AERIC AERP101HAW Portable Air Conditioner with Heat User Manual

June 17, 2024
AERIC

AERIC AERP101HAW Portable Air Conditioner with Heat

AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-
product

IMPORTANT SAFETY INTRODUCTIONS

READ THIS MANUAL

  • Inside you will find many helpful tips on how to use and maintain your air conditioner properly.
  • Just a little preventive care on your part can save you a great deal of time and money over the life of your air conditioner.
  • You’ll find many answers to common problems in the chart of troubleshooting tips. If you review our chart of Troubleshooting.
  • Tips first, you may not need to call for service at all.
  • To prevent injury to the user or other people and property damage, the following instructions must be followed.
  • Incorrect operation due to ignoring instructions may cause harm or damage. The seriousness is classified by the following indications.AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1 \(1\)

WARNING

AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1
\(2\)

CAUTIONAERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1
\(3\)

CAUTION

  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.
  • Children should be supervised to ensure that they do not play with the appliance.
  • If the SUPPLY CORD is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons to avoid a hazard.
  • The appliance shall be installed per national wiring regulations.
  • Do not operate your air conditioner in a wet room such as a bathroom or laundry room.
  • The appliance with an electric heater shall have at least 2 feet of space for the combustible materials.
  • Contact the authorised service technician for repair or maintenance of this unit.

NOTE

  • The power supply cord with this air conditioner contains a current detection device designed to reduce the risk of fire.
  • Please refer to the section Operation of Current Device for details.
  • If the power supply cord is damaged, it cannot be repaired it must be replaced with a cord from the
  • Product Manufacturer.

WARNING

  • Avoid fire hazards or electric shock.
  • Do not use an extension cord or an adaptor plug.
  • Do not remove any prong from the power cord.

Grounding-type wall receptacle

Power supply cord with 3-prong grounding plug and current detection device

WARNING For Your Safety

  • Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.

WARNING Prevent Accidents

  • To reduce the risk of fire, electrical shock, or injury to persons when using your air conditioner, follow basic precautions, including the following:
  • Be sure the electrical service is adequate for the model you have chosen. This information can be found on the serial plate, which is located on the back of the cabinet.
  • Be sure the air conditioner has been securely and correctly installed according to the installation instructions in this manual. Save this manual for possible future use in removing or installing this unit.
  • When handling the air conditioner, be careful to avoid cuts from sharp metal fins on the front and rear coils.

WARNING Electrical Information

  • The complete electrical rating of your new portable air conditioner is stated on the serial plate.
  • Refer to the rating when checking the electrical requirements.
  • Be sure the air conditioner is properly grounded. To minimize shock and fire hazards, proper grounding is important.
  • The power cord is equipped with a three-prong grounding plug for protection against shock hazards.
  • Your air conditioner must be used in a properly grounded wall receptacle.
  • If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit breaker, have a qualified electrician install the proper receptacle.
  • Ensure the receptacle is accessible after the unit installation.
  • Do not run the air conditioner without installing the exhaust hose and window panel in place.
  • This could result in mechanical damage to the air conditioner.
  • Do not use an extension cord or an adapter plug.

WARNING

  • All wiring must comply with local and national electrical codes and be installed by a qualified electrician, If you have any questions regarding the following instructions, contact a qualified electrician.
  • Check the available power supply and resolve any wiring problems before installation and operation of this unit.
  • Only install and operate this appliance as outlined in this instruction manual. At all times, use care when using this appliance.
  • The appliance shall be installed by national wiring regulations.
  • The appliance should be transported upright or on its side. Any internal circuit water should be emptied before moving. Do not turn on the appliance for at least one hour before starting it.
  • Do not store anything on top of the appliance, especially heavy or hot objects.
  • Do not store the appliance covered with plastic bags.
  • Please follow the regulations and guidelines for proper disposal of packaging as well as electrical devices in your area. Check with your local authority or retailer for recycling options.
  • Do not place the unit in front of curtains or drapes in case they fall against the back air intake.
  • This appliance is for household use only.

WARNING

  • Do not wet the housing or control panel.
  • Do not cover the air outlet while in use.
  • Do not place objects or let any person sit on top of the unit.
  • Do not attempt to remove any part of the casing unless by an authorised technician.
  • Remove the plug from the socket if the unit is not being used for long periods.
  • Use only the correct power supply AC 115V~60Hz.

SPECIFICATIONS

Figures noted, in the contents are for reference only; variation may result due to application in different countries or regions and shall be based on the best of practical operation.

NOTE

  • The wiring diagram affixed inside the rear panel

NOTE

  • Waste electrical products should not be disposed of with household waste.
  • Please recycle where facilities exist. Check with your local authority or retailer for recycling advice.
  • Applicable for models with Heating features only.

WARNING (FOR USING R32 REFRIGERANT ONLY)

  • READ THE MANUAL CAREFULLY BEFORE USING THE APPLIANCE.
  • Stagnation of possible leaks of refrigerant gas in unventilated rooms could lead to fire or an explosion hazard should the refrigerant come in contact with electric heaters, stoves or other sources of ignition.
  • Use care when storing the appliance to prevent mechanical faults.
  • Only persons authorized by an accredited agency certifying their competence to handle refrigerants in compliance with sector legislation should work on refrigerant circuits.
  • Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
  • The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance) and ignition sources or (for example: an operating electric heater) close to the appliance.
  • Do not pierce or burn.
  • Be aware that refrigerants may not contain an odour.
  • Compliance with national gas regulations shall be observed.
  • Keep ventilation openings clear of obstruction.
  • The appliance shall be stored to prevent mechanical damage from occurring.
  • A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
  • Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely following an industry-recognized assessment specification.
  • Servicing shall only be performed as recommended by the equipment manufacturer.
  • Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
  • DO NOT modify the length of the power cord or use an extension cord to power the unit.
  • DO NOT share a single outlet with other electrical appliances. The improper power supply can cause fire or electrical shock.
  • Please follow the instructions carefully to handle, install, clear or service the air conditioner to avoid any damage or hazard.
  • Flammable Refrigerant R32 is used within the air conditioner. When maintaining or disposing of the air conditioner, the refrigerant (R32) shall be properly recovered and not discharged into the air.
  • No open fire or device that may generate spark/arcing shall be around an air conditioner to avoid causing ignition of the flammable refrigerant used. Please follow the instructions carefully to store or maintain the air conditioner to prevent mechanical damage from occurring.
  • Flammable refrigerant R32 is used in air conditioners. Please follow the instructions carefully to avoid any hazards.AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1 \(6\)

Explanation of Symbols

Explanation of symbols displayed on the unit (The unit adopts R32 Refrigerant only)

AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1
\(7\)

WARNING (FOR USING R32 REFRIGERANT ONLY)

  1. Transport of equipment containing flammable refrigerants

    • See transport regulations.
  2. Marking of equipment using signs See local regulations.

  3. Disposal of equipment using flammable refrigerants

    • See national regulations.
  4. Storage of equipment/appliances

    • The storage of equipment should be by the manufacturer’s instructions.
  5. Storage of packed (unsold) equipment

    • Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge.
    • The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
  6. Information on servicing

    • a) Checks to the area: Before beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with before conducting work on the system.

    • b) Work procedure: Work shall be undertaken under a controlled procedure to minimize the risk of a flammable gas or vapour being present while the work is being performed.

    • c) General work area: All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

    • d) Checking for the presence of refrigerant: The area shall be checked with an appropriate refrigerant detector before and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

    • e) Presence of fire extinguisher: If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

    • f) No ignition sources: No person carrying out work about a refrigeration system that involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repair, removing and disposal, during which flammable refrigerant can be released to the surrounding space. Before work takes place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed.

    • g) Ventilated area: Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.

    • h) Checks to the refrigeration equipment: Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:

    • The charge size is by the room size within which the refrigerant-containing parts are installed;

    • The ventilation machinery and outlets are operating adequately and are not obstructed;

    • If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;

    • Marking the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;

    • Refrigeration pipes or components are installed in a position where they are unlikely to be exposed to any substance that may corrode refrigerant-containing components unless the components are constructed of materials that are inherently resistant to being corroded or are suitably protected against being so corroded.

    • i) Checks to electrical devices: Repair and maintenance of electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
      Initial safety checks shall include:

    • That capacitors are discharged: this shall be done safely to avoid the possibility of sparking;

    • That no live electrical components and wiring are exposed while charging, recovering or purging the system;

    • That there is continuity of grounding.

