ABB SWM4 Water Detector Instruction Manual
- June 17, 2024
- ABB
Table of Contents
ABB SWM4 Water Detector
Specification
SWM4 Technical data (excerpt)
Voltage (Un) | 12 V DC |
---|---|
Current quiet (I) | 0.01 mA |
Current alarm (I) | Max. 6.5 mA |
Alarm Contact Type | Transistor Relay 60V0, 5A DC |
LEDs | 1 Alarm (red) |
Size | 40 x 44 x 23 mm |
Colour | White |
Cable length | 5 m |
Environment class | IV |
Temp. Range | 0 … + 60 °C |
Degree of Protection | IP65 |
CE
SWM4/RN Technical data (excerpt)
Voltage (Un) | 12 V DC |
---|---|
Voltage Range (Un) | 10 … 23 V AC/DC |
Current quiet (I) | 0.01 mA |
Current alarm (I) | Max. 20 mA |
Alarm Contact Type | Transistor Relay 60V0, AC1 |
LEDs | 1 Alarm (red) |
Size | 40 x 44 x 23 mm |
Colour | White |
Cable length | 5 m |
Environment class | IV |
Temp. Range | 0 … + 60 °C |
Degree of Protection | IP65 |
Weight | 200 g |
CE
Device description
- Detects water ingression, e.g. burst pipes, ingression of ground water or effluent
- Not suitable for permanent wetness, e.g. as a water level sensor
SWM4
- Connection to zones of security systems
- Stores messages
- Reset by drying or by switching the voltage off
SWM4/RN
- Suitable for connection to control inputs of other systems.
- Connection of external LED possible
- External power source required 10 – 23 V AC/DC
Instruction For Use
Connection of SWM4
**1**
- To zone
- First detector
- Last detector
- Connection unit
Max. 20 detectors
**2**
Cable cross section
- Bridge
- Termination resistor
- NC contact
- Cable cross section
—- Alternative connection option
The connection of the wires in the contact always ensures that 2 adjacent wires can be connected to the alarm panel and the other two can be connected to the next detector or to the termination resistor. It is not necessary to test the conductors.
**3**
Connection of SWM4/RN
Suitable for connection to control inputs of other systems.
External power source required
-
Output for parallel indication (LED); use same supply voltage as for detectors
-
Alarm relay
Attention: Relay contacts drawn in standby state -
Operating voltage
**4**
Dimension drawing
- LED
- Connection cable
**5**
Dimension drawing
- Contacts
- LED
Important notes
The installation and commissioning may only be carried out by electrical specialists. The appropriate norms, guidelines, regulations and specifications for your country should be observed when planning and setting up electrical installations and security systems for intrusion and fire detection.
- The device should be protected from damp, dirt and damage during transport, storage and operation.
- The device should not be operated outside the specified technical data.
Cleaning
If devices become dirty, they can be cleaned using a dry cloth or a cloth
dampened with a soapy solution. Corrosive agents or solutions should never be
used.
Maintenance
No repairs should be carried out by unauthorized personnel if damage occurs,
e.g. during transport and/or storage.
Customers Support
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82
69123 Heidelberg, Germany
+49 (0) 6221 701 607
+49 (0) 6221 701 724
http://www.abb.com/knx
http://www.abb.com/knx
E-mail:knx.marketing@de.abb.com
References
- ABB Group. Leading digital technologies for industry — ABB Group
- ABB i-bus KNX - Building and Home Automation Solutions | ABB
- ABB i-bus KNX - Gebäude- und Hausautomatisierungslösungen
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>