thermokon JOY 5DO Digital Room Thermostat User Manual

June 17, 2024
thermokon

JOY 5DO | EC AO2DO | EC 3AO
Fancoil Regulator (from Version 2.6.x)

JOY 5DO Digital Room Thermostat

Datasheet
Subject to technical alteration
Issue date: 22.06.2023 • A126

thermokon JOY 5DO Digital Room Thermostat - icon

» APPLICATION

JOY Fancoil 5DO (85..260 V ~)
Modern design, flush mounting fan coil room thermostat. Used for individual control of temperature in commercial and residential buildings. It is tailored for two-pipe and four-pipe fan coil units with two-wire electric valves. The device combines a modern  design with a 2,5” LCD and a touchsensitive surface, 3 time program options each with 4 time periods options.

JOY Fancoil EC AO2DO (85..260 V ~)
Modern fan coil room thermostat to control fan coil units with EC fans. It is suitable for 2- and 4-pipe systems. It has 2 relays and 1 analogue output 0-10V (heating valve, cooling valve and EC fan). The device combines a modern design with a 2,5” LCD and a  touch-sensitive surface, 3 time program options each with 4 time periods options.

JOY Fancoil EC 3AO (24 V ~/=)
Modern design, flush mounting fan coil room thermostat. Used for individual control of temperature in commercial, industrial and residential buildings. It is tailored for two-pipe and four-pipe fan coil units with two-wire electric valves or controlling a 6-way  valve. The device combines a modern design with a 2,5” LCD and a touch-sensitive surface, 3 time program options each with 4 time periods options.

» SECURITY ADVICE – CAUTION

The installation and assembly of electrical equipment should only be performed by authorized personnel.
he product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
CAUTION! Risk of electric shock due to live components within the enclosure, especially devices with mains voltage supply (usually between 90..265 V).

Please comply with

  • Local laws, health & safety regulations, technical standards and regulations
  • Condition of the device at the time of installation, to ensure safe installation
  • This data sheet and installation manual

» PRODUCT TESTING AND CERTIFICATION

Declaration of conformity
The declaration of conformity of the products can be found on our website https://www.thermokon.de/

» NOTES ON DISPOSAL
As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as part of a building or a structure at a pre- defined and dedicated location, hence the Waste Electrical and Electronic Act (WEEE) is not applicable.  However, most of the products may contain valuable materials that should be recycled and not disposed of as domestic waste. Please note the relevant regulations for local disposal.

» MOUNTING ADVISE ROOM SENSORS

The Accuracy of the room sensors are influenced by the technical specifications as well as the positioning and the installation type.

During Assembly:

  • Seal mounting box (if present).
  • Installation type, air draught, heat source, radiation heat or direct sunlight can affect the measurement.
  • Bulding material specific properties of the installation place (brick-, concrete-, partition wall, cavity wall, …) can affect the measurement. (e.g.: Concrete accepts room temperature variation slower than cavity walls)

Assembly not recommendet in…

  • Air draught (e.g.: close to windows / doors / fans …)
  • Near heating sources,
  • Direct sunlight
  • Niches / between furniture / …

» MOUNTING ADVICE JOY
Plasterboard boxes shall be covered by wall paper or paint to avoid that the plasterboard box’s front rim will be partially visible underneath JOY.
Maybe consider using white plasterboard boxes (i.e. Kaiser 9063-77).

» APPLICATION NOTICE

Software| Software-description on https://www.thermokon.de/
---|---
MicroSD-Card| Data storage device for Update, Upgrade or configuration
– FAT-filesystem required
– NTFS and exFAT filesystems are not supported!
Bootloader| A MicroSD-card Bootloader for loading applications (Update, Upgrade) or configurations is integrated in the device.
active bootlader = ring illumination blinks (1 sec. cycle), display is not triggered!
Firmware Update| – Remove upper part, insert a microSD-card with valid Update file, mount upper part.
– Valid update file is recognized and the update process is started (ring illumination blinks in a  300ms cycle)
– New application is started automatically after Update (approx. 20-30 sec.).
– Remove upper part, to remove MicroSD-card from the device!
Device Configuration| – Remove upper part, insert a microSD-card with device configuration file, mount upper part.
– Configuration file is recognized and the device is configured.
– Device ready for operation.
– Remove upper part, to remove MicroSD-card from the device!

The parameters for the display, set point and the controller can only be changed via the configuration software.