  7. Repairs to sealed components

    • a) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon before any removal of sealed covers, etc. If it is necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
    • b) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.
    • Ensure that the apparatus is mounted securely.
    • Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be to the manufacturer’s specifications.
    • NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. intrinsically safe components do not have to be isolated prior to working on them.
  8. Repair to intrinsically safe components

    • Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while living in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
  9. Cabling

    • Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
  10. Detection of flammable refrigerants

    • Under no circumstances shall potential sources of ignition be used in the search for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
  11. Leak detection methods

    • The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate or may need re-calibration.
    • (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
    • Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
    • If a leak is suspected, all naked flames shall be removed/ extinguished. If leakage of refrigerant is found which requires brazing, all of the refrigerants shall be recovered from the system, or isolated (utilizing shut-off valves) in a part of the system remote from the leak.
    • Oxygen-free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
  12. Removal and evacuation

    • When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, best practice must be followed since flammability is a consideration. Opening of the refrigeration systems shall not be done by brazing. The following procedure shall be adhered to:
    • Remove refrigerant;
    • Purge the circuit with inert gas;
    • Evacuate;
    • Purge again with inert gas;
    • Open the circuit by cutting or brazing.
    • The refrigerant charge shall be recovered into the correct recovery cylinders.
    • The system shall be flushed with OFN to render the unit safe.
    • This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task.
    • Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to the atmosphere, and finally pulling down to a vacuum.
    • This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
    • This operation is vital if brazing operations on the pipe work are to take place.
    • Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
  13. Charging procedures

    • In addition to conventional charging procedures, the following requirements shall be followed.
    • Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
    • Cylinders shall be kept upright.
    • Ensure that the refrigeration system is earthed before charging the system with refrigerant.
    • Label the system when charging is complete (if not already).
    • Extreme care shall be taken not to overfill the refrigeration system.
    • Before recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but before commissioning. A follow-up leak test shall be carried out before leaving the site.
  14. Decommissioning

    • Before carrying out this procedure, the technician must be completely familiar with the equipment and all its details.
    • It is recommended good practice that all refrigerants are recovered safely.
    • Before the task is carried out, an oil and refrigerant sample shall be taken in case analysis is required before the re-use of reclaimed refrigerant.
    • Electrical power must be available before the tasks commence.
    • a) Become familiar with the equipment and its operation.
    • b) Isolate system electrically.
    • c) Before attempting the procedure ensure that: Mechanical handling equipment is available, if required, for handling refrigerant cylinders; All personal protective equipment is available and being used correctly; The recovery process is supervised at all times by a competent person; Recovery equipment and cylinders conform to the appropriate standards.
    • d) Pump down the refrigerant system, if possible.
    • e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
    • f) Make sure that the cylinder is situated on the scales before recovery takes place.
    • g) Start the recovery machine and operate following the manufacturer’s instructions.
    • h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
    • i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
    • j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from the site promptly and all isolation valves on the equipment are closed off.
    • k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
  15. Labelling

    • Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
    • The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
  16. Recovery

    • When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.

    • When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.

    • Ensure that the correct number of cylinders for holding the total system charge is available.

    • All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valves and associated shut-off valves in good working order.

    • Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

    • The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.

    • In addition, a set of calibrated weighing scales shall be available and in good working order.

    • Hoses shall be complete with leak-free disconnect couplings and in good condition.

    • Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.

    • Consult the manufacturer if in doubt.

    • The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.

    • Do not mix refrigerants in recovery units especially not in cylinders.
      If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant.

    • The evacuation process shall be carried out before returning the compressor to the suppliers. Only electric heating of the compressor body shall be employed to accelerate this process.

    • When oil is drained from a system, it shall be carried out safely.

IDENTIFICATION OF PARTS

  1. Control panel
  2. Air outlet
  3. Handle hole
  4. Caster
  5. Air filter
  6. Air intake (Evaporator)
  7. Air outlet (Heat exchange)
  8. Air intake (Condenser)
  9. Water outlet drain

Note: Please ensure the water outlet drain is well installed before use.

OPERATION

CONTROL PANEL

AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1
\(10\)

  1. Power control
  2. Mode control
  3. Fan Speed Control
  4. Timer
  5. Timer / Temp set control
  6. Swing Control
  7. Tank Full Light

POWER CONTROL

  • The power control turns the unit on and off.

MODE CONTROL

  • Settings:
    • Cooling
    • Dehumidify
    • Fan
    • Heating

The settings are adjusted with the Mode Control button. A light will indicate which setting is currently being used. Applicable for models with Heating features only.

COOLING MODE

  • During the cooling mode, the air is cooled and hot air is exhausted to the outside air through the exhaust tube.
  • Adjust the fan speed air through the temperature to suit your desired comfort level. Temperature setting range is 61°F ~ 89°F.
  • Note: The air exchange hoses must vent outside the room when using cool mode.

DEHUMIDIFY MODE

  • Air is dehumidified as it passes through the unit, without being in full cooling mode. If the room temperature is higher than 77 °F, the fan speed can be adjusted; otherwise, fan speed is fixed to “low “.
  • Note: If the unit is to be used as a dehumidifier, do not connect the exhaust hose, let the warm air return to the room. Continuous drainage is then necessary.

FAN MODE

  • Air is circulated throughout the room with no cooling.
  • Note: The unit does not need to be vented in Fan mode.

HEATING MODE

  • When the heating mode is selected, the indicator light will shine red. Heating is activated only when the ambient temperature is below 77°F. In this mode, the desired temperature can be set between 61-77°F.
  • Note: The air exchange hoses must vent outside the room when using heating mode.

FAN SPEED CONTROL

  • The Fan Speed Control has 3 settings: High, Medium and Low.

TIMER Auto turn off:

  • With the machine in running mode, press the timer button for or setting timer control. Press ” + ” or” – ” to select several hours you would like the unit to function before it automatically shuts off.

Auto turn on:

  • With the machine in standby mode, press the timer button to set the timer control. Press ” + ” or ” -” to select several hours before the unit automatically starts running in air conditioning mode.
  • Note: The time is adjustable between 1-and 24 hours.

TEMPERATURE CONTROLS

  • Used for adjusting the thermostat.
  • The default display is room temperature.
  • In cooling/heating* mode, when the ” + ” or ” – ” button is pressed, the set temperature is displayed and may be adjusted.
  • After a few seconds, the display will revert to room temperature. Temperature is only adjustable in cooling/heating* mode.
  • Note: By pressing both ” + ” / ” – ” buttons at the same time, the display will switch between Celsius and Fahrenheit.

SWING CONTROL

  • The SWING button moves the grille flap, evenly distributing the air into the room.
  • When the SWING button is pressed, the flap will begin to move up and down alternatively.
  • If pressed again, the flap will be locked into its current position
  • When the button is next pressed, the flap will start to move up and down again.
  • Note: to avoid damaging the internal mechanisms, the flap must not be moved manually.

TANK FULL LIGHT
If the internal tank becomes full, the Tank Full Light will turn red and the unit will not operate until the unit has been drained. To drain excess water:

  1. Begin by placing a pan under the water outlet drain.
  2. Unscrew the drain cover and let the water drain into the pan. When the water stops draining out, replace the drain cover.
  3. Remove the pan of water and empty into a sink.
  4. Operate the unit in Fan Mode to dry the interior of the unit.
    • NOTE: After switching the air conditioner off, you must wait 3 minutes before switching it back.

REMOTE CONTROL

The functions work the same as your air conditioner’s touch controls. All key functions can be accessed from the remote control.

  1. Power Control: On / Off
  2. Mode Control:
    • Cooling
    • Dehumidify
    • Fan
    • Heating
  3. Fan Speed Control: High, Medium and Low.
  4. Timer Control:
    • In running mode: Auto switch off
    • In standby mode: Auto switch on
  5. Timer/Temperature Set Control
    • Used for adjusting the timer and thermostat.
    • The default display is room temperature.
    • When the “+ ” or “-” button is pressed, the set temperature is displayed and may be adjusted. After a few seconds, the display will revert to room temperature.
  6. Swing Control: Press this button to send the air outlet grill swing automatically.
  7. Display Control: Press this button to turn the front and top panel lights on and off.

BATTERIES

  • Remove the cover on the back of the remote control and insert the batteries with the(+) and (-) poles pointing in the proper direction.

CAUTION

  • Use only AAA or lEC R03 1.5V batteries.
  • Remove the batteries if the remote control is not used for a month or longer.
  • Do not attempt to recharge the supplied batteries.
  • All batteries should be replaced at the same time.
  • Do not dispose of the batteries in a fire as they may explode.

