HEATCRAFT 25010301 Intelligen Refrigeration Controller User Guide

June 17, 2024
HEATCRAFT

HEATCRAFT logo QUICK START GUIDE
intelliGen™ Refrigeration Controller
JULY 2023
PART NO. 25010301

PRIOR ASSEMBLY NEEDED

Please keep these instructions for future reference.
Equipment assembly and wiring is required before using this guide.
Please make sure control circuit transformer is properly setup.
Please ensure your board has the latest firmware. Latest firmware revision can be found at https://intelligencontrols.com/resources
For assembly, please consult intelliGen installation & operation manual.

IMPORTANT!

BRAZING PIPING CONNECTIONS

CONTROL TRANSFORMERS COME WITH THE VOLTAGE TAP ON 240V (as shown)

If your site has less than 215VAC, the tap will need to be moved to 208V in order to ensure 25VAC to 29VAC power to IntelliGen board.

ANTI-SHORT CYCLE TIMER DELAY RELAY IN CONDENSING UNITHEATCRAFT
25010301 Intelligen Refrigeration Controller - CONDENSING
UNIT

Some condensing units may have an Anti-Short Cycle Time Delay Relay (ASCT) installed for compressor short cycle protection. These time delay relays should be removed when connecting the condensing unit to unit coolers with intelliGen installed. The intelliGen control has compressor short cycle protection functionality built-in, and failure to remove the electro- mechanical ASCT relay can result in system run-time conflicts and negative impacts to system performance.

Legend

Abbrev. Name Long Name
EV Evap/Evaporator
SP Set-Point
AUX Auxiliary
TEMP Temperature/Temp
CALIB Calibration
EXV Electronic Expansion Valve
CU Condensing Unit
COMP Compressor
LPS Low Pressure Switch
HPS High-Pressure Switch
DLT Discharge Line Therm.
C1 Compressor Contactor

U.S. Customer Service

Normal Business Hours – 8:00 AM – 8:00 PM EDT
800-537-7775
After Hours (After 5:00 PM EDT, weekends and holidays)
877-482-7238
heatcraft.com/intelligen/support
[email protected]

intelliGen REFRIGERATION CONTROLLER

Get to know the intelliGen Refrigeration Controller (iRC)

HEATCRAFT 25010301 Intelligen Refrigeration Controller - Refrigeration
Controller

HOW TO NAVIGATE?

A. Home Button: Press to go back to Main Menu
B. Back Button: Press to go back to Previous Menu
C. Favorites Button: Press to go to your Favorites
D. OLED Screen: Shows the content like temperature, paramenters and others.
E. LED Status Light Bar: Indicates the current status of all specific evaporators on the system (See below).
F. Knob / Enter Button: Rotate the knob left and right to navigate between Menu Options. Press the knob to ENTER.

LED Status Light Bar

GREEN| LED GREEN STATIC
The System or EV does not have any anomalies/issues.
---|---
RED| LED RED STATIC
The System or EXV  has an Alarm.
LED RED FLASHING
The EV Unit where theAlarm originated.
YELLOW| LED YELLOW STATIC
The System or EV has an Error.
LED YELLOW FLASHING
The EV Unit where the Error originated.
WHITE| LED WHITE FLASHING
The EV Unit is being identified.
NO LED ON| The EV Unit is currently powered off or in service mode.

Scan QR code to view the Quick Start Configuration video.

HEATCRAFT 25010301 Intelligen Refrigeration Controller - qr
codehttps://zxing.org/w/decodehttp://www.intelliGencontrols.com/resources

  • Figure shows a Low Profile unit cooler; location might vary on other units.

QUICK SETUP FROM iRC UI

STEP 1.
Enter Expert PIN| STEP 2.
Select Configuration Mode
---|---
First digit in PIN automatically flashes for edit.
Turn dial to change first PIN digit 0-9. Push Enter to choose digit. Repeat with all digits.
The Default Expert PIN is 999999.| Select EV to proceed with configuring the system from the iRC UI.
Select “Web – Local Wired” to get IP address for configuring the system from the Webserver card page.
STEP 3A.
Equipment Discovery| STEP 3B.
Equipment Discovery
After Configuration Mode is selected as ‘EV’, the iRC will automatically attempt to discover all units in the system.| After polling for connected units, the iRC UI will display the number of EV that are found to be wired together.
If all connected EVs were found, press Enter knob to continue.
STEP 4A.
Choose Unit Base Name| STEP 4B.
Choose Unit Suffix
The Unit being named will have its LED flashing white.
Turn knob to change base name: [Freezer, Cooler, Unit, Box].
Push the knob to choose the base name.| Turn knob to change unit name suffix: [ 1A, 1B, …, 8H ]. Push the knob to choose unit name suffix.
(Repeat this step with all your EV’s as necessary)
STEP 5.
Choose Box Temp Sensor| STEP 6A.
Select if Condensing Unit Wired
If more than 1 Evap was configured, turn knob to change primary evap which will be sensing the box temp.
Push knob to choose primary evap.| Press the knob to select YES, if there is a condensing unit wired to an evaporator.
(Special condensing units from Heatcraft with intelliGen wiring required.)
STEP 6B.
Select EV wired to Condensing Unit| STEP 7.
Setting Date & Time/Country
Turn the knob to select the evaporator wired to the condensing unit.
Press the knob to choose the evaporator.| Country field will automatically flash for edit.
Turn dial to change country.
Push the knob to choose the country.
STEP 8.
Time Zone| STEP 9.
Daylight Savings
Time Zone field will automatically flash for edit.
Turn knob to change time zone.
Push the knob to choose the time zone.| Turn the knob. Push knob to select either Yes or No.
STEP 10.
Date & Time| STEP 11.
Select Refrigerant
Year field will automatically flash for edit.
Turn knob to choose year.
Push the knob to choose year.
Repeat steps with Month, Day, Hours, Minutes and AM/PM| Refrigerant field will automatically flash for edit.
Turn knob to change refrigerant selection.
Push the knob to choose refrigerant.
STEP 12.
Select Valve Type| STEP 13.
Select Defrost Type
EXV type will automatically flash for edit.
Turn knob to change valve type.
EXV-Carel is the standard intelliGen EXV with yellow stator.| Defrost type field will automatically flash for edit.
Turn knob to change defrost type selection.
Push the knobto choose defrost type.
STEP 14.
Select Defrost Style| STEP 15.
Select Box Temp Set-Point
Defrost style field will automatically flash for edit.
Turn knob to change defrost style selection.
Push the knob to choose defrost style.| Box temp setpoint will automatically flash for edit.
Turn knob to change box temp setpoint selection.
Push the knob to choose box temp setpoint.
STEP 16.
Start System|
Start System will automatically flash for edit.
Push the knob to start the system when ready.|

intelliGen Installation & Operation Manuals and Support Document:

To find all intelliGen resources, including installation & operation manuals, technical bulletins, brochures, maintenance, troubleshooting information and more, simply scan the QR code or use the link below.

www.intelliGenControls.com/resourcesHEATCRAFT
25010301 Intelligen Refrigeration Controller - qr code 2

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HEATCRAFT User Manuals

Related Manuals