Dayton 7D851A Tube Heaters Instruction Manual
- June 17, 2024
- DAYTON
Table of Contents
- Dayton 7D851A Tube Heaters
- Product Information
- FAQs
- INTRODUCTION
- SAFETY
- Clearance to Combustibles
- Single Mounting Bracket
- Radiant Tube Assembly
- Burner Control Box Suspension
- Combustion Air Requirements
- Gas Supply
- Operation
- Troubleshooting
- Limited Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Dayton 7D851A Tube Heaters
Product Information
Specifications
- Model Numbers: 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
- Product Type: Gas-fired infrared heater
- Main Components: Burner control box, radiant tube, reflector assembly
- Installation: Suspended from the ceiling by chains
- Control: Thermostat-controlled
- Venting: Can be installed vented or unvented
- Combustion Air: May use outside air if necessary
Description
Dayton tube heaters are gas-fired infrared heaters designed to provide comfort heat. They consist of three (3) main components: a burner control box, radiant tube, and reflector assembly. The heaters are typically suspended from the ceiling by chains and controlled by a thermostat. They can be installed either vented or unvented and may use outside air for combustion if necessary. The radiant tube may be installed in different configurations depending on the heating requirements.
Installation
Important Note: This heater must be installed and serviced by trained gas installation and service personnel only!
- Read the installation, operating, and maintenance instructions thoroughly before attempting any installation.
- Ensure that the installation location complies with all safety requirements and clearances specified in the manual.
- If installing in a location used for the storage of combustible materials, post signs specifying the maximum permissible stacking height to maintain required clearances from the heater to the combustibles.
- Follow the provided instructions for suspending the heater from the ceiling using chains.
- Connect the gas supply line to the burner control box according to local gas codes and regulations.
- If necessary, provide outside air for combustion by following the instructions in the manual.
- Test the installation for gas leaks using a gas leak detector or soapy water solution.
Operation
Important Note: This section provides a brief overview of the operation. For detailed instructions, refer to the operation section in the manual.
- Ensure that the gas supply is turned on and the thermostat is set to the desired temperature.
- The burner control box will ignite the gas and produce infrared heat.
- The radiant tube will distribute the heat throughout the desired area.
- The reflector assembly helps direct the heat towards the desired direction.
- The thermostat will control the operation of the heater based on the temperature settings.
Maintenance
Important Note: Regular maintenance is essential for safe and efficient operation. Refer to the maintenance section in the manual for detailed instructions.
- Regularly inspect the heater for any signs of damage or wear.
- Clean the reflector assembly and radiant tube to remove any dust or debris accumulation.
- Check and clean the burner control box, ensuring proper functioning of all components.
- Inspect and replace any worn-out or damaged parts as necessary.
- Perform routine checks on the gas supply line and connections for leaks.
Troubleshooting Guide
Refer to the troubleshooting guide in the manual for assistance with common issues and their solutions.
Limited Warranty
Details about the limited warranty for the product can be found in the warranty section of the manual.
FAQs
- Q: Who should install and service this heater?
- A: This heater must be installed and serviced by trained gas installation and service personnel only.
- Q: Can this heater be installed vented or unvented?
- A: Yes, this heater can be installed either vented or unvented.
- Q: Does this heater require outside air for combustion?
- A: The heater may use outside air for combustion if necessary. Refer to the installation section in the manual for instructions.
- Q: How should I clean the reflector assembly and radiant tube?
- A: To clean the reflector assembly and radiant tube, use a soft cloth or brush to remove any dust or debris accumulation.
Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Please read and save these instructions. This heater must be installed and serviced by trained gas installation and service personnel only! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain these instructions for future reference.
Dayton® Tube Heaters
Description Dayton tube heaters are gas-fired infrared heaters designed to
provide comfort heat. They consist of three (3) main components: a burner
control box, radiant tube, and reflector assembly. The heaters are typically
suspended from the ceiling by chains and controlled by a thermostat. They can
be installed either vented or unvented, and may use outside air for combustion
if necessary. The radiant tube may be installed in different configurations
depending on the heating requirements.
These heaters use infrared energy to heat spaces. When heat is required, the
burner control box ignites a gas/air mixture and pushes the hot gases into the
radiant tube. As the gases pass through the assembly, the tubing is heated and
emits infrared, which is then directed toward the floor by reflectors. This is
known as primary infrared and is absorbed by the floor, objects and people in
the space, raising their temperatures. They in turn re-radiate this heat,
known as secondary infrared, to create a comfort zone at the floor level. This
is how Dayton tube heaters can heat large spaces without having to provide
primary infrared for every square foot of area. However, if the goal is to
spot heat a small area within a large space, only the primary infrared makes
this possible. Dayton tube heaters are design certified for use in industrial
and commercial buildings, such as warehouses, manufacturing plants, aircraft
hangars and vehicle maintenance shops. They are not certified for residential
use or where flammable gases or vapors are generally present, such as spray
booths.
! WARNING
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, injury or death. Read and understand the installation,
operating and maintenance instructions thoroughly before installing or
servicing this equipment.
This heater must be installed and serviced by trained gas installation and
service personnel only. Failure to comply could result in personal injury,
asphyxiation, death, fire and/ or property damage.
! WARNING
In locations used for the storage of combustible materials, signs must be
posted to specify the maximum permissible stacking height to maintain the
required clearances from the heater to the combustibles. Signs must either be
posted adjacent to the heater thermostats or in the absence of such
thermostats, in a conspicuous location.
For Your Safety – If you smell gas:
· Do not try to light any appliance. · Immediately call your gas supplier
from a neighbor’s phone. · Do not touch any electrical switch. · Follow the
gas supplier’s
instructions. · Do not use any phone in your
building. · If you cannot reach your gas
supplier, call the fire department.
Form 5S6496
Printed in U.S.A. 03460 1109/224/VCPVP
Keep these instructions for future reference.
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Kit Contents Prior to installation, verify that you have received all heater components included with your tube heater. Refer to the chart below for a list of the kit contents for your model heater. Materials not included in the kit (e.g. sheet metal screws, vent material, terminals, etc.) are the responsibility of the installer.
Filled By: Part #
Description
5VD67A-
5VD70A 20 ft.
5VD71A-
5VD72A 30 ft.
5VD73A- 5EAJ0-J2, 5VD79A-80A,
5VD78A 5EAH3-H5 5EAH6-H8
40ft.
50ft.
60ft.
TP-19B
4″ Tube Hanger with Tension Spring
3
4
5
6
7
TP-21B
4″ Tube Clamp
2
3
4
5
6
TP-33B
1/2″ Shut-off Ball Valve/Inlet Tap
1
1
1
1
1
TP-82
4″ Reflector Center Support
2
3
4
5
6
TP-83
24″ Stainless Steel Flexible Gas Connector
1
1
1
1
1
TP-105
Reflector End Cap
2
2
2
2
2
TP-106
Reflector End Cap Clips
8
8
8
8
8
THCS
Tube Heater Chain Sets
5
6
7
8
9
IOM
Installation, Operation & Maintenance Manual
1
1
1
1
1
2
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
INTRODUCTION
Overview The intent of this manual is to provide information regarding general safety, installation, operation and maintenance of this tube heater. You must read and understand all instructions and safety warnings before installing or servicing the tube heater.
Available Models – Tube Heater Burner Box and Tube Reflector Combinations
Combo # 7D837A
Burner Box #
5VD67A
Tube & Reflector Pkg #
5VD88
Tube Type 20-4″-ALUM
Length 20
7D838A
5VD68A
5VD88
20-4″-ALUM
20
7D839A
5VD69A
5VD88
20-4″-ALUM
20
7D840A
5VD70A
5VD88
20-4″-ALUM
20
7D841A
5VD71A
5VD89
30-4″-ALUM
30
7D842A
5VD72A
5VD89
30-4″-ALUM
30
7D843A
5VD73A
5VD91
40-4″-ALUM
40
7D844A
5VD74A
5VD91
40-4″-ALUM
40
7D845A
5VD75A
5VD91
40-4″-ALUM
40
7D846A
5VD76A
5VD91
40-4″-ALUM
40
7D847A
5VD77A
5VD90
40-4″-TITAN
40
7D848A
5VD78A
5VD90
40-4″-TITAN
40
7AR80
5EAJ0
5VD90 & 5EAH2 40-4″-TITAN & 10-4″-ALUM
50
7AR79
5EAJ1
5VD90 & 5EAH2 40-4″-TITAN & 10-4″-ALUM
50
7AR83
5EAJ2
5VD90 & 5EAH2 40-4″-TITAN & 10-4″-ALUM
50
7AR81
5EAH3
5VD90 & 5EAH2 40-4″-TITAN & 10-4″-ALUM
50
7AR87
5EAH4
5VD90 & 5EAH2 40-4″-TITAN & 10-4″-ALUM
50
7AR85
5EAH5
5VD90 & 5EAH2 40-4″-TITAN & 10-4″-ALUM
50
7D849A
5VD79A
5VD90 & 5VD88 40-4″-TITAN & 20-4″-ALUM
60
7D851A
5VD80A
5VD90 & 5VD88 40-4″-TITAN & 20-4″-ALUM
60
7AR84
5EAH6
5VD90 & 5VD88 40-4″-TITAN & 20-4″-ALUM
60
7AR82
5EAH7
5VD90 & 5VD88 40-4″-TITAN & 20-4″-ALUM
60
7AR88
5EAH8
5VD90 & 5VD88 40-4″-TITAN & 20-4″-ALUM
60
7AR86
5EAH9
5VD90 & 5VD88 40-4″-TITAN & 20-4″-ALUM
60
BTU/H 50,000 50,000 75,000 75,000 100,000 100,000 100,000 100,000 125,000 125,000 150,000 150,000 150,000 150,000 175,000 175,000 200,000 200,000 150,000 150,000 175,000 175,000 200,000 200,000
Gas Type NAT LP NAT LP NAT LP NAT LP NAT LP NAT LP NAT LP NAT LP NAT LP NAT LP NAT LP NAT LP
3
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
SAFETY
! WARNING
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, serious injury or death. Read and understand, the
installation, operating and maintenance instructions thoroughly before
installing or servicing this equipment. Only trained, qualified gas
installation and service personnel may install or service this equipment.
! WARNING
Not for residential use!
Do not use this heater in the home, sleeping quarters, attached garages, etc.
Safety Symbols
Safety is the most important consideration during installation, operation and
maintenance of the tube heater. You will see the following symbols and signal
words when there is a hazard related to safety or property damage.
! WARNING
Warning indicates a potentially hazardous situation which, if not avoided,
could result in death or injury.
Applications
This is not an explosion-proof heater. No heater may be used in a Class 1 or
Class 2 Explosive Environment. Consult the local Fire Marshall, fire insurance
carrier and other authorities for approval if the proposed installation is in
question.
Commercial and Industrial
This tube heater is designed and certified for use in industrial and
commercial buildings such as, warehouses, manufacturing plants, aircraft
hangars and vehicle maintenance shops.
! CAUTION
Caution indicates a potentially hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
Notice indicates a potentially hazardous situation which, if not avoided,
could result in property damage.
4
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Standards, Certifications and Governmental Regulations
The installation of this tube heater must comply with all applicable local, state and national specifications, regulations and building codes (contact the local building inspector and/or fire marshall for guidance) before installing the heater system.
In the absence of local codes, the installation must conform to the latest edition of the National Fuel Code ANSI Z223.1 (NFPA 54).
Refer to the following Standards and codes for application specific guidelines:
Public Garages: The installation of this heater in public garages must conform
with the Standard for Parking Structures, ANSI/ NFPA 88A (latest edition), or
the Code for Motor Fuel Dispensing Facilities and Repair Garages NFPA 30A
(latest edition) and must be at least 8 ft. above the floor.
Aircraft Hangars: The installation of this heater in aircraft hangars must
conform with the Standard for Aircraft Hangars, ANSI/ NFPA 409 (latest
edition). The heater must be installed at least 10 ft. above the upper wing
surfaces and engine enclosures of the highest aircraft which might be stored
in the hangar. In areas adjoining the aircraft storage area, the heaters must
be installed at least 8 ft. above the floor. The heaters must be located in
areas where they will not be subject to damage by aircraft, cranes, moveable
scaffolding or other objects.
High Altitude: The installation of this tube heater is approved, without
modifications, for elevations up to 6,000 ft. MSL (sea level). Contact Dayton
for installations above these elevations.
Electrical: The heater, when installed, must be electrically grounded in
accordance with the National Electrical Code ANSI/NFPA 70 (latest edition).
Under no circumstances is either the electrical supply line or gas supply line
to provide any assistance in the suspension of the heater.
Venting: Venting must be installed in accordance with the requirements set
forth in this manual and with the NFPA 54/ANSI Z223.1 National Fuel Gas Code
(latest edition).
This unit complies with or is Certified by one or more of the following
organizations or Standards:
· CSA International (CSA). · American National Standards (ANSI
Z83.20b). · National Fuel Gas Code (NFPA 54/
ANSI Z223.1). · Occupational Safety and Health Act
(OSHA).
5
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Clearance to Combustibles
! WARNING
This is not an explosion-proof heater. Do not store or use flammable objects,
liquids or vapor in the vicinity of the heater. Where there is the possibility
of exposure to flammable vapors or highly combustible materials, consult the
local fire marshall, fire insurance carrier and other authorities for approval
of the proposed installation.
! WARNING
This heater should be installed so that the minimum clearances to
combustibles, as marked on the heater, will be maintained from vehicles parked
below. If vehicle lifts are present, ensure that these clearances will be
maintained from vehicles parked below. If vehicle lifts are present, ensure
that these clearances will be maintained from the highest raised vehicle.
! WARNING
Fire Hazard. Always maintain published clearance to combustibles. Failure to
comply with the stated clearances to combustibles could result in personal
injury, death and/or property damage.
Hazards
For maximum safety, the building must be evaluated for hazards before
installing this heating system. A critical safety factor before installation
is the clearance to combustibles.
Clearances to combustibles is defined as the minimum distance that must be
maintained between the tube surface or reflector and combustible materials. It
also pertains to the distance that must be maintained from moving objects
(e.g. overhead doors, cranes, vehicle lifts, etc.) around the tube heater.
The following is a partial list of items to maintain clearances from:
· Gas and electrical lines · Combustible and explosive materials · Chemical
storage areas · Areas of high chemical fume
concentrations · Vehicle parking areas · Vehicle lifts · Hoists or cranes ·
Storage areas with stacked materials · Lighting · Sprinkler heads · Overhead
doors and tracks · Dirty, contaminated areas
If you are unsure about the proposed installation, consult your local fire
Marshall, fire insurance carrier or other qualified authorities for the
approval of the proposed installation.
Safety Signs and Labels It is important to provide warnings to alert
individuals to potential hazards and safety actions. ANSI Z83.20b and CSA
2.34, require you to post a sign “specifying the maximum permissible stacking
height to maintain the required published clearances from the heater to
combustibles” near the heater’s thermostat or, in the absence of such
thermostats, in a conspicuous location.
All safety labels must be maintained on this appliance. Contact Grainger if replacement labels are needed.
6
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Clearance to Combustibles
For the safe installation of this unit, the clearance to combustibles data
below (Figure 1.1) contains clearances that must be maintained. Check the
heater’s rating plate to verify the minimum clearance to combustibles and gas
type for your model heater.
Figure 1.1 · Clearances to Combustibles Data
0° Mounting
Angle
Top
Side
Side
Below
45° Mounting
Top
Angle
Front
Behind
Below
0° w/ 1
Top
Side Shield
Front
Behind
Below
0° W/ 2 Side Top Shields
Side
Side
Below
Mounting
Side
Model No.
Angle * Front Behind Top Below
Dayton – 5VD67A, 5VD68A (20′ min. to 40′ max.)
50,000 BTU/H [N, P]
0°
9
9
6
47
7D – 837A,838A
45°
39
8
10
47
0° w/ 1 side shield
0°
29
8
6
47
0° w/ 2 side shields
0°
9
9
6
47
20 ft. from burner
0°
7
7
6
30
Dayton – 5VD69A, 5VD70A (20′ min. to 40′ max.)
75,000 BTU/H [N, P]
0°
9
9
6
60
7D – 839A,840A
45°
39
8
10
60
0° w/ 1 side shield
0°
29
8
6
60
0° w/ 2 side shields 20 ft. from burner
0°
9
9
6
60
0°
7
7
6
30
Dayton – 5VD71A, 5VD72A, 5VD73A, 5VD74A (30′ min. to 40′ max.)
100,000 BTU/H [N, P]
0°
14
14
6
66
7D – 841A,842A,843A,844A
45°
39
8
10
66
0° w/ 1 side shield
0°
29
8
6
66
0° w/ 2 side shields
0°
16
16
6
66
20 ft. from burner
0°
7
7
6
30
Dayton – 5VD75A, 5VD76A (40′ min. to 60′ max.)
125,000 BTU/H [N, P]
0°
20
20
6
76
7D – 845A,846A
45°
58
8
10
76
0° w/ 1 side shield
0°
42
8
6
76
0° w/ 2 side shields
0°
20
20
6
76
20 ft. from burner
0°
7
11
6
30
Dayton – 5VD77A, 5VD78A, 5VD79A, 5VD80A, 5EAJ0, 5EAJ1 (40′ min. to 60′ max.)