» NOTES ON THE UPDATE FUNCTION
An update of the device software is only possible within the version main numbers.

thermokon JOY 5DO Digital Room Thermostat - FUNCTION

» CONFIGURATION VIA UCONFIG | MICRO SD-CARD

Configuration software:
uConfig | Windows 10 is required to use the uConfig configuration software
The JOY room thermostat can be parameterised using the uConfig configuration software. An SD card is used to transfer the created configuration file to the device.
The installer for the configuration software can be found in the Download- Section on our website. The installer retrieves all necessary files and plug- ins from our web server. In this version an update function is integrated in the software.
Download-Section

» TECHNICAL DATA

» JOY Fancoil 5DO | JOY Fancoil EC AO2DO | JOY Fancoil EC 3AO

Measuring values temperature, humidity (optional)
Measuring range temp. 0..+50 °C
Accuracy temperature ±1 K (typ. bei 21 °C)

Measuring range humidity
(optional)| 0..100% rH non-condensing
Accuracy humidity
(optional)| ±2% between 10..90% rH (typ. at 21 °C)
Control function| setpoint adjustment +0..+50 °C, fan stages
Display| LCD 2,5“, 240×160 px, white backlighting
Functions| integrated PI- and 2-point-/ 3-point-controllers, 2nd control loop: 2-point controller
Enclosure| PC and glass, optional black or white
Protection| IP30 according to EN 60529
Connection electrical| Terminal 1..8
terminal block max. 1,5 mm²| Terminal 9..12
terminal block max. 1.0 mm²
Ambient condition| 0..+50 °C, max. 85% rH non-condensing
Weight| 195 g
Mounting| flush mounted with standard EU box (Ø=60 mm)
» JOY Fancoil 5DO
Output switch contact| 3x normally open contacts (fan speed), 240 V, load max. 3 A| 2x normally open contacts (heating/cooling), 240 V, load max. 500 mA
Power supply| 85..260 V ~
Power consumption| max. 2,5 VA (260 V ~)
Inputs| DI1
input for NTC 10 K or floating contact| DI2
digital input for non-floating contact (230 V ~)| DI3
digital input for floating contact
» JOY Fancoil EC AO2DO
Output voltage| 1x 0..10 V, max. load 5 mA, EC FAN control
Output switch contact| 2x normally open contacts (heating/cooling), 240 V max. load 500 mA
Power supply| 85..260 V ~
Power consumption| max. 3 VA (260 V ~)
Inputs| DI1
input for NTC 10 K or floating contact| DI2
digital input for non-floating contact (230 V ~)| DI3
digital input for floating contact
» JOY Fancoil EC 3AO
Output voltage| 3x 0..10 V, max. load 5 mA, EC Fan control, heating & cooling or control 6-way valves (configurable via Software)
Power supply| 24 V = (±10%) oder 24 V ~ (±10%) SELV
Power consumption| max. 2,5 W (24 V =)
Inputs| DI1
input for NTC 10 K or floating contact| Di 2 | DI 3
2 digital inputs for non-floating contact

» FUNCTION DESCRIPTION – CONTROLLER/FAN STAGES

JOY Fancoil 5DO (85..260 V ~)| JOY Fancoil EC AO2DO (85..260 V ~)| JOY Fancoil EC 3AO (24 V ~/=)
---|---|---
PI controller (PWM) & 2-point/3-point controller
(configurable)| PI controller (PWM) & 2-point/3-point controller
(configurable)| PI controller (0..10 V)

Fan stages (all types)
In automatic mode the fan speed is linked to the controller. The assignment of the fan stage to the control (heating / cooling, only heating, only cooling) is freely selectable. To ensure that the fan motor starts reliably, a period of time can be configured in which  the fan starts with maximal value. Using one or more time channels, the fan control have to be set per timechannel and per period. Via the touch surface the user has the option to override the settings of the device every time. When the next time channel starts,  the fan speed is set to the configured value. The fan is set to automatic mode when the user changes the occupancy state (occupied ↔unoccupied).
Heating/ cooling with PI-controller (PWM) (only 5DO and EC AO2DO)
The time response of the PI control loop depends on the control parameters xp for the proportional area and tn for the reset time of the integral range. In case of an error, the P portion immediately changes the position value proportionally to the error variable,  while the integral portion takes effect after a certain time.
The resulting actuating variable is output as a pulse-width-modulated signal directly to the outputs.
Heating/ cooling with 2-point-/ 3-point-controller (only 5DO and EC AO2DO)
In the case of temperature control, the 2-point controller only knows the switching states heating ON and heating OFF. The 3-point controller also knows the switching state of cooling. Two – and three-point controller work with a hysteresis.
Heating/ cooling with PI-controller (0..10 V) (only EC 3AO and EC AO2DO)
The time response of the PI control loop depends on the control parameters xp for the proportional area and tn for the reset time of the integral range. In case of an error variable, the P portion immediately changes the position value proportionally to the error  variable, while the integral portion takes effect after a certain time.
The resulting manipulated variable is output as an analogue 0..10 V signal directly to the outputs.
EC Fan automatic mode with PI-controller (only EC 3AO and EC AO2DO)
(for EC AO2DO with two-point/three-point controller, the temperature range for controlling the 0..10 V EC fan is parameterised separately)
The 0..10 V (0..100%) control of the fan is proportional to the calculated manipulated variable of the PI controller.
example: Calculated actuating variable 65% = Fan control with 6,5 V Calculated actuating variable 22% = Fan control with 2,2 V
EC Fan manual with PI-controller (only EC 3AO and EC AO2DO)
Up to 5 steps (stages) can be set using the configuration software. The set number is divided linearly to the manipulated variable of 0..100%.

