Honker EZ1X Temperature Controller User Manual
- June 17, 2024
- Honker
Table of Contents
EZ1X TEMPERATURE CONTROLLER
USER MANUALEZ11RXC EZ12RXC
EZ12DRXC
Please read this manual before using the product.
DIMENSIONS AND CUT OUT
Installation Precautions
- Do not place the equipment near heat sources, strong magnetic equipment, or in places exposed to direct sunlight, rain, humidity, dust, or mechanical vibration.
CONNECTIONS
Note (1): The second relay;
Note (2): The second probe;
FRONT PANEL AND COMMANDS
Set key | Set
- Press and release to enter the interface for changing the setpoint;
- Press and hold for 3 seconds to enter the manger parameter interface;
- Switch menu and parameter interface;
OK/Defrost key |
- View the temperature of the second probe;
- Save the parameters and exit;
- Press and hold this key for 3 seconds to start/terminate defrosting;
Up/Light key |
- Scrolled up the values or parameters;
- Turn on or turn off the lights (only valid for EZ12 series and Pr=2);
Down key |
- Scrolled down the values or parameters;
Combination key | Set +
- In power-on mode, press and hold the set key and the OK/defrost key for 3 seconds, the controller enters the standby mode;
- In standby mode, press and hold the set key and the OK /defrost key for 3 seconds, the controller restarts.
Danger: Before performing any type of maintenance, cut off the electrical connection,Do not maintain in standby mode to avoid electric shock!
Change setpoint
Change other parameters(manager parameters)
Note(1): In the process of changing the shutdown temperature or changing
other parameters, if there is no key operation for more than 15 seconds, the
controller will automatically save the value and exit ;
Note(2): The default password is 55 ;
PARAMETERS
| No.| Label| Default| Description| Range
---|---|---|---|---|---
0| SP| 4℃| Set point| r1~r2
1| Pd| 0| Password input (1)| 0~255
| 2| P1| 0.0℃| First probe calibration (2)| -10.0℃(-20℉)~10.0℃(20℉)
3| P2| 0.0℃| Second probe calibration (2)| -10.0℃(-20℉)~10.0℃(20℉)
4| PP| 1| Second probe function| 0: disable 1:Evap. 2:Cond.
5| Pr| 0| Second relay function (3)| 0:defrost 1:fan 2:light
6| Pu| 1| Temperature unit (4)| 0:℉ 1:℃
7| Pt| 0| Display delay (5)| 0~90(unit:10s), 0:disable
| 8| P7| 1| Set point unlock (6)| 0:disable 1:enable
9| POF| 1| Standby mode function| 0:disable 1:enable
10| PAS| 55| Password setting| 0~255, 0:no password
| 11| rd| 4.0℃| Differential| 0.5℃(1℉)~10.0℃(20℉)
12| r1| -2℃| Minimum Set point| -50℃(-58℉)~St
13| r2| 8℃| Maximum Set point| St~85℃(185℉)
| 14| c1| 0| minimum compressor off time| 0~30 min
15| cF| 1| Comp. operating mode with faulty probe| 0:always Off
1:ON-OFF as prog. c4/c5
16| c4| 10| Comp. Off time with faulty probe| 5~60 min
17| c5| 20| Comp. On time with faulty probe| 5~60 min
| 18| di| 2| Interval between def. cycles (7)| 0~90 h, 0:defrost
19| dt| 12℃| Defrost termination temp. (8)| 0 ℃(32 ℉)~50 ℃(122 ℉)
20| dP| 30| Maximum length for defrost (8)| 1~90 min
| 21| F0| 0| Fan operating mode| 0:continuous mode
1:continuous mode,Off during def.
2:runs with comp.,On during def.
3:runs with comp.,Off during def.
