Touche Controls SES-D010 Smart Emergency Shunt Dimmer User Manual

June 17, 2024
Touche Controls

Touche-Controls-LOGO

Touche Controls SES-D010 Smart Emergency Shunt Dimmer

Product Information

Specifications

  • Part Number: SES-D010
  • Resistive Load: 3 Amp (120V / 277V)
  • Electronic Ballast Load: 3 Amp (120V / 277V)
  • Standard Ballast Load: 3 Amp (120V / 277V)
  • Tungsten Load: 300 Watt (120V)

Product Usage Instructions

Installation

  1. Ensure all connections are per National Electrical Code and local regulations.
  2. Do not use the product outdoors.
  3. Avoid mounting near gas or electric heaters.
  4. Mount the equipment in locations and at heights where it will not be tampered with by unauthorized personnel.
  5. Use only accessory equipment recommended by the manufacturer to prevent unsafe conditions.
  6. Do not use the equipment for purposes other than its intended use.
  7. Installation and servicing should be performed by qualified personnel.

Connectivity

The product features SmartNet ports for RJ45 connections and 0-10V wires for easy connectivity.

Manual override button functions:

  • Press and release: Toggle relay on/off
  • Press and hold: Communication check (solid blue status LED
    indicates communication present with RM)

Mounting

The product is designed to be mounted in a standard 4 square electrical box (not included). A 1-1/2 extension ring is provided with the Smart Emergency Shunt Dimmer and must be installed for  warranty coverage.

LED Indications

The LED color blinking indicates different statuses:

  • Green: Relay is closed with line voltage
  • Blinking Green Cyan: Relay is closed with no line voltage
  • Blinking Cyan: Relay is open with line voltage
  • Cyan: Relay is open with no line voltage

FAQ

How long can the total SmartNet length be?

The total SmartNet length should not exceed 400 feet, and CAT 5 cables are recommended for connectivity.

IMPORTANT SAFEGUARDS

  1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
  2. Ensure all connections are per National Electrical Code and local regulations.
  3. Do not use outdoors.
  4. Do not mount near gas or electric heaters.
  5. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
  6. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
  7. Do not use equipment for other than intended use.
  8. Installation and servicing should be performed by qualified personnel

SAVE THESE INSTRUCTIONS

ELECTRICAL SPECIFICATIONS

  • 3 AMP RESISTIVE LOAD (120V / 277V)
  • 3 AMP ELECTRONIC BALLAST LOAD (120V / 277V)
  • 3 AMP STANDARD BALLAST LOAD (120V / 277V)
  • 300 WATT TUNGSTEN LOAD (120V)

INSTALLATION INSTRUCTIONS

SMART EMERGENCY SHUNT DIMMER 0-10vTouche-Controls-SES-D010-Smart-
Emergency-Shunt-Dimmer-FIG-1

TIPS / NOTES

  1. SMARTNET PORTS – RJ45 CONNECTIONS
  2. 0-10V WIRES
  3. STATUS LED
  4. MANUAL OVERRIDE BUTTON
    • PRESS AND RELEASE = TOGGLE RELAY ON/OFF
    • PRESS AND HOLD = COMM CHECK (SOLID BLUE STATUS LED = COMM PRESENT WITH RM)
  5. STANDARD 4″ SQUARE ELECTRICAL BOX – NOT INCLUDED
  6. 1-1/2″ EXTENSION RING – PROVIDED WITH SMART EMERGENCY SHUNT DIMMER – MUST BE INSTALLED
    • FOR WARRANTY COVERAGE
  7. SMART EMERGENCY SHUNT DIMMER

MOUNTING

SMART EMERGENCY SHUNT DIMMER 0-10v CONNECTIVITYTouche-Controls-SES-D010
-Smart-Emergency-Shunt-Dimmer-FIG-3

TESTING / MAINTENANCE

TESTING

  • ENSURE ROOM MANAGER IS POWERED BY NORMAL POWER SOURCE
  • ENSURE SMART EMERGENCY SHUNT DIMMER MODULE IS CONNECTED TO EMERGENCY POWER SOURCE
  • NORMAL OPERATION
  • TURN LIGHTS TO FULL BRIGHT
  • EMERGENCY AND NORMAL LIGHTS (IF APPLICABLE) WILL TURN ON FULL BRIGHT
  • REDUCE LIGHT LEVEL TO 50%
  • EMERGENCY AND NORMAL LIGHTS (IF APPLICABLE) WILL DIM TO 50%
  • TURN LIGHTS OFF
  • EMERGENCY AND NORMAL LIGHTS (IF APPLICABLE) WILL TURN OFF
  • MERGENCY OPERATION
  • WHEN NORMAL POWER IS LOST TO ROOM MANAGER, THE SMART EMERGENCY SHUNT DIMMER MODULE WILL AUTOMATICALLY CLOSE THE POWER RELAY AND
  • OPEN THE 0-10V SIGNAL RELAY TURNING THE LIGHTS ON AND TO FULL BRIGHTNESS.
  • EMERGENCY OPEATION TESTS
  • TEST #1 – TURN OFF NORMAL POWER TO ROOM MANAGER
  • TEST #2 – DISCONNECT SMART NET CABLING TO SMART EMERGENCY SHUNT DIMMER MODULE

MAINTENANCE

  • NO MAINTENANCE IS REQUIRED FOR SMART EMERGENCY SHUNT DIMMER MODULES
  • EMERGENCY OPERATION SHOULD BE TESTED IF LIGHT FIXTURES ARE REPLACED

Contact

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Touche Controls User Manuals

Related Manuals