Siemens RDE10.1DHW Room Temperature Controller User Manual
- June 17, 2024
- SIEMENS
Table of Contents
Siemens RDE10.1DHW Room Temperature Controller User Manual
- 2-position control with ON / OFF output for heating
- Independent ON / OFF control of DHW
- Operating modes: Auto, normal operation, energy saving and frost protection
- 7-day time switch and manual control
- Battery-powered DC 3 V (2 x 1.5 V AA)
Use
The RDE10.1DHW is used for the control of the room temperature in heating systems with independent control of DHW.
Typical applications
- Residential apartments
For the control of the following plant components and of DHW:
- Thermal valves or zone valves
- Gas or oil burners
- Fans
- Pumps
- Heat exchanger
- Continuous-flow water heater
- Small water heating systems
Functions
Function diagram
- T Room temperature
- SD Switching differential
- W Room temperature setpoint
- Q14 Output signal for heating
Operating modes
The RDE10.1DHW provides auto, normal operation, energy saving (or OFF) or frost protection mode. The difference between normal operation and energy- saving mode is merely the room temperature setpoint. The changeover from normal operation to energy saving or frost protection mode, or vice versa, is made by pressing a button. In auto mode changeover between operating modes is accomplished automatically according to the 7-day switching pattern.
Normal operation
When normal operation is activated, the symbol appears on the display. The set
point can be readjusted by pressing buttons and .
Energy saving or OFF
When energy saving mode is activated, the symbol appears on the display.
The set point can be readjusted by pressing buttons, and .
In energy-saving mode, the unit can also be switched to OFF. This is accomplished by selecting a setpoint of 5 °C and then keeping the button depressed for 4 seconds. In that case, the symbol does not appear.
Frost protection
When frost protection mode is activated, the symbol appears on the display.
7-day time switch The changeover between “normal” and “energy saving”
temperature setpoints can take place either automatically ( ) or manually ( ),
depending on the selection of the operating mode. When pressing the operating
mode button until appears on the display, the changeover will take place
automatically according to the selected switching pattern. A specific
switching pattern can be selected for every weekday.
Factory setting
The current setpoint can be temporarily readjusted by pressing buttons and . The setpoint will then be reset to its initial value the next time automatic or manual changeover takes place. When the operating mode button is set to or the controller will maintain normal operation or energy saving mode respectively. DHW mode The RDE10.1DHW features independent control of DHW.
The following DHW operating modes can be selected:
- Continuously ON: Symbol appears on the display
- Continuously OFF: No symbol on the display
- Auto: Symbol appears on the display, DHW is switched according to the selected switching pattern
Factory setting: Time switch for DHW
Display The digital display shows the actual room temperature, the time of day, the weekday, the current switching pattern for heating, the switching pattern for DHW, and the symbol of the operating mode currently active. When the heating output is activated, the triangle symbol appears. The display of the switching pattern is split up into upper and lower rows.
Upper row with switching pattern for DHW control
When the segment is displayed and flashing, the DHW output is activated. When
no segment is displayed, the DHW output is deactivated.
Lower row with switching pattern for heating
When the segment is displayed and flashing, the normal temperature setpoint is
active. When no segment is displayed, the energy saving or frost protection
temperature setpoint is active.
OFF mode and frost protection display
Backup When taking out the batteries, the setpoints and the information
required for operating mode changeover are memorized. However, the real-time
clock must be reset after the batteries are replaced.
Ordering
When ordering, please give name and type reference: Room temperature
controller RDE10.1DHW. Valve actuators are to be ordered as separate items.
Equipment combinations
Accessories
Mechanical design
The controller consists of 2 parts:
- Plastic housing with digital display, which accommodates the electronics, the operating elements and the built-in room temperature sensor
- Mounting base
- The housing engages in the mounting base and snaps on.
- The base carries the screw terminals.
Legend
- Display of the room temperature in °C, or setpoints
- The current time of day using the 00:00… 23:59 format
- Current weekdays from 1 (Monday) to 7 (Sunday)
- Current heating and DHW switching pattern with flashing time pointer
- Symbol when the actual room temperature is displayed
- Button for operating mode
- Button for DHW control
- Selecting and leaving the setting mode for the DHW switching pattern
- Symbol in automatic mode or when selecting the switching pattern
- Heating ON
- or will show when DHW heating is activated
- A symbol indicating that batteries need to be replaced
- Buttons for adjusting the setpoints, the time of day and the switching times
- Setting the weekday
- Setting the time of day
- Selecting and leaving the setting mode for the heating switching pattern
- Setpoint adjustment for energy-saving mode
- Setpoint adjustment for normal operation
- Button for confirming the switching pattern settings
- Battery compartment
Notes
The room temperature controller should be mounted in a location where the air
temperature can be acquired as accurately as possible without getting
adversely affected by direct solar radiation or other heat or refrigeration
sources. The mounting height is about 1.5 m above the floor.
