IFM O1D106 Optical Distance Sensor User Manual
- June 16, 2024
- ifm
Table of Contents
- IFM O1D106 Optical Distance Sensor
- Safety instructions
- Functions and features
- Functions
- Installation
- Electrical connection
- Operating and display elements
- Menu
- Operating modes
- Parameter setting
- IO-Link
- Set-up / Operation
- Maintenance, repair and disposal
- Factory setting
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
IFM O1D106 Optical Distance Sensor
Preliminary note
Symbols used
Warning signs used
WARNING
Warning of serious personal injury. Death or serious irreversible injuries may result.
Safety instructions
- Please read this document prior to set-up of the unit. Ensure that the product is suitable for your application without any restrictions.
- Improper or non-intended use may lead to malfunctions of the unit or to unwanted effects in your application. That is why installation, electrical connection, set-up, operation and maintenance of the unit must only be carried out by qualified personnel authorized by the machine operator.
- In case of a malfunction of the unit please contact the manufacturer. If the unit is tampered with and/or modified, any liability and warranty is excluded.
WARNING
Visible laser light; laser protection class 2. Use of controls or adjustments other than those specified herein may result in hazardous radiation exposure. Damage to the retina is possible.
- Do not stare into the laser beam!
- Apply the enclosed labels (laser warning) in the immediate vicinity of the unit.
- Adhere to the caution and warning notes on the product label.
- Use the enclosed label for the power supply cable.
- EN/IEC 60825-1 : 2007 and EN/IEC 60825-1 : 2014 complies with 21 CFR 1040 except for deviations pursuant to Laser Notice No. 50, dated June 2007
Label for supply cable
Product label
Functions and features
The unit is used as an optical distance sensor.
Applications
- The optical distance sensor measures distances of 1…75 m on the reflector.
- It has a background suppression at > 75…150 m.
- The measured value is shown in a 10-segment display.
- According to the set output functions, 2 output signals can be generated.
Functions
Output function hysteresis
The hysteresis keeps the switching state of the output stable if the measured value varies about the sensing range. Both outputs (OUT1 and OUT2) can be set as hysteresis function. → 10.2.4 Hysteresis function
Output function window
The window function enables the monitoring of a defined acceptable range. Both outputs (OUT1 and OUT2) can be set as window functions. → 10.2.6 Window function
Analogue output function
The sensor can also output an analogue signal on output 2 (OUT2) which is proportional to the distance. → 10.2.11 Scaling of the measuring range (analogue output)
Switch off the laser
For safety and maintenance purposes the laser of the unit can be temporarily switched off via the input on pin 5.
Input signal at pin 5 | Laser |
---|---|
Low / not connected | On |
High | Off |
Installation
Installation conditions
- Install the unit so that the reflector to be detected is within a measuring range of 1…75 m.
The unambiguity range of the sensor is fixed to 150 m. Reflections within a range
- 75…150 m are suppressed.
Reflectors in the direct beam path of the sensor – also in the range > 150 m – are to be avoided by the customer. Otherwise, the measured values can be ambiguous.
Mounting accessories
The unit is supplied without mounting accessories.
Examples of mounting accessories | Art. no. |
---|---|
Reflector 226 x 262 mm | E21159 |
Protective cover O1D | E21133 |
Mounting set E2D101 + E20938 + E20951 | E21079 |
Mounting set O1D (for rod mounting Ø 12 mm) | E2D101 |
Mounting rod straight Ø 12 mm / M10 | E20938 |
Mounting set O1D (for rod mounting Ø 14 mm) | E2D111 |
Mounting rod straight Ø 14 mm / M12 | E20939 |
Fixture for mounting and fine adjustment of O1D laser units | E1D100 |
Electrical connection
The unit must be connected by a qualified electrician.
- The national and international regulations for the installation of electrical equipment must be adhered to.
- Ensure voltage supply according to EN 50178, SELV, and PELV. O1D106: cULus, Supply Class 2
- Disconnect power.
- Connect the unit as follows:
O1D106 PNP
Core colours of ifm sockets:
- 1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4=BK (black), 5 = GR (grey).
Operation with IO-Link master
The unit is compatible with the IO-Link master port class A (type A).