| 22| A1| -10℃| Minimum temperature alarm| -50℃(-58℉)~A6
23| A2| 30℃| Maximum temperature alarm| A5~85℃(185℉)
24| Ad| 180| Temperature alarm delay| 0~240 min
| 25| cdH| 58℃| Condenser High temp. alarm| 30℃(86℉)~90℃(194℉)
26| cdP| 70℃| Condenser High temp. protect| 30℃(86℉)~90℃(194℉)
27| cdd| 5℃| Cond. High temp. differential| 1℃(2℉)~15℃(30℉)
Note (1): The Default password is 55, and the user can cancel or modify
the password through the parameter PAS;
Note (2): Display temperature = cabinet temperature probe temperature +
first probe calibration P1, the display temperature is also used for
compressor ON-OFF control;
Note (3): This parameter is only valid for the product model (EZ12/EZ12D
series) that supports the second relay (10A relay in the wiring diagram);
Note (4): If you need to change the temperature unit, all you need to do
is change the Pu parameter and save it. The controller automatically converts
the corresponding temperature parameter;
Note (5): When the cabinet temperature rises, the cabinet temperature
display needs to delay Pt time every time 1℃ or 1℉ is updated (if Pt=2, the
delay time is 20 seconds);
Note (6): If P7=0, it is not allowed to adjust the set point; if POF=0,
it is forbidden to enter the standby mode;
Note (7): The defrost time interval refers to the interval between the
end of the last defrost and the start of the next defrost;
Note (8): At the beginning of defrosting, if the temperature of the
evaporator probe (if second probe and PP=1) ≥ the defrosting termination
temperature dt, the defrosting will not be performed this time;
During the defrosting process, if the evaporator probe temperature ≥ defrost
termination temperature dt, the defrosting will be terminated ;
If the defrosting process lasts for the longest defrosting time dP, the
temperature of the evaporator probe is still smaller than the defrost
termination temp. the defrosting is terminated;
If the evaporator probe is not activated (PP=0 or 2) or malfunction (E2), the
dt parameter is invalid, and each defrost is executed according to Maximum
length for defrost;
Note (9): Parameter modification will not be notified.
ALARM SIGNALLING
Code| Description| Alarm activation conditions| Alarm
release conditions
---|---|---|---
E1| Cabinet probe fault| Wrong probe is used or the probe is disconnect ted or
short-circuited| Use the correct type of probe and connect correctly and
reliably
E2| Evap. probe fault
E3| Cond. probe fault
rH| High temp. alarm| Cabinet probe temp.≥A2 last longer than Ad time| Cabinet
probe temp.<A2
rL| Low temp. alarm| Cabinet probe temp.≤A1 last longer than Ad time| Cabinet
probe temp.>A1
cH| Cond. high temp. alarm| Cond. probe temp.≥cdH last longer than 30 mins|
Cond. probe temp.≤ cdH-cdd
cP| Cond. high temp. protections| Cond. probe temp.≥cdP| Cond. probe temp.≤
cdP-cdd last longer than 15 mins
dEF| Defrost is progress| /| /
Loc| Set point lock| Attemp to modify the setpoint when P7=0| Disappear
automatically
rSt| Parameters reset successfully| /| /
Note (1): If the second probe is not connected, but the parameter PP is
set to 1 (evaporator) or 2 (condenser), the E2 fault code (evaporator probe
fault) or E3 fault code (condenser probe) will appear. At this time, you only
need to set the parameter PP to 0 to solve the fault;
Note (2): When the condenser high temperature alarms, only the fault code
cH is displayed, and the output is not affected. The fault code will be
automatically cleared after meeting the alarm release conditions;
Note (3): In addition to displaying the fault code cP when the condenser
is under high temperature protection, the compressor, defrost heating wire,
and fan are forced to shut down; the compressor, defrost heating wire, and fan
return to normal control after meeting the fault removal conditions. But the
fault code cP cannot be cleared automatically, it can only be cleared by a)
powering off and then powering on the controller or b) first entering standby
mode and then powering on.
TECHNICAL DATA
Material| Front panel: PC
Housing: ABS (UL94-V0)
Waterproof cover: ABS (optional) (UL94-V0)
---|---
Dimensions| Front panel 77.5×34.0mm
Installation size| 71×29mm
Protection| Frontal IP64
Power supply| 220VAC±10%,50/60Hz(EZ1xx2 series)
or 110VAC±10%,50/60Hz(EZ1xx1 series)
or 12VAC/VDC±5%(EZ1xx12 series)
Power consumption| 3.0VA max
Display mode| three-digit digital tube (red/white/blue optional)
Resolution| 0.1℃
measurement range| -50℃~90℃
measurement accuracy| -40℃~50℃ ±1℃, the rest ±2℃
Input signal| 2 NTC temperature probes
Relay| Compressor relay: 30A/240VAC normally open output, can directly drive
single-phase 1.5HP compressor
The second relay: 10A/240VAC normally open output (can be configured by Pr
parameter used as a defrost heater, fan or light relay)
Operating temperature| 0℃~55℃
Storage temperature| -25℃~75℃
Relative humidity| 20%~85%(no condensation)
EZ1X User Manual
Code M03C200726
JUL 26th,2020 Ver1.02