ABB SWM4 Water Detector Instruction Manual

June 17, 2024
ABB

ABB SWM4 Water Detector

ABB SWM4 Water Detector

Specification

SWM4 Technical data (excerpt)

Voltage (Un) 12 V DC
Current quiet (I) 0.01 mA
Current alarm (I) Max. 6.5 mA
Alarm Contact Type Transistor Relay 60V0, 5A DC
LEDs 1 Alarm (red)
Size 40 x 44 x 23 mm
Colour White
Cable length 5 m
Environment class IV
Temp. Range 0 … + 60 °C
Degree of Protection IP65

CE

SWM4/RN Technical data (excerpt)

Voltage (Un) 12 V DC
Voltage Range (Un) 10 … 23 V AC/DC
Current quiet (I) 0.01 mA
Current alarm (I) Max. 20 mA
Alarm Contact Type Transistor Relay 60V0, AC1
LEDs 1 Alarm (red)
Size 40 x 44 x 23 mm
Colour White
Cable length 5 m
Environment class IV
Temp. Range 0 … + 60 °C
Degree of Protection IP65
Weight 200 g

CE

Device description

  • Detects water ingression, e.g. burst pipes, ingression of ground water or effluent
  • Not suitable for permanent wetness, e.g. as a water level sensor

SWM4

  •  Connection to zones of security systems
  • Stores messages
  • Reset by drying or by switching the voltage off

SWM4/RN

  • Suitable for connection to control inputs of other systems.
  • Connection of external LED possible
  • External power source required 10 – 23 V AC/DC

Instruction For Use

Connection of SWM4

**1**

  1. To zone
  2. First detector
  3. Last detector
  4. Connection unit
    Max. 20 detectors
    Connection of SWM4

**2**

Cable cross section

  1. Bridge
  2. Termination resistor
  3. NC contact
  4. Cable cross section
    —- Alternative connection option
    Cable cross section

The connection of the wires in the contact always ensures that 2 adjacent wires can be connected to the alarm panel and the other two can be connected to the next detector or to the termination resistor. It is not necessary to test the conductors.

**3**

Connection of SWM4/RN

Suitable for connection to control inputs of other systems.
External power source required

  1. Output for parallel indication (LED); use same supply voltage as for detectors

  2. Alarm relay
    Attention: Relay contacts drawn in standby state

  3. Operating voltage
    Instruction For Use

**4**

Dimension drawing

  1. LED
  2. Connection cable
    Instruction For Use

**5**

Dimension drawing

  1. Contacts
  2. LED
    Instruction For Use

Important notes

The installation and commissioning may only be carried out by electrical specialists. The appropriate norms, guidelines, regulations and specifications for your country should be observed when planning and setting up electrical installations and security systems for intrusion and fire detection.

  • The device should be protected from damp, dirt and damage during transport, storage and operation.
  • The device should not be operated outside the specified technical data.

Cleaning
If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive agents or solutions should never be used.

Maintenance
No repairs should be carried out by unauthorized personnel if damage occurs, e.g. during transport and/or storage.

Customers Support

ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82
69123 Heidelberg, Germany
+49 (0) 6221 701 607
+49 (0) 6221 701 724
http://www.abb.com/knx
http://www.abb.com/knx
E-mail:knx.marketing@de.abb.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals