ABB C1900 Recorder Controller Circular Chart User Guide
- June 17, 2024
- ABB
Table of Contents
- C1900 Recorder Controller Circular Chart
- Product Information
- Specifications
- Product Usage Instructions
- Basic Configuration
- Setup Relays
- Setup Digital Inputs
- Access Page
- Scale Adjustment
- Setup Digital Outputs
- Setup Analog Output
- Q: How do I adjust the pen lift on the recorder?
- Q: How can I acknowledge alarms or go back to the home
C1900 Recorder Controller Circular Chart
Product Information
Specifications
- Model Number: C1900
- Manufacturer: ABB Limited Measurement & Analytics
- Product Type: Recorder
- Power Supply: 12V
- Input Types: mV THC, mA V RTD & Resistance
- Output Types: Analog, Digital
Product Usage Instructions
Basic Configuration
To configure the basic settings of the recorder, follow these
steps:
-
Select the desired configuration by pressing the ‘SELECt’
button. -
Set up the input parameters by navigating to ‘SEtup INPUt’ and
adjusting the type, linearizer, ranges, and fault levels for each
input. -
Adjust the pen range by selecting ‘SEtUP PENrNG’ and setting
the desired magnification of the trace in engineering units. -
Set up the chart speed by choosing ‘SEtUP CHArt’ and
configuring the duration of one chart revolution and pen lift/drop
parameters. -
Configure alarms by navigating to ‘SEtUP ALArMS’ and setting
the trip conditions for each alarm, such as process value, control
output, setpoint deviation, and rate of change.
Setup Relays
To configure the relays, follow these steps:
- Navigate to ‘Setup Relays’.
- Select the source used to activate each relay.
- Define the normally open/closed state for each relay.
Setup Digital Inputs
To configure the digital inputs, follow these steps:
- Navigate to ‘Setup Digital Input’.
- Set the polarity of external digital signals.
Access Page
To disable access to configuration and tuning facilities, follow
these steps:
- Navigate to ‘Access Page’.
- Select the option to disable access.
Scale Adjustment
To perform spot calibration for eliminating system loop errors,
follow these steps:
- Navigate to ‘Scale Adjustment’.
- Perform the spot calibration according to the provided
instructions.
Setup Digital Outputs
To configure the digital outputs, follow these steps:
- Navigate to ‘Setup Digital Outputs’.
- Select the source used to activate each output.
- Define the normally open/closed state for each output.
Setup Analog Output
To configure the analog output, follow these steps:
- Navigate to ‘Setup Analog Output’.
- Select an output as control or re-transmission.
Frequently Asked Questions (FAQ)
Q: How do I adjust the pen lift on the recorder?
A: To raise or lower the chart pen, use the ‘Pen Lift’ button on
the recorder faceplate.
Q: How can I acknowledge alarms or go back to the home
screen?
A: To acknowledge alarms or return to the home screen, refer to
the Programming Guide for instructions on using the ‘Alarm
acknowledge’ or ‘Home’ function key.
100.00 99.99
SECOdE MMMMMM
OPrtOr LEVEL
Note. Refer to the relevant page of the Programming Guide for further information.
bASIC CONFIG
SEtup INPUt
SEtUP PENrNG
SEtUP CHArt
SEtUP ALArMS
Setup Inputs — p4 Set the type, linearizer, ranges and fault levels for each input — see overleaf.
Setup Pen Range — p8 Used to adjust the ‘magnification’ of the trace. Default is 0 to 100% of engineering range. Set in engineering units.
Setup Chart Speed — p9 Setup Alarms — p13 SEtUP
Set the duration of one Set alarms to trip on rELAYS
chart revolution and pen process value, control
lift/drop parameters.
output , setpoint
deviation, rate of change.
Basic configuration overview
SEtUP ALArMS
SEtUP rELAYS
Setup Relays — p15 Set source used to activate each relay and define normally
open/closed state.
dIGtAL OUtPtS
SEtUP ANALOG
dIGtAL INPUtS
Setup Digital Input — p21 Set polarity of external digital signals.
ACCESS PAGE
Access Page — p22 Disable access to configuration and tuning facilities.
SCALE ADJUSt
Scale Adjustment — p24 Allows spot calibration to eliminate system loop
errors.
Setup Digital Outputs — p18 Set source used to activate each output and define normally open/closed state.
Setup Analog Output — p20 Set an output as control or re-transmission.
Displays and controls
Recorder Faceplate
100.8
Currently Displayed
Channel
CH1 CH2 CH3 CH4
AL1
AL2
AL3
AL4
Alarm Status
Sideways Scroll
Advance to next page
Page 1
Page 2
Down Scroll
Frame 1
Advance to next frame
Frame 2
Raise and Lower Parameter Value
Frame 1 Frame 2
Adjust
or Parameter X Y Z
Select
Function Key
‘Alarm acknowledge’ or ‘Home’ — See Programming Guide, ‘Advanced Configuration’
Pen Lift
Raises and lowers the chart pen.
Note. All programming is carried out using the faceplate keys and displays.
ABB Limited Measurement & Analytics Howard Road, St. Neots Cambridgeshire,
PE19 8EU, UK Tel: +44 (0)870 600 6122 Fax: +44 (0)1480 217948 Email:
enquiries.mp.uk@gb.abb.com
www.abb.com/measurement
© ABB 2019 Specifications subject to change without notice.
IM/C1900-QR Rev. F 08.2019
ABB ME A SUREMENT & ANALY TICS | IM/C1900 – QR
C1900 recorder Quick reference guide
INS
Installation Guide Accessories …………………………. 2 Electrical installation ……………… 6
Siting ………………………………….. 3 Mounting/dimensions …………… 4 Power supplies ……………………
12 Inputs/outputs ……………………… 7
OGR
PGR
Operating Guide Alarms
Acknowledge ………………….. 10 LED status …………………….. 10 Chart ………………………………….. 4
Displays & controls …………… 5, 6 Fault-finding ……………………….. 13 Input error
messages …………. 3 Power-up error codes ……….. 2 Pen fitting …………………………. 4
Process variable …………………… 9 Security Access Configuration level …………… 12
Password ……………………….. 12 Tune level access …………. 12 Self-test ………………………………. 2
Time/date ……………………………. 9 Totalizer …………………………….. 11
Programming Guide Alarms ………………………………. 10 Analog outputs …………………… 19 Chart set
up ………………………… 9 Configuration level ………….. 3, 26 Digital outputs ……………………. 17
Function keys …………………….. 27 Inputs (PV, RSP, P-FB) ………….. 4 Logic equations
………………….. 28 Logic inputs ……………………….. 28 Passwords …………………….. 2, 22 Pen
…………………………………….. 8 Process variable see Inputs Relays ……………………………….. 15
Retransmission outputs
see Analog outputs Scale adjust (span/offset) …….. 23 Spot calibration
see Scale adjust
Setting analog input links
2
3
4
5
6
5
4
5
4
PL1 PL1
mV THC
or
mA V RTD & Resistance
8
1
8
1
PL8
2-wire 1 Transmitter 2
4 or
3
PL8
1
4 All Other
2
3 Input Types
Fig. 1 Input Links Channel 1
2-wire Transmitter
PL3
3
2
4
1
PL3
3
2 All Other
4
1 Input Types
INPUT/OUTPUT MODULE
mV THC
4
1
5 PL1 8
4
1
mA V RTD & Resistance 5 PL1 8
Warning. Ensure that the unit is isolated from all power supplies before removing I/O boards.
Fig. 2 Input Links Channels 2 to 4 (If fitted)
Configuring analog inputs
1000. 999.
SECOdE MMMMMM
OPrtOr LEVEL
bASIC CONFIG
SELECt ____
Select Channel Choose the input channel to be configured
SEtup INPUt
Information. The alphabet used to display page and parameter titles is as follows:
A A B b C C or c D d E E F F G G H H or h I I J J K K L L
M M N N or n O O or o P P Q Q R r S S T t U U V V Y Y
INtYP _
LNtYP
Input type _A_P (mA), VOLt (V), _UL. t (mV), tCPL (Thermocouple), rtd (RTD) and LO OH (< 750 Ohms) HI OH (> 750 Ohms).
ENG-HI
Linearizer: If using a thermocouple set to J, K, B, N, E, T, S, A. Other options are 5/2,, 3/2, SQrt, rtd or NONE.
dEC-Pt ____
Decimal Point: Select the decimal point position for the process variable, e.g. 300.0.
rNG-HI ___
Range High: For a 4 to 20mA current input, set this to 20.00, or for 0 to 5V, set to 5.0. The frame does not appear if tCPL or rtd are used.
ENG-LO ___
rNG-LO ___
Range Low: Set the low end of the electrical input range, e.g. 40. 0, for 4 to 20mA, or 00. for 0 to 5V.
bSPd ___
UNItS ___
Units: Select NONE if the input is not temperature, FdLP
otherwise select dEG F or dEG C.
ENG-HI ____
dEC-Pt
Engineering Range High: Select the highest engineering value that will be displayed when the input is at its maximum value e.g. for an engineering range of 0 to 300.0 °F set to 3000.
PrGFLt ___
Engineering Range Low: Select the lowest engineering value that will be
displayed when the input is at its minimum value e.g. for an engineering
range of 0 to 300.0 °F set to 00. .
Broken Sensor Drive: Determine pen action when the input signal fails: NONE
pen follows failed input; UP pen driven to full scale; dN pen driven to
zero scale.
Fault Detection Drive: Determine maximum input travel outside engineering
range before an error is detected. E.g. for a 0 to 300°F range, a 10% fault
level will trigger at 330°F.
Input Filter: Adjust the instrument response time from 0 to 60 seconds in one
second increments to reduce pen jump & dampen out noisy signals.
—
ABB ME A SUREMENT & ANALY TICS | INSTALL ATION GUIDE | IM/C1900 – INS RE V. P
C1900 Circular chart recorder and recorder/controller
Measurement made easy
—
C1900 circular chart recorder and recorder/controller
For more information
Further publications are available for free download from:
www.abb.com/recorders
or by scanning this code:
Data Sheet C1900
Circular chart recorder
Search for or click on DS/C1900R-EN
Operating Guide C1900
Circular chart recorders
Data Sheet C1900
Circular chart recorder/controller
DS/C1900RC-EN
Programming Guide C1900
Circular chart recorders
Quick Reference Guide C1900 recorders
IM/C1900-QR
Operating Guide C1900
Circular chart recorder/controllers
Quick Reference Guide C1900 recorder and recorder/controller
IM/C1900-QC
Programming Guide C1900
Circular chart recorder/controllers
Search for or click on IM/C1900-OGR IM/C1900-PGR IM/C1900-OGC IM/C1900-PGC
Electrical safety
This equipment complies with the requirements of CEI/IEC 61010-1:2001-2
`Safety Requirements for Electrical Equipment for Measurement, Control and
Laboratory Use’. If the equipment is used in a manner NOT specified by the
Company, the protection provided by the equipment may be impaired.
Symbols
One or more of the following symbols may appear on the equipment labelling:
Warning refer to the manual for instructions
Caution risk of electric shock
Protective earth (ground) terminal
Earth (ground) terminal
Direct current supply only
Health and safety
To ensure that our products are safe and without risk to health, the following
points must be noted:
· The relevant sections of these instructions must be read carefully before
proceeding.
· Warning labels on containers and packages must be observed.
· Installation, operation, maintenance and servicing must only be carried out
by suitably trained personnel and in accordance with the information given.
· Normal safety precautions must be taken to avoid the possibility of an
accident occurring when operating in conditions of high pressure and/or
temperature.
· Chemicals must be stored away from heat, protected from temperature extremes
and powders kept dry. Normal safe handling procedures must be used.
· When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or
any relevant hazard data sheets (where applicable) may be obtained from the
Company address on the back cover, together with servicing and spares
information.
Alternating current supply only
Both direct and alternating current supply
The equipment is protected through double insulation
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for any other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of the Technical Publications Department.
CONTENTS
1 INTRODUCTION
Section
Page
1 INTRODUCTION ………………………………………………….. 1
2 PREPARATION ……………………………………………………. 2 2.1 Accessories ……………………………………………….. 2 2.2 Checking the Code Number …………………………. 2 2.2.1 Non-upgradeable Version …………………. 2
3 MECHANICAL INSTALLATION ……………………………… 3 3.1 Siting ………………………………………………………… 3 3.2 Mounting …………………………………………………… 3 3.2.1 Wall-/Pipe-Mounting ………………………… 4 3.2.2 Panel Mounting ………………………………. 5
4 ELECTRICAL INSTALLATION ……………………………….. 6 4.1 Identifying the Input/Output Modules ……………… 7 4.2 Channel Connections ………………………………….. 7 4.2.1 Selecting the Analog Input Type(s) ……… 8 4.2.2 Voltage and Current ………………………… 9 4.2.3 2-wire Transmitter Input ……………………. 9 4.2.4 Thermocouple ………………………………… 9 4.2.5 Resistance Thermometer (RTD) …………. 9 4.2.6 Logic Inputs …………………………………… 9 4.2.7 Analog Output ………………………………… 9 4.2.8 Relay Output …………………………………. 9 4.2.9 Motorized Valve …………………………….. 10 4.3 Module Connections ………………………………….. 11 4.3.1 Standard I/O or Analog + Relay (Module Types 1, 2 and 7) ………………. 11 4.3.2 Four Relay Module (Module Type 3) ….. 11 4.3.3 Eight Digital Inputs or Outputs (Module Types 4 and 5 respectively) …. 11 4.4 Power Supply Connections …………………………. 13
5 INSTALLATION RECORD ……………………………………. 13
The documentation for the C1900 series of circular chart recorders is shown in
Fig. 1.1. The Standard Manuals, including the data sheet, are supplied with
all instruments. The Supplementary Manuals supplied depend on the
specification of the instrument.
This manual includes an Installation Record which should be completed as a log
of the electrical installation. The record is useful when carrying out initial
instrument programming and can be retained for future reference.
INSTALLATION
Product Identification Siting Mounting Electrical Connections Installation
Record
Part No. IM/C1900INS
DATA SHEET Full Specification
Part No. SS C1900
Recorders and Controllers
OPERATION
Setting Up Error Messages Displays & Controls Operating Level Simple Fault
Finding
Part No. IM/C1900OGR
PROGRAMMING
General Programming Basic Config. Level Advanced Config. Level Connections &
Links
Part No. IM/C1900PGR
Recorders Only
OPERATION
Setting Up Error Messages Displays & Controls Operating Level Simple Fault
Finding
Part No. IM/C1900OGC
PROGRAMMING
General Programming Basic Config. Level Control Config. Level Advanced Config.
Level Connections & Links
Part No. IM/C1900PGC
Controllers Only A Standard Manuals
ADVANCED SOFTWARE OPTIONS
Flow Totalization Ramp/Soak Profile Math Functions Timer Functions
Part No. IM/C1900ADV
MODBUS (RTU)
Serial Adaptors Serial Connections Programming Pages ASCII Tables
Part No. IM/C1900MOD
B Supplementary Manuals
Fig. 1.1 C1900 Documentation
1
2 PREPARATION
2.1 Accessories Fig. 2.1
Pen Capsule 1 to 4
(depending on no. of channels)
Charts (Pack of 3)
Keys (door lock versions only)
A Standard Accessories
(kit contains 2 sets of items shown)
Pipe-mounting Kit C1900/1713
2.2 Checking the Code Number Fig. 2.2
2.2.1 Non-upgradeable Version
Note. The 1901J is a basic, non-upgradeable single pen recorder. This version
is not fitted with an analog output, relay, transmitter power supply unit or
digital inputs and no additional modules can be fitted. The full
identification code is shown below.
1901J A 0 0 1 1 00000 STD
C1900 single pen recorder Electrical code standard Option module none
Options none Door lock not fitted Power supply 115V AC Modules fitted in
module positions 2 to 6 none Special Settings company standard
1
Push to release handle
2
Pull handle to release door…
Case-to-Panel Gasket C1900/0149
(see Note below)
Wall-mounting Kit C1900/1712
(kit contains 4 sets of items shown)
B Optional Accessories
Note. If panel-mounting to NEMA 4X standard is required, a continuous bead of
suitable silicon sealant must be applied between the case flange and the
panel. Do not use the optional gasket.
Fig. 2.1 Accessories
2
6 Check code number against
the Data Sheet SS/C1900R or SS/C1900RC
4
Loosen captive screw
5 Swing chart plate forward 3 …and open door Fig. 2.2 Checking the Code Number
3 MECHANICAL INSTALLATION
3.1 Siting Figs 3.1 and 3.2
Minimum
Sensor
A Close to Sensor
3.2 Mounting Figs. 3.3 to 3.5 Dimensions in inches (mm)
15.04 (382)
B At Eye-level Location
15.23 (386.8)
C Avoid Vibration Fig. 3.1 General Requirements
0°C (32°F) Min.
55°C (131°F) Max.
A Within Temperature Limits
0 to 95% RH
0 to 80% RH
B Within Humidity Limits
Caution. Select a location away from strong electrical and magnetic fields. If
this is not possible, particularly in applications where mobile communications
equipment is expected to be used, screened cables within earthed (grounded)
metal conduit must be used.
C Use Screened Cables
Fig. 3.2 Environmental Requirements
1.30 (33) 2.60 (66)
1.38 (35.1)
7.22 (183.4)
1.44 (36.6) Typical Space Between Adjacent Knockout Centers
0.94 (22.4)
12.63 (320.8)
0.32 (8.3)
12.63 ( 320.8)
1.18 (30.1)
2.23 (56.8)
Fig. 3.3 Overall Dimensions
1.18 (30.1)
3
…3 MECHANICAL INSTALLATION 3.2.1 Wall-/Pipe-Mounting Fig. 3.4
1
Secure mounting brackets (4) to case
2 Mark fixing centers on wall (4)
14.81 (376.3)
1(218.10.60)
Drill suitable
3 holes (4)
4
Secure instrument to wall using suitable fixings
A Wall-mounting (Optional)
1 Position mounting
brackets to suit horizontal
Secure using two nuts and
4
washers
pipe-mounting or vertical
pipe-mounting as required
2 Secure mounting
brackets to case using bolts and washers
2 3/8 in. (60mm) OD horizontal or vertical pipe
3
Fit ‘U’ bolts into brackets
B Pipe-Mounting (Optional) Fig. 3.4 Wall-/Pipe Mounting
4
3.2.2 Panel Mounting Fig. 3.5
Dimensions in inches (mm) 2 Mark four mounting holes
4 holes 0.281 dia. or tap for 1/4 in. thread
14.00 (355.6)
14.19 (360.4)
1.70 (43.2)
12.72 (323.08) minimum
12.72 (323.1) minimum
11.25 (285.8)
0.64 (16.25)
1 Cut hole in panel
(see Note 1 below)
Minimum Cut-out Dimensions
3 MECHANICAL INSTALLATION 3 Drill four suitable holes
Optional gasket (see Note 2 below)
4
Locate instrument in cut-out
5
Secure in panel using four bolts, washers and nuts
0.20 (5.0)
13.7 (348.0) maximum
14.6 (371.0) maximum
0.15 (3.8) minimum
Ensure cut-out positioned centrally between mounting holes
0.15 (3.8) minimum
Notes. 1. The instrument can be inserted into a panel cut-out
of any size between the minimum and maximum dimensions illustrated, provided
the cut-out is positioned centrally relative to the fixing holes. If the panel
cut-out is larger than the maximum, a locally manufactured adaptor plate will
be required. 2. If panel-mounting to NEMA 4X hosedown standard is required, a
continuous bead of suitable silicon sealant must be applied beween the case
flange and the panel. Do not use the optional gasket.
Maximum Cut-out Dimensions
Fig. 3.5 Panel Mounting
5
4 ELECTRICAL INSTALLATION
Warnings. · To comply with Underwriter Laboratories (UL) and Canadian
Standards Association (CSA) certification, route signal leads
and power cables in earthed (grounded), flexible metal conduit. Use the
Position 1 protective ground stud (NOT the terminal module ground stud) to
ground the flexible metal conduit. · Instruments not fitted with the optional
internal on/off switch and fuse must have a disconnecting device such as a
switch or circuit breaker conforming to local safety standards fitted to the
final installation. It must be fitted in close proximity to the instrument
within easy reach of the operator and must be marked clearly as the
disconnection device for the instrument. · Remove all power from supply, relay
and any powered control circuits and high common mode voltages before
accessing or making any connections. · Use cable appropriate for the load
currents. The terminals accept cables up to 14AWG (2.5mm2). · The instrument
and all inputs and outputs conform to Mains Power Input Insulation Category
II. · All connections to secondary circuits must have basic insulation. ·
After installation, there must be no access to live parts e.g. terminals. ·
Terminals for external circuits are for use only with equipment with no
accessible live parts. · If the instrument is used in a manner not specified
by the Company, the protection provided by the equipment may be impaired. ·
All equipment connected to the instrument’s terminals must comply with local
safety standards (IEC 60950, EN601010-1).
Notes. · Always route signal leads and power cables separately. · Use screened
cable for signal inputs and relay connections. Connect the screen to the earth
(ground) stud see Fig. 4.10. · The terminal blocks can be removed from the
main PCB when making connections see Fig. 4.1. Before removing a
module, note its position. · If wall- or pipe-mounting to NEMA 4X hosedown
standard is required, suitable cable glands must be used to prevent
water ingress.
1
Push to release handle
Pull handle to release
2
door…
4
Loosen captive screw
6
Unplug Module
7 Release
Clip
8
Remove Terminal Block Assembly
5 Swing chart plate forward 3 …and open door
Fig. 4.1 Removing Terminal Block Assembly
6
4.1 Identifying the Input/Output Modules Fig. 4.2 To gain access to the
modules, open the door and chassis see Fig. 2.2. There are six module
positions as shown in Fig. 4.2.
4.2 Channel Connections Channel 1 connections are made directly to the
terminal block mounted on the motherboard.
Other Channel connections are made to standard I/O modules, fitted in
positions 2, 3 or 4 see Fig. 4.2.
4 ELECTRICAL INSTALLATION…
2
3
4
5
6
Warning. The maximum channel to channel voltage (between any 2 channels) must not exceed 500V DC.
See Note Below
Channel 1 (Red Pen)
Module 2 3 4 5 6 Positions
Channel 2 (Green Pen)
Channel 3 (Blue Pen)
Channel 4 (Black Pen, Violet Event Pen or Additional Functions)
Not available on non-upgradeable version
Additional Functions
Additional Functions
Notes. · Module positions can also be used for
additional I/O modules (module types 1 and 2) for use with math functions. ·
The module type is marked on the component side of the PCB.
Fig. 4.2 Module Positions and Functions
7
…4 ELECTRICAL INSTALLATION
4.2.1 Selecting the Analog Input Type(s) Figs. 4.3 and 4.4
Plug-in links are used to select the input type:
Channel 1
PL1 & PL8 on the main p.c.b. (Fig. 4.3)
Channels 2 to 4
PL1 & PL3 on the module (Fig. 4.4)
5
4
PL1
8
1
mV THC
PL8
1
4
2
3
2-wire Transmitter
5
4
PL1
8
1
mA V RTD & Resistance
PL8
1
4
C110
STAR C104
C83
R50
DJ4 IC19
C25 L14
R44
IC6
PL1
5
4
TR6
8
1
C122 C18
C117 C119
1
4
L22
R64 JC50
2
3
PL8
C126
TR9 R53 +
D15
L11
TRA9 L17
+ IC5
C12 C13
2
3
All Other Input Types
Fig. 4.3 Selecting the Input Type (Main Board)
2
3
4
5
6
C33
PL3
3
2
4
1
2-wire Transmitter
4
1
PL3
3
2
4
1
All Other Input Types
4
1
R56
C17 C16 R21 C10
PL3
4
R26 C15 R30 R44
R24
C34
C35
C19
C21 C14 C25 IC20
C20 PL1
R36
R27
L5
R22
C38 R25
INPUT/OUTPUT MODULE
C29 C24 C26 C27
C23 C22 C13
C30
5
PL1 8
mV THC
5
PL1 8
mA V RTD & Resistance
Fig. 4.4 Selecting the Input Type (I/O Modules)
Type of Thermocouple Ni-Cr/Ni-Al (K) Ni-Cr/Cu-Ni (E) Nicrisil/Nisil ( N) Pt
/Pt-Rh (R and S) Pt-Rh/Pt-Rh (B) Cu/Cu-Ni (T) Fe/Con (J)
Fe/Con (DIN 43710)
Compensating Cable
BS1843
ANSI MC 96.1
DIN 43714
BS4937 Part No.30
Case
Case
Case
Case
Brown Blue Red Yellow Red Yellow Red Green Green Green White Green*
—
—
—
Violet White Violet*
Orange Blue Orange Orange Red Orange
—
Pink White Pink
White Blue Green Black Red Green Red White White Orange White Orange*
—
—
—
Grey White Grey*
White Blue Blue Blue Red Blue
Red Brown Brown Brown White Brown*
Yellow Blue Black White Red Black
Red
Blue Blue Black White Black*
- Case Blue for intrinsically safe circuits
DIN 43710
—
—
—
Blue/Red Blue Blue
Table 4.1 Thermocouple Compensating Cable
8
4.2.2 Voltage and Current Fig. 4.5
Input impedances:
Low voltage (mV)
10M
Voltage
10M
Current (mA)
100
4.2.3 2-wire Transmitter Input Fig. 4.5 Power for the transmitter is
supplied by terminal 6.
Note. The voltage across terminals 4 and 6 is 20V (nominal). This is due to
internal voltage drops across a shunt resistor and measurement circuitry.
4 ELECTRICAL INSTALLATION…
4.2.5 Resistance Thermometer (RTD) Fig. 4.5 If long leads are necessary it
is preferable to use a 3-lead resistance thermometer.
If 2-lead resistance thermometers are used each input must be calibrated to
take account of the lead resistance.
4.2.6 Logic Inputs Fig. 4.5 The two logic inputs accept either volt-free
(switch) or TTL (5V) input types and can be used for remote switching of many
recorder functions, e.g. chart stop/go, alarm acknowledgment, totalizer reset
etc. Refer to the Programming Guide, IM/C1900PGR or IM/C1900PGC.
4.2.4 Thermocouple Fig. 4.5 Use correct compensating cable between the
thermocouple and the terminals see Table 4.1 (previous page).
Automatic cold junction (ACJC) is incorporated but an independent cold
(reference) junction may be used.
4.2.7 Analog Output Fig. 4.5
4.2.8 Relay Output Fig. 4.5
Relay specification:
Type
single pole changeover
Voltage
250V AC 250V DC
Current
5A AC
5A DC
Loading (non inductive)
1250VA
50W
Isolation, contacts to earth 2kV RMS
1
2
Analog Output (See Note below)
3
4 Analog Input see B to H
5
6
7
Common
8
Logic 1 Logic Inputs (See Note below)
9
Logic 2
10
Normally Open
1
Common
Relay Output
12
Normally Closed
Note. Not applicable on Type 2 Modules. A Summary of Connections
4
6
Tx See Note below
D 2-wire Transmitter (not available on non-upgradeable version)
3
- 6
E Thermocouple
3
6
F Low Voltage (mV)
3
3
4
6
4
5
6
Red White Red
Link
4
5
White
6
Red
B Voltage
C Current
(non 2-wire transmitters) *
G 3-wire RTD
H 2-wire RTD & Resistance
- Recommended diode: Diode forward voltage > 0.8 V @ 20 mA or use 2 x 1N4001 general purpose diodes in series
Fig. 4.5 Channel Connections
9
…4 ELECTRICAL INSTALLATION
4.2.9 Motorized Valve Fig. 4.6 A motorized valve with or without feedback
requires 2 relays (common and normally open terminals) to drive the valve in
either direction. Any two relays can be allocated for this function. Fig. 4.6
A shows two possible combinations.
Note. For valves with position feedback using low voltage (mV), voltage (V) or current (C), refer to Fig. 4.5 B, C and F for connections.
(L)
Valve
L
Positioner
Power
Supply
N
1st Module
2nd Module
(N) Four Relay Module
10 2 11 3
4 10 5 11 6
Type 1 and/or Type 2 Modules (see Note 1 below)
100% 0%
Type 1 or Type 2 Module
Motorized Valve Drive
0% 4
5
6
100%
Link (see Note 2 below)
A Standard Feedback Slidewire Configuration
1st or 2nd Module
Type 1 or Type 2 Module
Motorized Valve Drive
0% 4
5
6
100%
Link (see Note 2 below)
B Alternative Feedback Slidewire Configuration
Notes. 1 Type 1 and type 2 modules have one relay output, therefore two
modules are required. 2 Link must be connected at valve drive end, not at the
controller terminals.
Fig 4.6 Motorized Valve Connections (using feedback slidewire)
1st or 2nd Module
10
4 ELECTRICAL INSTALLATION…
4.3 Module Connections
4.3.1 Standard I/O or Analog + Relay (Module Types 1, 2 and 7) Fig. 4.5 The
connections are the same as Channel connections to the main board. Refer to
Section 4.2.
4.3.3 Eight Digital Inputs or Outputs (Module Types 4 and 5 respectively) Figs. 4.8 and 4.9 A plug-in link is used to select the board’s function; digital inputs or digital outputs see Fig. 4.8. The maximum current drain from each TTL output must not exceed 5mA.
4.3.2 Four Relay Module (Module Type 3) Fig. 4.7
1
Normally Closed
2
Normally Open
Relay 1
3
Common
4
Normally Closed
5
Normally Open
Relay 2
6
Common
7
Normally Closed
8
Normally Open
Relay 3
9
Common
10
Normally Closed
11
Normally Open
Relay 4
12
Common
Fig. 4.7 Four Relay Module Connections (Module Type 3)
PL2
4
1
PL2
3
2
PL2
3
2
4
1
Digital Inputs
4
1
Digital Outputs
Fig. 4.8 Selecting the Digital Module Function (Module Types 4 and 5)
1
Common
Common
2
Input 1
Output 1
3
Input 2
Output 2
4
Input 3
Output 3
5
Input 4
Output 4
6
Input 5
Output 5
7
Input 6
Output 6
8
Input 7
Output 7
9
Input 8
Output 8
10
Common
Common
11
12
Input
Output
Connections or Connections
Fig. 4.9 Eight Digital Inputs or Outputs Connections (Module Types 4 and 5)
11
…4 ELECTRICAL INSTALLATION 4.4 Power Supply Connections Fig. 4.10
2
3
4
5
6
X
Power Switch (Optional) Fuse (Optional)
see Note 1 below
Note. Recorders manufactured before June 2005 are fitted with a Mainboard that is not equipped with a universal power supply. Ensure the supply voltage selector switch is set correctly and the appropriate fuse is fitted see Fig 4.11.
Digit 10 Code Label
1 9 x x x x x x x x x x x x x x
1 or 4
115
3 or 6 Selector not Fitted (24V AC Version)
2 or 5
230
Line Neutral
Earth (Ground) Stud see Note 2 below
Remove Plug, Connect Power Supply Leads to Plug and Refit Plug
Warning. If the optional internal power switch and fuse are not fitted, an
external disconnection device and fuse must be fitted see also Warnings on
page 6.
Line Neutral
Before making any electrical connections, see Warnings on page 6
Notes. 1. Fuse rating:
500mA (20 X 5mm) Type T 2. Ensure that the Earth (Ground) lead is longer than
the Line and Neutral leads.