example: max. steps (stages) = 5
Stage 1 = 20% Stage 2 = 40% Stage 3 = 60% Stage 4 = 80% Stage 5 = 100%| max. steps (stages) = 3
Stage 1 = 33% Stage 2 = 66% Stage 3 = 100%
---|---

» DISPLAY

| Value Screen
internal sensor values external sensor values configurable)
(additional humidity value optionally configurable)|
---|---|---
| Header (value/ symbol display)
Time, weekday, date, ECO symbol (mode dependent)
Alarm symbol (higher priority than ECO-Symbol)|
| Footer (symbol display)
Symbols for heating/cooling mode, occupancy,  window contact, etc.
The symbol „Timechannel active“ is only shown  when a time channel is active.| thermokon JOY 5DO Digital Room Thermostat - FUNCTION5

» FUNCTION DESCRIPTION – BUTTONS

On the touch surface, there are adjustment options for setpoint and fan speed regulation.
While pressing these buttons, the white ring-LED of the Power-button lights up for visual feedback.

Fan speed adjustment: „fan speed
up“ / „fan speed down“| Setpoint change (setpoint range
± 3 °C, default, configurable).| Power button for Standbymode,
or Presence key| If the key is used as a
presence key at the same time,
the key must be pressed for at
least 3s, in all other cases a
short press is sufficient.
---|---|---|---
| |

3 seconds without any interaction, the display returns back to main screen.

Standby mode (not compatible with Keycard-switch function)
In standby mode the display and all outputs are switched off (controller deactivated). The frost and heat protection monitoring remains active.

Navigation Parametermenu
(up, down, left, right)| Open submenu (right)
In header left to leave the submenu| Confirmation
---|---|---
thermokon JOY 5DO Digital Room Thermostat - BUTTONS3| |

» DIAGNOSTICS MENU

To access the diagnostics menu, select the header in the startscreen of the parameter menu, and press the ENTER key. Here you will find various information, such as device type, software version, state of the inputs and outputs and controller state (current manipulated variable).

» CONFIGURATION

» Parametermenu

| Access to Parametermenu:
Press buttons for 3 seconds simultaneously
---|---

If no entry is made for 8 minutes, the parameter menu is left automatically.

» MENU → TIME CHANNELS
In the Time Channels menu, setpoint and timer can be set. Up to 3 time channels with 4 time periods each can be parameterized. The time channels are prioritised. Channel 3 has the highest priority. After selecting the line of the time channel to be edited, the  next submenu is called up with the “Right” key. It is possible to set any time period within one week in the first two lines with the “Left” (-)/ “Right”(+) keys. In addition, the ECO mode is available in the menu sections. In ECO mode, the dead zone between  heating and cooling is automatically set to the ECO dead zone configured in the “General Settings” menu (default: 10 K).

thermokon JOY 5DO Digital Room Thermostat - BUTTONS8

» MENU → INPUTS
Up to 3 inputs are configurable for functions such as windows contact, dew point, occupancy, change-over or external sensor option.
The overview of possible combinations can be found in the software specification of the JOY.