150,000 BTU/H [N, P]
0°
24
24
6
81
7D-847A,848A,849A,851A, 7AR-79,80
45°
58
8
10
81
0° w/ 1 side shield 0° w/ 2 side shields
0°
42
8
6
81
0°
23
23
6
81
20 ft. from burner
0°
11
11
6
44
Dayton – 5EAJ2, 5EAH3, 5EAH6, 5EAH7 (50′ min. to 60′ max.)
175,000 BTU/H [N, P]
0°
34
34
6
92
7AR – 81, 82, 83, 84
45°
63
8
10
92
0° w/ 1 side shield
0°
50
8
6
92
0° w/ 2 side shields
0°
30
30
6
92
20 ft. from burner
0°
11
11
6
44
Dayton – 5EAH4, 5EAH5, 5EAH8, 5EAH9 (50′ min. to 60′ max.)
200,000 BTU/H [N, P]
0°
41
41
6
94
7AR – 85, 86, 87, 88
45°
63
8
10
94
0° w/ 1 side shield
0°
54
8
6
94
0° w/ 2 side shields
0°
30
30
6
94
20 ft. from burner
0°
11
11
6
44
Minimum end clearance for all models is 12 inches. *Heaters mounted on an angle between 0°
to 45° must maintain clearances posted for both 0° and 45° mounting angles; whichever is greater.
7
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Installation
Design Considerations and Prechecks
Placement of infrared tube heaters is influenced by many factors. Aside from safety factors, considerations such as the number of elbows that are allowed, maximum vent lengths, ducting of combustion air and combining vents are a few examples. This manual, along with national, state
and local codes, addresses these issues. It is critical that all guidelines
and instructions are followed.
To ensure a properly designed heating system, a heating layout should be
developed for the correct placement of the burner control box, radiant
tubing, venting and combustion air intake ducts. Inspect and evaluate the mounting conditions, vent locations, gas supply and electrical wiring. Refer to the chart below for the recommended distances for the model being installed.
Heater Installation Chart
Model # 7D837A-7D838A 7D839A-7D840A 7D841A-7D844A 7D845A-7D846A 7D847A-7D851A, 7AR79-7AR80 7AR81-7AR84 7AR85-7AR88
BTU/H 50,000 75,000 100,000 125,000
150,000
175,000 200,000
Recommended Mounting Heights
9′ to 14′ 11′ to 18′ 13′ to 23′ 14′ to 25′
Distance Between Heaters 10′ to 20′
20′ to 30′
20′ to 30′
20′ to 30′
15′ to 35′
30′ to 40′
17′ to 35′ 18′ to 40′
30′ to 40′ 30′ to 40′
Distance Between Heater Rows 20′ to 40′
30′ to 50′
30′ to 50′
30′ to 50′
Maximum Distance Between Heater and Wall
16′
20′
20′
25′
40′ to 60′
25′
40′ to 60′
30′
40′ to 60′
30′
When designing an infrared radiant heating system, consider the following:
-
Has the building’s heat loss been evaluated?
· Does the design meet the needs of the space?
· Have all clearance to combustible situations been observed?
· Have recommended mounting heights been observed?
· Is the supply (burner) end of the heater located where more heat is required?
· Is it best to offset the heaters and/ or rotate the reflectors towards the heat zone? -
Are protective guards, side shields,
U’ or
L’ reflector covers needed?
· Does the heater require outside fresh air for combustion?
· Is the environment harsh or contaminated (requiring outside air for combustion)?
· Are chemicals or vapor a concern (requiring outside air for combustion)?
NOTE: The effective infrared surface temperature of a person or object may be diminished with wind above 5 mph. The use of adequate wind barrier(s) may be required.
NOTE: When heated, materials high in hydrocarbons (solvents, paint thinner,
mineral spirits, formaldehydes, etc.) can evaporate. This may result in odors
or fumes being emitted into the environment. To correct this problem, clean
the area and/or introduce additional ventilation.
Heaters installed and serviced in accordance with the installation manual do
not emit odors into the environment. See notice on page 28 additional
information.
8
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Design Scenario
A tube heater system is being installed in 70′ (L) x 40′ (W) space with 12′
ceilings. Two overhead doors are located at one end and an equipment storage
area exists on one side. The calculated heat load is 300,000 BTU/H.
Figure 2.1 · Poor Design
· Two burners (150,000 BTU/H each) are placed at one end, opposite the area of
highest demand (overhead doors).
· Recommended mounting heights are not observed.
· Produces an uneven heat distribution.
Doors and tracks
Too Cold
Doors and tracks
70′ Gas Supply
60′ – 150,000 BTU (2 total)
Equipment storage
Too Hot
40′
Poor Design
Figure 2.2 · Good Design
· Four burners (75,000 BTU/H each) are placed in each corner. Burner (hotter)
ends direct heat to areas of highest head demand.
· Recommended mounting heights observed.
· Distributes heat more evenly.
Doors and tracks
Doors and tracks
70′ Gas Supply
Equipment storage
20′ – 75,000 BTU (4 total)
Better Heat Distribution
40′
Good Design
Sidewall Vent (2 total)
9
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Recommended Mounting Heights
Model BTU Range Recommended Mounting Heights Coverage Straight Config. (LxW) Coverage U-Tube Config. (LxW) Distance Between Heater Rows (Ft.) Dim. A Distance Between Heater Rows (Ft.) Dim. B Max. Distance Between Heaters and Wall (Ft.) Dim C
20 ft.
50 MBH
10′ – 16′
20′ x 12′
12′ x 12′
10′ – 20′
20′ – 40′
16′
75 MBH
12′ – 20′
22′ x 15′
12′ x 12′
20′ – 30′
30′ – 50′
18′
30 ft. 100 MBH
13′ – 20′
33′ x 18′
N/A
20′ – 30′
30′ – 50′
20′
40 ft. 100-125 MBH 13′ – 25′
44′ x 21′
23′ x 17′
20′ – 30′
30′ – 50′
20′
150 MBH
16′ – 30′
45′ x 26′
24′ x 20′
30′ – 40′
40′ – 60′
25′
50 ft. 150-200 MBH 16′ – 30′
56′ x 30′
N/A
30′ – 40′
40′ – 60′
25′
60 ft. 150-200 MBH 17′ – 40′
67′ x 34′
34′ x 26′
30′ – 40′
40′ – 60′
25′
NOTE: Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted to low or to high, they may result in heat discomfort or lack of heat. It is generally recommended to
observe the recommended mounting heights to optimize comfort conditions. However, certain applications such as spot heating, freeze protection, outdoor patio heating or very high ceilings may result in the heaters
being mounted outside of the factory recommended mounting heights. Clearances to combustibles must always be maintained.
Figure 2.3 · Recommended Mounting Heights and Distances – see chart above for dimensions.
Dimension B Distance between heater rows
Dimension A Dimension A
Dimension C Maximum distance between heater and wall
Dimension C Maximum distance between heater and wall
10
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Hanger Placement and Suspension
Suspension of the heater must conform to applicable codes referenced in the
Safety section and these instructions.
1. Lay radiant tubing out in the following order. Position tubes in their
approximate locations. Figure 2.4.
· 10 ft. primary combustion chamber.
· Radiant emitter tubes.
- Mark locations for hanging points. Figure 2.4 Chart.
NOTE: If the available hanging points do not allow for the recommended spacing (or if an alternative hanging method is utilized) then additional hangers may be necessary.
· The spacing between the burner control box mounting brackets and the first hanger should be approximately 2′-4″.
IMPORTANT! 150 MBH models must use the 10 ft. titanium alloy treated combustion chamber as the first tube connected to the burner control box. The combustion chamber has an orange identification sticker located on the swaged end of the tube.
- The space between the first two hangers placed on the first tube should be approximately 8′-10″.
· The space between hangers thereafter, one per tube, should be approximately 9′-8″.
! WARNING
Failure to maintain the published clearance to combustibles may result in fire
and/or explosion, property damage, serious injury or death. Always maintain
clearances and post signs where needed.
! WARNING
Improper suspension of the heater may result in collapse and being crushed.
Always suspend the appliance from a permanent part of the building structure
that can support the total weight and force of the heater.
11
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Hanger Placement and Suspension Figure 2.4 · Heater Suspension Layout
NOTE: A sticker identifying the combustion chamber(s) is located on the swaged
end of the tube(s).
Burner Control Box Hanging Points
Hanging Point
8′-10″
Hanging Point
Hanging Point
9′-8″
9′-8″ Radiant Emitter Tube(s)
Radiant Emitter Tube
2′-4″ 16″ Burner
Tube
10 ft. Primary Combustion Chamber
Igniter/Sensor Box Burner Control Box
Heater Mounting Requirements and Weights
Model Dimension Straight Config. Hanging Points Control Box Hanging Points Shipping Weight Chain Set Qty. Straight Config. Chain Set Qty. U-Tube Config. Optional Brass Knuckles (P/N: 5VD54) Optional Single Mount Bracket (P/N: 5VD85) U Config. Only.
20 ft.
21′-8″
3
30 ft.
31′-4″
4
40 ft.
41′-0″
5
50 ft.
50′-8″
6
60 ft.
60′-4″
7
2
120 lbs.
5
6
3
2
2
160 lbs.
6
N/A
4
N/A
2
190 lbs.
7
8
5
3
2
235 lbs.
8
N/A
6
N/A
2
265 lbs.
9
10
7
4
12
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Heater Placement and Suspension
Suspension of the heater must conform to applicable codes referenced in the
Safety section and these instructions.
3. Prepare the mounting surface. If necessary, weld blocks, drill holes, etc.
Figure 2.5. NOTE: The burner control box and radiant tubes should be in
straight alignment and level.
-
Fasten beam clamp, screw hook or other type of suspension anchor to hanging point.
5. Attach and close S-hook and #1 double-loop chain to anchor. Check that it is securely attached. NOTE: Threaded rod and turnbuckles may be used. -
Attach hangers to chains. Adjust chain lengths until radiant tubing is level and equal weight distribution is achieved.
NOTE: Chains must be straight up and down. Do not install chains at an angle as this can result in tube warpage or separation.
Figure 2.5 · Mounting the Hangers
3. I-Beam 4. Beam Clamp 6. Threaded Rod
5. Threaded Rod and Turnbuckle
-
I-Beam 4. Beam Clamp
5. S-hook and #1 double-loop chain
6. Chain -
Concrete Beam
4. Screw Hook -
Chain
-
Screw hook
with locknut
and washer -
Wood Beam
6. Chain
13
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Optional U-Bend or Elbow Accessory Configuration Figure 2.6 · U-Tube Hanger Mounting Options
Single Mounting Bracket
Brass Knuckle
Exhaust End
U-Tubes can be mounted from a single suspension point using a Single Mounting
Bracket (P/N: 5VD85) with five S-hooks and #1 double-loop chains.
Figure 2.7 · Angled Hanger Mounting Options
U-Tubes can be mounted at a 15°, 30° or 45° angle with two suspension points, using two Brass Knuckle (P/N: 5VD54) fittings, #1 double-loop chains and S-hooks.
45° 30° 15°
For 45° hanging angle use two S-hooks and two #1 double-loop chains.
For variety of hanging angles, use the Brass Knuckle (P/N: 5VD54) fitting with a #1 double-loop chain and S-hook.
14
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Radiant Tube Assembly To install the radiant tubes:
1. Place tubes in hangers with the welded seam facing downward and the swaged
end of the tube towards the exhaust end of the heater system. Figure 2.8.
Refer to Figure 2.20 on page 22 for tube installation sequence. Figure 2.8 ·
Attach Hangers
Swaged end
Hanger
Radiant tube
Welded seam faces down
- Slide tube clamps onto radiant tubes. Figure 2.9. Figure 2.9 · Attach Tube Clamps
Concave surface
Tube clamp
NOTE: If the tube clamp comes apart, the spacer must be reassembled with the
spacer’s concave surface facing against the radiant tube surface.
15
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Radiant Tube Assembly
3. Slip-fit the radiant tube sections together until tightly connected
(install swaged end of each tube towards exhaust end). NOTE: If it is
difficult to mate the tubes, they may be installed incorrectly.
4. Center tube clamps over the seams where two radiant tube sections connect.
If necessary, rotate tube clamps so they will not interfere with the reflector
end caps during expansion and contraction of the heater while operating.
5. Tighten tube clamp bolts to secure. When proper compression is obtained
(40-60 ft-lbs. torque), the tube seam will create a visible mark on the tube
clamp. NOTE: Excessive torque may damage the tube clamp.
6. Determine the location of the burner control box and note the placement of
the mounting chains.
The tube clamp is tight when proper torque is achieved (normally when seam becomes visible).
- A maximum of one 180° U-bend or two 90° elbows can be installed on a heater.
· Omit one 36″ section of turbulator baffle. Refer to Baffle Assembly section.
Optional U-Bend or Elbow Accessory Configurations
Figure 2.11 · Optional Tube Connections
Tubes are not fit snuggly together and the tube clamp is not centered over the seam.
90 Degree Elbow Bend (P/N: 3TZ71)
Incorrect Tube Connection
Figure 2.10 · Tube Connections Tubes fit snuggly together and the tube clamp
is centered over the seam.
Correct Tube Connection
A 180 degree U-bend or 90 degree accessory fitting may be installed in the
radiant tube heater system. Refer to chart on page 17 for minimum distance
requirements from the burner control box.
When installing a U-bend or Elbow Accessory Fitting:
· The top clearance of an uncovered (no reflector) U-bend or elbow accessory
fitting to combustibles is 18″.
· If operating the heater un-vented, separate the intake air to the heater
from its exhaust products a minimum of 4′; further separation may be
necessary. Combustion air may also be supplied.
180 Degree U-Bend
(P/N: 3F835)
16
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Radiant Tube Assembly Figure 2.12 · Elbow and U-Bend Clearances
Dimension A
Elbow can be set in both directions
Tube Clamp
Tube Clamp
Dimension A
U-Bend can be set in both directions
Tube Clamp 8″
12″ Dimension B
Figure 2.13 · U-Bend and Elbow Dimensions
16″ 6″
Tube Clamp
12.5″
16″
20″
12.5″
P/N: 3TZ71
10″ 20″
P/N: 3F835
Minimum Distance from Burner Control Box to U-Bend or Elbow Accessory
Models 50-100 MBH
Dimension A 10 ft.
125 MBH 150-175 MBH
200 MBH
15 ft. 20 ft. 25 ft.
Overall Dimensions for Heaters Configured with U-Bend (P/N: 3F835)
Model 20 ft. 30 ft. 40 ft. 50 ft. 60 ft.
Dimesion B 13′-0″ N/A 22′-8″ N/A 32′-4″
17
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Burner Control Box Suspension
Suspending the burner control box must be done in accordance with applicable
codes listed in the Safety section and these instructions.
The burner control box must be in straight alignment with the radiant tubes
and level.
1. Determine the mounting chain locations for hanging the burner control box.
2. Fasten beam clamp, screw hook or other type of suspension anchor to
hanging point.
3. Attach and close S-hook and #1 double-loop chain to anchor. Check that is
securely connected.
4. Attach chain assemblies and S-hooks to mounting brackets on the burner
control box. Adjust chain lengths until level and in straight alignment with
the radiant tubes. The burner sight glass will be visible from the floor.
Figure 2.14 · Burner Control Box Assembly · Side View
1 2 3
Burner Control Box tube is in
straight alignment with 10′
4
Primary Combustion Chamber
8.1″
Burner Sight Glass
12″
(bottom side of the tube)
16″
Figure 2.15 · Burner Control Box with U-Bend · End View
29.6″ 16″
8.1″
3.5″
3″
5.5″
5″
18″
18
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Reflector Assembly
To install the reflectors:
1. Attach reflector center supports onto radiant tubes.
2. Slide each reflector section through the hangers and adjust the reflector
tension spring into the V-groove on the top of the reflector. The reflectors
should overlap approximately 4″.
- To prevent the reflectors from shifting, secure the reflector sections together using sheet metal screws except at the expansion joint. Figure 2.18. NOTE: Installer to provide sheet metal screws.
4. Attach reflector end caps, with polished side inward, to each end of the reflector run.
Reflectors, and reflector accessories, direct infrared energy to the floor
level. The reflector assembly depends on the heater configuration, proximity
to combustibles and the space surrounding the heater.
Before you begin assembly, determine if the use of reflector accessories are
necessary. Figure 2.17.
Figure 2.16 · Reflector Assembly
Reflector Center Support
Hanger Radiant and Chain Tube
Reflector
Place at the mid-point of the tube
Reflector Tension Spring
4″ Overlap
Reflector End Cap
Clips
19
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Reflector Assembly
Common Optional Accessories
Reflector Accessories
Description
Part #
Elbow Reflector*
90° bend, highly polished aluminum reflector elbow. Designed to fit atop one 5VD83 elbow accessory fitting.
U-Reflector*
180° bend, highly polished aluminum reflector U-bend. Designed to fit atop one U-bend accessory fitting.
5VD84
Side Shield Reflector *^
Highly polished side shield extension used to direct infrared rays downward, away from side walls and combustibles.
5VD86
Protective Guard
Used to prevent debris or objects from becoming lodged between the radiant 5VD81 tube and reflector. Required when mounting heaters below 8 ft.
- Reflectors cannot be rotated when used with this accessory. ^ Refer to the Clearance to Combustibles chart on page 7 for minimum distances to combustibles when side shield
extension(s) are used.
Additional accessory options are available in the W.W. Grainger catalog.
Figure 2.17 · Reflector Shield Accessories
Elbow reflector (P/N: 5VD83) Used over a 90-degree elbow radiant tube.
U-shaped reflector (P/N: 5VD84) Used over a `U-shaped radiant tube.
Side shield extension (P/N: 5VD86) Directs infrared rays downward, away from
sidewalls and combustibles.
20
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Baffle Assembly and Placement
To assemble the baffles: NOTE: Baffles may be inserted into the tube while being assembled.
- Install the baffle tabs at a 90° angle to the baffle keyhole. Figure 2.18.
- Adjust the tabs to the center of the keyhole and rotate the baffle 90° to lock the baffle sections together.
- Determine the number of baffles needed for your model number. Remove one 36″ baffle section if heater is installed with an elbow or U-bend accessory.
- Insert one baffle tab into keyhole and slide completely to one side until both baffle tabs appear in the keyhole.
- Repeat this process with remaining baffle sections to complete assembly.
Figure 2.18 · Assembling the Baffles
Baffle keyhole Baffle tabs
2
3
4
To insert the baffles:
Completed connection
-
Insert baffles with the keyhole end first.
2. Rotate baffle assembly so that it is in the vertical position. -
Slide baffle assembly into the last radiant tube section, furthest from burner control box.
NOTE: Baffle assemblies longer than 10′ will continue to be fed into next tube section.
Figure 2.19 · Inserting the Baffles
1
2
3
IMPORTANT: Baffle assembly must be flush with the end of the last tube
section and in the vertical position.
21
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Final Heater Assembly
NOTICE
Different inputs and models utilize different baffle lengths. Remove all
enclosed baffle sections from box and retain with applicable heater. Reference
shipping label for proper baffle size.
Each 36″ baffle section must be assembled with other baffles and placed in the
radiant tube section furthest from the burner. Important: Omit one section of
baffle if heater is configured with a U-bend or Elbow accessory fitting.
Figure 2.20 · Secured Reflector Joints and Baffle Location 20 Foot 30 Foot 40 Foot
Key
Burner Control Box with 16″ Burner Tube
Expansion Joint on Reflectors
Secured Joint on Reflectors
Primary Combustion Chamber Tube with Clamp Radiant Tube with Clamp
Baffle Location
50 Foot
60 Foot
22
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Venting
! WARNING
Insufficient ventilation and/or improperly sealed vents may release gas into
the building which could result in health problems, carbon monoxide poisoning
or death.
Improper venting may result in fire, explosion, injury or death.
Seal vent pipes with high temperature sealant and three (3) #8 sheet metal
screws. Vent enclosed spaces and buildings according to the guidelines in this
manual and applicable national, state, provincial and local codes.
The heating system may operate either vented or un-vented (see page 27).
Venting can terminate through the sidewall (horizontal) or the roof (vertical)
and be individually or commonly vented.
Follow these guidelines and all applicable codes for all models, prior to
installing vent material. Local codes may vary. In the absence of local codes,
refer to the National Fuel Code ANSI Z223.1 (NFPA 54) latest edition or the
National Standards of Canada.
Venting Requirements
· 4″ single wall galvanized steel vent pipe or Dura/Connect single wall
flexible exhaust vent must be used.
· Seal single wall vent with high temperature sealant and three (3) #8 sheet
metal screws.
· Single wall galvanized vent pipe must be insulated in cold environments.
· Do not use more than two 90° elbows in the exhaust vent.
- To maintain clearances to combustibles, the use of an approved wall or roof thimble and double-wall Type B-vent is required for the portion of vent pipe that runs through combustible material in the building wall or roof (see figures 2.21 & 2.22).
- The maximum vent length is 20′.
23
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Vent Assembly Figure 2.21 · General Vent Requirements:
Vent Cap
Storm Collar Adjustable Roof Flashing 1 in. minimum clearance 1 in. minimum
clearance
B to C Adapter
24 in. Min.*
Roof*
Double-wall B Vent Firestop Spacer
Heater
Single-wall Elbow or Alternate Tee Fitting
Single-wall Vent (field supplied)
*Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12
Figure 2.22 · Sidewall Venting Requirements
Building Overhang
Sidewall Vent Cap
Wall Thimble
36 in. min. 6 in.
min.
Sidewall B to C Adapter
Double-wall Single
B-Vent
Wall Vent
1/4 in. downward pitch per foot
Heater
Sidewall Venting Guidelines:
· To prevent moisture from entering the heater system, slope the vent pipe
down toward the outlet 1/4″ per foot of length. Do not pitch the heater.
· Vent must extend beyond any combustible overhang.
24
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Vent Assembly
Vent Termination
· Vent must terminate a minimum of 4′ (1.2m) below, 4′ (1.2m) horizontally
from or 12″ (30 cm) above any window or door that may be opened and gravity
air inlet into the building.
· Vent must terminate a minimum of 3′ (.9m) above any forced air inlet that is
located within 10′ (3.1m).
-
The bottom of the vent terminal must be located a minimum of 12″ (30 cm.) above grade level and must extend beyond any combustible overhang. Vents adjacent to public walkways must terminate a minimum a 7′ (2.1 m) above grade level.
· The vent cap must be a minimum of 6′ (15.2 cm) from the sidewall of the building. -
The vent terminal must be installed to prevent blockage by snow and protect building materials from degradation by flue gases.
· Vents must extend beyond any combustible or be a minimum of 36″ below a combustible overhang.
Roof Venting
Guidelines: · Separate air intake duct from vent
pipe a minimum of 4′ (1.2 m) by placing vent pipes higher than adjacent air
intake duct.
- Venting may utilize a standard B-vent cap.
- The vent terminal must extend a minimum of 2′ (.6 m) above the roof.
Figure 2.23 · Rooftop Venting – Side View
Vent Cap Roof
B to C Adapter Single-wall Elbow or Alternate Tee Fitting
24 in. Min. Roof
Double-wall B Vent Pipe Firestop Spacer
Heater
Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12.
25
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Vent Requirements
Common Venting
Figure 2.24 · Common Rooftop Venting – Side View
- A dual exhaust assembly (P/N: 3F817) must be used when joining two heaters to a common vent so that byproducts of one heater do not flow into the adjoining vent of the other heater.
· 6″ diameter double-wall B-vent and 6″ vent cap must be used.
· Common vented heaters must be controlled with the same thermostat. Do not operate individually.
Rooftop Vent Cap Double-wall B Vent
24 in. Min.*
Roof
Firestop Spacer Heater
Heater
Dual Exhaust Assembly
*Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12.
Figure 2.25 · Common Sidewall Venting – Top View
Sidewall 6 in. min.
B To C Adapter
Heater
Sidewall Vent Cap Wall Thimble Double-wall B-Vent Single Wall Vent
Dual Exhaust Assembly Heater
26
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Optional Unvented Operation
When installing in an un-vented configuration:
-
A factory supplied vent cap/diffuser (P/N: 3F839) must be used.
· Ventilation of the space is required to dilute the by-products of combustion. Sufficient displacement of fresh air intake and exhaust byproduct must be provided.
· The minimum clearance between the air intake and the exhaust terminal is 4′. NOTE: When installing in a U-bend configuration, use caution to separate vent gases from heater intake. -
A minimum positive air displacement (movement) of 4 ft3/1000 Btu/hr input of installed heaters is required.
NOTE: Gravity or mechanical means may be used to accomplish the air displacement. Local codes may require that the mechanical exhaust system be interlocked with the electrical supply line to the heaters, enabling both to function simultaneously.
· The use of combustion air intake is recommended.
! WARNING
Not for residential use. The use of unvented tube heaters in residential
indoor spaces may result in property damage, serious injury or death. Use
unvented operation in commercial and industrial installations with proper
ventilation rates only.
Figure 2.26 · Minimum end clearance for unvented heater
1231″0mm
12″
27
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Combustion Air Requirements
NOTICE
This heater has a factory preset air orifice for proper combustion air supply.
If using combustion air intake from indoors, the required volume of the space
must be a minimum of 50 ft3/1000 Btu/hr of installed heater input unless the
building is of unusually tight construction. If the building has air
infiltration rates of less than 0.40 air changes per hour, outside combustion
air is typically needed unless the sheer size of the building allows
otherwise.
Non-contaminated air for combustion must be ducted to the heater if
chlorinated or fluorinated contaminants, high humidity and other contaminants
such as sawdust or welding smoke are present in the area where the heater is
installed, or if the building has a negative pressure.
Figure 2.27 · Vertical Outside Air Supply for Single Heater Side View
Roof Intake Cap
Roof 18″ Min.
4″ pipe
Flexible Air Inlet Boot
Burner Control Box
Figure 2.28 · Horizontal Outside Air Supply for Single Heater Side View
Flexible Air Inlet Boot
Air Intake Cap
4″ pipe Wall
Burner Control Box
Combustion air intake may be located on either the sidewall or the roof. Figures 2.27 – 2.29.
Figure 2.29 Vertical Outside Air Supply for Common Heater · Side View
Note: Common intake heaters
Roof Intake Cap
must share the same thermostat.
18″ Min.
6″ pipe
Flexible Air Inlet Boot
Roof
Burner Control Box
4″ pipe
4″ pipe
28
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Combustion Air Requirements
Guidelines:
General Requirements · No more than two 90° elbows are
allowed.
· Allow for expansion. Use a 4″ flexible hose to connect the duct to the
burner control box.
· Do not draw air from attic space.
-
In humid environments, use insulated duct, PVC pipe or DWV (drain waste vent) to prevent condensation on the outer surface.
· Separate air intake duct from vent pipe a minimum of 4′. Also, place pipe higher than adjacent air intake duct. -
A factory approved wall intake cap (P/N: 3F837) must be used with horizontal outside intake ducts. The wall intake cap (P/N: 3F837) must be installed to prevent blockage. Locate the intake where dirt, steam, snow, etc. will not contaminate or clog the intake screen.
Limitations for length and size of combustion air intake duct
Single Heater Intake
Air Intake Duct Size
Max. Intake Length
Dual Heater Intake
Duct Size
Max. Intake Length
4 in.
20 ft.
4 in.(single)/6 in.(dual)
20 ft.
5 in.
30 ft.
4 in.(single)/8 in.(dual)
30 ft
6 in.
40 ft.
Consult factory for longer intake lengths.
Figure 2.30 · Combustion Air Intake
Air Intake Cap
Burner Control Box
29
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Gas Supply
! WARNING
Improperly connected gas lines may result in fire, explosion, poisonous fumes,
toxic gases, asphyxiation or death. Connect gas lines in accordance to
national, state, provincial and local codes.
IMPORTANT! Before connecting the gas supply to the burner control box:
· Verify that the heater’s gas type (as listed on the rating plate) match that
of your application.
· Check that the gas piping and service has the capacity to handle the total
gas consumption of all heaters being installed, as well as any other gas
appliances being connected to the supply line.
· Check that the main gas supply line is of proper diameter to supply the
required fuel pressures.
- If utilizing used pipe, verify that its condition is clean and comparable to a new pipe. Test all gas supply lines in accordance with local codes.
· Test and confirm that inlet pressures are correct. Refer to the rating plate on the burner control box for required minimum and maximum pressures (see chart below). The gas supply pipe must be of sufficient size to provide the required capacity and inlet pressure to the heater (if necessary, consult the local gas company). Do not exceed the maximum allowed pressure for the heater, the space or the gas piping system.
Manifold Pressure
Type of Gas Natural
Liquefied Petroleum
Required Manifold Pressure
3.5 Inches W.C.
10.0 Inches W.C.
Minimum Inlet Pressure
5.0 Inches W.C.
11.0 Inches W.C.
Maximum Inlet Pressure
14.0 Inches W.C.
14.0 Inches W.C.
Note: Check manifold pressure at the tap on the gas valve. Readings will be above atmospheric pressure.
Pressure Equivalents: 1 Inch W.C. = .058 oz/sq. in. = 2.49 Mbar
30
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Gas Connection To connect the gas:
! WARNING
Failure to install, operate or service this appliance in the approved manner
may result in property damage, injury or death. Only trained, qualified gas
installation and service personnel may install or service this equipment.
This heater must be installed and service by trained gas installation and
service personnel only.
The installation must conform with local building codes or, in the absence of
such codes, the National Fuel Code (NFPA 54) and in conjunction with ANSI
Z21.24/CSA 6.10 “Connectors for Gas Appliances”.
IMPORTANT! The heating system will expand and contract during operation.
Allowances for expansion must be made between the connection to the heater and
the gas supply. Excessive bending, kinks, twists or vibration must be avoided.
A flexible gas connection of approved type is required. Flexible stainless
steel gas connectors installed in one plane, and without sharp bends, kinks or
twists is recommended.
The gas pipe and connection must be supported independently. Do not install
gas supply line in a manner that bears the weight of the heater. Connect the
main gas supply line with an approved flexible connector (Figures 2.31 & 2.32)
or, if national or local codes require rigid piping, a swing joint. See the
safety messages at the beginning of this section.
The gas outlet must be in the same room as the appliance and accessible. It
may not be concealed within or run through any wall, floor or partition. When
installing the heater in a corrosive environment (or near corrosive
substances), use a gas connector suitable for the environment. Do not use the
gas piping system to electrically ground the heater.
- Install a sediment trap / drip leg if condensation may occur at any point of the gas supply line. This will decrease the possibly of loose scale or dirt in the supply line entering the heater’s control system and causing a malfunction.
NOTE: High pressure gas above 14 Inches W.C. (water column pressure) requires a high pressure regulator and ball valve.
2. Form the stainless steel flexible connector into a smooth C-shape allowing 12 in. between the flexible connector’s end nuts. Figure 2.31.
3. Attach the ball valve to the gas supply pipe. Apply pipe compound to NPT adapter threads to seal the joint. Use only a pipe compound resistant to LP.
NOTE: Provide a 1/8 in. NPT plugged tapping accessible for test gauge connection immediately upstream of gas connection to the heater (provided on ball valve).
31
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Gas Supply
- Attach the flexible connector to the adapter and burner control box inlet. Seal the joints.
Figure 2.31 · Flexible Gas Connection Side View Ball Valve / Inlet Tap
NOTE: Excessive torque on the manifold may misalign the orifice. Always use
two wrenches to tighten mating pipe connections.
5. Final assembly must be tested for gas leaks according to NFPA or local
codes.
Adapter
Drip Leg/ Sediment Trap 2″ max displacement 12″
! CAUTION
When using a stainless steel flexible connector, do not attach the connector
nuts directly to the gas pipe supply. Connector nuts must be installed to an
approved adapter.
Heater Movement
Burner Control Box
Adapter
Stainless Steel Gas Connector, formed into smooth C-Shape
! WARNING
Testing for gas leaks with an open flame or other sources of ignition may lead
to a fire or explosion and cause serious injury or death. Test in accordance
with NFPA or local codes.
Figure 2.32 · Flexible Gas Connection End View Ball Valve/Inlet Tap
Stainless Steel Gas Connector
45° 45°
Horizontal
Burner Control Box Remove cap to clean sediment trap
32
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Electrical Requirements
-
Verify that the heater’s voltage (as listed on the rating plate) matches that of your application.
· Heaters operate on 120 volts, 60Hz., single phase. The maximum amperage requirement is 4.8 amps starting current; 1.1 amps running current per heater.
· Observe proper electrical polarity. -
The heater must be grounded in accordance with the National Electrical Code ANSI/NFPA70 (latest edition).
-
Clearance to combustibles must be maintained between electrical apparatus and wiring. See clearance data on page 7.
-
It is recommended that the thermostat be installed on the hot side of a fused supply line and have sufficient amp rating for the heater(s) that it controls.
-
Wiring must not be run above or below the heater or exposed to the radiant output.
· Installations utilizing a 24 volt thermostat require a relay transformer. Figure 2.34.
Figure 2.33 – Field Wiring 120V Connection(s)
L1 Neutral
Heaters on the same vent must share the same thermostat.
T
NOTE: Up to 4 line voltage tube heaters can be wired to most thermostats.
Additional heaters
Ground
120V-60 Hz. Supply
Burner Box
Multiple Burner Box (if applicable)
Figure 2.34 – Field Wiring 24V Thermostat Connection
Common required for thermostats that require constant power.
1/4″ spade terminals required (field supplied)
Common
COM 24V
Burner Control Box w/ 24VAO
W
COM 24V
Burner Control Box
w/ 24VAO
R
–
24V
24V Digital Thermostat
120 V
COM 24V
Burner Control Box w/ 24VAO
External
L1
Transformer (field suppied)
120 Volt Power (Observe polarity) N
33
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Internal Wiring Diagrams
If any of the original wire as supplied with this appliance must be replaced,
it must be replaced with wiring material having a temperature rating of at
least 105°C.
Figure 2.35 · Ladder Diagram: Mark 17DU-117 with Lights
L1 120VAC
N
BK
Blower
BK
BK
Indicator Lights
BK
BK
BK
BK
Gas Valve
Pressure Switch
BK
Ignitor
BK W
BR
Flame Rod
PROBE SIC1 LINE1 TH NEUT VALVE NEUT GND
O
BK
R
W
G
Ignition Module
Figure 2.36 · Block Diagram: Mark 17DU-117 with Lights
Terminal
Block
BK
O
BK BK BK
L1 120VAC
N
Pressure Switch
BK
BK
Indicator Lights
BK
BK
BK
W
W R W
G
W
Burner
Ignitor
Flame Rod
BK BR
Probe SIC1 Line1 TH Neutral Valve Neutral
Ground
Ignition Module
W
Blower
Gas Valve
34
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Operation
! WARNING
This heater is not equipped with a pilot ignition system.
Do not attempt to light the system manually.
LIGHTING PROCEDURES:
1. Verify that service lid is secured.
2. Open (turn on) gas supply to the heater.
3. Close (turn on) electrical circuit (typically thermostat).
4. If the heater fails to light, turn off gas, open electrical circuit (set
thermostat to lowest setting or to off). Wait five (5) minutes before
repeating above steps.
SHUTDOWN PROCEDURES:
1. Open (turn off) electrical circuit.
2. Close (turn off) gas supply to the heater.
3. Wait five (5) minutes before relighting heater.
Sequence of Operation
Starting Circuit
Upon a call for heat, the fan is energized. Once operational static pressure
is achieved, the differential switch will close initiating the ignition
sequence. After a 5-second delay, the hot surface igniter is energized for 45
seconds and the control allows the gas valve to open.
The trial for ignition is 8 seconds. If flame sense is not established within
8.5 seconds, the heater will attempt two (2) additional ignition sequences
before proceeding to soft lockout. Soft lockout automatically retries after
one (1) hour or the control can be reset by briefly interrupting the power
source.
Running Circuit
After ignition, the flame rod monitors the burner flame. If sense of flame is
lost, the control immediately acts to reignite the gas-air mixture (identical
to the starting sequence). If flame sense is not established within 8.5
seconds, the heater will attempt two (2) additional ignition sequences before
proceeding to soft lockout. The control can be reset by briefly interrupting
the power source.
35
t
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Routine Inspection
! WARNING
Personal injury or death may result if maintenance is not performed by
properly trained gas installer or service personnel. Contact the installing
distributor or place of purchase for service. Do not operate heating system if
repairs are necessary.
! WARNING
Allow heater to cool prior to servicing.
! WARNING
Disconnect power to heater before servicing.
! WARNING
Use protective glasses when cleaning the heater.
At least once per year, the heating system should be inspected and serviced by
trained gas installation and service personnel only. This inspection should be
performed at the beginning of the heating season to insure that all heater
components are in proper working order and that the heating system operates at
peak performance. Particular attention should be paid to the following items.
· Blower Motor: Annual oiling of the blower motor with SAE 20 oil will extend
bearing life significantly. Ensure that the squirrel cage in the blower is
kept clean. If dirt becomes a problem, installation of outside air intake
ducts for combustion is recommended.
· Vent pipe system: Check the outside termination and the connections at the
heater. Inspect the vent exhausts for leakage, damage, fatigue, corrosion and
obstructions. If dirt becomes a problem, installation of outside air intake
ducts for combustion is recommended.
· Combustion air intake system (when applicable): Check for blockage and/or
leakage. Check the outside termination and the connection at the heater.
- Heat exchangers: Check the integrity of the heat exchangers. Replace if there are signs of structural failure. Check for corrosion and/or buildup within the tube exchanger passageways.
· Burner: Check for proper ignition, burner flame and flame sense. Flame should extend directly outward from burner without floating or lifting.
· Wiring: Check electrical connections for tightness and/or corrosion. Check wires for damage.
· Gas Connection: Inspect the integrity of the gas connection to the heater. Check for leaks, damage, fatigue or corrosion. Do not operate if repairs are necessary and turn off gas supply to the heater. Contact service personnel.
· Reflectors: To maintain effective infra-red heating, always keep both sides of the reflector clean. Maintenance can vary significantly depending on the environment. Dirt and dust can be vacuumed or wiped with a soap and water solution. Use metal polish if the reflectors are severely dirty.
Contact service personnel if repairs are necessary. Do not operate unit.
36
t
Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Troubleshooting
Symptom
Possible Cause
Thermostat closed, fan doesn’t operate.
- Blown fuse. · Faulty thermostat. · Loose or disconnected wire. · Faulty fan.
Thermostat closed. Fan operates. Switch · Loose or disconnected wire.
does not close.
- Box lid or gasket not in place.
- Plugged pressure switch lines.
Note: If hot surface igniter is
- Plugged or restricted exhaust vent.
energized, the indicator light is faulty. · Baffle location incorrect.
- Faulty pressure switches.
Thermostat closed. Fan operates. Pressure · Faulty hot surface igniter.
switch closes. No hot surface igniter.
- Faulty circuit board.
Thermostat closed. Fan operates. Pressure switch closes. Hot surface igniter energizes. Valve does not open.
- Disconnect gas valve wires. · Faulty circuit board. · Faulty gas valve.
Thermostat closed. Fan and hot surface igniter operate. Ignition occurs, burner cycles off in less than 60 seconds.
- Low gas pressure. · Baffle improperly positioned. · Faulty exhaust pressure switch. · Restricted flue vent. · No electrical ground. · Reversed polarity.
Thermostat closed. Fan and hot surface igniter operate. After 45 seconds hot surface igniter shuts off. No ignition.
- Closed gas supply. · Dirty or restricted orifice. · Faulty valve. Disconnected wire. · Inlet pressure exceeds 14 Inches W.C.
Loss of heater efficiency.
- Low gas pressure. · Dirty or restricted orifice. · Foreign matter inside burner. · Unit cycles on and off. · Reflector is dirty or not in place. · Clogged fan blower.
Radiant tube leaking burnt gases.
- Loose tube connections.
Condensation.
Tube bowing.
Tube corroding. Visual inspection of burner operation not possible. Stack
sooting.
Odor or fumes in space (normal during first firing and will subside after
initial burn off, approximately 20 minutes).
- Holes or cracks in radiant tubes.
· Stack length is too long. · Light gauge flue stack used. · Contaminated combustion air.
· Insufficient combustion air. · Over fired. · Contaminated combustion air. · Heater unable to expand properly. · Contaminated combustion air. · Dirty or sooted sight glass. · Unit mounted upside-down.
· Insufficient combustion air. · Improper gas. · Dirty fan or blockage.
· Vaporized solvents decomposing when contacting radiant tubes.
· Evaporation of oils, solvents at floor level. · Fork lifts. · Loose tube / vent connections.
Corrective Action
· Replace. · Replace. · Repair as required. · Lubricate, repair or replace. ·
Repair as required. · Put in place. · Clean as necessary. · Remove foreign
matter. · Re-position baffles at vent end. · Replace only. Do not adjust.
· Replace. · Replace. · Repair as required. · Replace. · Replace. · Provide
required gas pressure. · Re-position baffle at vent end. · Replace. · Remove
foreign matter. · Connect electrical ground to junction box. · Repair. · Open
all gas connections. · Remove. Clean with a soft object. · Replace or repair.
· Lower inlet pressure. · Provide required gas pressure. · Remove. Clean with
a soft object. · Clean as necessary. · Check previous symptom. · Clean with
aluminum cleaner and soft cloth. · Clean. · Ensure that tubes are fully
connected
and clamped properly. · Replace.
· Shorten stack length. · Minimum of 26 ga. vent pipe required. · Provide
fresh air inlet duct.
· Provide 1 sq. in. of free air for every 5,000 BTU/H of input. · Check gas
pressure and orifice size. · Provide fresh air inlet duct. · Remount with
flexible inlet or vent pipe. · Provide fresh air inlet duct. · Remove, clean
or replace. · Mount correctly. · Provide 1 sq. in. of free air for every
5,000 BTU/H of input. · Correct with proper gas input (or clean). · Provide
proper ventilation.
· Provide proper ventilation. · Tighten tube clamps to 50-100 ft-lb. · Seal
vent pipes.
37
t
Dayton Installation, Operation, Maintenance and Parts Manual
For Repair Parts, call 1-800-323-0620
24 hours a day – 365 days a year
Please provide following information: -Model number -Serial number (if any)
-Part description and number as shown in parts list
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
26 13
38
t
30
15
24
47
64
59
34
54, 55
1
12
41
58
8
38
11 9
14 21
15, 16 14
20 65
66
63 62
22 17
10 46
68
61
48
2
45 67
40
19
49 50 44
5
3
23
17
4
35
7
51
6
43
18
39
28 27
25
52, 53 42
36, 37 60
Repair Parts Illustration for Dayton Tube Heater
Dayton Installation, Operation, Maintenance and Parts Manual
Repair Parts List for Dayton Tube Heater
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
39
t
Ref. Description No.
Part No. Quantity
1
Control Box Cover
TP-1
1
2
Flange Gasket
TP-5
1
3
Conduit Coupling
TP-9
1
4
Conduit 4″ x 1/2″
TP-10
1
5
Hot Surface Igniter Box
TP-11
1
6
Hot Surface Igniter Box Cover
TP-12
1
7
8 x 1/2″ Self-drilling Screw
TP-13
4
8
Sight Glass Gasket
TP-14
1
9
Sight Glass
TP-15
1
10
Sight Glass Washer
TP-16
1
11
Sight Glass Kit
TP-17
1
12
4″ Wire Hanger with Tension Spring
TP-19B
3-7
13
120″ Aluminum Reflector
TP-20C
2-6
14
4″ Standard Tube Clamp
TP-21B
2-6
15
120″ ALUM Combustion/Radiant Tube TP-26A
1-5
16
120″ AL-TI Combustion Tube
TP-26B
1
17
Control Box Mounting Bracket
TP-31B
2
18
1/2″ Shut-off Ball Valve/ Inlet Tap
TP-33B
1
19
Silcone Carbide Hot Surface Igniter
TP-50
1
20
Fan Blower
TP-55A
1
21
36″ Interlocking Heat Baffle
TP-65I
2-5
22
2″ x 4″ Outlet Box
TP-66
1
23
2″ x 4″ Outlet Box Cover
TP-67
1
24
Control Box Gasket (per foot)
TP-70
6
25
Rubber Grommet
TP-76
1
26
Reflector Center Support
TP-82
2-6
27
Stainless Steel Flexible Gas Connector TP-83
1
28
1/2″ Female/Male Flare Fitting
TP-84
1
29
1/4″ x 1/4″ Brass Atmos. Barb Fitting TP-97
1
30
Aluminum Reflector End Cap
TP-105
2
31
Reflector End Cap Clip (pkg. of 8)
TP-106
1
32
60″ ALUM Radiant Tube w/ Tube Clamp TP-111
1
33
60″ Aluminum Reflector
TP-112
1
34
Reflector Tension Spring
TP-113
1
Ref. Description
No.
35
Plastic Air Orifice w/ Screen – Consult Factory
36
Burner (50-100 MBH models)
37
Burner (125-200 MBH models)
38
16″ Burner Tube w/ Flange (fittings included)
39
Gas Orifice – Consult Factory
40
Hot Surface Igniter Holder
41
Pressure Switch Mounting Bracket
42
Gas Valve Mounting Bracket
43
1/2″ x 3″ Pipe Nipple
44
Hot Surface igniter Wiring Harness
45
Pressure Switch Barb
46
Vinyl Pressure Sensing Tube (exhaust)
47
Vinyl Pressure Sensing Tube (burner)
48
Hot Surface Igniter Holder Gasket
49
Flame Rod
50
Flame Rod Wire
51
Gas Manifold
52
Gas Valve Assembly – Natural Gas
53
Gas Valve Assembly – Propane Gas
54
Differential Pressure Switch (50-100 MBH)
55
Differential Pressure Switch (125-150 MBH)
56
Differential Pressure Switch (175 MBH)
57
Differential Pressure Switch (200 MBH)
58
Divider Panel w/ Pressure Switch Mtg. Tabs
59
Left End Panel with Light Holes
60
Right End Panel
61
Ignition Plate Gasket
62
120V Amber Operational Indicator Light
63
1/4″ Neutral Terminal Block
64
Green Self-tap Screw
65
Potted Circuit Board
66
Circuit Board Wiring Harness
67
Hot Surface Igniter Plate
68
Burner Control Box Outer Shell
- Conversions from natural gas to LP gas require the use of one TP-241 and one TP-204-Size and TP-114-Size. · Conversions from LP gas to Natural gas require the use of one TP-240 and one TP-204-Size and TP-114-Size. · Conversions between different BTU’s sizes are not allowed.
Part No.
TP-114 TP-200A TP-201B TP-380 TP-204 TP-205 TP-207 TP-208B TP-212 TP-214
TP-217 TP-218 TP-219 TP-221 TP-222 TP-222A TP-223 TP-240 TP-241 TP-264B TP-
264E TP-264D TP-264F TP-301 TP-302 TP-303 TP-321 TP-328 TP-329 TP-331 TP-351A
TP-352A TP-383 TP-804
Quantity
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
Dayton Installation, Operation, Maintenance and Parts Manual
7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
Dayton® Tube Heaters
Limited Warranty
Dayton One-Year Limited Warranty. Dayton Radiant Tube Heaters, Models 7D837A
thru 7D849A, 7D851A, 7AR79 thru 7AR88 covered in this manual, are warranted by
Dayton Electric Mfg. Co. (Dayton) to the original user against defects in
workmanship or materials under normal use for one year after date of purchase.
Any part which is determined to be defective in material or workmanship and
returned to an authorized service location, as Dayton designates, shipping
costs prepaid, will be, as the exclusive remedy, repaired or replaced at
Dayton’s option. For limited warranty claim procedures, see PROMPT DISPOSITION
below. This limited warranty gives purchasers specific legal rights which vary
from jurisdiction to jurisdiction.
Additional Limited Warranty. In addition to the above mentioned one-year
warranty, Dayton warrants the original purchaser an additional 4-year
extension on the combustion chamber, radiant tubes and stainless steel burner.
This 4-year extension excludes electrical/purchased components.
General Conditions. Dayton will not be responsible for labor charges for the
analysis of a defective condition of the heater or for the installation of
replacement parts. The warranties provided herein will not apply if the input
of the heater exceeds the rated input at time of manufacturing or if the
heater in the judgement of the Company has been subjected to misuse, excessive
dust, improper conversion, negligence, accident, corrosive atmospheres,
excessive thermal shock, excessive vibration, physical damage to the heater,
alterations by unauthorized service personnel, operation contrary to Dayton’s
instructions or if the serial number has been altered, defaced or removed.
Dayton shall not be liable for any default or delay in the performance of
these warranties caused by contingency beyond its control, including war,
government restriction or restraints, strikes, fire, flood, short or reduced
supply of raw materials, or parts. The warranties herein shall be null and
void if the heater is not installed by a competent heating contractor and/ or
if the heater is not installed according to Dayton’s instructions, normal
industry practices and/or if the heater is not maintained and repaired
according to Dayton’s instructions. Normal product degradation and wear (rust,
oxidation, etc.) does not constitute a material defect and applicable warranty
claim.
Limitation of Liability. To the extent allowable under applicable law,
Dayton’s liability for consequential and incidental damages is expressly
disclaimed. Dayton’s liability in all events is limited to and shall not
exceed the purchase price paid.
Warranty Disclaimer. Dayton has made a diligent effort to provide product
information and illustrate the products in this literature accurately;
however, such information and illustrations are for the sole purpose of
identification, and do not express or imply a warranty that the products are
merchantable, or fit for a particular purpose, or that the products will
necessarily conform to the illustrations or descriptions. Except as provided
below, no warranty or affirmation of fact, expressed or implied, other than as
stated in the “LIMITED WARRANTY” above is made or authorized by Dayton.
Product Suitability. Many jurisdictions have codes and regulations governing
sales, construction, installation, and/or use of products for certain
purposes, which may vary from those in neighboring areas. While Dayton
attempts to assure that its products comply with as many codes, it cannot
guarantee compliance, and cannot be responsible for how the product is
installed or used. Before purchase and use of a product, review the product
applications, and all applicable national and local codes and regulations, and
be sure that the product, installation, and use will comply with them.
Certain aspects of disclaimers are not applicable to consumer products: e.g.,
(a) some jurisdictions do not allow the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply
to you: (b) also, some jurisdictions do not allow a limitation on how long an
implied warranty lasts, consequently the above limitation may not apply to
you: and (c) by law, during the period of this limited warranty, any implied
warranties of implied merchantability or fitness for a particular purpose
applicable to consumer products purchased by consumers, may not be excluded or
otherwise disclaimed.
Prompt Disposition. Dayton will make a good faith effort for prompt correction
or other adjustment with respect to any product which proves to be defective
within limited warranty. For any product believed to be defective within
limited warranty, first write or call dealer from whom the product was
purchased. Dealer will give additional directions. If unable to resolve
satisfactorily, write to Dayton at address below, giving dealer’s name,
address, date and number of dealer’s invoice, and describe the nature of the
defect. Title and risk of loss pass to buyer on delivery to common carrier. If
product was damaged in transit to you, file claim with carrier.
Manufactured for Dayton Electric Mfg. Co., 5959 W. Howard St., Niles, Illinois
60714 U.S.A.
Manufactured for Dayton Electric Mfg. Co. Niles, Illinois 60714 U.S.A.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>