Fig. 4.10 Power Supply Connections
Position 1 Position 2 Position 3 Position 4 Position 5 Position 6
115
Fuse (Optional) see Note below
Note. Fuse ratings: 115V Supply 1A (20 x 5mm) Type T 230V Supply 1/2A (20 x
5mm) Type T 24V Supply 4A (20 x 5mm) Type T
Fig. 4.11 Power Supply Selection (Recorders Manufactured Before June 2005
Only)
12
13
Position 1
Module Type 1
Analog Output
1+
2
3
Link Positions
(Tick Boxes)
4
Analog Input
5
6
7C
Logic Inputs
8 L1
9 L2
10 NO
Relay Output
1C
12 NC
Position 4
Module Type (Tick Box) 1
2
6
7
Analog Output
1+
2
3
Link Positions
(Tick Boxes)
4
Analog Input
5
6
- 7C
Logic Inputs
- 8 L1
9 L2
10 NO
Relay Output
1C
12 NC
- Not available on Module Type 2
Position 2
Module Type (Tick Box) 1
2
Analog Output
1+
2
3
Link Positions
(Tick Boxes)
4
Analog Input
5
6
7C
Logic Inputs
- 8 L1
9 L2
10 NO
Relay Output
1C
12 NC
- Not applicable on Module Type 2
Relay Output 1
Relay Output 2
3
1 NC 2 NO 3C 4 NC 5 NO 6C 7 NC 8 NO 9C 10 NC 1 NO 12 C
Relay Output 3
Relay Output 4
Position 3
Module Type (Tick Box) 1
2
Analog Output
1+
2
3
Link Positions
(Tick Boxes)
4
Analog Input
5
6
7C
Logic Inputs
8 L1
9 L2
10 NO
Relay Output
1C
12 NC
- Not applicable on Module Type 2
4
5
1C
Logic I/Ps (Type 4) or Logic O/Ps (Type 5)
21
32
43
54
65
76
87
98
10 C
Link Positions (Tick Box) Type 4
Type 5
5 INSTALLATION RECORD
14
Position 5
Module Type (Tick Box) 2
Analog Output
1+
2
3
Link Positions (Tick Boxes)
4
Analog Input
5
6
- 7C
Logic Inputs
- 8 L1
9 L2
10 NO
Relay Output
1C
12 NC
- Not available on Module Type 2
Position 6
Module Type (Tick Box) 2
Analog Output
1+
- 2
3
Link Positions (Tick Boxes)
4
Analog Input
5
6
- 7C
Logic Inputs
- 8 L1
9 L2
10 NO
Relay Output
1C
12 NC
- Not available on Module Type 2
Relay Output 1
Relay Output 2
3
1 NC 2 NO 3C 4 NC 5 NO 6C 7 NC 8 NO 9C 10 NC 1 NO 12 C
Relay Output 3
Relay Output 4
4
5
1C
Logic I/Ps (Type 4) or Logic O/Ps (Type 5)
21
32
43
54
65
76
87
98
10 C
Link Positions (Tick Box) Type 4
Type 5
4
5
Logic I/Ps (Type 4) or Logic O?ps (Type 5)
1C
21
32
43
54
65
76
87
98
10 C
Link Positions (Tick Box) Type 4
Type 5
…5 INSTALLATION RECORD
NOTES
15
…NOTES
16
Sales
Service
Software
— ABB Limited Measurement & Analytics Howard Road, St. Neots Cambridgeshire,
PE19 8EU UK Tel: +44 (0)870 600 6122 Fax: +44 (0)1480 217 948 Email:
enquiries.mp.uk@gb.abb.com ABB Inc. Measurement & Analytics 125 E County Line
Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183
abb.com/measurement
— We reserve the right to make technical changes or modify the contents of
this document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any responsibility whatsoever
for potential errors or possible lack of information in this document. We
reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third parties
or utilization of its contents in whole or in parts is forbidden without
prior written consent of ABB. © ABB 2018
IM/C1900-INS Rev. P 09.2018
—
ABB ME A SUREMENT & ANALY TICS | OPER ATING GUIDE | IM/C1900 – OGR RE V. L
C1900 Circular chart recorder
Measurement made easy
—
C1900 circular chart recorder
For more information
Further publications are available for free download from:
www.abb.com/recorders
or by scanning this code:
Data Sheet C1900 Circular chart recorder
Quick Reference Guide C1900 Circular chart recorder
Installation Guide C1900 Circular chart recorder and
recorder / controller
Programming Guide C1900 Circular chart recorder
Operating Instructions C1900 Circular chart recorder and
recorder/controller
User Guide C1900 Circular chart recorder and
recorder/controller
Search for or click on DS/C1900R-EN IM/C1900-QR IM/C1900-INS IM/C1900-PGR IM/C1900-MOD IM/C1900-ADV
Use of instructions
Health and safety
Warning an instruction that draws attention to the risk of injury or death.
Caution an instruction that draws attention to the risk of damage to the
product, process or surroundings.
Note clarification of an instruction or additional information. Information.
Information further reference for more detailed information or technical
details.
It must be understood that operation of damaged equipment could, under certain
operational conditions, result in degraded process system performance leading
to personal injury or death. Therefore, comply fully with all Warning and
Caution notices.
Information in this manual is intended only to assist our customers in the
efficient operation of our equipment. Use of this manual for any other purpose
is specifically prohibited and its contents are not to be reproduced in full
or part without prior approval of the Technical Publications Department.
To ensure that our products are safe and without risk to health, the following
points must be noted:
· The relevant sections of these instructions must be read carefully before
proceeding.
· Warning labels on containers and packages must be observed.
· Installation, operation, maintenance and servicing must only be carried out
by suitably trained personnel and in accordance with the information given.
· Normal safety precautions must be taken to avoid the possibility of an
accident occurring when operating in conditions of high pressure and/or
temperature.
· Chemicals must be stored away from heat, protected from temperature extremes
and powders kept dry. Normal safe handling procedures must be used.
· When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or
any relevant hazard data sheets (where applicable) may be obtained from the
Company address on the back cover, together with servicing and spares
information.
CONTENTS
1 INTRODUCTION
Section
Page
1 INTRODUCTION ………………………………………………….. 1
2 SETTING UP ……………………………………………………….. 2 2.1 Instrument Power-up …………………………………… 2 2.1.1 Power-up Error Codes …………………….. 3 2.2 Fitting the Chart ………………………………………….. 4 2.3 Fitting the Pen Capsule(s) …………………………….. 4
3 DISPLAYS & CONTROLS ……………………………………… 5 3.1 Displays and LED Indicators …………………………. 5 3.2 Use of Controls …………………………………………… 6
4 OPERATION ………………………………………………………… 7 4.1 Input Error Messages …………………………………… 8 4.2 Operating Page Displays ………………………………. 9 4.3 Alarm Acknowledge Page …………………………… 10 4.3.1 Alarm Indications …………………………… 10 4.3.2 Acknowledging Alarms …………………… 10 4.3.3 Using the Alarm Acknowledge Page ……………………….. 10 4.4 Totals Page Displays ………………………………….. 11 4.5 Access to Configuration Levels ……………………. 12
5 SIMPLE FAULT FINDING ……………………………………. 13
6 SPARES LIST ……………………………………………………. 14
The documentation for the C1900 series of circular chart recorders is shown in Fig. 1.1. The Standard Manuals, including the data sheet, are supplied with all instruments. The Supplementary Manuals supplied depend on the specification of the instrument.
INSTALLATION
Product Identification Siting Mounting Electrical Connections Installation
Record
Part No. IM/C1900INS
OPERATION
Setting Up Error Messages Displays & Controls Operating Level Simple Fault
Finding
Part No. IM/C1900OGR
PROGRAMMING
General Programming Basic Config. Level Advanced Config. Level Connections and
Links
DATA SHEET Full Specification
Part No. IM/C1900PGR
Part No. SS C1900
A Standard Manuals
ADVANCED SOFTWARE OPTIONS
Flow Totalization Ramp/Soak Profile Math Functions Timer Functions
Part No. IM/C1900ADV
MODBUS (RTU)
Serial Adaptors Serial Connections Programming Pages ASCII Tables
Part No. IM/C1900MOD
B Supplementary Manuals Fig. 1.1 C1900 Documentation
1
2 SETTING UP
2.1 Instrument Power-up Fig. 2.1 and 2.2
Caution. Ensure that all connections, especially to the earth stud, are made
correctly.
a) Check that the input sensors are installed correctly. b) Check that the
pen(s) are installed correctly see Fig. 2.1. c) Switch on the supply to the
instrument, any power-operated
control circuits and the input signals. Wait for the pens to settle.
Note. On power-up, the pens are moved to an offchart position for automatic
referencing. Pen chatter may occur on those pens nearest the reference
position. This is a normal function of the instrument.
d) The start-up sequence shown in Fig. 2.2 is displayed on faceplate 1 when
the supply is first switched on.
Blue Pen (Channel 3)
Red Pen (Channel 1)
Green Pen (Channel 2)
Black Pen (Channel 4) see Note
0.175 (4.4) Chart Time Line
0.175 (4.4)
0.35 (8.8)
Dimensions in inches (mm)
Note. If the true time line event option is fitted, the violet event pen records on the same time line as the red pen, but on the outer edge of the chart.
Fig. 2.1 Checking the Pen(s) Installation
1914 J tESt
Instrument Test identifies the instrument type, e.g. 1914J see Table 2.1 in
the Installation Manual.
CPU PASS
CPU
or
FAIL
CPU Test carries out check of processor circuitry see Error Codes below.
CONFIG
CONFIG
PASS
or
FAIL
Configuration Test carries out check of non-volatile memories containing the instrument configuration, then indicates pass or fail see Error Codes below.
CAL PASS
CAL
or
FAIL
Calibration Test carries out check of non-volatile memories containing the calibration data for each analog input and output, then indicates pass or fail see Error Codes below.
bb rAM
bb rAM
PASS
or
FAIL
Battery Back RAM Test carries out check of batterybacked RAM, then indicates pass or fail see Error Codes below.
!00.3
AF
200.3
or
24
AL
RMT
AT
MAN
Normal Display
Not applicable on single channel instruments
Error Codes are displayed in the event of a fault see Section 2.1.1.
Fig. 2.2 Instrument Displays at Start-up
2
2 SETTING UP…
2.1.1 Power-up Error Codes If any of the power-up tests fail (see Fig. 2.2),
error codes are displayed to identify the fault. Refer to Fig. 2.3 for error
code interpretations.
AF 24
Configuration and battery-backed RAM errors Calibration errors
Code No error 1 Main board
Error
2 Module in position 2
3 Module in position 3 4 Module in position 4
Analog input and/or analog output calibration is corrupt
5 Module in position 5
6 Module in position 6
None
Action
Power down and then up again.
If fault remains, contact the local Service Organisation.
Code
Error
No error
A
Main program data stored in non-volatile memory on main board is corrupt
C Timer set up stored in battery backed RAM is corrupt
None
Action
Check and correct program data
Check and correct data in Set Up Timer Page*
d Maths set up stored in battery back RAM is corrupt
Check and correct data in Set Up Maths Page*
F Totalizer set up in battery backed RAM has been corrupt Check and correct data in Set Up Totals Page*
Acknowledging Error Codes
ACKNLG ErrOrS
- Refer to the Advanced Software Manual
or
100.3
200.5
Note. Acknowledging the Error Code clears the error state but does not rectify
the fault. After acknowledging the error, carry out the relevant action
detailed in the above tables.
Fig. 2.3 Power-up Error Codes
3
…2 SETTING UP 2.2 Fitting the Chart Fig. 2.4
75.0
dEG F
AL
RMT
AT
MAN
1 Raise pens
2.3 Fitting the Pen Capsule(s) Fig. 2.5
75.0
dEG F
AL
RMT
AT
MAN
1 Raise pens
2 Lift the chart clamp
and remove the chart
2 Gently pull the arm off
the bracket see Note
3 Fit new chart ensuring
that it is beneath the pen lifter bars
Note. Take care not to bend the arms during removal and refitting, as pen clashing may result.
4 Locate chart
under guides
5 Rotate chart to align the
time line with the red pen (see also Fig. 2.1)
6 Lower the chart clamp
3
Remove spent capsule
4
Fit new pen capsule ensuring that the arm
locates in the pen
capsule slot
5 Remove cap
Fig. 2.4 Fitting the Chart 4
Lifter bars
7 Slide pen assembly onto
the appropriate bracket until it clips into place see Note
6
Ensure that the arm is positioned above its lifter bar
Fig. 2.5 Fitting the Pen Capsules
3 DISPLAYS & CONTROLS
The displays, LED indicators and operation/programming controls are located on
the faceplate on the front panel of the instrument see Fig 3.1.
3.1 Displays and LED Indicators Fig. 3.1 The displays comprise 2 rows of 6
characters.
At the top of each programming page (the page header) both displays are used
to describe the particular page selected.
When parameters within the selected page are viewed the upper display shows
the parameter and the lower display shows the value or setting for that
parameter.
Alarm and Channel states are indicated by separate LEDs on the faceplate of
the front panel of the instrument see Sections 4.1, 4.2 and 4.3.
8.8.8.8.8.8.
Displays
8.8.8.8.8.8.
LED Indicators see Section 4
Controls Refer to Fig. 3.2(a) to (f) for functions
Information. AL1 Channel 1 AL2 Channel 2 AL3 Channel 3 AL4 Channel 4
Status of process variable alarms
CH1 Channel 1 CH2 Channel 2 CH3 Channel 3 CH4 Channel 4
Current channel displayed
Fig. 3.1 Location of Displays, Controls and LED Indicators
A
A
L
L
B
b
M
M
C
C or c
N
N or n
D
d
O
O or o
E
E
P
P
F
F
Q
Q
G
G
R
r
H
H or h
S
S
I
I
T
t
J
J
U
U
K
K
V
V
Y
Y
Table 3.1 Character Set
5
…3 DISPLAYS & CONTROLS 3.2 Use of Controls Fig. 3.2(a) to (f)
Return from any frame
Page 1 Frame 1 Frame 2 Frame 3 Frame 4
Page 2 Frame 1 Frame 2 Frame 3
Fig. 3.2(a) Advancing to Next Page
Page X Frame 1
Advance to next Frame
Frame 2 Frame 3 Frame 4
Fig. 3.2(b) Moving Between Parameters
Parameter Value
Adjust
Note. Continued pressure on the and keys causes the rate of change of the
displayed value to increase. To make small adjustments operate the keys
momentarily.
Fig. 3.2(c) Adjusting a Parameter Value
Parameter X Y Z
Select
Note. Continued pressure on the and keys causes the rate of change of the displayed value to increase. To make small adjustments operate the keys momentarily.
Fig. 3.2(d) Selecting a Parameter Choice
Lift/Lower pen on alternate operations
Notes. · The key can be enabled or disabled in the Set Up
Chart Page, BASIC CONFIGURATION LEVEL. · If ‘Auto Pen Lift Drop’ has been
selected in the Set Up
Chart Page, the pens return automatically to their operating positions after a
five minute delay.
Fig. 3.2(e) Lifting/Lowering the Pens
Information. The key is programmed in the Set Up Function Keys Page, ADVANCED
CONFIGURATION LEVEL.
Acknowledge all alarms or
Return operator to top of Operating Page.
Op. Page Parameter 1 Parameter 2
Page X Parameter 1 Parameter 2
Page X Parameter 1 Parameter 2
Note. The key returns the instrument display to the start of the operating page only when the display is at the top of any page.
Fig. 3.2(f) Selecting Programmable Functions
6
7
Fig. 4.1 Summary of Operating Level
Faceplate 1 Pages See Note
If Totalizer option is not fitted or
Totalizers 1 & 2 are off
Operating Page Section 4.2 Page 9
PV1 & PV2
PV1 & Units
PV2 & Units
tIME
Time
dAtE
Date
Alarm Acknowledge Page
Total Page
Section 4.3 Page 10
Section 4.4 Page 11
ACKNLG ALArMS
Acknowledge Alarms
tOtALS PAGE
Totalized Value
Alarm Identity/Type
Total 1
rESEt t1___
Reset Total
Only applicable with Timer option
COUNt ____
Stop/Go
Total 2
rESEt t2___
Reset Total
COUNt ____
Stop/Go
Security Code Page Section 4.5 Page 12
SECOdE
Security Code
__ ISS _
EPROM Identity
OPrtOr LEVEL
Operator Level
bASIC CONFIG
Basic Config
AdVNCd CONFIG
Advanced Config
Note. The Alarm Acknowledge pages are displayed only if an alarm is active.
Faceplate 2 Pages See Note
If Totalizer option is not fitted or Totalizers
3 & 4 are off
Operating Page Alarm Acknowledge Page
Total Page
Section 4.2 Page 9 Section 4.3 Page 10 Section 4.4 Page 11
ACKNLG
tOtALS
PV3 & PV4
ALArMS
Acknowledge Alarms
PAGE
Totalized Value
PV3 & Units
Alarm Identity/Type
Total 3
rESEt
t3___
PV4 & Units
Reset Total
tIME ____
Time
dAtE
Only applicable with Timer option
COUNt ____
Stop/Go
Date
Total 4
rESEt
t4___
Reset Total
COUNt
Stop/Go
4 OPERATION
…4 OPERATION
The instrument has dedicated Operating Pages in the OPERATOR LEVEL see
Sections. 4.1 to 4.4. These pages are used for general monitoring of the
process measurements and are not affected by the security system which
inhibits access to the PROGRAMMING LEVELS only see Section 4.5 on page 12.
4.1 Input Error Messages Fig. 4.2
Message
Reason
Ad.FAIL Internal analog to digital converter system hardware has failed
FINPt
Input is above or below fault detection level. or Input exceeds the limits for the linearizer selected
Action
· Check that the input/output board is located correctly in its socket.
· Power down and up
If the ‘Ad.FAIL’ message is still present, contact the local service
organization
· Check input source for possible broken sensor · Check input connections ·
Check input link position · Check input configuration in Set Up Input Page
Examples
Ad.FAIL 200.5
Hardware failure on Process Variable 1
200.5 FINPt
Input out of range on Process Variable 4
Note. Error messages are cleared automatically when the fault condition no longer exists. Fig. 4.2 Input Error Messages Displayed in the Operating Page
8
4.2 Operating Page Displays
4 OPERATION…
Faceplate 1 for channels 1 and 2
Faceplate 2 for channels 3 and 4
100.3
200.5
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Process Variable 1 (PV1)
Process Variable 2 (PV2) Not displayed on single pen recorder.
300.3
400.5
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Process Variable 3 (PV3)
Process Variable 4 (PV4) Not displayed on three pen recorders.
100.3
dEG
CH1
AL1
AL2
CH2
CH3
CH4
F
AL3
AL4
Process Variable 1 (PV1)
Temperature Units for PV1
as set in the BASIC
CONFIGURATION
LEVEL.
Display is blank if ‘NONE’ is
selected.
300,3
dEG F
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Process Variable 3 (PV3)
Temperature Units for PV3
as set in the BASIC
CONFIGURATION
LEVEL.
Display is blank if ‘NONE’ is
selected.
200.5
dEG F
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Process Variable 2 (PV2)
Temperature Units for PV2
as set in the BASIC
CONFIGURATION
LEVEL.
Display is blank if ‘NONE’ is
selected.
400.5
dEG F
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Process Variable 4 (PV4)
Temperature Units for PV4
as set in the BASIC
CONFIGURATION
LEVEL.
Display is blank if ‘NONE’ is
selected.
tIME
12. 00
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Current Time
Time (displayed using 24hr clock) *Displayed only when timer option is
fitted.
tIME
12. 00
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Current Time
Time (displayed using 24hr clock) *Displayed only when timer option is
fitted.
dAtE
24
CH1
AL1
CH2
CH3
CH4
JAN
AL2
AL3
AL4
Current Date
Day and Month *Displayed only when timer option is fitted.
dAtE
24
CH1
AL1
CH2
CH3
CH4
JAN
AL2
AL3
AL4
Current Date
Day and Month *Displayed only when timer option is fitted.
9
…4 OPERATION
4.3 Alarm Acknowledge Page
4.3.1 Alarm Indications Fig. 4.3 The definitions for alarm states (on, off
or flashing) are detailed in Fig. 4.3.
4.3.2 Acknowledging Alarms
Note. Channel 1 and 2 alarms can be acknowledged only from faceplate 1. Channel 3 and 4 alarms (if applicable) can be acknowledged only from faceplate 2.
Unacknowledged alarms can be acknowledged from the faceplate controls on the front panel in two ways:
In the OPERATING LEVEL by pressing the key at any frame (providing the key is programmed for this function see Section 4.1 in the Programming Manual).
In the Alarm Acknowledge Page by pressing the see Section 4.3.3 following.
key
4.3.3 Using the Alarm Acknowledge Page
302
No Alarm Active No LED indicators illuminated.
795
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Alarm Activated
302
802
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Alarm Active AL2 LED indicator flashing, indicating active alarm on channel 2.
Use
key to go to top of
Alarm Acknowledge Page.
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
No LED illuminated indicates no alarms active. The Alarm Acknowledge Page is not displayed in the OPERATOR LEVEL.
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
A flashing LED indicates an unacknowledged alarm on that channel. For example,
a flashing AL1 LED indicates an unacknowledged alarm on channel 1. The Alarm
Acknowledge Page is now displayed in the OPERATOR LEVEL.
A constant LED indicates that all active alarms have been acknowledged on that
channel. The Alarm Acknowledge Page remains in the OPERATOR LEVEL until all
alarm conditions are cleared on that channel.
Fig. 4.3 Alarm LED Indications
ACKNLG
ALArM5
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Alarm Acknowledge Page Use key to advance to next frame
A2HPrC
800
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Alarm Identity Upper display: shows the alarm identity and type.
Lower Display: shows the trip level of the alarm identified in the upper
display.
A2HPrC
ACKNGd
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Acknowledge Alarm Use key to acknowledge the alarm (see). When the alarm is acknowledged, ‘ACKNGd’ is displayed and a constant LED indicates the acknowledged alarm.
If there are more active alarms on channel 2 the LED continues to flash until
all alarms for that channel have been acknowledged.
Note. The key or a digital input can also be used to acknowledge alarm, if
programmed.
10
4 OPERATION…
4.4 Totals Page Displays This page is omitted from both faceplates if the
Totalizer Option is not fitted. The page is also omitted from faceplate 1 if
both Totals 1 and 2 are set to OFF and from faceplate 2 if both Totals 3 and 4
are set to OFF refer to the Set Up Totals Page in the Advanced Software
Options Manual.
tOtALS
PAGE
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
tOtALS
PAGE
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
1234
5678
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
rESEt
tI
CH1
AL1
CH2
CH3
CH4
NO
AL2
AL3
AL4
8765
4321
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
If YES selected
t1 YES
t1 YES t1 NO
rESEt
tI NO
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Front Panel (Batch) Flow Total 1 (3) The batch flow total is calculated from
process variable 1 (3). The flow total can be reset if Reset Enable in Set Up
Totals Page is set to ‘ENbLY’.
The flashing channel LED indicates the flow total displayed.
For example, a flashing channel 1 LED indicates Flow Total 1 parameters
displayed.
Counter Reset The Front (Batch) Flow Total can be reset to the Preset Value in
Set Up Totals Page if required.
Select ‘t1 YES’ to reset the counter ( ‘t1’ indicates Flow Total 1 ).
Note. If the Counter Reset is disabled in Set Up Totals Page, the counter
reset frame is omitted.
COUNt
StOP
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Repeat for Total 2 (if applicable)
GO
GO StOP
COUNt
StOP
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Repeat for Total 4 (if applicable)
Counter Stop/Go Select ‘GO’ to start the counter or ‘StOP’ to stop it.
Note. If the Counter Stop/Go is disabled in Set Up Totals Page, the frame can
be viewed but not altered. If a digital signal is assigned to the Totalizer
Stop/Go, an active digital signal sets the counter to GO and the Counter
cannot be stopped from the front panel.
1234
5678
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
8765
4321
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Front Panel (Batch) Flow Total 2 (4) Repeat the above procedure for Flow Total
2 (4). Note. The number of totalizers is dependent on the number of pens
fitted to the instrument e.g. a 3 pen instrument has 3 totalizers.
11
…4 OPERATION
4.5 Access to Configuration Levels A security system is used to prevent tampering with the programmed parameters by utilizing a password giving access to all programming pages refer to the Programming Manual.
SECOdE
100
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Security Code the pen adjustment password
Incorrect Password
100.0
75.5
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Security Code Page Set the security code to the correct password using the and
keyes and use the key to advance to other programming levels (OPERATOR, BASIC
CONFIGURATION and ADVANCED CONFIGURATION).
The password is programmed in the Access Page in the BASIC CONFIGURATION
LEVEL.
Correct Password
PEN 1
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
PEN 4
CH1 CH2 CH3 CH4
AL1
AL2
AL3
AL4
Pen Position Adjustment (Pens 1 to 4) The position of any trend pen can be
adjusted against a reference standard (without changing the displayed value).
Each pen can be adjusted in steps upwards (towards the edge of the chart) or
downwards (towards the center of the chart).
When this feature is enabled, a password must be entered before adjustments
can be made.
Note if pen adjustment is disabled or if the password is incorrect, the four
Pen Adjustment frames are not displayed.
For each trend pen, the lower part of the frame shows the pen position
adjustment.
Pen position adjusted downwards by > 25 steps
Pen position adjusted downwards by between 1 and 25 steps
Pen position not adjusted
Pen position adjusted upwards by between 1 and 25 steps
Pen position adjusted upwards by > 25 steps
adjusts the pen position upwards (towards outer edge of chart) adjusts the pen
position downwards (towards center of chart) The pen adjustment frame for any
given pen only appears if the pen is a Trend pen
2001
ISS _
CH1 CH2 CH3 CH4
AL1
AL2
AL3
AL4
EPROM Version
EPROM Issue Number
EPROM Identification Use the key to advance to the EPROM Identification Frame. The upper display shows the EPROM version, e.g. 2001 and the lower display shows the EPROM issue number.
OPrtOr
LEVEL
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
BASIC
CONFIG
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
AdUNCd
CONFIG
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
OPt ION
tYPE 0
CH1 CH2 CH3 CH4
AL1
AL2
AL3
AL4
Option Shows the software key option type. For details of the options, refer to the Data Sheet, SS/C1900R
12
5 SIMPLE FAULT FINDING
Symptom Does not power up
Chart does not appear to move
Possible Cause
a) Internal fuse (if fitted) is blown b) Internal power switch (if fitted) is
OFF c) Power supply connections are incorrect
a) Very slow chart speed selected
b) Chart stop function enabled
Pens in recording position but do not drop Chart stop function enabled onto paper
Red pen does not move beyond 94% position on chart
When real time event pen is fitted the red pen cannot go beyond 94% to prevent pens clashing
Pen lift switch on front panel does not work
Pen lift switch is disabled
Pens do not remain lifted when pen lift key Auto pen drop feature is enabled is used
Analog inputs are slow to respond
A large filter time has is set
Time or date incorrect
Not set for correct local time
Totalizers cannot be set to STOP or GO
Totalizer cannot be set to STOP
External relays connected to relays in instrument fail to de-energize
Operator STOP/GO selection is not enabled in the OPERATOR LEVEL
Digital signal assigned to the total STOP/GO function is active
Arc suppression capacitors are provided across the relay contacts and
capacitor leakage current may be sufficient to prevent an external relay from
de-energizing
Action
a) Check wiring, rectify fault and replace fuse b) Turn power switch ON c)
Check connections
a) Select required chart speed in Set Up
Chart Page
b) De-activate source being used to stop chart see Set Up Chart Page
De-activate source used to stop chart see
Set Up Chart Page
Use chart range which prevents the need to go beyond 94% of maximum on chart
Enable pen-lift switch in Set Up Chart Page
Disable auto pen drop in Set Up Chart Page if this is not required
Set digital filter value to give required response in Set Up Inputs
Set correct time and date in Set Up Clock Page refer to Advanced Software
Manual
Enable counter STOP/GO in the Set Up
Totals Page
De-activate digital signal assigned to total STOP/GO function
Remove the arc suppression components IC4 and IC5 on mainboard IC6 and IC7
on standard I/O and analog relay IC3 to IC10 on 4 relay module
13
6 SPARES LIST
Item
Part No.
Pen Capsules (pack of 3) Black ……………………………………………………………………………………………………………………………………………………….. C1900/0119 Blue …………………………………………………………………………………………………………………………………………………………. C1900/0120 Red ………………………………………………………………………………………………………………………………………………………….. C1900/0121 Green ……………………………………………………………………………………………………………………………………………………….. C1900/0122 Violet* ………………………………………………………………………………………………………………………………………………………. C1900/0123
Pen Arm Assemblies ER/C Type Chart (J or R in Code Number) Standard Pen ………………………………………………………………………………. C1900/0076 ER/C Type Chart (J or R in Code Number) Event Pen …………………………………………………………………………………… C1900/0078 PX105 and PXR105 Type Chart (K or S in Code Number) Standard Pen …………………………………………………………. C1900/0075 PX105 and PXR105 Type Chart (K or S in Code Number) Event Pen ………………………………………………………………. C1900/0077
Fuses 24V ………………………………………………………………………………………………………………………………………………………….. B11071
(4A) 115V ………………………………………………………………………………………………………………………………………………………… B11070
(1A) 230V ………………………………………………………………………………………………………………………………………………….. B11069
(500mA)
*True time line event option only.
14
NOTES
15
NOTES
16
Sales
Service
Software
— ABB Limited Measurement & Analytics Howard Road, St. Neots Cambridgeshire,
PE19 8EU UK Tel: +44 (0)870 600 6122 Fax: +44 (0)1480 217 948 Email:
enquiries.mp.uk@gb.abb.com ABB Inc. Measurement & Analytics 125 E County Line
Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183
abb.com/measurement
— We reserve the right to make technical changes or modify the contents of
this document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any responsibility whatsoever
for potential errors or possible lack of information in this document. We
reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third parties
or utilization of its contents in whole or in parts is forbidden without
prior written consent of ABB. © ABB 2018
IM/C1900-OGR Rev. L 09.2018
—
ABB ME A SUREMENT & ANALY TICS | PROGR AMMING GUIDE | IM/C1900 – PGR RE V. M
C1900 Circular chart recorder
Measurement made easy
—
C1900 circular chart recorder
For more information
Further publications are available for free download from:
www.abb.com/recorders
or by scanning this code:
Data Sheet C1900 Circular chart recorder
Quick Reference Guide C1900 Circular chart recorder
Installation Guide C1900 Circular chart recorder and
recorder / controller
Operating Guide C1900 Circular chart recorder
Operating Instructions C1900 Circular chart recorder and
recorder/controller
User Guide C1900 Circular chart recorder and
recorder/controller
Search for or click on DS/C1900R-EN IM/C1900-QR IM/C1900-INS IM/C1900-OGR IM/C1900-MOD IM/C1900-ADV
Use of instructions
Health and safety
Warning an instruction that draws attention to the risk of injury or death.
Caution an instruction that draws attention to the risk of damage to the
product, process or surroundings.
Note clarification of an instruction or additional information. Information.
Information further reference for more detailed information or technical
details.
It must be understood that operation of damaged equipment could, under certain
operational conditions, result in degraded process system performance leading
to personal injury or death. Therefore, comply fully with all Warning and
Caution notices.
Information in this manual is intended only to assist our customers in the
efficient operation of our equipment. Use of this manual for any other purpose
is specifically prohibited and its contents are not to be reproduced in full
or part without prior approval of the Technical Publications Department.
To ensure that our products are safe and without risk to health, the following
points must be noted:
· The relevant sections of these instructions must be read carefully before
proceeding.
· Warning labels on containers and packages must be observed.
· Installation, operation, maintenance and servicing must only be carried out
by suitably trained personnel and in accordance with the information given.
· Normal safety precautions must be taken to avoid the possibility of an
accident occurring when operating in conditions of high pressure and/or
temperature.
· Chemicals must be stored away from heat, protected from temperature extremes
and powders kept dry. Normal safe handling procedures must be used.
· When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or
any relevant hazard data sheets (where applicable) may be obtained from the
Company address on the back cover, together with servicing and spares
information.
CONTENTS
1 INTRODUCTION
Section
Page
1 INTRODUCTION ………………………………………………….. 1
2 GENERAL PROGRAMMING …………………………………. 2 2.1 Preparation for Changes to the Parameters …….. 2 2.2 Security System ………………………………………….. 2
3 BASIC CONFIGURATION LEVEL …………………………… 3 3.1 Set Up Input (Process Variable) ……………………… 4 3.2 Set Up Pen Range/Event Source …………………… 8 3.3 Set Up Chart ……………………………………………… 9 3.4 Set Up Alarms ………………………………………….. 10 3.5 Set Up Relay Output ………………………………….. 15 3.6 Set Up Digital Output …………………………………. 17 3.7 Set Up Analog Output ………………………………… 19 3.8 Digital Inputs …………………………………………….. 21 3.9 Access Page ……………………………………………. 22 3.10 Scale Adjust …………………………………………….. 23
4 ADVANCED CONFIGURATION LEVEL …………………. 26 4.1 Set Up Function Keys ………………………………… 27 4.2 Set Up Logic …………………………………………….. 28 4.3 Set Up Pen Functions ………………………………… 31
5 CONNECTIONS & LINKS ……………………………………. 32
The documentation for the C1900 series of circular chart recorders is shown in Fig. 1.1. The Standard Manuals, including the data sheet, are supplied with all instruments. The Supplementary Manuals supplied depend on the specification of the instrument.
INSTALLATION
Product Identification Siting Mounting Electrical Connections Installation
Record
Part No. IM/C1900INS
OPERATION
Setting Up Displays & Controls Operating Level Simple Fault Finding
Part No. IM/C1900OGR
PROGRAMMING
General Programming Basic Config. Level Advanced Config. Level Connections and
Links
DATA SHEET Full Specification
Part No. IM/C1900PGR
Part No. SS/C1900
A Standard Manuals
ADVANCED SOFTWARE OPTIONS
Flow Totalization Ramp/Soak Profile Math Functions Timer Functions
Part No. IM/C1900ADV
MODBUS (RTU)
Serial Adaptors Serial Connections Programming Pages ASCII Tables
Part No. IM/C1900MOD
B Supplementary Manuals
Fig. 1.1 C1900 Documentation
1
2 GENERAL PROGRAMMING
The programming procedures are used to make changes to the operating parameter
values and for scale adjustment.
The programming of all channels is performed using faceplate 1 see Fig. 2.1.
When changing the input type it may be necessary to reposition the input
selector links accordingly see Section 5, CONNECTIONS & LINKS.
2.1 Preparation for Changes to the Parameters Isolate all external
alarm/control circuits to prevent inadvertent operation during programming.
Changes to the operating parameters are implemented using the or keys see
Section 3 of the Operating Guide.
2.2 Security System A security system is used to prevent tampering with the
programmed parameters by restricting access to programming levels, other than
the OPERATOR LEVEL; all users have access to this level.
A security password is used to give access to the programming pages. The
password can be set to any value from 0 to 9999. The recorder is despatched
with the password set to ‘0’ see Section 4.5 of Operating Guide.
Note. The recorder responds instantly to parameter changes which are saved automatically when leaving the current frame.
Faceplate 1
Fig. 2.1 Location of Faceplate 1
2
3 BASIC CONFIGURATION LEVEL
OPrtOr LEVEL
Operator Level
bASIC CONFIG
Basic Config
AdVNCd CONFIG
Advanced Config
Set Up Inputs Section 3.1 Page 4
SEtUP INPUt
Set Up Input (PV)
SELECt
Select Channel
IntYP
Input Type (PV)
LNtYP _
Linearizer Type
rNGHI ._
Input Range High
rNGLO .
Input Range Low
UNItS
Temperature Units
ENGHI
Engineering High
dECPt
Decimal Point
ENGLO
Engineering Low
bSPd _
Broken Sensor Drive
FdLP-I ._
Fault Detection Level
PrGFLt .
Programmable Filter
Set Up Pen Range Section 3.2 Page 8
SEtUP PENrNG
Set Up Pen Range
SELECt
Select Pen
PENHI
Pen Range High
PENLO
Pen Range Low
IN SrC __
In Source
OUt.SrC __
Out Source
Setup Chart Section 3.3 Page 9
SEtUP CHArt
Set Up Chart
CHArt
Chart Time
CHStP __
Stop Chart Signal
AUtdrP
Auto Pen Drop
LIFt.EN
Pen Lift Enable
PENLFt ____
Pen Lift/Pen Status
Set Up Alarms Section 3.4 Page 10
SEtUP ALArMS
Set Up Alarms
ACKtYP
Acknowledge Type
ACKSrC __
Alarm Ack Source
SELECt
Select Alarm
tYPE __
Alarm Type
trIP
Trip Level
HYSt
Hysteresis
tHYSt
Time Hysteresis
dELAY
Alarm Delay
EN-Sr-C ____
Enable Source
-
Set Up Relay Output* Set Up Digital Output Set Up Analog Output
-
Digital Inputs
Section 3.5 Page15
Section 3.6 Page 17
Section 3.7 Page 19
Section 3.8 Page 21
SEt UP rELAYS
Set Up Relay
SELECt
Select Relay
SOUrCE
Relay Source
POLrtY ____
Polarity
dIGtAL OUtPtS
Digital Outputs
SELECt
Select Output
SOUrCE
Output Source
POLrtY ____
Polarity
SEt UP ANALOG
Set Up Output
SELECt
Select Output
OPSrC
Output Source
rNGHI
Retrans. Range Hi
rNGLO
Retrans. Range Low
HIOP
Output Range High
LOOP
Output Range Low
dIGtAL INPUtS
Digital Inputs
SELECt _
Select Digital I/P
POLrtY
Polarity
- These pages do not appear on the
non-upgradeable version (1901J)
Access Page Section 3.9 Page 22
Scale Adjust Section 3.10 Page 23
ACCESS PAGE
Access Page
C PASS
Configure Password
PEN-AJ __
Pen Adjust Enable
PA-PAS ____
Pen Adj. Password
SCALE AdJUSt
Scale Adjust
SELECt __
Select PV/Pen/Filter
rESEt
Scale Reset
OFFSEt
Offset Adjustment
SPAN
Span Adjust
SEtPEN At100
Cal. Pen At 100%
SEtPEN At 0
Cal. Pen At 0%
CHECK _.
Check Pen Cal.
FILtEr __ Hrt
Mains Filter
Fig. 3.1 Basic Configuration Level Overview
3
…3 BASIC CONFIGURATION LEVEL
3.1 Set Up Input (Process Variable)
Information. · Universal inputs mV, mA, V, THC, RTD and resistance. ·
Internal cold junction compensation. · Linearization of temperature sensors
to allow use of non-linearizing transmitters or any electrical input. ·
Programmable fault levels and actions. · Digital filter to reduce the effect
of noise on inputs.
Example A setting up: · a current input of 4 to 20mA · displaying a range of 0 to 200psi · a fault detection level 10% above 200psi (engineering/display range) and 10% below 0psi (engineering/display range) · in the event of a fault being detected and/or the fault detection level being exceeded the process variable is driven downscale.
Input Type
RTD THC
Current
Voltage Millivolts Low resistance High resistance
Linearizer Type
5/2 3/2 RTD THC B THC N THC E THC J THC T THC S THC R THC K
None
Temp. Units
°F °C
None
Electrical Range
Engineering Range (Display Range)
220
20.0 (Input Range High)
Fault Detection
Level 10%
200
Broken Sensor Protection Drive
Programme Filter
Value set to 0
Upscale Downscale
Value set low
4.0 (Input Range Low)
20
0
Fault Detection
Level 10%
Value set high
Example B setting up:
· a Type K thermocouple · displaying temperature in °F · displaying a range of
0 to 2000°F · a fault detection level 10% above 2000°F (engineering/display
range) and 10% below 0°F (engineering/display range) · in the event of a fault
being detected and/or the fault detection level being exceeded the process
variable is driven upscale.
Input Type
RTD THC Current Voltage Millivolts Low resistance High resistance
Linearizer Type
5/2 3/2 RTD THC B THC N THC E THC J THC T THC S THC R THC K None
Temp. Units
°F °C None
Engineering Range (Display Range)
2200
Fault Detection Level 10%
2000
Broken Sensor Protection Drive
Programme Filter
Value set to 0
Downscale Upscale
Value set low
200
0
Fault Detection Level 10%
Value set high
4
3 BASIC CONFIGURATION LEVEL…
…3.1 Set Up Input (Process Variable)
SEt UP INPUt
Page Header Set Up Input (Process Variable) To advance to Set Up Pen Range Page press the key.
SELECt PV4 PV3 PV2 PV1
Select Channel
Select the channel to be programmed:
PV 1
Channel 1
PV 2
Channel 2
PV 3
Channel 3
PV 4
Channel 4
Note. In the remaining frames press the key to view the channel selected.
INtYP rtd
tCPL VOLt LO OHM HI OHM MAMP MVLt NONE
NONE
Input Type (Process Variable)
Caution. Ensure the correct input link positions are selected and the input is wired correctly see Section 5, CONNECTIONS & LINKS.
Select the input type required:
rtd
Resistance thermometer
tCPL Thermocouple
VOLt Voltage
LO OHM Low resistance (750)
HI OHM High resistance (>750)
MAMP Current
MU.Lt Millivolt (150mV)
NONE None
LNtYP 5/2 3/2
SQrt rtd
tCb tCN tCE tCJ tCt tCS tCr tCK NONE
Linearizer Type
Select the linearizer type required:
5/2 3/2
x5/2 x3/2
Open channel flow applications
SQrt Square Root
rtd
Resistance thermometer
tCb Type B thermocouple
tCN Type N thermocouple
tCE Type E thermocouple
tCJ Type J thermocouple
tCt Type T thermocouple
tCS Type S thermocouple
tCr Type R thermocouple
tCK Type K thermocouple
NONE No linearizer
Continued on next page.
5
…3 BASIC CONFIGURATION LEVEL
…3.1 Set Up Input (Process Variable)
rNGHI 20.0
Input Range High Set the maximum electrical input value required (in electrical units).
Note. The value set must be within the limits detailed in the table below.
Input Type rtd
or
tCPL
Input Type Millivolts Volts Milliamps Resistance Low Resistance High
Range Low Min. 0 0 0 0 0
Range High Max. 150 5 50 750 9999
Min. Range (Low to High) 5.0 0.1 1.0 20 400
rNGLO 4.0
UNItS dEGF dEGC NONE
ENGHI 1000
Input Range Low Set the minimum electrical input value required (in electrical
units).
Note. The value set must be within the limits detailed in the above table.
Temperature Units Select units required.
Engineering Range High Set the maximum engineering (display) value required.
Note. The value set must be within the limits detailed in the tables below.
Linearizer Type
Type B Type E Type J Type K Type N Type R & S Type T
Degrees Fahrenheit
Min.
Max. Min. Span
0
3272
1278
148
1652
81
148
1652
90
148
2372
117
328
2372
162
0
3092
576
418
572
108
Degrees Celsius
Min.
Max. Min. Span
18
1800
710
100
900
45
100
900
50
100
1300
65
200
1300
90
18
1700
320
250
300
60
RTD
328
1112
45
200
600
25
Performance accuracy is not guaranteed below 725°F/400°C for types B, R and S
thermocouples. Minimum span below zero Type T 126°F/70°C Minimum span below
zero Type N 189°F/105°C
THC standard DIN 4730 IEC 584
RTD standard DIN 43760 IEC 751
Linearizer Type
5/2 3/2 Square Root None
Engineering Range High and Low
Min.
Max.
9999
+9999
Continued on next page.
6
3 BASIC CONFIGURATION LEVEL…
…3.1 Set Up Input (Process Variable)
dECPt 1000
Decimal Point Set the decimal point position required for both the engineering range high and engineering range low values.
ENGLO 0
Engineering Range Low Set the minimum engineering (display) value required,
Note. The value set must be within the limits detailed in Engineering Range
High tables opposite.
bSPd UP
NONE dN
FdLP
SELECt
PrGFLt
Broken Sensor Protection Drive In the event of a fault being detected on the
input and/or if the Fault Detection Level Percentage is exceeded (see next
frame), the process variable is driven in the direction of the drive selected.
Select the broken sensor drive required: NONE No drive UP Upscale drive dN
Downscale drive.
Fault Detection Level Percentage A fault level percentage can be set to detect
a deviation above or below the display limits.
For example, if FdLP is set at 10.0%, a fault is detected if an input goes
more than 10% above Engineering Range High or more than 10% below Engineering
Range Low.
On some ranges the input circuitry may saturate before the fault level set is
reached. In this case an error is detected below the level set.
Set the level required, between 0.0 and 100.0% of engineering span (range low
to high) in 0.1% increments.
Note. If an input exceeds the minimum or maximum value for the linearizer
selected an error is detected regardless of any fault level.
Programmable Filter Filters the process variable input, i.e. if the input is
stepped it smooths the transition between steps and may also be used for some
degree of cleaning of noisy inputs. The filter time represents the time a step
in the input takes to change the displayed process variable from 10 to 90% of
the step.
Set the value required, between 0 and 60 in 1 second increments.
Return to Select Channel frame.
7
…3 BASIC CONFIGURATION LEVEL
3.2 Set Up Pen Range/Event Source
Information. · Trend pens have an independent chart range allowing a
selected part of the engineering (display) range to be used for
extra resolution on the chart. · Three position event pen function can be
driven by digital inputs, alarms, logic equation results and real time events
(when timer option is fitted).
Select Pen Range (in engineering units)
1000 (Eng. Range High) 700 (Pen Range High) 400 (Pen Range low)
Select ‘In’ Source
*Source on Source off
Select ‘Out’ Source
Source on Source off
Event Pen Chart Position
*Pen 4 at 80% Pen 3 at 60% Pen 2 at 40% Pen 1 at 20%
0 (Eng. Range Low)
Record Function
*In source takes priority if both sources enabled
Event Function
*With Real Time Event Pen option fitted, Pen 4 is above 100%
SEt UP PENrNG
SELECt PEN 4 PEN 3 PEN 2 PEN 1 NONE
NONE TREND
Page Header Set Up Pen Range
To advance to Set Up Chart Page press the key.
Select Pen Select the pen to be programmed
Note. · In the remaining frames press the key to view the pen selected. ·
Record (trend) or event pen function is set in the ADVANCED CONFIGURATION
LEVEL (if True
Time Event Pen option is selected, the fourth pen is fitted with a special pen
arm and is set automatically for event pen function) see Section 4.3, Set Up
Pen Functions.
EVENT
PEN HI
SELECt
PEN LO
IN SrC EQN4
SELECt
NONE
OUt.SrC EQN4
NONE
Pen Range High Set the maximum value required on the chart, in engineering
units (the value must be within the engineering range set in Set Up Input Page
see Section 3.1).
Pen Range Low Set the minimum value required on the chart, in engineering
units (the value must be within the engineering range set in Set Up Input
Page).
In Source Select a source to move the pen inwards on the chart.
For a description of sources see Table 3.1 on page 16.
Out Source Select a source to move the pen outwards on the chart.
For a description of sources see Table 3.1 on page 16.
Return to Select Pen frame.
8
3 BASIC CONFIGURATION LEVEL…
3.3 Set Up Chart
Information. · Programmable chart duration between 1 and 167 hours or 7 and
32 days. · Chart stop function the chart can be stopped by an alarm, digital
input, logic equation result or a real time event (if timer
option is fitted). · Auto pen drop automatically drops the pen(s) onto the
chart after a 5 minute delay to ensure recording is not left
disabled inadvertently.
SEt UP CHArt
Page Header Set Up Chart To advance to Set Up Alarms Page press the key.
CHArt 32dY
1Hr
Chart Duration Select the chart duration required per revolution of the chart; between 1 and 167 hours or 7 and 32 days.
CHStP EQN4
NONE
Stop Chart Source Select the source required for stopping the chart.
For a description of sources see Table 3.1 on page 16.
AUtdrP
SEt UP CHArt
LFt EN
PENLFt rECOrd
LIFt PArK
drOP rEtUrN
At rEF
Auto Pen Drop Select ‘YES’ to enable or ‘NO’ to disable.
If ‘YES’ selected, pen(s) drop automatically onto the chart 5 minutes after
they are lifted.
If ‘NO’ selected, the pen(s) remain lifted until they are manually dropped by
the operator.
Pen Lift Enable/Disable The key can be disabled if required. Select ‘YES’ to
enable or ‘NO’ to disable.
Pen Lift/Pen Status To raise pen(s) press key. The following status displays
are shown:
rECOrd pen records on chart LIFt pen lifts off chart PArK pen moves to
park position At rEF pen at reference position
To lower pen(s) press key. The following status displays are shown: rEtUrN
pen returns to record position drOP drops (lowers) onto chart rECOrd pen
records on chart
Return to top of Set Up Chart Page.
9
…3 BASIC CONFIGURATION LEVEL
3.4 Set Up Alarms
Information. · Four alarms per channel identified A1 to D1 (for channel 1)
up to A4 to D4 (for channel 4). · Three operator acknowledge options. · Global
alarm acknowledgment by digital input, alarm, logic equation result or real
time event (if option fitted). · High/low process alarms. · Delayed high/low
process alarms. · Fast/slow rate of change of process variable alarms. ·
Adjustable hysteresis value to prevent oscillation of alarm state. · Time
hysteresis to allow delayed triggering of alarms.
Process Variable
High Process
Low Process
Fig. 3.2 High and Low Process Alarm with Hysteresis
Hysteresis Trip Point Hysteresis
Alarm On Alarm Off Alarm On Alarm Off
Alarm Trip Point
Output
0 Time in seconds
Counter Started
40
Counter Reset
0
Counter Started
70
Hysteresis Time Elapsed
130 Alarm On
Alarm Off
Counter Reset
Time Hysteresis Status Example shows time hysteresis set to 70 seconds used with a high process alarm
Fig. 3.3 Time Hysteresis Alarm
10
…3.4 Set Up Alarms
3 BASIC CONFIGURATION LEVEL…
Process Variable
Trip Point
Hysteresis
Alarm Enabled
Delay Time
Alarm Disabled Alarm On
Alarm Off
1
2
34
5
67
The operation of a delayed high/low process alarm is identical to that of the
standard high/low process alarm but the alarm can be enabled/disabled by use
of a digital signal.
The alarm state is held off whilst the enable signal is off and continues to
be held off for a pre-configured period of time after the enable signal is
switched ON (irrespective of the process variable value). Once the pre-
configured alarm delay time has expired then the alarm operates in the same
manner as a standard high/low process alarm.
1 Process variable goes above trip point but alarm is not activated because
enable signal is low (Alarm Disable). 2 Alarm Enable signal is switched On.
Alarm delay timer started. 3 Process variable goes above trip point but alarm
is not activated because alarm delay time has not expired. 4 Alarm delay timer
expires, alarm is now enabled. Alarm is activated because process variable is
above trip point. 5 Process variable goes below trip (hysteresis) point
therefore alarm is de-activated. 6 Process variable goes above trip point,
alarm is activated (alarm is enabled and delay time has expired). 7 Alarm
Enable signal is switched Off. Alarm is disabled immediately. Alarm de-
activates.
Fig. 3.4 Delayed High Process Alarm
11
…3 BASIC CONFIGURATION LEVEL …3.4 Set Up Alarms
9.5 1 hour
The maximum time it takes to detect an alarm condition is present (T), in seconds, is calculated as follows:
T = 10.81 +
1800 Trip Value
x 2
The time it takes for the alarm state to be cleared once the alarm condition has been removed is also equal to T.
10.1 1 hour
9.5 1 hour
10.1 1 hour
T
T
T
T
Alarm On Alarm Off
Falling Fast Rate
Alarm On Alarm Off
Rising Fast Rate
Examples shown are for a trip value of 10%/hour on a PV engineering range of 0.0 to 100.0
T = 10.81 + 1800 x 2 10
T = 382 seconds
Fig. 3.5 Slow Rate Alarms with Hysteresis
10.1 1 hour
The maximum time it takes to detect an alarm condition is present (T), in seconds, is calculated as follows:
T = 10.81 +
1800 Trip Value
x 2
The time it takes for the alarm state to be cleared once the alarm condition has been removed is also equal to T.
9.5 1 hour
9.5 1 hour
10.1 1 hour
T
T
T
T
Alarm On Alarm Off
Falling Slow Rate
Alarm On Alarm Off
Rising Slow Rate
Examples shown are for a trip value of 10%/hour on a PV engineering range of 0.0 to 100.0
T = 10.81 + 1800 x 2 10
T = 382 seconds
Fig. 3.6 Fast Rate Alarms with Hysteresis
12
…3.4 Set Up Alarms
SEt UP ALArMS
ACKtYP LAtCH
NOrMAL NONE
3 BASIC CONFIGURATION LEVEL…
Page Header Set Up Alarms
To advance to Set Up Relay Output page press the key.
Alarm Acknowledge Type Alarms may be acknowledged while they are displayed.
Select the alarm acknowledge type:
NONE no acknowledge facility. If the cause of the alarm no longer exists,
the alarm state and display are cleared automatically.
Alarm cause Present
Not Present
LED Flashing
Off
Alarm State Active Inactive
NOrMAL and LAtCH if the cause of the alarm no longer exists, the alarm display remains until it has been acknowledged.
Alarm cause
Acknowledge
LED
Alarm State
Present
No
Flashing
Active
Present
Yes
Steady
Active
Not Present
Previously acknowledged
Off
Inactive
Present
No
Flashing
Active
Not Present
No
Flashing
Active/Inactive*
Not Present
Yes
Off
*Alarm state is active if LAtCH is selected or inactive if NOrMAL is selected.
Inactive
ACKSrC ALM d4
NONE
Global Alarm Acknowledge Source Select the alarm acknowledgment source
required.
For a description of sources see Table 3.1 on page 16.
SELECt ALM d4
Ch. 4
ALM A4
ALM d3
Ch. 3
ALM A3
ALM d2
Ch. 2
ALM A2
ALM d1
Ch. 1
ALM A1
NONE
NONE
Select Alarm Select the alarm to be programmed.
Note. In the remaining frames press the
key to view the alarm selected.
Continued on next page.
13
…3 BASIC CONFIGURATION LEVEL
…3.4 Set Up Alarms
tYPE dLY-LO dLY-HI SrAtE FrAtE LOPrC HIPrC
OFF
SELECt
Alarm Type Select the alarm type required for the alarm selected.
dLY-LO delayed low process
dLY-HI delayed high process
HIPrC high process
LOPrC low process
FrtE fast rate (rate of change of process variable)
SrtE slow rate (rate of change of process variable)
OFF
alarm off
OFF
trIP
HYSt
SELECt
tHYSt
All Others
dLY-HI or
dLY-LO
Trip Level Set the trip value required for the alarm selected.
The following are displayed in engineering units: HPrC, LPrC.
The following are displayed as a percentage of the engineering span
(engineering range high engineering range low) per hour between ±0.5 and
±500%:
FrtE and SrtE.
Hysteresis Hysteresis is operational when the alarm is active.
Set the hysteresis value required for high/low process, in engineering units
(within the engineering range) or in 0.1% increments for rate alarms. The
alarm is activated at the trip level but is only turned off after the alarm
variable has moved into the safe region by an amount equal to the hysteresis
value. For rate alarms this setting is a percentage of the trip rate see
‘FrtE’ and ‘SrtE’ in previous frame.
Time Hysteresis Set the time hysteresis value required between 0 and 9999
seconds.
Note. The alarm condition must be present continually for the time set, before
the alarm becomes active. If a hysteresis level is also set, the alarm
condition remains active until the process variable moves outside the
hysteresis band. When the alarm condition no longer exists the alarm becomes
inactive, i.e. time hysteresis does not affect turning off of alarm states.
dELAY 0
SELECt
EN-SrC NONE
Alarm Delay After a transition of the enable signal from disabled to enabled,
the alarm remains disabled for this period of time. Set 0 to 250 minutes.
Enable Source Any digital signal can be assigned as the signal to
enable/disable the alarm.
Return to Select Alarm frame.
14
3 BASIC CONFIGURATION LEVEL…
3.5 Set Up Relay Output
Information. · Relay Output not applicable to 1901J (non-upgradeable
version). · Relays can be energized by alarms, logic equation results,
digital inputs, real time events (timer option) and totalizer
wrap signal (totalizer option). · External Totalizer count function external
counter can only be driven by module type 3 (4 relays module) fitted in
module positions 4, 5 and 6. · Polarity to allow failsafe settings.
Select Relay Output
Relay 5.1 Relay 5.2 Relay 5.3 Relay 5.4 Module Position Relay No.
Relay Source
Alarm Acknowledge Logic Equation 1 Logic Equation 8 Digital Input 1 Digital
Input 2 Alarm A1 Alarm D4 None
Polarity Selection
Source State
Polarity
Relay State
Alarm A1 Active
Alarm A1 Active
Positive Negative
Energized De-energized
Alarm A1 Inactive
Alarm A1 Inactive
Positive Negative
De-energized Energized
Relay Contacts
NC C
NO
NC C
NO
NC C
NO
NC C
NO
SEt UP rELAYS
SELECt rLY 1.1
Module Position Relay No.
NONE
NONE
SOUrCE EQN4
NONE
NONE
Page Header Set Up Relays
To advance to Set Up Digital Output Page press the key.
Select Relay Output Select the output to be programmed. The selections in this
frame relate to the number of fitted modules with relays and their relative
module positions.
Example for a type 3 (four relays) module fitted in position five the
following selections are also programmable:
rELAY 5.1 (position 5, relay 1) rELAY 5.2 (position 5, relay 2) rELAY 5.3
(position 5, relay 3) rELAY 5.4 (position 5, relay 4)
Note. In the remaining frames press the key to view the relay selected.
Relay Source Select the source required to activate the selected relay.
For a description of sources see Table 3.1 on page 16.
Note. To drive an external counter COUNt.x must be selected.
Continued on next page
15
…3 BASIC CONFIGURATION LEVEL
…3.5 Set Up Relay Output
POLrtY POStVE NEGtVE
SELECt
Polarity The polarity selection is used to invert the effect of the digital source state on the relay state as shown in the following table:
Active
Source State
Non-active
Positive Negative
Positive Negative
Polarity
Relay State
Energized De-energized
De-energized Energized
Select the polarity required
Caution. Check connections before operating see Section 5, CONNECTIONS & LINKS.
Return to Select Relay Output frame.
Source
Description
AL_ACK
Alarm Acknowledge Unacknowledged process alarm anywhere in the unit
tIMEr.2 tIMEr.1
Real time event 2 Real time event 1
Real time events (available only if timer option fitted see Advanced Software Options Manual).
EQN4 EQN3 EQN2 EQN1
Programmable logic equation 4 Programmable logic equation 3 Programmable logic equation 2 Programmable logic equation 1
Programmable logic equations see Section 4.2, Set Up Logic
rAP4 COUNt. 4
rAP1 COUNt.1
Wrap around on total 4 Total 4 external counter drive
Wrap around on total 1 Total 1 external counter drive
Wrap around and count (available only if totalizer option fitted)
dIG6.8
Digital Input 6.8
dIG1.1
ALd4 ALC4 ALb4 ALA4
Digital input 1.1
Digital Input number Module number
Alarm D Alarm C Alarm B Alarm A
Channel 4 Alarms (if applicable)
ALd3 ALC3 ALb3 ALA3
Alarm D Alarm C Alarm B Alarm A
Channel 3 Alarms (if applicable)
ALd2 ALC2 ALb2 ALA2
Alarm D Alarm C Alarm B Alarm A
Channel 2 Alarms (if applicable)
ALd1 ALC1 ALb1 ALA1
Alarm D Alarm C Alarm B Alarm A
Channel 1 Alarms
NONE
No source required
- Available only on 4-relay and 8-digital output modules (types 3 and 5), fitted in module positions 4,5 and 6.
Table 3.1 Description of Sources
16
3 BASIC CONFIGURATION LEVEL…
3.6 Set Up Digital Output
Information. · This page is displayed only if digital outputs are fitted. · Up
to 24 digital outputs are available depending on the module types fitted. ·
Digital outputs can be energized by alarms, logic equations results, digital
inputs, real time events (timer option) and
totalizer wrap signal (totalizer option). · External Totalizer count function
external counter can only be driven by module type 5 (8 digital outputs
module) fitted
in module positions 4, 5 and 6. · Polarity inverts the effect of the
selected source on the output state.
Select Digital Output
Module Position Output No.
Output 5.1 Output 5.2 Output 5.3 Output 5.4 Output 5.5 Output 5.6 Output 5.7 Output 5.8
Digital Source Alarm Acknowledge Logic Equation 1 Logic Equation 4 Digital input 1 Digital input 2 Alarm A1 Alarm D4 None
Polarity Selection
Source State
Polarity
Output State
Digital Input 1 Active
Digital Input 1 Active
Positive Negative
Energized De-energized
Digital Input 1 Inactive
Digital Input 1 Inactive
Positive Negative
De-energized Energized
17
…3 BASIC CONFIGURATION LEVEL
…3.6 Set Up Digital Output
dIGtAL OUtPtS
Page Header Set Up Digital Outputs to advance to Set Up Analog Output page press the key.
SELECt OUt 1.1
Module Position Output No.
NONE
NONE
Select Digital Output Select the output to be programmed the selections in
this frame relate to the number of fitted digital output modules and their
relative module positions.
Example for a type 5 (eight digital outputs) module fitted in position five
the following selections are also programmable:
OUt 5.1 (position 5, output 1) OUt 5.2 (position 5, output 2) OUt 5.3
(position 5, output 3) OUt 5.4 (position 5, output 4) OUt 5.5 (position 5,
output 5) OUt 5.6 (position 5, output 6) OUt 5.7 (position 5, output 7) OUt
5.8 (position 5, output 8)
Note. In the remaining frames press the key to view the output selected.
SOUrCE EQN4
NONE
NONE
Output Source Select the source required to activate the selected digital
output.
For a description of sources see Table 3.1 on page 16.
Note. To drive an external counter COUNt.x must be selected.
POLrtY POStVE NEGtVE
SELECt
Polarity The polarity selection is used to invert the effect of the source state on the output as shown in the following table:
Active
Source State
Non-active
Select the polarity required.
Positive Negative
Positive Negative
Polarity
Output State
Energized De-energized
De-energized Energized
Caution. Check connections before operating see Section 5, CONNECTIONS & LINKS.
Return to Select Digital Output frame.
18
3 BASIC CONFIGURATION LEVEL…
3.7 Set Up Analog Output
Information. · Analog Output not applicable to 1901J (non-upgradeable
version). · Fitted analog outputs assignable to retransmit any process
variable. · Selectable retransmission range allows maximum resolution on
range of interest. · Adjustable output range for non-standard and reversed
outputs.
Note. The example below shows analog output 1 set to retransmit part of process variable 1’s engineering range (250 to 750°C) as a 4.0 to 20.0mA current output.
Select Analog Output
Select Output Source
Position 1
PV1 PV2 PV3 PV4
Position 6
Setting Output Ranges
1000°C (Engineering Range High)
750°C (Retransmission Range High)
Range to be transmitted
250°C (Retransmission Range Low) 0°C (Engineering Range Low)
20.0mA (Output Range High) 4.0mA (Output Range Low)
19
…3 BASIC CONFIGURATION LEVEL
…3.7 Set Up Analog Output
SEt UP ANALOG
Page Header Set Up Analog Output To advance to Digital Inputs Page press the key.
SELECt POSN1
OPx NONE
NONE
Select Analog Output Select the analog output position to be programmed. The
selections in this frame relate to the number of fitted modules with analog
output.
Example Output 1 is the analog output in position 1 (fitted on the main
board), output 3 is the analog output fitted in module position 3.
Note. In the remaining frames press the key to view the analog output
selected.
OPSrC PV4
PV1 NONE
NONE
rNGHI
Output Source Select output source required. The selections in this frame
correspond to the channels on the recorder (as available) PV1 (channel 1),
PV2 (channel 2) etc.
Retransmission Range High Set the engineering range value (in engineering
units) at which maximum output is required.
rNGLO
Retransmission Range Low Set the engineering range value (in engineering units) at which minimum output is required.
HIOP .