Sensor (NTC10K| The value of an external sensor will be shown if connected and configured accordingly. In this case, the room thermostat controls according to the external sensor. Alternatively, an external temperature sensor can be used at the universal input to protect floor heating. If a configured temperature is exceeded, the heating  sequence is suspended.
---|---
Change-Over DI| Which controller is active depends on the state of the Change- Over contact. (Factory default: contact open  heating controller active, contact closed cooling controller active). The terminals 4 and 5 are used as outputs  for heating rsp. cooling.
Change-Over Sensor| The Change-Over Sensor is used for switching between heating and cooling mode automatically. If the  temperature is below 22 ° C, the controller is in cooling mode. If it is above 25 ° C, it is a heating mode.
If an input is configured as a change-over, the room thermostat is automatically in 2-pipe operating mode  and both outputs (terminals 4 and 5) are used as outputs for heating rsp. cooling.
Window contact/Energyhold off| If a window contact is enabled via the digital input, the reference will switch to a setback set point (Heat  SP/Cool SP).
Dewpoint| An active dewpoint contact locks the cooling controller.
Occupancy| If occupancy-function is active, the symbol will be displayed automatically. In state of “unoccupied” the  heating set point is reduced by 2K (default setting) rsp. the cooling set point raised by 2K.
Keycard-Switch| When the card is not inserted, the device is switched in sleep mode. Operation of the keys is locked, the  display is switched off and the controller adjusts to the nominal values of the “unoccupied”-State.
Alarm contact| An alarm symbol can be shown in the header of the display. The backlight flashes when the alarm is active.  This symbol is in the same position as the ECO symbol. The alarm symbol has a higher priority and overwrites the ECO symbol!

» MENU → TIME/DATE
Time, Date and display format can be configured in the menu settings. The room thermostat is equipped with a real-time clock so that it automatically adjusts for daylight-saving time. This function can be disabled in the datetime settings.

thermokon JOY 5DO Digital Room Thermostat - MENU2

» MENU → SENSOR SETTINGS
Offset correction for internal and external sensor value.
The temperature display can also be changed from °C to °F.

» MENU → COMMON SETTINGS

thermokon JOY 5DO Digital Room Thermostat - COMMON
SETTINGS

Common device settings:
Brightness
Valve protection
ECO deadband
Fanstages (5DO only)
Language
Factory setting (reset)

Brightness
Configuration of the LCD brightness/ LED ring brightness during button operation/ usage.

Valve protection
A valve protection function actuates the heating and cooling valves regularly to prevent locking during non-usage times.
The function is executed fridays at 11.00 (heating valve) and 11.15 (cooling valve). The corresponding valve is triggered for 5 minutes, if not activated during the last 96 hours.

ECO deadband
The dead band can be adjusted (default 10.0 K)

  • further information in the software specification file

Factory setting
By selecting “Factory setting”, the room thermostat will be reset and restore the device to factory default settings.

» CONNECTION PLAN

JOY Fancoil 5DO (85..260 V ~)
| JOY Fancoil EC AO2DO (85..260 V ~)
| JOY Fancoil EC 3AO (24 V ~/=)
---|---|---
1 Fan Speed 3
2 Fan Speed 2
3 Fan Speed 1
4 Cooling
5 Heating
6 Digitaler Input 2 (230 V)
7 L
8 N
12 GND DI 3
11 Digital Input 3
10 GND DI 1
9 Digital Input 1 (or NTC10K)| 1 EC Fan GND
2 EC Fan (0..10 V)
4 Cooling
5 Heating
6 Digital Input 2 (230V)
7 L
8 N
12 GND DI 3
11 Digital Input 3
10 GND DI 1
9 Digital Input 1 (or NTC10K)| 1 Digital Input 2
2 EC Fan (0..10 V)
3 Cooling (0..10 V) or 6-way valve
4 Heating (0..10 V) or 6-way valve
5 GND DI 2
6 GND
7 24 V = (±10%) or 24 V ~ (±10%)
8 GND
12 GND DI 3
11 Digital Input 3
10 GND DI 1
9 Digital Input 1 (or NTC10K)

Note: Parallel connection of the potential-loaded inputs is not permitted!
If the operating mode (change-over DI) of several devices is to be switched together by one contact, the potential-free 230V input must be used (DI2, only possible with the 230V version). It must be ensured that the same phase is used for jointly switched devices.

» DIMENSIONS (MM)

thermokon JOY 5DO Digital Room Thermostat - JOY
Fancoil3

» ACCESSORIES (OPTIONAL)

Frame for surface mounting JOY pure white Item No. 760201
Frame for surface mounting JOY black Item No. 760951
Decorative frame pure white for JOY Item No. 681452
Decorative frame black for JOY Item No. 740951
MicroSD card 2GB Item No. 500098

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany ·
tel: +49 2778 6960-0 ·
fax:-400 ·www.thermokon.com · email@thermokon.com
JOY_Fancoil_Datasheet_en © 2023

Documents / Resources

| thermokon JOY 5DO Digital Room Thermostat [pdf] User Manual
JOY 5DO Digital Room Thermostat, JOY 5DO, Digital Room Thermostat, Room Thermostat, Thermostat
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

thermokon User Manuals

Related Manuals