Altronix SMP10C24X Series Power Supply Chargers Instruction Manual

June 4, 2024
Altronix

SMP10C24X Series Power Supply Chargers
Instruction Manual

SMP10C24X Series
Power Supply/Chargers
Models Include:
SMP10C24X SMP10PMC24X
– Single Output.
SMP10PM24P4
– Four (4) Fuse Protected Outputs.
SMP10PM24P8
– Eight (8) Fuse Protected Outputs.
SMP10PM24P16
– Sixteen (16) Fuse Protected Outputs.
SMP10PM24P4CB
– Four (4) PTC Protected Outputs.
SMP10PM24P8CB
Eight (8) PTC Protected Outputs.
SMP10PM24P16CB
– Sixteen (16) PTC Protected Outputs.
Installation Guide
Rev. 071212
More than just power.TM
Installing Company: __
Service Rep. Name:

Address: _____
Phone #: ____

Overview:

Altronix SMP10C24X Series power supply/chargers convert a 115VAC, 60Hz input into a regulated 24VDC output with up to 10A of continuous load current (see specifications).
SMP10C24X Series Power Supply Configuration Reference Chart:

Altronix Model Number| Accessory
power distribution
Module(s)| Number
of Outputs| Fused
Outputs| PIC Outputs
(auto resettable)| | Supervised| 115VAC 50/60Hz
Input Current
(A)| 24VDC Total Output Current (A)
---|---|---|---|---|---|---|---|---
Individu
Output Rating I
SMP10C24X| –| 1| –| –| 10A| –| 2.7A| 10A
SMP1OPMC24X| –| –| ✓
SMP1OPM24P4| PD4| 4| ✓| –| 3.5A
SMP1OPM24P4CB| PD4CB| | ✓| 2.5A
SMP1OPM24P8| PD8| 8| ✓| –| 3.5A
SMP1OPM24P8CB| PD8CB| | ✓| 2.5A
SMP1OPM24P16| PD1 6W| 16| ✓| | 3.5A
SMP10PM24P16CB| PD16WCB| –| ✓| 2.5A

Specifications:

Input:

  • Input 115VAC, 50/60Hz, 2.7A.

Output:

  • 24VDC output.
  • 10A supply current.
  • Filtered and electronically regulated outputs.
  • Short circuit and thermal overload protection.

Battery Backup:

  • Built-in charger for sealed lead acid or gel-type batteries.
  • Maximum charge current 0.7A.
  • Zero voltage drop when switching over to battery backup.

Features:

  • Power ON/OFF switch.

Supervision (select models):

  • AC fail supervision (form “C” contacts).
  • Battery presence and low battery supervision (form “C” contacts).

Visual Indicators:

  • AC input and DC output LED indicators.

Electrical:

  • Operating temperature: 0ºC to 49ºC ambient.
  • BTU/Hr. (approx.): 122 BTU/Hr.
  • System AC input VA requirement: 310.5VA.

Mechanical:

  • Enclosure Dimensions (H x W x D approx.):
    13.5″ x 13″ x 3.25″ (342.9mm x 330.2mm x 82.6mm) – Accommodates up to two (2)12VDC/7AH batteries.

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. The product is intended for indoor use only.

  1. Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground.

  2. Slide [Power ON/OFF] switch to the OFF position (Fig. 1a, pg. 4).

  3. Connect AC power to the terminals marked [L & N], and connect the ground to the green flying lead (Fig. 1, pg. 4, Fig. 2, pg. 5).
    Use 18 AWG or larger for all power connections (Battery, DC output).
    Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

  4. Slide [Power ON/OFF] switch to the ON position.

  5. Measure output voltage before connecting devices. This helps avoid potential damage.
    Keep power-limited wiring separate from non-power-limited wiring (115VAC, 60Hz Input,
    Battery Wires). Minimum 0.25″ spacing must be provided.
    CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user-serviceable parts inside. Refer installation and servicing to qualified service personnel.

  6. Slide [Power ON/OFF] switch to the OFF position.

  7. Connect devices to be powered:
    a. For Power Supply Board connect to the terminals marked [­ DC +].
    b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked [1P & 1N] through [4P & 4N] (Fig. 3, pg. 6), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 4, pg. 6), or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 5, pg. 6), carefully observing correct polarity.
    Note: A power switch is used to disconnect the L (HOT) terminal from the rest of the board (Fig. 1a, pg. 4, Fig. 2a, pg. 5). When servicing the unit, AC mains should be removed.

  8. When using stand-by batteries, they must be lead acid or gel type. Connect the battery to the terminals marked [­ BAT +] (battery leads included). Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
    For supervised models only:

  9. Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs marked [NC, C, NO] (Fig. 1b, pg. 4 or Fig. 2b, pg. 5). 10. Slide [Power ON/OFF] switch to ON position.

LED Diagnostics:

Power Supply Board

Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. The standby battery is supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.

Terminal Identification:

Terminal Legend Function/Description
L, G, N Connect 115VAC to these terminals: L to Hot, N to Neutral.
— DC + 24VDC @ 10A continuous output.

AC FAIL
NC, C, NO| Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay is normally energized when AC power is present.
Contact rating 1 A @ 120VAC / 28VDC.
Low Battery
NC, NO C,| Used to indicate low battery condition, e.g. connect to the alarm panel. Relay is normally
energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.
Low battery threshold: 24VDC output threshold set @ approximately 21VDC.
— BAT +| Stand-by battery connections. Maximum charge rate 0.7A.

*Note: Supervised models only
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB – Power Distribution Module:

Terminal Legend Function/Description
PD4/PD4CB PD8/PD8CB
1Pto4P 1P to 8P
1N to 4N 1N to 8N

Caution: Equipment to be installed/serviced by authorized/trained personnel only. Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.
The lightning flash with an arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open the enclosure. There are no user-serviceable parts inside. Refer servicing to qualified service personnel.
Fig. 1a Switch disables power mains line voltage input. If standby battery (batteries) are connected, the DC output remains on

Power Distribution Module(s)

Enclosure Dimensions (BC300):
13.5″ x 13″ x 3.25″ (342.9mm x 330.2mm x 82.6mm)
Enclosure accommodates up to two (2) 12VDC/7AH batteries.
Also available to accommodate up to two (2) 12VDC/12AH batteries (please contact Altronix).

Altronix is not responsible for any typographical errors. ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­
140 58th Street, Brooklyn, New York 11220 USA
phone: 718-567-8181
fax: 718-567-9056
website: www.altronix.com 
e-mail: info@altronix.com
Lifetime Warranty
IISMP10C24X Series
H18U SMP10C24X Series Installation Guide

Read User Manual Online (PDF format)