SELECt
Output Range High Set the maximum current output required for the Retransmission Range programmed between 2.0 and 20.0mA.
LOOP .
Output Range Low Set the minimum current output required for the Retransmission Range programmed between 2.0 and 20.0mA.
Return to Select Analog Output frame.
20
3 BASIC CONFIGURATION LEVEL…
3.8 Digital Inputs
Information. · Digital Input not applicable to 1901J (non-upgradeable
version). · Up to 30 digital inputs are available depending on the module
types fitted. · Volt-free contacts or TTL levels. · Polarity sets the logic
state (unchanged or inverted) for the module position(s).
Select Digital Input
Position 1 Position 2 Position 3 Position 4 Position 5 Position 6
Input State
Switch Input (volt-free)
Logic Input (TTL)
5V
or
0V
or
5V
0V
Polarity Selected
Negative Positive
Negative Positive
Logic State
Input Active Input non-active
Input non-active Input Active
dIGtAL INPUtS
SELECt POSN 1
POSN x NONE
SELECt
NONE
POLrtY POStVE NEGtVE
Page Header Digital Inputs To advance to Access Page press the key.
Select Digital Input Select digital module position to be programmed. Note. In
the remaining frames press the key to view the module selected.
Polarity Select the polarity required for the module position selected above:
POStVE logic input state unchanged NEGtVE logic input state inverted
Return to Select Digital Input frame.
21
…3 BASIC CONFIGURATION LEVEL
3.9 Access Page
Information. · Configurable password protection of PROGRAMMING LEVELS. ·
Internal security link enable/disable password protection.
ACCESS PAGE
Page Header Access Page. To advance to Scale Adjust Page press the key.
C-PASS 0
PEN-AJ ENbL-Y
Configuration Password Prevents access to the Programming Pages.
Pen Adjust Enable Enables / Disables the pen adjustment feature. This allows
the position of any trend to be adjusted for checking against a reference
standard. The displayed value is not changed.
PA-PAS 0
Pen Adjust Password Prevents access to the pen adjustment.
Set the required password, between 0 and 9999.
Return to top of Access Page.
Without Correct Security Code
With Correct Security Code
Operating Pages
SECODE ____
Enter Security Code (programmed in Access Page)
OPrtOr LEVEL
bASIC LEVEL
AdVNCd LEVEL
2
3
4
5
6
LK3
LK3
4
3 ON
1
2 OFF
Enable Security position, allows access to configuration levels with correct security code.
4
3 ON
1
2 OFF
Disable Security position, allows unprotected access to configuration level.
Fig. 3.7 Use of Security Code in Operator Level 22
Fig. 3.8 Location of Security Link
3 BASIC CONFIGURATION LEVEL…
3.10 Scale Adjust
Information. · Analog Inputs do not require re-calibrating when the input
type or range is changed. · Process variable adjust reset removes any
previously programmed offset or scale adjustment settings. · System offsets
errors can be removed using process variable scale offset adjustment. ·
System scale errors can be removed using process variable span adjustment. ·
Process variable offset/span adjustment can be used to perform spot
calibration · Pen(s) can be independently calibrated and checked across the
full range of the chart. · Mains filter selectable for maximum noise
rejection. · Pen Linearity Check automatically draws a pen linearity test
pattern.
Scale Adjustment
Chart
PV1
(x) Span Adjust
(+) Offset
PV1
AND
Display
200.3
CH1 CH2 CH3 CH4
AL1
AL2
AL3
AL4
100°C 225°C
Engineering Range 250.0°C
50.0°C
Offset Adjustment
Display
OFFSEt
99.8
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Engineering Range 250.0°C
50.0°C
Span Adjustment
Display
SPAN
225.5
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Offset Adjustment Span Adjustment
Note. As a general rule: use Offset adjustment for spot calibration at <50% of engineering range span. use Span adjustment for spot calibration at >50% of engineering range span.
Display
OFFSEt
100.0
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
Display
SPAN
225.0
CH1
AL1
AL2
AL3
AL4
CH2
CH3
CH4
23
…3 BASIC CONFIGURATION LEVEL
…3.10 Scale Adjust
SCALE AdJUSt
Page Header Scale Adjust To advance to BASIC CONFIGURATION LEVEL frame use the key.
SELECt LINCHK FILtEr
PEN4
PEN1
PV4
PV1 NONE
NONE
rESEt YES NO
Select Process Variable/Pen Select linearity check, process variable or pen
required:
LINCHK the pens automatically draw a test pattern to check pen linearity.
dONE is displayed on completion
FILtEr mains frequency filter PEN x pens 1 to 4 PV4 process variable on
channel 4 PV3 process variable on channel 3 PV2 process variable on
channel 2 PV1 process variable on channel 1 NONE None
Note. In the remaining frames press the key to view the process variable or
pen selected.
Process Variable Scale Adjustment Reset Set YES to reset the process variable
offset and span values to their nominal values (values are reset when frame is
exited).
OFFSEt
SELECt
Process Variable Offset Adjustment Electrical and resistance thermometer
inputs: apply the correct input for the spot calibration required.
RTD inputs: use resistance values obtained from standard tables.
Thermocouple Inputs: measure the ambient temperature at the output terminals
of the signal source (calibrator). From thermocouple tables obtain the
millivolt equivalent of this temperature (a) and that for the spot calibration
temperature (b). Subtract (a) from (b) and set the signal source to the
resultant value. (The voltage is negative if the spot calibration temperature
is below the measured ambient temperature).
Note. The displayed units are engineering units.
Set the value required. The decimal point position is set automatically.
Example If the display range is 50.0 to 250.0 and a spot calibration is
required at 100 and 225, inject a signal equivalent to 100 and set the display
to 100.0 using the and keys.
SPAN
Span Adjust Proceed as for Offset Adjustment above and apply the correct input
for the spot calibration required. The displayed units are engineering units.
Set the value required. The decimal point is set automatically.
For the example above, inject a signal equivalent to 225 and set the display
to 225.0.
Continued on next page.
24
…3.10 Scale Adjust
SELECt SEtPEN PEN At 100
SEtPEN At 0
SELECt PEN
CHECK __
SELECt FILtEr
FILtEr 60 Hrt 50 Hrt
SELECt FILtEr
3 BASIC CONFIGURATION LEVEL
Calibrate Pen At 100% Drives the pen automatically to the full scale position
on the chart.
Use the and keys to set pen to 100% on the chart.
Calibrate Pen At 0% Drives the pen automatically to the zero position on the
chart.
Use the and keys to set pen to 0% on the chart.
Check Pen Calibration The pen calibration can be checked at any point on the chart.
Use the and the chart.
keys to move the selected pen from the zero point up to the 100% position on
Note. If the true time event option is fitted the red pen does not move beyond the 94% position on the chart.
Select Filter Select the mains frequency of the supply used to ensure maximum noise rejection on analog inputs.
Return to Select Process Variable/Pen frame.
25
4 ADVANCED CONFIGURATION LEVEL
OPrtOr LEVEL
Operator Level
bASIC CONFIG
Basic Config
AdVNCd CONFIG
Advanced Config
Set Up Functions Keys
Set Up Logic
Section 4.1 Page 27 Section 4.2 Page 28
SEt UP F KEYS
Set up Function Keys
FKEY1 __
Function Key 1
FKEY 2 __
Function Key 2
SEtUP LOGIC
Set Up Logic
SELECt ECN.
Select Equation
EQN. _.1 __
Configure Logic
EQN. _.7 __
Configure Logic
Set Up Pen Functions Section 4.3 Page 31
PEN FUNCtN
Pen Functions
PEN 1
Pen 1 Function
PEN 4
Pen 4 Function
Fig. 4.1 Advanced Configuration Level Overview
26
4 ADVANCED CONFIGURATION LEVEL…
4.1 Set Up Function Keys
Information. · Programmable function key on each faceplate · Home function
returns the instrument display to the start of the operating page when at the
top of any page. · Global alarm acknowledge function acknowledges any
unacknowledged alarms on all channels.
SEt UP FKEYS
FKEY1 HOME
ALMACK
Page Header Set Up Function Keys
To advance to the Set Up Logic press the key.
Function Key 1 Select function required.
HOME Home (return to Operating Page in OPERATING LEVEL) ALMACK Acknowledge
alarm
FKEY2 ALMACK
Function Key 2 Select function required (if applicable).
Return to Set Up Function Keys frame.
27
…4 ADVANCED CONFIGURATION LEVEL
4.2 Set Up Logic
Information. · 4 logic equations · 7 elements per equation · OR/AND operators
· Can combine internal and external digital signals i.e. alarms, digital
inputs, other logic equation results and real time
events (timer option).
For each equation, the logic elements 1 to 7 are arranged sequentially, as shown below. Odd numbered elements are used for logic inputs and even numbered elements for logic gates.
Logic inputs must be set to one of the digital sources listed in Table 3.1 on page 16.
Logic gates must be set to ANd, Oror End. Setting an element to End terminates the equation.
Logic Inputs
EQN1.1 EQN1.3 EQN1.5
EQN1.2 ANd/Or
EQN1.7
EQN1.4 ANd/Or
EQN1.6 ANd/Or
Result
Note. Elements on each equation are calculated sequentially, i.e. elements 1, 2 and 3 are evaluated first and this result is then combined with elements 4 and 5. Similarly, this resultant is then combined with elements 6 and 7 to give the logic equation result.
28
4 ADVANCED CONFIGURATION LEVEL…
…4.2 Set Up Logic
Example Reservoir level monitoring using: · process variable 1 with an
engineering range 0 to 100 feet · logic equation 1 result assigned to relay
1.1 which is used to operate the control valve.
Control Valve
Relay Output
Manual Overide
Alarm B1 Alarm A1
80
50
feet feet
Flow Conditions
Close reservoir control valve if: · Reservoir level >50 feet AND rate of
change
10 ft/hr OR · Reservoir level >80 ft OR · Manual override switch operated
Level Sensor
Level Alarm C1
Rate of change > 10ft/hr
Time
Input Elements
· Alarm A1 set to high process trip at 50 ft · Alarm B1 set to high
process trip at 80 ft · Alarm C1 set to fast rate trip at 10% of
range per hour (10 ft/hr) · Manual override switch:
Connected to digital input 1.1 Digital input number Module number
Negative polarity Volt-free switching
Entering the Logic Equation
EQN1.1 EQN1.2 EQN1.3 EQN1.4 EQN1.5 EQN1.6 EQN1.7
ALA1 ANd ALC1 Or ALB1 Or dIG1.1
29
…4 ADVANCED CONFIGURATION LEVEL
…4.2 Set Up Logic
SEt UP LOGIC
Page Header Set Up Logic To advance to Set Up Pen Functions Page press the key.
SELECt EQN1
EQN2 EQN3
Select Equation Select equation to be constructed.
In the remaining frames press the
EQN4
NONE
NONE
Equation No. Element No.
key to view the equation selected.
EQN 1-1 EQN4
NONE
NONE
Equation n/Element 1 Select the source required for element 1.
For a description of sources see Table 3.1 on page 16.
EQN1-2 Or
ANd ENd
END
EQN 1-3 EQN4
NONE
Equation n/Element 2 Select the operator required to combine elements 1 and 3:
Or Or ANd And ENd Ends equation
Equation n/Element 3 Repeat previous two steps for elements 3 to 7.
Odd numbered elements = sources Even numbered elements = operators
Return to Select Equation frame.
30
4 ADVANCED CONFIGURATION LEVEL 4.3 Set Up Pen Functions
Information. Any fitted pen can be assigned to a trend or an event function.
PEN FUNCtN
Page Header Pen Functions To advance to Advanced Configuration frame press the key.
PEN1 trENd EVENt
PEN FUNCtN
PEN2
PEN4
Pen 1 Select pen function required:
trENd Trend pen EVENt Event pen
Note. The event pen and true time line event pen are separate functions and
only the event pen can be selected in this page. The true time line event pen
option allows event marking on the same time line as the red pen and requires
a special pen arm and motor assembly. Refer to the order code in the
Specification Sheet.
Pen 2 to 4 Repeat as for Pen 1 (if applicable).
Return to top of Set Up Pen Functions Page.
31
5 CONNECTIONS & LINKS
32
Main Input, Standard Input & Analog + Relay
1
Analog Output *
2
3
4 Analog Input
5
6
7
Common
8
Logic 1
Logic Inputs*
9
Logic 2
10
Normally Open
1
Common
Relay Output
12
Normally Closed
- Not fitted on Analog + Relay Module
4 Relays Module
1
NC
2
NO Relay 1
3
C
4
NC
5
NO Relay 2
6
C
7
NC
8
NO Relay 3
9
C
10
NC
1
NO Relay 4
12
C
8 Digital Inputs/Outputs Module
1
Common
Common
2
Input 1
Output 1
3
Input 2
Output 2
4
Input 3
Output 3
5
Input 4
Output 4
6
Input 5
Output 5
7
Input 6
Output 6
8
Input 7
Output 7
9
Input 8
Output 8
10
Common
Common
1
3
2
3
2
12
4
1
4
1
Digital I/Ps Digital O/Ps
Digital I/O Module PL2
THC & mV
Voltage
Current
RTD (3-lead)
RTD (2-lead) & Resistance
3
3
3
3
Link
4
4
4 Red
4
5
5 White
White 5
6
6
6
6 Red
6 Red
Main Board
2
3
4
5
6
I/O Module
INPUT/OUTPUT MODULE
5
4
PL1
8
1
1
4
PL8
2
3
4
1
PL1
5
8
3
2
PL3
4
1
5
4
PL1
8
1
1
4
PL8
2
3
4
1
PL1
5
8
3
2
PL3
4
1
- Recommended diode: Diode forward voltage > 0.8 V @ 20 mA or use 2 x 1N4001 general purpose diodes in series.
2-wire Transmitter*
4
Tx
6
5
4
PL1
8
1
1
4
PL8
2
3
4
1
PL1
5
8
3
2
PL3
4
1
Sales
Service
Software
— ABB Limited Measurement & Analytics Howard Road, St. Neots Cambridgeshire,
PE19 8EU UK Tel: +44 (0)870 600 6122 Fax: +44 (0)1480 217 948 Email:
enquiries.mp.uk@gb.abb.com ABB Inc. Measurement & Analytics 125 E County Line
Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183
abb.com/measurement
— We reserve the right to make technical changes or modify the contents of
this document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any responsibility whatsoever
for potential errors or possible lack of information in this document. We
reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third parties
or utilization of its contents in whole or in parts is forbidden without
prior written consent of ABB. © ABB 2018
IM/C1900-PGR Rev. M 09.2018
—
ABB MEASUREMENT & ANALY TICS | DATA SHEET
C1900 series Circular chart recorder
2
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
— Measurement made easy A rugged, reliable recorder with the full capability to meet your needs
1 to 4 pen recording · full application flexibility
NEMA 4X/IP66 construction · hose-down protection
Analog, relay outputs, digital inputs and transmitter power supply as standard
· range of inputs and outputs built-in
Multiple indicator panels · continuous display of all signal values
0.1% measurement accuracy · precise process information
High noise immunity · robust, dependable operation
RS485 Modbus serial communications · open system compatibility
Totalizers and math functions built-in · fully integrated solutions
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
3
— C1900
The C1900 is a fully programmable circular chart recorder for up to four
process signals. The C1900’s straightforward operator controls and robust
construction make it suitable for a variety of industrial environments.
Excellent standard facilities are complemented by a powerful range of options
to give the flexibility to match your application.
— Simple Operation
— Comprehensive Process Information
The C1900 lets you see the status of your process at a glance: high visibility
6-digit displays provide a clear indication of up to four process values
simultaneously and active alarms are signalled by flashing LEDs below the main
display.
The clearly-labelled tactile keypad gives direct access for operator adjustments and configuration programming, without the need to open the recorder’s door. Clear text prompts on the digital displays guide the user around the various menus. A password-protected security system prevents unauthorized access to configuration adjustment menus.
The chart is easily set up to show the information you need in the way you want. Pen ranges are individually set to give the best resolution for each signal; the time per revolution can be selected between 1 hour and 32 days. Additionally a true time event pen facility enables one pen to be set up as a 3-position event marker on the same time line as Pen 1.
