Balancing valve ASV-P is used together with shut-off and measuring valve
ASV-M to control the differential pressure in riser pipes where radiator
valves have presetting facilities ❶.
ASV-P maintains constant differential pressure across the pipes.
Max. working pressure…………………………………16 bar
Differential pressure across valve …………………………………..10-max.150 a
Max. flow temperature ………………………………..120 °C
Valve size | Internal thread | External thread |
---|---|---|
DN 15 | Rp ½ | G ¾ A |
DN 20 | Rp ¾ | G 1 A |
DN 25 | Rp 1 | G 1 ¼ A |
DN 32 | Rp 1 ¼ | G 1 ½ A |
DN 40 | Rp 1 ½ | G 1 ¾ A |
Impulse line: G 1/16
Installation
ASV-P must be installed in the return pipe. The flow must be in the direction
of the cast-in arrow ❸①.
It is recommended that an FV filter be installed in the system flow pipe.
The impulse tube must be fitted on the flow pipe, e.g. via an ASV-M valve. The
tube must be flushed through before being fitted on the + connection of the
ASV-P balancing valve ❷.
ASV-P must in addition be installed as determined by installation conditions.
When the system has been in use for some time, the connections with external
threads should be
tightened once again to minimize the risk for leakage.
Shut-off
Turning the ASV-P knob fully clockwise will shut off the balancing valve ❷①.
Pressure testing
Max. test pressure ………………………………………..25 bar
Note: When pressure testing you must secure that both sides of the
membrane have the same static pressure. That means the impulse tube must be
connected and any needle valves must be open.
If ASV-P/PV is installed in combination with ASV-M both valves can be opened
or closed (both valves must be in the same position!). If ASV-P/ PVis
installed in combination with ASV-I both valves must be open. If this
instruction is ignored, the membrane of the automatic balancing valve might be
damaged.
Starting
You can fill the system with the drain connection on ASV-P/PV. The system
shall be ventilated at the highest point. When opening the shut-off from
ASV-P/PV please secure that you have the same static pressure on both sides of
the membrane.
Note!
If this procedure is not followed ASV-P may become locked in a closed position
even if the valve is fully opened.
Tapping
The connection (closed, ❸② – open, ❸③ can be used for water tapping and
filling.
Fault location
Check the following if the balancing valve does not function correctly:
- Is the flow direction through the valve correct?
- Is the impulse tube fitted correctly and are any needle valves open?
- Is the valve shut-off open?
Accessory | Code no. |
---|---|
Impulse tube, 1.5 m | 003L8152 |
Impulse tube, 5 m | 003L8153 |
Measuring connection for drain connection | 003L8143 |
Insulation
The styrofoam packaging in which the valve is supplied can be used as an insulation jacket for temperatures up to 80 °C.
Danfoss A/S
Climate Solutions
- danfoss.com
- +45 7488 2222
Any information, including, but not limited to information on the selection of
the product, its application or use, product design, weight, dimensions,
capacity or any other technical data in product manuals, catalogs
descriptions, advertisements, etc., and whether made available in writing,
orally, electronically, online or via download, shall be considered
informative and is only binding if and to the extent, explicit reference is
made in a quotation or order confirmation. Danfoss cannot accept any
responsibility for possible errors in catalogs, brochures, videos, and other
material. Danfoss reserves the right to alter its products without notice.
This also applies to products ordered but not delivered provided that such
alterations can be made without changes to the form, fit or function of the
product.
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>