The controller can be fitted to a recessed conduit box.
- Only authorized staff may open the unit.
- Caution: AC 230 V!
- The cables used must satisfy the insulation requirements for the main potential
Mounting, installations and commissioning
When mounting the controller, fix the base first. Then, make the electrical
connections and fit and secure the cover (also refer to the relevant Mounting
Instructions). The controller must be mounted on a flat wall and in compliance
with local regulations. If there are thermostatic radiator valves in the
reference room, they must be set to their fully open position.
Maintenance The controller is maintenance-free. Sensor calibration If the temperature on the display does not agree with the room temperature effectively measured, the temperature sensor can be recalibrated. For that purpose, both buttons and must be pressed simultaneously for 3 seconds. Then, the temperature displayed can be changed by a maximum of +/- 3 K by pressing the and buttons. 5 seconds after the last push of a button, the controller will automatically return to the normal operating state. Change of batteries If the battery symbol appears, the battery power is almost exhausted and the batteries should be replaced. To make a reset, first press and hold the button, then press the 2 buttons simultaneously for 3 seconds. All individual settings will be reset to their standard values.
Reset
Technical data
- Operating voltage DC 3 V (2 x 1.5 V AA Alkaline batteries)
- Battery life (RDE10.1DHW) > 1 year (AA Alkaline batteries)
Power supply
- Heating valve or wall-hung boiler – Y1
- Control output Q12 (NC contact)
- Rating RDE0.1DHW (AC 24…250 V) max. 5(2) A
- Control output Q14 (NO contact)
- Rating RDE10.1DHW (AC 24…250 V) max. 5(2) A
Control outputs
- DHW control – Y2
- Control output Q22 (NC contact)
- Rating RDE10.1DHW (AC 24…250 V) max. 5(2) A
- Control output Q24 (NO contact)
- Rating RDE10.1DHW (AC 24…250 V) max. 5(2) A
- Switching differential SD 1 K
Setpoint setting range
- Normal operation 5…35 °C
- Energy saving 0 (OFF) and 5…35 °C
- Factory setting normal operation 20 °C
- Factory setting energy saving 8 °C
- Frost protection 5 °C (fixed)
Resolution of settings and displays
- Setpoints 0.5 °C
- Switching times 60 min
- Actual temperature value displays 0.5 °C
- Time of day displays 1 min
O perational data
- An operation to IEC 721-3-3
- Climatic conditions class 3K5
- Temperature 0…+50 °C
- Humidity <95 % r.h.
- Transport to IEC 721-3-2
- Climatic conditions class 2K3
- Temperature -25…+60 °C
- Humidity <95 % r. h.
- Mechanical conditions class 2M2
Environmental conditions
- Storage to IEC 721-3-1
- Climatic conditions class 1K3
- Temperature -25…+60 °C
- Humidity <95 % r. h. conformity to
- EMC directive 89/336/EEC
- Low-voltage directive 73/23/EEC and 93/68/EEC
- N474 C-Tick conformity to EMC emission standard AS/NSZ 4251.1:1994
Product standards
- Automatic electrical controls for EN 60 730 – 1 and household and similar use EN 60 730–2-9
- Electromagnetic compatibility
- Emissions EN 61 000–6-3
- Immunity EN 61 000–6-1
- Safety class II to EN 60730
Pollution class normal
- Degree of protection of housing IP30 to EN 60529
- Connection terminals for solid wires or prepared stranded wires.
- 2 x 1.5 mm2
- or 1 x 2.5 mm2
- (min. 0.5 mm2)
- Weight 0.21 kg
- The colour of the housing front is white, NCS S 0502-G (RAL 9003)
General
Connection diagram
Application examples
- Room temperature controller with direct control of a gas-fired wall-hung boiler and independent control of DHW
- Room temperature controller with direct control of a gas-fired floor-standing boiler and independent control of DHW
Legend
- Thermal reset limit thermostat
- Safety limit thermostat
- Circulating pump
- RDE10.1DHW room temperatures controller
- 3-port valve with manual adjustment
- Magnetic valve
- DHW heating equipment
Room temperature controller with direct control of a heating circuit pump (control by manual mixing valve) and independent control of DHW
Dimensions
Controller and base
Building Technologies Room temperature controller RDE10.1DHW CE1N3038en 2005 Siemens Switzerland Ltd Subject to alteration HVAC Products
Download PDF: Siemens RDE10.1DHW Room Temperature Controller User Manual
Read User Manual Online (PDF format)