4
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
— Flexibility to Solve Problems
The C1900 offers seamless integration of loop functionality to solve process
problems, eliminating the need for auxiliary devices.
— Totalizers, Math And Logic
Integrating fluid flow to calculate total volume is performed by the built-in
totalizers available for each channel. Relays can be assigned to increment or
reset external counters to match the recorder’s totalizer values. User
configurable math functions, mass flow calculations and RH tables are all
fully supported. Logic capability allows interlocking and integration of
discrete and continuous functions to solve a wide range of process problems.
— Timers and Clock
The C1900 offers two event timers driven by the recorder’s real-time clock.
The timers can be configured to operate relays, start/stop the chart or
trigger other actions within the recorder.
Timer 1
Annunciator
Channel 1 Alarm
Relay Logic Equation
AND
Flow A
Commander C1900
Flow B
Flow C
Alarm annunciation enabled during night hours only
— Modbus RS485 Communications
Communications with PCs or PLCs are achieved via the RS485 serial
communications link, enabling the C1900 to serve as the front end of plant-
wide data acquisition systems. Using Modbus RTU protocol all process inputs
and other variables can be continuously read by a host PC running any of a
wide variety of standard SCADA packages.
A + B + C Math Equation
Totalizer
Summation of Three Flows
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
5
— Built to Meet Your Needs
The C1900’s modular architecture gives rise to a high level of hardware
choice: up to five I/O modules can be added to the basic instrument.
The standard input/output module supplied with every pen comes complete with a
fully isolated analog input, a relay output, transmitter power supply,
isolated analog retransmission and two digital inputs.
Further input and output capability is provided by a range of plug-in modules:
· Analog input and relay for use with math functions · Four relays channel
alarm outputs · Eight digital inputs linked using logic equations · Eight
digital outputs TTL level alarm outputs · Modbus RS485 communications
interfaces with PCs
— Expandable for the Future
The C1900 may be quickly upgraded to meet your changing process requirements.
Additional recording channels, math capability or input and output functions
can be retrofitted on-site using plug-in cards and easily fitted pen arms.
Input calibration data is stored on each card, allowing quick changes to input
cards without the need for recalibration. Changes to input sensors or
recording procedures are accommodated by reconfiguration using the main
keypad.
— Designed to Survive
NEMA 4X protection ensures the C1900 can survive in the harshest environments
and makes the recorder ideal for use in panels which are regularly hosed down.
The tough, acidresistant case and secure cable-entry glands maintain the NEMA
4X rating for wall-mounted or pipe-mounted instruments.
— Noise Immunity
Recording accuracy is maintained in noisy industrial environments due to the
advanced EMC shielding within the recorder. The power supply has been designed
to give excellent protection from power spikes and brownouts and all
configuration and status information is held in nonvolatile memory to ensure
rapid recovery after a power failure.
— Minimal Maintenance
Excellent long-term stability keeps recalibration to a minimum, cutting the
costs of ownership. User-selectable chart speeds and long-life pens combine to
limit usage of consumables.
— Built-in Quality
The C1900 is designed, manufactured and tested to the highest quality
standards, including ISO 9001.
— Easy to Install
A choice of mounting options enables simple installation of the recorder in a
panel, on a wall or on a pipe. Detachable terminal blocks allow for trouble-
free connection of input and output wiring, with mains isolation provided by a
power switch within the instrument.
—
Wall-mounting
Pipe-mounting
Panel-mounting
6
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
— Summary
1, 2, 3 or 4 pens
10 in. chart size
Standard I/O with each pen includes: · Analog input, analog output,
transmitter power supply,
relay output and 2 digital inputs.
—
Specification
General
Construction Size
Weight Case material Window material Door latch
15.23 in. (h) × 15.04 in. (w) × 5.57 in. (d) (386.8 × 382.0 × 141.5mm) 18lb (8.2kg) Glassfiber-filled reinforced polyester Polycarbonate High-compression with optional lock
Environmental Operational temperature range Operational humidity range
Case sealing Fast transients
0° to 55°C (32° to 130°F) 5 to 95%RH (non-condensing) 5 to 80%RH (chart only) NEMA 4X (IP66) IEC 801-4 Level 3
Installation Mounting options Terminal type Wire size (max.)
Panel, wall or pipe Screw 14 AWG (I/O), 12 AWG (power)
Operation and Configuration
Programming method Via front panel keys
Security
Password-protected menus
Safety General safety Dielectric
Memory protection Approvals
IEC348 500V DC (channel/channel) 2kV DC (channel/ground) Nonvolatile EEPROM CSA UL CSA/FM Class 1 Div. 2 CE
Power Supply Voltage
Consumption Line interruption
100 to 240V AC ±10% (90V min. to 264V max. AC), 50/60 Hz <30VA (typical for full spec. unit) Up to 60ms
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
7
Process Inputs And Outputs
General
Noise rejection
Common mode
120 dB at 50/60 Hz
Normal (series) mode
60dB at 50/60 Hz
CJC rejection ratio
<0.05°C/°C
Sensor break protection Upscale or downscale drive
Out of range detection 0 to 100% of engineering span
Temperature stability
<0.02% of reading/°C or 1
µV/°C
Long-term drift
<0.01% of reading 10 µV
Input impedance
annually >10M (mV and V inputs) 39 (mA inputs)
Analog Inputs Signal types Thermocouple types Resistance Thermometer Other linearizations Sample interval Dielectric Digital filter
mV, V, mA, B, E, J, K, N, R, S, T Pt100 x1/2, x3/2, x5/2, linear 250ms per channel 500V DC channel/channel 0 to 60s programmable
2-Wire Transmitter Power Supply
Number
1 per channel
Voltage
24V DC nominal
Drive
Up to 25 mA
Isolation
500V DC channel/channel
Analog Outputs Type Accuracy Maximum load Dielectric
4 to 20mA ± 0.1% 750W 500V DC
Relay Outputs Type Rating (with non-inductive load)
SPDT 5A at 115/230V AC
Digital Inputs Type Minimum pulse Dielectric
TTL or volt-free 250 ms 50V DC between modules, no isolation within module
Digital Outputs Type Rating Dielectric
5V TTL 5mA per output 500V DC between modules, no isolation within module
Serial Communications Connections Protocol
RS485, 4-wire Modbus RTU
Analog input performance
Type mV V mA Ohms (high) Ohms (low)
Range Lo 0 0 0 0 0
Range Hi 150 5 50 750 10k
Min. Span 5
0.1 1
20 400
Accuracy ±0.1% reading or 10µV ±0.1% reading or 20mV ±0.2% reading or 0.2µA ±0.2% reading or 0.1W ±0.5% reading or 10W
Type B E J K N R S T PT100
°C
Range Lo 18
100 100 100 200
18 18 250 200
Range Hi 1800 900 900 1300 1300 1700 1700 300 600
°F
Range Lo 0
140 140 140 325
0 0 400 325
Range Hi 3270 1650 1650 2350 2350 3000 3000 550 1100
Accuracy (excl. CJC) ± 2 °C (above 200 °C) (3.6 °F above 434 °F)
± 0.5 °C (± 0.9 °F) ± 0.5 °C (± 0.9 °F) ± 0.5 °C (± 0.9 °F) ± 0.5 °C (± 0.9
°F) ± 1 °C (above 300 °C) (1.8 °F above 572 °F) ± 1 °C (above 200 °C) 1.8 °F
above 572 °F) ± 0.5 °C (± 0.9 °F) ± 0.5 °C (± 0.9 °F)
8
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
—
…Specification
Recording System
Pens
Number
1, 2, 3, or 4 (red, blue, green, black)
Response
7 seconds (full scale)
Resolution
0.1% steps
Pen lift
Motor-driven, with
optional auto-drop
Event Pens Standard
Real time
3-position event recording on any channel 3-position event recording on the same time line as Pen 1
Chart Chart size Chart speed
Rotation accuracy
10 in. or 105 mm 1 to 167 hours or 7 to 32 days per revolution <0.5% of rotation time
Advanced Software Functions
Totalizers
Number
1 per pen
Size
99,999,999 max.
Output
External counter driver,
‘wrap’ pulse signal
Math Number of equations Type
4 +, , x, ÷, low & high select, max., min., average, mass flow, RH
Timers Number Type
Output
2 Real-time clock driven event, adjustable duration Relay, digital output, logic equation
Display and Operator Panels
Displays
Number
2 (1 or 2 pens) or 4 (3 or 4 pens)
Type
6-digit red LED, 0.56 in. (14mm) high
Status indicators Indicate channel number on display
Alarm indicators Indicate channels with active alarms
Panel keys Function
Programming access, increment/ decrement, pen lift and user-defined function key
Option Module* Number
Connection
5 plus 1 x standard input/output module Plug-in cards with detachable connection blocks
EMC
Design & Manufacturing standards
CSA General Safety
Approved
UL General Safety
Approved
CSA/FM Class 1 Div. 2 Approved
Alarms and Logic
Alarms Number Type
Adjustments
4 per channel High/Low process, fast/slow rate of change, time delay Hysteresis, time delay
Emissions and Immunity Meets requirements of: · EN 50081-2 · EN 50082-2 · IEC 61326 for an Industrial Environment · CE Mark
Logic Equations Number Function Inputs
Outputs
4 OR, AND Alarm states, digital inputs, totalizers, logic Relays, digital outputs, chart stop, alarm acknowledge
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
9
Option Module Types
Option module types Standard I/O Analog I/P + relay 4 relays 8 digital I/P 8 digital O/P RS485 communications 1901J (non-upgradeable)
Analog I/P 1 1
Analog O/P 1
I/O per module
Trans. PSU 1
Relays 1
Digital I/P 2
1
4
8
Digital O/P 8
1
Comms. 1
Max. no. per instrument
3 5 2 3 3 1
10
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
— Ordering Information
PART 1
C1900 recorder Recorders *
Chart Type
Electrical Code Option Module Options Door Lock Power Supply
One Pen (Red) Two Pens (Red & Green) Three Pens (Red, Green, Blue) Four Pens
(Red, Green, Blue, Black)
Standard (Recorder/Controller) KPC 105 PX and PXR type charts Chessell Brand
charts
Standard CSA approval UL approval CSA/FM Class 1 Div. 2
None Additional Modules Complete PART 2
None Totalizer Math & Timer Totalizer, Math & Timer
Not Fitted Fitted 115 V AC 230 V AC 115 V AC with On/Off Switch 230 V AC with
On/Off Switch
19XX X X X X X X X X X X X 11 12 13 14
J
K
C
A
B
U
F
0 A
0 3 A
B
1 2
1 2 4 5
XXX OPT
PART 2 Additional Modules Module Position 2 / Channel 2 Input Module Position 3 / Channel 3 Input Module Position 4 / Channel 4 Input* Module Position 5
Module Type
012
012
0123456
0
2345
Module Position 6
02458
Special Settings
Company Standard Custom configuration (customer to complete and supply C1900R
custom configuration sheet INF08/032) Special
Engineered configuration (customer to supply configuration details required)
Calibration certificate **
STD CUS SXX ENG
C1
- Each pen fitted has an associated standard input/output module comprising Analog Input, Analog Output, Relay, Transmitter Power Supply and Two Digital Inputs. Additional Input/Output modules may be fitted in the unused module positions as required. These additional modules should be specified in PART 2 of the ordering information.
** When a calibration certificate is ordered it is performed according to the specified configuration type: CUS/ENG Inputs and outputs calibrated according to the customer supplied configuration details and ranges. STD Inputs and outputs calibrated according to the instrument factory standard configuration and ranges.
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
11
— Accessories
Case-to-panel gasket Wall-mount kit Pipe-mount kit Pack of red pens Pack of
green pens Pack of blue pens Pack of black pens Pack of purple pens After-
sales engineered configuration service
C1900/0149 C1900/1712 C1900/0713 C1900/0121 C1900/0122 C1900/0120 C1900/0119 C1900/0123 ENG/REC
Key to module types
0
No module fitted / Pen input channel *
1
Standard Input/Output
2
Analog input (Math input) + Relay
3
Four Relays
4
Eight Digital Inputs
5
Eight Digital Outputs
6
True Time Event Pen (Violet)
8
Modbus RS485 Communications
- On 2, 3 or 4 pen instruments a standard I/O module is always fitted in the corresponding module position (enter ‘0’ in the corresponding order code field).
Example.
1 9 1 3 J A A 0 1 1 0 0 3 0 8 STD
3 pens
4 relays
Modbus RS485 Communications
1 2 3 45 6
Module Positions
12
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
— Electrical Connections
1 2
+
Analog Output
3
4 5
Analog Input see b to h
6
7
Common
8
Logic 1
Logic Inputs
9
Logic 2
10
Normally Open
11
Common
Relay Output
12
Normally Closed
Summary of Connections
4
Tx
6 +
d 2-wire Transmitter
3 +
6
e Thermocouple
3 6 b Voltage
3
4
c Current (non 2-wire Transmitters
4
Red
5
White
6
Red
f 3-wire RTD
Standard Input/Output Modules
3
6
g Low Voltage (mV)
Link 4
5 6
White Red
h 2-wire RTD and
Resistance
1
Normally Closed
2
Normally Open
Relay 1
3
Common
4
Normally Closed
5
Normally Open
Relay 2
6
Common
7
Normally Closed
8
Normally Open
Relay 3
9
Common
10
Normally Closed
11
Normally Open
Relay 4
12
Common
Four-Relay Output Module
1
Common
Common
2
Input 1
Output 1
3
Input 2
Output 2
4
Input 3
Output 3
5
Input 4
Output 4
6
Input 5
Output 5
7
Input 6
Output 6
8
Input 7
Output 7
9
Input 8
Output 8
10
Common
Common
11
12
Input
or Output
Connections
Connections
Digital input/output module
Power Switch (Optional) Fuse (Optional)
Power Supply Connections
Earth (Ground) Stud
Line Neutral
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
13
— Overall dimensions
Dimensions in mm (in.) 382
(15.04)
386 (15.23)
320.8 (12.63)
320.8 (12.63)
360.4 (14.19)
355.6 (14.00) 323 (12.72)
323 (12.72)
285.75 (11.25)
183.4 (7.22)
33 (1.30) 66 (2.60) 35 (1.38)
43.2 (1.70)
36.6 (1.44) Typical Space Between Adjacent Knockout Centers 22.35 (0.88)
16.25 (0.64) 4 holes 7.14 (0.281) dia. or tap for 1/4 in. thread
Cut-out size
14
— Notes
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
Sales
Service
Software
C1900 SERIES CIRCULAR CHART RECORDER | DS/C1900R-EN REV. AB
15
—
ABB Limited Measurement & Analytics Howard Road, St. Neots Cambridgeshire,
PE19 8EU UK Tel: +44 (0)1480 475 321 Fax: +44 (0)1480 217 948 Email:
instrumentation@gb.abb.com
ABB Inc. Measurement & Analytics 125 E. County Line Road Warminster, PA 18974
USA Tel: +1 215 674 6000 Fax: +1 215 674 7183
abb.com/measurement
DS/C1900R-EN Rev. AB 09.2019
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB.
© 2019 ABB. All rights reserved.
3KXA835550R1001.
References
- ABB Group. Leading digital technologies for industry — ABB Group
- ABB Measurement & Analytics - instrumentation and analyzer technology
- Manual-Hub.com - Free PDF manuals!
- search.abb.com/library/Download.aspx?DocumentID=DS/C1900R-EN&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=DS/C1900RC-EN&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1300-ADV&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-ADV&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-INS&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-MOD&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-OGC&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-OGR&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-PGC&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-PGR&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-QC&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=IM/C1900-QR&LanguageCode=en&DocumentPartId=&Action=Launch
- search.abb.com/library/Download.aspx?DocumentID=INF08%2F032&LanguageCode=en&DocumentPartId=&Action=Launch
- ABB Measurement & Analytics - instrumentation and analyzer technology
- Recorders & Controllers | ABB
- Manual-Hub.com – Free PDF manuals!
- Recorders & Controllers | ABB
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>