Modbus,EnOcean, Button) will be accepted. If several EnOcean motion sensors have been learned-in, the “ROOM UNOCCUPIED” value will only be accepted once all sensors have signaled “ROOM UNOCCUPIED”.
KEY| Controls the internal keycard function. When learning a key card switch, the card must not be plugged in AND pulled immediately during the learn-in process. It is necessary to wait at least 5 seconds until the second action is performed with the card. Only then will the switch be assigned as key card switch, otherwise it will be learned in as a radio rocker switch (function group RPS).
SUP| A superior control unit to override the internal functions.
SAB

(5+1 Bath)

| Up to 6 SAB´s can be learned in. One pcs. can be assigned with the „Bath“ function. The other channels can be used optionally for heating or cooling. For each SAB channel, an offset for the setpoint can be configured via Modbus.
OUT| Only in direction of transmission. A controller status (A5-11-02) every 15 minutes (configurable) and with every change of any value.

INFORMATION ABOUT EASYSENS® (RADIO) / AIRCONFIG GENERAL USAGE

EasySens® – airConfig
Basic information about EasySens® radio and about general usage of our airConfig software, please download from our website.

OVERVIEW OF THE RADIO TELEGRAMS

EEP
The structure of the data contained in the telegram can be found in the EEP (EnOcean equipment profile) list provided by the EnOcean Alliance.

SUPPORTED PROFILES

Receiving profiles


EnOcean- EEP

| ****

Type

| ****

Direction

| ****

Description

| ****

Thermokon Devices

| Max. Quantity| LCD/

Funktion s-gruppe

|
---|---|---|---|---|---|---|---
F6-02- 01| RPS| Rx| EnOcean button| Diverse| 1| RPS|
D5-00- 01| 1BS| Rx| Windows contacts| SRW01| ****

max.5

| SRW|
F6-10- 00| RPS| Rx| Windows handle| SRG02| SRG|
A5-02- 06| 4BS| Rx| Temperature 0-50°C| ****

SR65 VFG, SR65 TF,

| ****

1

| VFG|
A5-02- 16| 4BS| Rx| Temperature 0-80°C| VFG|
SR65 AKF, SR65|  |


A5-02- 05

| ****

4BS

| ****

Rx

| Room Sensor (Temperature 0-40°C)| SR04, LC-SR04, SR07, SR65| ****


1

| ****

EXT

|
 | ****

4BS

| ****

Rx

| (Room Operating Panel) Temperatur, Set Point| SR07P, SR04P, SR06 2T/2T+|  |
A5-10- 03|  | WRF|


A5-07- 01

| ****

4BS

| ****

Rx

| ****

Room Sensor (Occupancy)

| SR-MDS Solar, SR- MOC Solar, SR-MOW

Solar

|  | ****

OCC

|
 | max. 3|  |
 | ****

4BS

| ****

Rx

| Room Sensor

(Occupancy, Light, Temperature)

| ****

SR-MDS

|  |
A5-08- 01|  | OCC|
F6-04- 01| RPS| Rx| Keycard| SR-KCS02, SR-KCS| 1| KEY|
A5-20- 01| 4BS| Rx/Tx| SAB| SAB+, SAB05| max. 6| SAB|


A5-20- 12

| ****

4BS

| ****

Rx

| Superior Control Unt

(Fan. Set Point, Controller, Energy Hold OFF/Dew point, Occup)

| ****

1

| ****

SUP

|


Transmitting profiles

| ****



Direction

|  | ****



LCD

|
EnOcean- EEP| Type| Descripton| Max. Quantity|
A5-10- 02| ****

4BS

| ****

Tx

| Valid from Version 2.1.1 (up to 2.1.0: A5-10-01)

Room operating panel (Fan,Temp, Sollwert, Occup)

|  |  |
(V2.1.1 +)|  |  |
 | 1| WRF|
 | ****

4BS

| ****

Tx

| Valid from Version 2.1.1 (up to 2.1.0: A5-10-05)

Room operating panel (Temp, Sollwert, Occup)

|
A5-10- 06|  |  |
(V2.1.1 +)|  |  |


A5-11- 02

| ****

4BS

| ****

Tx

| Temperature Controller (Fan, Set point, alarming, Controller state, Energy Hold OFF, Occup)| ****

1

| ****

OUT

|
A5-20- 01| 4BS| Rx/Tx| SAB| max. 5+1| SAB|

INPUTS
Up to 2 inputs are configurable for functions such as Windows contact, dew point, occupancy, change-over or external sensor option. The overview of possible combinations can be found in the software specification of the JOY.

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-24DIMENSIONS (MM)

thermokon-JOY-SR-5DO-Electronic-Fancoil-Thermostat-
FIG-25

ACCESSORIES (OPTIONAL)

  • Frame for surface mounting JOY pure white Item No. 760201
  • Frame for surface mounting JOY black Item No. 760951
  • Decorative frame pure white for JOY Item No. 681452
  • Decorative frame black for JOY Item No. 740951
  • MicroSD card 2GB Item No. 500098
  • RS485 Biasing Adapter Item No. 811378
  • USB RS485 Modbus RTU Logger Item No. 809917
  • Converter RS485 Modbus – USB Item No. 668293

FAQ

  • Q: Where can I find the Declaration of Conformity for Thermokon products?
  • Q: What file system is required for formatting the MicroSD card?
    • A: The MicroSD card should be formatted in FAT file system. NTFS and exFAT are not supported

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany

JOY_SR Fancoil_Modbus_Datasheet_en © 2023

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals