Installation Guide Lindab UltraBT™RoomControl System
Commissioning instruction
Ultra BT Room Control System
© 2023-11-30 Lindab Ventilation. All forms of reproduction without written
permission are forbidden. is the registered trademark of Lindab AB.
Lindab’s products, systems, product and product group designations are
protected by intellectual property rights (IPR).
System overview
1.1 Introduction
Ultra BT room control system is compatible with Lindab Bluetooth sensors and
UltraLinks type 4. You can read the type number on the product label.
This commissioning instruction describes the features and the commissioning
steps of the Ultra BT room control system that is related to wireless sensors
and airflow control based on the sensor readings.
The setup and configuration of sensors and room regulation is done in Lindab
OneLink application via smartphone.
The room comfort can be adjusted by the room visitor via Lindab OneSet
application via smartphone.
1.2 System features
Ultra BT room control system contains of at least one supply UltraLink unit,
up to 5 different sensors (regulation types) and one extract UltraLink.
1.3 Set up overview
- Change control settings to UltraLinks
- Pairing sensor to supply UltraLink
- Pairing supply UltraLink to extract UltraLink
- Enable room regulation
Click here to see specific products and detailed product information used in Ultra BT room control system >>
1.4 Download applications
Commisioning application – Lindab OneLink™
End user application – Lindab OneSet™
http://qr.lindab.com/?code=linktoonelinkapp
Commissioning application|
---|---
End user application|
1.5 Wireless sensors
Up to five wireless sensors can be connected to one
UltraLink using a smart device and the Lindab OneLink app. After successful
pairing of a sensor, its readings are available both in the app but also in
the registers where they are accessed under the following modbus registers:
Register| Reading|
---|---|---
3×2012| Presence| Sum
3×2021
3×2022
3×2023| Temperature| Min
Max
Average
3×2034| Airflow| Sum
3×2041
3×2042
3×2043| Humidity| Min
Max
Average
3×2051
3×2052
3×2053| CO2| Min
Max
Average
If you connect more than one sensor that reports the same variable type (for
example two temperature sensors) then you can choose to read either the max,
min or average value according to the table above.
1.6 Room regulation
The regulation will not strive to always reach a given set point. It will
maintain the climate within the allowed deviation that is configured.
It can only maintain a climate where the supply air has the possibility to
support it. It means that it can not give a lower temperature than the
temperature in the supply air, if not connected to any cooling source.
The room regulation works by applying a multiplication factor to the normal
flow.
As long as the regulation is within its deadband the regulation factor is 1.0. As soon as it move outside the deadband a multiplication factor is applied to the normal flow – meaning that the flow will increase. Before the system applies to the factor a check is automatically made to make sure that an increase of the flow actually improves the conditions. It will for example not increase the flow if the indoor temperature is too low and the supply air temperature is even l owe r.
1.7 Presence regulation
The multiplication factor from presence is always used when the room is
unoccupied and it either overrides the other factors (Economy mode) or it is
multiplied with the highest factor from the other regulation types (Comfort
mode).
When the room is occupied its factor is treated just like the factor from
temperature, CO2 and humidity and will only be used if it is the highest among
the enabled regulation types.
The graph below (graph 1) shows the global set point factor that will be used
in a case where regulation is active for all of the four regulation types
mentioned above. Each regulation type is producing its own multiplication
factor and at any given moment the highest of them will be used (as long as
the room is occupied). The red areas shows the effect you get by activating
Comfort mode.
Graph 1
1.8 Temperature, CO2 and humidity regulation
Each regulation type that is used for the room regulation will produce its own multiplication factor. The system will always be governed by the regulation type and the multiplication factor that demands the highest amount of air.
1.9 Signal for controling heating and cooling sources
Control of heating and cooling sources can be added using analog signals from
the Ultralink. The signals on the analog ports AO1 and AO2 can be configured
for heating and/ or cooling using the OneLink app. If heating and/or cooling
is enabled on the analog ports, the same control curve that controls the
temperature by air is used, but with one important difference. The max scale
factor used to calculate the signal is always 100% and the minimum factor is
0%.
This means that the proportional regulation on the analog ports will always
vary between 0-100%. The percentage is converted to the corresponding voltage
level based on what type of control signal we have specified when configuring
the analog ports (0-10V, 2-10V, 10-0V or 10-2V). The analog signals can be
used for any passive heating or cooling source with an analoge actuator.
The UltraLink has a smart programming which prohibits both heating and cooling
at the same time.
1.10 Airflow regulation
When regulation on airflow is used all other regulation types are deactivated.
It can only be used alone. In this case the product will act as a slave to
other airflow sensors of type FTMU or FTCU.
1.11 Firmware update
By regularly searching for and carrying out firmware upgrades, you ensure
optimal performance and the latest functionality of your UltraLink.
How to upgrade your firmware
- Open OneLink app and log in to UltraLink
- Go to “Configuration” > “Device info”
- Click on “Firmware update”
Change control settings to UltraLinks
2.1 Open OneLink application.
2.2 Scan for devices and connect to UltraLink.
2.3 Go to “Configuration”.
2.4 Go to “Device settings”.
2.5 Change the control settings from “Analog” to “Bus”.
2.6 Set flow rate set point.
Pairing instructions
3.1 Pairing of presence, temperature, relative humidity and/or CO2 sensor
to supply UltraLink.
3.1.1 Turn on sensor according to specific sensor instruction.
3.1.2 Open OneLink application.
3.1.3 Scan for devices and connect to supply UltraLink.
3.1.4 Go to “Configuration”
3.1.5 Go to “Wireless sensors”.
3.1.6 Tap on one of the avaliable (grey colored) sensor slots.
3.1.7 Click on “MAC address” and scan the QR-code attached to your sensor.
If the sensor is not avaliable for pairing – please make sure you have the latest firmware update. See “1.11 Firmware update” on page 5
3.1.8 Click on enable sensor.
Wait for the sensor to connect. When the sensor icon turns green, it’s
connected. This might take a few seconds.
3.2 Pairing UltraLink to UltraLink
To complete the commissioning of the Ultra BT room controle system you need to
pair the supply UltraLink to the extract UltraLink so that the extract
UltraLink acts as slave to the supply UltraLink.
If you wish to use the extraxt UltraLink as sensor to the supply UltraLink to
read airflow or temperature, you need to pair the extraxt UltraLink as sensor
to the supply UltraLink.
The steps in this paragraph describes the pairing steps.
3.2.1 Open OneLink application.
3.2.2 Scan for devices and connect to your UltraLink.
3.2.3 Copy the UltraLink MAC address.
3.2.4 Disconnect UltraLink.
3.2.5 Scan for devices again and connect to the other UltraLink.
3.2.6 Go to “Configuration”.
3.2.7 Go to “Wireless sensors”.
3.2.8 Tap on one of the avaliable (grey colored) sensor slots.
3.2.9 Click on “MAC address” and paste the copied UltraLink MAC-address.
3.2.10 Click on enable sensor.
Wait for the sensor to connect. When the sensor icon turnes green, it’s connected. This might take a few seconds.
3.3 If sensor doesn’t connect
3.3.1 Check the sensor battery.
3.3.2 Check that the distance between the sensor and the UltraLink doesn’t
exceed maximum bluetooth range.
You can find the maximum distance value and other require-ments for your
specific sensor in the sensor data sheet.
[Link to sensor documentation
](https://itsolution.lindab.com/SoftwareStats/SoftwareService.svc/redirect?scope =sdb-resource&url-version=2&streamId=G0Dl2DRwWjy&resourceId=RDyq4JKlEVv)
Enable room regulation
4.1 Assign control variables for your system.
4.1.1 Open OneLink application.
4.1.2 Scan for devices and connect to the supply UltraLink.
4.1.3 Go to “Configuration”.
4.1.4 Go to “Room Regulation”.
4.1.5 The top bar represents the different variables which you can use to control your room/zone.
Regulation types:
| Temperature
---|---
| CO2
| Relative humidity
| Presence
| Airflow
Status light:
| Working
---|---
| Stand by
| Not avaliable
| Inactive
4.2 Temperature control
4.3 CO2 control
- Since the UltraLink has no CO2 measurement we need to add an estimated value to the supply air. This estimate will be the comparison to the value registered from the sensor in the room and will determine if the multiplication factor will be applied or not.
Typical CO2 value for outdoor air is 400 ppm.
4.4 Relative humidity control
- Since the UltraLink has no relative humidity measurement we need to add an estimated value to the supply air. This estimatisation will be the comparesion to the value registered from the sensor in the room and will determine if the multiplication factor will be applied or not.
4.5 Presence control
4.6 Airflow control
- Set point calculation settings
Use summed airflow as set point| With this selection enabled the set point for
the product will be calculated as the sum of the flows that are received as
sensor data multiplied by the “Scale factor” and with “Flow offset” added.
New set point = (UltraLink sensor 1 + UltraLink sensor 2 +….) x Scale factor +
Flow offset
---|---
Reduce products set point with summed airflow| With this selection enabled the
set point that will be used corresponds to the products own set
point reduced by the summed flows that are received as sensor data multiplied
by the “Scale
factor” and with “Flow offset” added.
New setpoint = (Setpoint – (UltraLink sensor 1 + UltraLink sensor 2….)) x
Scale factor + Flow offset
Add summed airflow to products set point| With this selection enabled the set
point that will be used corresponds to the products own set
point added with the summed flows that are received as sensor data multiplied
by the “Scale
factor” and with “Flow offset” added.
New setpoint = (Setpoint +(UltraLink sensor 1 + UltraLink sensor 2….)) x Scale
factor + Flow offset
Set UltraLink to control heating and cooling sources via analog signal
5.1 Run cable between UltraLink and heating/cooling source
5.1.1 Cut the power supply to the UltraLink.
5.1.2 Install analog actuator onto the heating/cooling source
5.1.3 Run cable between actuator and UltraLink AO1 or AO2
5.1.4 Restore the power supply to the UltraLink and turn it on.
5.2 Make settings to analog output signal inside OneLink app
5.2.1 Inside OneLink app; Go to “Configuration”.
5.2.2 Go to “Device settings”.
5.2.3 Go to “Setting of analog output AO1″/”AO2”
5.2.4 Click on “Variable” and select “cooling” or “heating”
If you are not able to select cooling or heating as analog output, you need to
do a firmware update to your UltraLink. See “1.11 Firmware update” on page 5.
5.2.5 Click on “Voltage range” and select the voltage range according to the actuator.
To enable additional heating and/or cooling steering the following steps are also mandatory:
- Pairing temperatur sensor to supply UltraLink.
You can choose to read the room temperature via wireless sensor placed in the
room, or via the extract UltraLink.
To read temperature via wireless room sensor, see paragraph (“3.1 Pairing of
presence, temperature, relative humidity and/or CO2 sensor to supply
UltraLink.” on page 7.
To read temperature via extract UltraLink, see paragraph: “3.2 Pairing
UltraLink to UltraLink” on page 8.
- Enable room regulation via temperature, see paragraph: “4.2 Temperature control” on page 11
5.3 Disable increased airflow when heating/cooling
If your setup is based on disabling increased airflow when heating/cooling you
need to set the “Max scale factor” for temperature control to 100%. By doing
so, the temperature will be adjusted using only the heating/cooling source.
Give the end user control to adjust the room climate
The end user may control the room temperature via Lindab OneSet application.
To get access for controling the room the end user need to scan a QR-code
connected to the room (generated from commissioning app OneLink).
6.1 Generate QR-codes associated to different rooms in the comissioning app
OneLink™
The QR codes are generated in the commissioning app OneLink.
6.1.1 Go to “Configuration > Device info”
6.1.2 Go to “End user application access”
6.1.3 Fill in end-user permissions and generate QR code.
The QR code can be generated with different access per-missions (read only or
read and write) and different duration of validity. This feature allows for
flexibility and you can, for example, generate 24h codes for hotel rooms, but
in a residential application you can generate codes that gives eternal access.
6.1.4 Save to phone gallery by clicking “Save to gallery”.
When everything is set up for use, download the end-user app OneSet for easy
control of the temperature in the room.
The OneSet app can replace a traditional wall mounted room controller.
End-user app OneSet™
Ultra BT comes with an optional end-user app where it is possible to monitor
the room and make some personal settings, for example room temperature. To be
able to access the specific room control settings from this end-user app, you
can easy scan the QR-code associated with the room you want to control.
The code is created via the commissioning application OneLink. See chapter
“6.0 Give the end user control to adjust the room climate” on page 15
As soon as a QR-code is scanned, access- duration- and validity rights to the specific room is stored locally in the app. As long as you have right to access the room control settings, all stored rooms will appear in a list view in the OneSet end-user app. Access to these rooms can now be made without need of scanning the code again until the duration rights has exceeded. As soon as the duration is exceeded the room will be removed from the list view and you need to scan the code again to get new access.
Most of us spend the majority of our time indoors. Indoor climate is crucial
to how we feel, how productive we are and if we stay healthy.
We at Lindab have therefore made it our most important objective to contribute
to an indoor climate that improves people’s lives. We do this by developing
energy-efficient ventilation solutions and durable building products. We also
aim to contribute to a better climate for our planet by working in a way that
is sustainable for both people and the environment.
Lindab | For a better climate
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>