For operation with IO-Link master port class B (type B) observe the following:
As a standard, the unit is not compatible with master port class B (type B). Pin 2 (OU2) and pin 5 (IN1) are used for manufacturer-specific functions. That means that the main supply voltage of the unit and the additional voltage supply (master port class B on pins 2/5) are not electrically isolated
With the following configurations, the unit can be used with master port class B:
- Connect unit and IO-Link master via 3 wires: Connect pins 1, 3 and 4 of the unit with the IO-Link master (do not connect pins 2 and 5).
- Connect unit and IO-Link master via 4 wires: Deactivate pin 2 (OU2) via
- IO-Link (setting OU2 = “off”) and connect pins 1, 2, 3 and 4 of the unit with the
- IO-Link master (do not connect pin 5).
Operating and display elements
1:| 4 x LED green| Lighting LED = power and set display unit (mm, m, inch)
2:| 4 x LED yellow (two not connected)| Indication of the switching status;
lights, if the corresponding output is switched
3:| 4-digit alphanumeric display| Indication of the measured distance, the
parameters and parameter values
4:| Programming button [SET]| Setting of the parameter values (scrolling by
holding pressed; incrementally by pressing once)
5:| Programming button [MODE/ENTER]| Selection of the parameters and
acknowledgement of the parameter values
Menu
Menu structure
Explanation of the menu
For the factory settings please refer to the end of these instructions (→ 14 Factory setting).
Operating modes
Run mode
The run mode is the normal operating mode. After power on the unit is in the Run mode. It carries out its monitoring function and generates output signals according to the set parameters. The display indicates the current distance, the yellow LEDs signal the switching status of the outputs.
Display mode
Indication of the parameters and the set parameter values.
- Press [MODE/ENTER] briefly.
- The unit goes to the Display mode. Internally it remains in the operating mode. The set parameter values can be read.
- To scroll through the parameters, press [MODE/ENTER] briefly.
- To display the respective parameter value, press [SET] briefly.
- After 15 s the unit returns to the Run mode.
Object reflectivity – orientation value for the signal strength
- Press [SET] in the Run mode.
- The unit displays an orientation value for the signal strength (e.g. +100 means max. signal strength and full repeatability. A lower value, e.g. +020, means decreasing signal strength and restricted repeatability).
Programming mode
Setting the parameter values → 10.1 Parameter setting in general.
Parameter setting
During parameter setting the unit remains internally in the operating mode. It continues its monitoring function with the existing parameters until the change has been finished.
Parameter setting in general
Setting of the parameter value
Select the display unit [Uni] before you define the values for the parameters. In case of subsequent changes of the display unit rounding errors during internal conversion to other units may falsify the set values. 10.2.1 Selection of the display unit
Change from menu level 1 to menu level 2
Electronic lock
The unit can be locked electronically to prevent unintentional settings. On delivery the unit is not locked.
Timeout
If no button is pressed for 15 s during the setting procedure, the unit returns to the Run mode with unchanged values.
Configuration of the basic settings 1
Selection of the display unit
Configuration of OUT1
Hysteresis function
The hysteresis keeps the switching state of the output stable if the measured value varies about the sensing range. In either case set and reset points are symmetrically arranged around the selected switch point [SPx]. The hysteresis is the distance between set and reset points; it is calculated on the basis of the repeatability with a safety factor of 1.5.
Example Hno
- For the output function [Hno] the output switches when the object approaches and when the switch point (A) is reached.
- When the object is removed again, the output does not switch back before the reset point (B) is exceeded.
- The reset point (B) is greater than the set point (A).
When the output function [Hnc] was selected, set and reset point are reversed. The output is switched off when the object approaches. When the object is re- moved, the output switches on.
Switching the status of the outputs
Output function Object distance (D) Output status
[Hno]| D < [SPx]| Closed
D > [SPx]| Open
[Hnc]| D < [SPx]| Open
D > [SPx]| Closed
Example of output function [Hno]
Sampling rate 33 Hz, distance to the object 2 m:
Hysteresis = ± 15 mm (→ 10.3.3 Table repeatability and accuracy) x factor 1.5
= 22.5 mm
- Reset point 2 m + (22.5 mm) = 2.02 m
- Set point 2 m – (22.5 mm) = 1.98 m
Setting of the switch point for hysteresis function OUT1
Window function
It is possible to define a window for the object recognition for each of the two outputs (OUT1 / OUT2).
Switches off when the object is detected
[nSPx] = switch point “near”; [FSPx] = switch point “far”; FE = window
If the measured value is between the switch point “near” [nSPx] and the switch point “far” [FSPx], the output is open (when [OUx] = [Fnc]).
