UTE 3500 Electronic Temperature Controllers
Product Information
Specifications
-
Model: UTE 3500, UTE 3800-U
-
Area of Use: Control the floor and room temperature in
water-based and electric heating systems -
Mounting: Non-conductive (plastic) flush-mounting boxes
only -
Indicator LEDs: Yes
Product Usage Instructions
Electrical Connection
- Important! Disconnect the electric circuit from the mains.
- Connect the Powermodule according to the circuit diagram (see bottom of housing or circuit diagram in these instructions). Note the mounting direction of the power module in the box (arrow pointing upwards).
- Mount the cover frame with the decorative frame holder on the power module.
- Mount the logic module to the Decorative Frame Holder.
Wiring Diagram
Refer to the wiring diagram below:
UTE 3500
L N
1 A
L
ry N
H/C >
limina UTE 3800-U Pre 16 A
Actuator NC / NO
Setback Input / Presence Input
The function of the universal input can be defined in the installer settings (default: setback input). If the setback input is energized (230 VAC), the thermostat switches to unoccupied mode. If the presence input is energized (230 VAC), it means that the thermostat switches to occupied mode.
Presets
Depending on the variant, the default preset values are:
- Heating: 21°C
- Cooling: 19°C
Operation in Normal Mode
Visual Feedback:
- Locked: The device is locked
- Unlocked: The device is unlocked
Menu Item Setpoint: Change occupied setpoint
Child Lock: Lock / Unlock – Press and hold [+] and [-] button for 5 seconds to unlock
User Menu
To access the user menu, press and hold the [-] and [O] buttons simultaneously for 3 seconds. The WiFi LED lights up yellow. The following settings can be made:
Preliminary
Installer Settings
Installer Menu (Level 1): Depending on the respective heating application, preset values and functions can be selected at menu level 1. Press and hold [+] and [O] buttons simultaneously for 5 seconds to access the menu. Enter code: 19. The WiFi LED lights up purple.
Menu item: Heating application
- UTE 3500: P2 Hydronic Underfloor Heating – Room
- UTE 3800-U: P4 Blow Convector – Room, P5 Electrical Radiator, Infrared – Room
FAQ
Can this product be used with electric heating systems?
Yes, the UTE 3500 and UTE 3800-U are suitable for water-based and electric heating systems.
How do I unlock the device?
Press and hold [+] and [-] buttons for 5 seconds to unlock the device.
How do I access the installer menu?
Press and hold [+] and [O] buttons simultaneously for 5 seconds, enter code: 19.
Can I dispose of this product with household waste?
No, please recycle the product where facilities for electronic waste exist. Check with your local authorities for recycling advice.
Important!
- The device may only be opened by an electrically skilled person and must be installed as shown on the circuit diagram on the device and in these instructions. The existing safety regulations must be followed. The relevant installation measures must be taken to achieve the requirements of protection class II.
- This independently mountable electronic device is used to control the temperature in dry and enclosed rooms only, with normal environment. This device conforms to EN 60730, it operates according to type 1Y (UTE 3500) and 1B (UTE 3800-U).
Area of use
The electronic temperature controllers UTE 3500 and UTE 3800-U can be used to control the floor and room temperature. They are suitable for water-based and electric heating systems.
Installation Environment
- The thermostat should be mounted in a place in the room that is easy to access for operation.
- Mounting height: approx. 1.5 m above the floor.
- Preference should be given to installation on an internal wall. Avoid external walls and draughts from windows and doors.
- Ensure that the room’s normal convection air reaches the thermostat freely without restriction. The thermostat should therefore not be mounted inside shelf units or behind curtains and similar coverings.
- Extraneous heat has a negative influence on the control accuracy.
- Direct sunshine, proximity to televisions, radios and heaters, lamps, stoves and heating pipes must be avoided.
- Install in flush-mounting box 60mm
Electrical Connection
Important!
Disconnect the electric circuit from the mains
Connection in the following steps:
- Connect the Powermodule according to the circuit diagram (see bottom of housing or circuit diagram in these instructions.) Note the mounting direction of the power module in the box (arrow pointing upwards)
- Mount the cover frame with the decorative frame holder on the power module
- Mount the logic module to the Decorative Frame Holder
Important!
Mount in non-conductive (plastic) flush-mounting boxes only.
Wiring Diagram
UTE 3500
UTE 3800-U
Caution!
Risk of fatal injury, due to electric shock. The appliance is not a safety
extra-low voltage device (SELV). The sensor cables are connected to 230 V AC
mains voltage. Only use sensors with insulated cables. Failure to do so may
result in serious injury or death.
Presets (depending on variant)
Selection after the first start or inside the menu:
- P2: Hydronic Underfloor Heating – Room
- P3: Hydronic Radiator – Room
- P4: Blow Convector – Room
- P5: Electrical Radiator, Infrared – Room
- P6: Hydronic Underfloor Heating – Limiter
- P7: Electrical Underfloor Heating – Floor
- P8: Electrical Underfloor Heating – Limiter
Technical data
Actuator NC / NO
Via the installer menu it can be adjusted whether the thermostat controls the
actuators normally closed (NC) or normally open (NO). The preset is normally
closed (NC).
Setback Input / Presence Input
The function of the universal input can be defined in the installer settings
(default: setback input). If the setback input is energized (230 VAC) the
thermostat switches to unoccupied mode. If the Presence input is energized
(230 VAC), it means that the thermostat switches to occupied mode.
