Touche Controls SES-D010 Smart Emergency Shunt Dimmer
Product Information
Specifications
- Part Number: SES-D010
- Resistive Load: 3 Amp (120V / 277V)
- Electronic Ballast Load: 3 Amp (120V / 277V)
- Standard Ballast Load: 3 Amp (120V / 277V)
- Tungsten Load: 300 Watt (120V)
Product Usage Instructions
Installation
- Ensure all connections are per National Electrical Code and local regulations.
- Do not use the product outdoors.
- Avoid mounting near gas or electric heaters.
- Mount the equipment in locations and at heights where it will not be tampered with by unauthorized personnel.
- Use only accessory equipment recommended by the manufacturer to prevent unsafe conditions.
- Do not use the equipment for purposes other than its intended use.
- Installation and servicing should be performed by qualified personnel.
Connectivity
The product features SmartNet ports for RJ45 connections and 0-10V wires for easy connectivity.
Manual override button functions:
- Press and release: Toggle relay on/off
- Press and hold: Communication check (solid blue status LED
indicates communication present with RM)
Mounting
The product is designed to be mounted in a standard 4 square electrical box (not included). A 1-1/2 extension ring is provided with the Smart Emergency Shunt Dimmer and must be installed for warranty coverage.
LED Indications
The LED color blinking indicates different statuses:
- Green: Relay is closed with line voltage
- Blinking Green Cyan: Relay is closed with no line voltage
- Blinking Cyan: Relay is open with line voltage
- Cyan: Relay is open with no line voltage
FAQ
How long can the total SmartNet length be?
The total SmartNet length should not exceed 400 feet, and CAT 5 cables are recommended for connectivity.
IMPORTANT SAFEGUARDS
- READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
- Ensure all connections are per National Electrical Code and local regulations.
- Do not use outdoors.
- Do not mount near gas or electric heaters.
- Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use equipment for other than intended use.
- Installation and servicing should be performed by qualified personnel
SAVE THESE INSTRUCTIONS
ELECTRICAL SPECIFICATIONS
- 3 AMP RESISTIVE LOAD (120V / 277V)
- 3 AMP ELECTRONIC BALLAST LOAD (120V / 277V)
- 3 AMP STANDARD BALLAST LOAD (120V / 277V)
- 300 WATT TUNGSTEN LOAD (120V)
INSTALLATION INSTRUCTIONS
SMART EMERGENCY SHUNT DIMMER 0-10v
TIPS / NOTES
- SMARTNET PORTS – RJ45 CONNECTIONS
- 0-10V WIRES
- STATUS LED
- MANUAL OVERRIDE BUTTON
- PRESS AND RELEASE = TOGGLE RELAY ON/OFF
- PRESS AND HOLD = COMM CHECK (SOLID BLUE STATUS LED = COMM PRESENT WITH RM)
- STANDARD 4″ SQUARE ELECTRICAL BOX – NOT INCLUDED
- 1-1/2″ EXTENSION RING – PROVIDED WITH SMART EMERGENCY SHUNT DIMMER – MUST BE INSTALLED
- FOR WARRANTY COVERAGE
- SMART EMERGENCY SHUNT DIMMER
MOUNTING
SMART EMERGENCY SHUNT DIMMER 0-10v CONNECTIVITY
TESTING / MAINTENANCE
TESTING
- ENSURE ROOM MANAGER IS POWERED BY NORMAL POWER SOURCE
- ENSURE SMART EMERGENCY SHUNT DIMMER MODULE IS CONNECTED TO EMERGENCY POWER SOURCE
- NORMAL OPERATION
- TURN LIGHTS TO FULL BRIGHT
- EMERGENCY AND NORMAL LIGHTS (IF APPLICABLE) WILL TURN ON FULL BRIGHT
- REDUCE LIGHT LEVEL TO 50%
- EMERGENCY AND NORMAL LIGHTS (IF APPLICABLE) WILL DIM TO 50%
- TURN LIGHTS OFF
- EMERGENCY AND NORMAL LIGHTS (IF APPLICABLE) WILL TURN OFF
- MERGENCY OPERATION
- WHEN NORMAL POWER IS LOST TO ROOM MANAGER, THE SMART EMERGENCY SHUNT DIMMER MODULE WILL AUTOMATICALLY CLOSE THE POWER RELAY AND
- OPEN THE 0-10V SIGNAL RELAY TURNING THE LIGHTS ON AND TO FULL BRIGHTNESS.
- EMERGENCY OPEATION TESTS
- TEST #1 – TURN OFF NORMAL POWER TO ROOM MANAGER
- TEST #2 – DISCONNECT SMART NET CABLING TO SMART EMERGENCY SHUNT DIMMER MODULE
MAINTENANCE
- NO MAINTENANCE IS REQUIRED FOR SMART EMERGENCY SHUNT DIMMER MODULES
- EMERGENCY OPERATION SHOULD BE TESTED IF LIGHT FIXTURES ARE REPLACED