Vent-Axia MVDC-MS Lo-Carbon Multivent MVDC and Sentinel Multivent User Guide
- June 17, 2024
- Vent-Axia
Table of Contents
Vent-Axia MVDC-MS Lo-Carbon Multivent MVDC and Sentinel Multivent
Full instructions and feature explanations are available online by scanning
the QR code or by visiting:
https://www.vent-axia.com/range/centralised-mechanical-extract-ventilation-
mev
Installation and Wiring Instructions
- Do not install this product in areas where the following may be present or occur:
- Excessive oil or a grease laden atmosphere.
- Corrosive or flammable gases, liquids or vapours.
- Subject to direct water spray from hoses.
- Ambient temperatures higher than 40°C and lower than -20°C.
- Possible obstructions that may hinder access to or removal of the unit.
- All wiring must be in accordance with the current IET wiring regulations BS7671, or appropriate standards of your country. Installation should be inspected and tested by a suitably qualified person after completion.
- Ensure the mains supply (voltage, frequency and phase) complies with the rating label.
- The unit should be provided with a local double pole fused spur fitted with a 3A fuse having a contact separation of at least 3mm.
- Units showing on the rating label incorporate an earth connection for functional purposes only.
- Units showing on the rating label have a Protective Earth.
- Precautions must be taken to avoid the backflow of gases into the building from the open flue of gas or other fuel-burning appliances.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
- Young children should be supervised to ensure that they do not play with the appliance.
- Cleaning and user maintenance shall not be made by children
- The installer is responsible for the installation and electrical connection of the unit on site. It is the responsibility of the installer to ensure that the equipment is safely and securely installed and left only when mechanically and electrically safe.
- All regulations and requirements must be strictly followed to prevent hazards to life and property, both during and after installation, and during any subsequent servicing and maintenance.
- Certain applications may require the installation of sound attenuation to achieve the sound levels required.
- The unit must not be connected directly to a tumble drier.
- The exhaust grille should be located at least 600mm away from any flue outlet.
- This product and associated duct installation should be carried out in accordance with the Domestic Ventilation Compliance Guide.
Models that support Radio and Bluetooth communication the below applies
- Bluetooth variants contain FCC ID: S9NSPBTLERF
- Bluetooth LE: -12dBm EIRP (63μW), nominal 2450MHz.
- Bluetooth v4.1 compliant
- Bluetooth and radio variants obtained RED certificate: No. 0051-RED-0011 REV. 0
- Zirconia Wireless: -14dBm EIRP nominal 868MHz.
- The manufacturer hereby assure that this type of Bluetooth radio and 868MHz radio equipment complies with RED Directive 2014/53 / EU
The full text of the EU Declaration of Conformity can be found at the following URL: https://www.vent-axia.com/range/centralised-mechanical-extract- ventilation-mev
INSTALLATION
Position the unit, taking into consideration the position of the rooms to be
ventilated, the exhaust position and the electrical services. Ensure there is
adequate access for installation and maintenance.
If the unit is sited in the heated void of the dwelling a condensate drain
should not be necessary.
When sited in a cold loft, consideration should be given to fitment of a
condensate drain. Alternatively, the unit and ducting can be externally
insulated to minimize condensation within the units housing.
To reduce the system resistance in your duct system, and therefore lower the speed, power consumption and noise of the fan, follow these guidelines:
- Keep the length of duct runs to a minimum, particularly the exhaust duct run.
- If you need to use flexible ducting, make sure that it is fully extended and not crushed, sagging or torn.
- Try to minimize the use of diffusers/valves by having similar length duct runs to the inlets.
- The bend radius (measured to the inside of the bend) should be at least 1x the duct diameter.
- Avoid having any bends, filters or other obstructions within 250mm of the fan inlets and outlet.
Securely mount the unit through the mounting holes on the casing using
appropriate fixings (not supplied) for the mounting substrate. Fixings to be
capable of securing 4x the weight of the unit. Unit weight: 4.1kg.
Anti-vibration mounts, acoustic mats or rubber bushes can also be used.
Mounting point dimensions and installation example shown below:
To maintain the IPx2 rating of the unit, the unit must not be mounted with the
cover removal slots facing upwards, or at an angle where they are visible from
above.
All other orientations are acceptable.
WIRING
WARNING: THE UNIT AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE. THIS UNIT MUST BE EARTHED.
-
To remove the cover, use a coin or similar; depress the retaining tabs via the slots in the side of the unit.
-
With the power off, connect a suitable mains power cable from a switched, fused spur to the screw terminal block. Use the cable clamps and clip provided to secure the lead.
-
Two mains voltage Live Switched (LS1 and LS2) connections are provided and can be used to trigger a change in speed. Common inputs would be from a bathroom lighting circuit. When commissioning the unit, a delay on timer and an overrun timer can be selected and adjusted in the software using the buttons and screen. See Commissioning section on page 5 of this document for details.
-
The switched live output (230Vac) from any other switch or controller, (such as a simple latching pullcord or push-button switch, humidistat or PIR detector) can be connected to the LS terminal instead of connecting to a lighting circuit.
-
Important: Use 4-core, low voltage, twisted pair, telecoms type cable for accessories (Vent-Axia part number 459931). Accessories are connected via the IO (Input Output) PCB; see the Low Voltage
Connections diagram in the Main fitting and wiring guide, downloadable on the website. -
There are no delay-on or overrun timers with the volt-free connection as the controller should determine when the fan is running at Boost or Normal speeds. Use the LS connection described above if you want a timer.
-
Units showing on the rating label incorporate an earth connection for functional purposes only.
Units showing on the rating label have a Protective Earth.
Main power connections
The LS1, LS2 and NS terminals are electrically isolated.
Note : Neutral link between 2 & 6 should be removed if different RCD
protection circuits are used for mains power a & Live Switch connections.
Note : Ensure all live & neutral are isolated before servicing.
Connection | Description |
---|---|
1 | L |
2 | N |
3
| | Functional Earth
| Protective Earth
4| LS1| Live Switched 1, (220-240Vac), isolated
5| LS2| Live Switched 2 (220-240Vac), isolated
6| NS| Neutral Switched, isolated
7| N + NS| Link Wire (Blue)
COMMISSIONING
- Commissioning and configuration on all products is supported by the 3-digit user interface and associated push buttons:
- When powered on, the unit will display the firmware revision number, after a few seconds the unit will display the first option in the User Parameters (see table on next page).
- The display will enter standby mode after defined timeout (default 10min) or user selects “END” option in menu, press the Mode button to turn the display back on.
- Changes to the settings can be made via the + and – buttons, the Mode button will accept changes and move onto the next menu option.
- When setting the speeds, there is an internal logic: low<Normal<Boost<Purge. I.e., Boost is always higher than Normal.
- The actions for each of the Live Switched (LS), inputs are selectable. The setting for delays and over run timers are applicable to all inputs.
- If the unit being commissioned is not fitted with the relevant hardware, the associated menu options will not be available.
Pairing wired and wireless accessories (If supported by model)
To enter pairing mode, with the display illuminated, press and hold the Mode
button until LED illuminates solid White, release the Mode button and the LED
will flash White, indicating pairing mode is active along with the paired
device count on the display. Pairing mode will time out after 5 minutes.
To activate pairing on the accessory, refer to the device manual.
Control via Bluetooth
Selected units can be controlled via the Bluetooth linked App.
With the display on, press and hold the Mode button until the Blue LED
illuminates, release the button and the LED will flash signifying that pairing
mode is enabled.
Use the QR codes on the coversheet to download the App.
SERVICING & MAINTENANCE
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTENANCE.
- At intervals appropriate to the installation, the fan should be inspected and cleaned to ensure there is no significant buildup of dirt or other deposits.
- To inspect the inside of the product, isolate the power, use a coin or similar to depress the cover retention clips.
- Remove the cover, remove the scroll assembly by unscrewing the two screws and unclipping the clips in the two corners and pulling away. If necessary, vacuum the inside of the unit.
- The fan has sealed for life bearings, which do not require lubrication. Expected service life is at least 45,000 hours continuous running.
- Check all fixings are tight and secure
User Configurable Parameters
Display text | Function | Selections | Default |
---|---|---|---|
Lxx | Low speed | 1 to 97% motor speed | 10% |
nxx | Normal speed | 2 to 98% motor speed | 25% |
bxx | Boost speed | 3 to 99% motor speed | 35% |
Pxx | Purge Speed | 4 to 100% motor speed | 50% |
LS1 | Live switch 1 | Low, Boost or Purge speed | Low |
LS2 | Live switch 2 | Low, Boost or Purge speed | Boost |
LS3 | Live switch 1&2 | Low, Boost or Purge speed | Purge |
c-n | Comfort mode | Comfort mode – yes or no | No |
d-n | Delay On | Delay on – yes or no | No |
dxx | Delay On time | Delay to boost duration 1 to 60 minutes | 10m |
o-n | Overrun | Overrun – yes or no | No |
oxx | Overrun time | Overrun duration 1 to 60 minutes | 10m |
r-y | Humidity – Rapid Rise | Rapid rise – yes or no | No |
A-n | Humidity – Ambient Response | Ambient response – yes or no | No |
hxx | Humidity threshold | Ambient response threshold 40 to 90% RH | 70% |
C2b | CO2 threshold boost | Boost threshold 650 – 4950 PPM in increments of 50 |
100
C2P| CO2 threshold purge| Purge threshold 700– 5000 PPM in increments of 50|
120
A1LA| Analogue 1 – low action| Low, Normal, Boost or Purge speed| Low
A1HA| Analogue 1 – high action| Low, Normal, Boost or Purge speed| Boost
A1tL| Analogue 1 – low threshold| Analogue Input Threshold Low 1 – 99| 15
A1tH| Analogue 1 – high threshold| Analogue Input Threshold High 1 – 99| 75
A2LA| Analogue 2 – low action| Low, Normal, Boost or Purge speeds| Low
A2HA| Analogue 2 – high action| Low, Normal, Boost or Purge speeds| Boost
A2tL| Analogue 2 – low threshold| Analogue Input Threshold Low 1 – 99| 15
A2tH| Analogue 2 – high threshold| Analogue Input Threshold High 1 – 99| 75
D1| Digital input 1 Action| Low, Boost or Purge speeds| Low
D2| Digital input 2 Action| Low, Boost or Purge speeds| Boost
unl| Unlock code| Turn on/off the menu lock| – – –
PIn| Display Pin| 3 characters A to 9| LoC
dtxx| Display time| Adjust how long the display is illuminated| 10m
rot| Rotate display| Invert the display| rot
hu| Humidity| Show the current internal humidity| %
tu| temperature| Show the current internal temperature| °C
CO2| CO2| Show the current CO2 level| PPM
rEf| Calibration reference value| 40 to 200| 40 (400ppm)
cAL| Calibration Mode| Y to enable| n
end| end| End of menu (loop to start)|
If the unit being commissioned is not fitted with the relevant hardware, the associated menu options will not be available.
Product Fiche
Name: | Vent-Axia |
---|
Model ID (Stock Ref.) :
| ****
437634C
| ****
443298B
| ****
445655B
| ****
495360
| ****
495361
| ****
407849A
496186
| ****
495362
| ****
495363
SEC Class| B| B| B
SEC Value (‘Average’)| -27.2| -27| -26.9
SEC Value (‘Warm’)| -11.7| -11.5| -11.4
SEC Value (‘Cold’)| -54.3| -54.1| -54.0
Label Required? (Yes/No=Out of scope)| Yes
Declared as: RVU or NRVU/UVU or BVU| RVU/UVU
Speed Drive| Multi Speed
Type HRS (Recuperative, Regenerative, None)| None
Thermal Eff: [ (%), NA(if none)]| N/A
Max. Flow Rate (m3/h)| 338.8| 400| 505.1
Max. Power Input (W): (@Max.Flow Rate)| 43| 52| 85
LWA: Sound Power Level dB)| 46.4| 50.7| 52.2
Ref. Flow Rate (m3/s)| 0.066| 0.078| 0.098
Ref. Pressure Diff. (Pa)| 201| 203| 206
SPI [W/(m3/h)]| 0.07| 0.08| 0.09
Control Factor & Control Typology: (CTRL/ Typology)|
Control Factor; CTRL| 0.65
Control Typology
| ****
Local Demand Control
Declared: -Max Internal & External Leakage Rates(%) for BVUs or carry over (for regenerative heat exchangers
only), Ext. Leakage Rates (%) for Ducted UVUs;
| ****
<5% Internal, <5% External
Mixing Rate of Non-Ducted BVUs not intended to be equipped with one duct connection on either supply or
extract air side;
| ****
N/A
Position and description of visual filter warning for RVUs intended for use with filters, including text pointing out the importance of regular filter changes for performance and
energy efficiency of the unit
| ****
N/A
For UVUs (Instructions Install Regulated Supply/Extract Grilles Façade)| ****
In F&W
Internet Address (for Disassembly Instructions)| www.vent-
axia.com
Sensitivity p. Variation@+20/- 20 Pa: (for Non-Ducted VUs)| N/A
Air Tightness-ID/OD-(m3/h) (for Non-Ducted VUs)| N/A
Annual Electricity Consumption: AEC (kWh/a)| 0.4| 0.5| 0.6
Annual Heating Saved: AHS (kWh/a)|
AHS: Average| 28.3| 28.3| 28.3
AHS: Warm| 12.8| 12.8| 12.8
AHS: Cold| 55.4| 55.4| 55.4
Disposal
This product should not be disposed of with household waste.
Please recycle where facilities exist. Check with your local authority for
recycling advice.
Applicable only to products installed and used in the United Kingdom. For
details of guarantee outside the United Kingdom contact your local supplier.
Vent-Axia guarantees its products for two years from date of purchase against
faulty material or workmanship. In the event of any part being found to be
defective, the product will be repaired, or at the Company’s option replaced,
without charge, provided that the product: –
- Has been installed and used in accordance with the instructions given with each unit.
- Has not been connected to an unsuitable electricity supply. (The correct electricity supply voltage is shown on the product rating label attached to the unit).
- Has not been subjected to misuse, neglect or damage.
- Has not been modified or repaired by any person not authorised by the company.
IF CLAIMING UNDER TERMS OF GUARANTEE
Please return the complete product, carriage paid to your original supplier or
nearest Vent-Axia Centre, by post or personal visit. Please ensure that it is
adequately packed and accompanied by a letter clearly marked “Guarantee Claim”
stating the nature of the fault and providing evidence of date and source of
purchase.
The guarantee is offered to you as an extra benefit and does not affect your
legal rights.