INSTALLATION INSTRUCTIONS

ACCESSORIES INCLUDE

AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1
\(14\)AERIC-AERP101HAW-Portable-
Air-Conditioner-with-Heat-fig-1 \(25\)

INSTALLATION
At least 19.7 inches (50 cm) air space between the front/ left/right/top sides of the portable air conditioner and the adjacent obstacle and at least 31.5 inches (80 cm) of air space between the rear side of the portable air conditioner and adjacent obstacle should be maintained during normal operation.

  1. Slide the hose assembly with (#2) exhausted connector into the rear panel.
  2. Insert the window panels B and C to each end of main panel A. Adjusting to fix the length of window panels by using the screws and nuts mounted on the 2 ends of main panel A.
  3. Open the window and place window panels into the window. Adjust the extension panels to fit the width or height of the window. Use the screw and nuts to tighten or loosen the extension panels.
  4. Insert the other end of the exhaust hose assembly onto the window panel and turn counterclockwise to secure.
  5. Plug the power cord into the wall outlet and press the “Reset” button.
  6. When removing the portable air conditioner for storage, the window panel may be left in place. Simply place the cover (#5) to cover the hole on the window panel.

CONTINUOUS DRAINAGE

When a suitable drainage system is available nearby, the continuous drainage function can be initiated by following these steps.

  1. Prepare a hose (inside dia. 0.51 inches (13mm), not included) to drain out water.
  2. Take out the drain cover from the drainage outlet.
  3. Connect the hose with the drainage outlet.

IMPORTANT:

  • The drain hose must be installed during dehumidifier mode.
  • In cooling/heating* mode, when the surrounding humidity is high, water may not fully evaporate.
  • It will therefore be necessary to drain excess water from the internal tank of the unit, and continuous drainage is recommended.

TROUBLESHOOTING

AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1
\(21\)

CARE AND MAINTENANCE

AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1
\(22\) AERIC-AERP101HAW-Portable-
Air-Conditioner-with-Heat-fig-1 \(23\)AERIC-AERP101HAW-Portable-Air-Conditioner-with-Heat-fig-1
\(24\)

WARRANTY

LIMITED CARRY IN APPLIANCE WARRANTY

  • This product is warranted to be free from the manufacturer’s defects in material and workmanship, provided that the unit is used under the normal operating conditions intended by the manufacturer.
  • This warranty is available only to the person to whom the unit was originally sold by the manufacturer or by an authorized distributor of the manufacturer and is non-transferable.

TERMS OF WARRANTY

  • Plastic parts are warranted for thirty (30) days only from the purchase date, with no extensions provided.

FIRST 24 Months:

  • During the first twenty-four (24) months, any functional parts of this product found to be defective will be repaired or replaced, at the warrantor’s option, at no charge to the ORIGINAL purchaser.
  • Please keep your purchase receipt as a warranty proof of purchase date.

To obtain service, see the contact information below:

RETURN TO THE STORE WHERE PURCHASED FOR REPLACEMENT.

EXCLUSIONS

  • Save as herein provided by the manufacturer, there are no other warranties, conditions, representations or guarantees, express or implied, made or intended by the manufacturer or its authorized distributors and all other warranties, conditions, representations or guarantees, including any warranties, conditions, representations or guarantees under any Sale of Goods Act or like legislation or statue is hereby expressly excluded. Save as herein provided, the manufacturer shall not be responsible for any damages to persons or property, including the unit itself, howsoever caused or any consequential damages arising from the malfunction of the unit and by the purchase of the unit, the purchaser does hereby agree to indemnify and hold harmless manufacturer from any claim for damages to persons or property caused by the unit.
  • As some states do not allow the limitation or exclusion of incidental or consequential damages or do not allow limitation on implied warranties, the above limitations and exclusions may not apply to you.
  • This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.

GENERAL PROVISIONS

No warranty or insurance herein contained or set out shall apply when damage or repair is caused by any of the following:

  1. Power failure.
  2. Damage in transit or when moving the appliance.
  3. Improper power supply such as low voltage, defective house wiring or inadequate fuses.
  4. Accident, alteration, abuse or misuse of the appliance such as inadequate air circulation in the room or abnormal operating conditions (extremely high or low room temperature). Use for commercial or industrial purposes (ie. If the appliance is not installed in a domestic residence).
  5. Fire, water damage, theft, war, riot, hostility, acts of God such as hurricanes, floods, etc.
  6. Service calls result in customer education.

Please read the manual carefully before using the appliance.

  • AERIC LLC
  • Ramsey New Jersey 07446
  • USA

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

AERIC User Manuals

Related Manuals