Heating / Cooling input
H/C-terminal connected to voltage means cooling mode, not connected means
heating mode. In case of cable used longer than 100m an anti-interference
capacitor (Merten 542895 Capacitor 230 VAC 0,33µF or comparable) between
control line H/C and neutral line N can be installed at any position to avoid
a malfunction.
Dimensions
This product should not be disposed of with household waste. Please recycle the products where facilities for electronic waste exist. Check with your local authorities for recycling advice.
Part Overview
Operation in normal mode
Visual Feedback| Menu Item| Functional description| Options
and display of dot matrix LEDs| Default values| UTE 3500| UTE
3800-U
---|---|---|---|---|---|---
| ****
Setpoint
| ****
Change occupied setpoint
| min. setpoint – max. setpoint in °C [+] or [-] Button (Settable range limits adjustable via user menu)| Heating: 21
Cooling: 19
| ****
•
| ****
•
Locked Unlocked| ****
Child Lock
| ****
Lock / Unlock
| ****
Press and hold [+] and [-]
button for 5 sec
| ****
Unlocked
| ****
•
| ****
•
User menu
- To access the user menu, press and hold the [-] and [O] buttons simultaneously for 3 seconds.
- The WiFi LED lights up yellow.
- The following settings can be made:
Installer Settings
Installer Menu (Level 1):
Depending on the respective heating application, preset values and functions
can be selected at menu level 1.
Press and hold [+] und [O] buttons simultaneously for 5 seconds to access the
menu.
Enter code: 19
The WiFi-LED lights up purple.
Menu item | Heating application | UTE 3500 | UTE 3800-U |
---|---|---|---|
P2 | Hydronic Underfloor Heating – Room | • | – |
P3 | Hydronic Radiator – Room | • | – |
P4 | Blow Convector – Room | • | • |
P5 | Electrical Radiator, Infrared – Room | • | • |
P6 | Hydronic Underfloor Heating – Limiter | – | • |
P7 | Electrical Underfloor Heating – Floor | – | • |
P8 | Electrical Underfloor Heating – Limiter | – | • |
99
| Ex-factory reset
no: Cancel and go back
Yes: Yes and hold [O] for 3 seconds: confirm
|
•
|
•
Overview of set values for selected preset
| Function description| P2| P3| P4| P5| P6|
P7| P8
---|---|---|---|---|---|---|---|---
01| Floor Probe Type in kΩ (UTE 3800-U
only)
| –| –| 00 (Not
fitted)
| 00 (Not
fitted)
| 33| 33| 33
02| Min Floor limit in °C (UTE 3800-U only)| –| –| 10| 10| 10| 10| 10
03| Max Floor limit in °C (UTE 3800-U only)| –| –| 40| 40| 40| 40| 40
04| Control Method| PWM 20 Min| PWM 10 Min| 2-pt (ON/OFF)
0,5 K
| 2-pt (ON/OFF)
0,5 K
| PWM 20 Min| PWM 20 Min| 2-pt (ON/OFF)
0,5 K
05| 2-pt min On/Off Time| –| –| 02| 02| –| –| 02
06| Application Type (Control sensor)| Room control| Room control| Room
control| Room control| Room control with
floor limit
| Floor control| Room control with
floor limit
07| Actuator Type| Normally closed
valve
| Normally closed valve| Normally closed
valve
| Normally closed
valve
| –| –| –
08| Universal Input Configuration| Setback| Setback| Setback| Setback|
Setback| Setback| Setback
09| Cool Input Configuration (UTE 3500 only)| On| On| On| On| –| –| –
10| Occupancy – Switch to
unoccupied delay (min)
| 10| 10| 10| 10| 10| 10| 10
11| Occupancy – Switch to occupied
delay (sec)
| 60| 60| 60| 60| 60| 60| 60
12| Valve Protection| On| Off| Off| Off| On| Off| Off
13| Valve Protection – Maximum Idle Time| 14| 14| –| –| 14| –| –
14| Valve Protection – AntiIdle Exercise Time| 03| 03| –| –| 03| –| –
15| Temporal Limit acc to EN50559 (UTE
3800-U floor control only)
| –| –| Off| Off| Off| On| On
16| Window open detection| Off| Off| Off| Off| Off| Off| Off
17| Window open detection – Threshold
(in 0.1°C steps)
| 02| 02| 02| 02| 02| 02| 02
18| Windows open detection – Event
Duration (in Min)
| 20| 20| 20| 20| 20| 20| 20
19| Windows open detection – Guard
Period (in Min)
| 02| 02| 02| 02| 02| 02| 02
Installer menu (Level 2):
For advanced settings of individual menu items after preset selection
Press and hold the [+] and [O] buttons simultaneously for 3 seconds. The WiFi
LED lights up purple.
Enter code: 32
Menu options: See next page
Error Codes
- E1 = Room sensor error
- E2 = Floor sensor error
Matter WiFi Configuration
The thermostat can be connected to smart home apps and the respective controllers/hubs from Apple, Google, Amazon and Samsung via Matter.
How-to Video
To integrate the thermostat into a Smart Home App and the respective Matter network, scan the QR code on the back of the logic module with a smartphone or type in the Matter provisioning code. Press the [0] button for 5 seconds until the thermostat displave ” ja” for Join Mode. The WiFi I ED lichts un vellow.
If an error occurs during connection, the controller displays “Er” for error:
The WiFi LED lights up red.