Switches when the object is detected
[nSPx] = switch point “near”; [FSPx] = switch point “far”; FE = window
If the measured value is between the switch point “near” [nSPx] and the switch point “far” [FSPx], the output is closed (when [OUx] = [Fno]).
Switching the status of the outputs
Output function Object distance (D) Output status
**** [Fno]| D < [nSPx]
D > [FSPx]
| Open
[nSPx] < D < [FSPx]| Closed
**** [Fnc]| D < [nSPx]
D > [FSPx]
| Closed
[nSPx] < D < [FSPx]| Open
Both window limit values ([nSPx] and [FSPx]) work with a switching hysteresis
→ 10.2.4 Hysteresis function/example of the output function [Hno].
Setting of the switch points for window function OUT1
Configuration of OUT1
Setting of the switch point for hysteresis function OUT2
Setting of the switch points for window function OUT2
Scaling of the measuring range (analogue output)
Current output 4 … 20 mA
MEW = final value of the measuring range In the set measuring range the output signal is between 4 and 20 mA. Faults are also displayed: Too much light or object too near: 3.5 mA for a rising edge ([ASP] < [AEP]), 20.5 mA for a falling edge ([ASP] > [AEP]). Object too far or no object present: 20.5 mA for a rising edge; 3.5 mA for a falling edge.
Voltage output 0 … 10 V
MEW = final value of the measuring range
In the set measuring range, the output signal is between 0 and 10V.
Teach mode
Setting of the sampling rate
Setting of the repeatability
Table repeatability and accuracy
Values for sampling rate 33 Hz on the reflector
Distance in [m] | Repeatability | Accuracy |
---|---|---|
1….25 | ± 15 mm | ± 35 mm |
30 | ± 15 mm | ± 35 mm |
40 | ± 15 mm | ± 35 mm |
50 | ± 19 mm | ± 39 mm |
60 | ± 27 mm | ± 47 mm |
75 | ± 43 mm | ± 63 mm |
Values for sampling rate 1 Hz on the reflector
Distance in [m] | Repeatability | Accuracy |
---|---|---|
1……75 | ± 15 mm | ± 35 mm |
The values apply at:
- constant ambient conditions (23° C / 960 hPa)
- extraneous light of max. 100 klx
- only after unit is powered up for 10 minutes.
Extended functions
Setting of the time delay for switching outputs
Setting of the fault suppression time for switching outputs / analogue output
With [dFo], the error types “too much light” and “not enough light” are suppressed (→ 12.1 Fault indication).
Reset of all parameters to the factory setting
Display of the software version number
IO-Link
General information
This unit has an IO-Link communication interface which requires an IO-Link-
capable module (IO-Link master) for operation.
The IO-Link interface enables direct access to the sensor values and
parameters and provides the possibility to set the parameters of the unit
during operation. In addition communication is possible via a point-to-point
connection with a USB adapter cable.
You will find more detailed information about IO-Link at www.ifm.com.
Device-specific information
You will find the IODDs necessary for the configuration of the IO-Link device and detailed information about sensor values, diagnostic information and parameters in the overview table at www.ifm.com.
Parameter setting tools
You will find all necessary information about the required IO-Link hardware and software at www.ifm.com.
Extended functions
With IO-Link extended functions and measured data are available.
Teach function
The following teach functions are available:
- Teach on background
- Two-point teaching
The teaching functions are described in detail in the IODD.
Set-up / Operation
- After mounting, wiring and programming check whether the unit operates correctly.
- If the unit has been correctly set up, the distance to the object is indicated.
A lifetime of a laser diode: 50000 hours
Fault indication
Display| Possible cause| Switching output| Current
output/voltage output| IO-Link process value distance 3)
---|---|---|---|---
[Hno]| [Hnc]| [Fno]| [Fnc]| [ASP] < [AEP]|
[ASP] > [AEP]
[++]
| too much light,
eg reflective surface
| ****
ON
| ****
OFF
| ****
OFF
| ****
ON
| ****
3,5 mA /
0 V
| ****
20,5 mA /
10 V
| ****
NoData
[- -]| too little light, no object| OFF| ON| OFF| ON| 20,5 mA / 10 V| 3,5 mA /
0 V
| NoData
[nEAr]
| object to be measured outside the measuring range < 0 2 m| ****
ON
| ****
OFF
| ****
OFF
| ****
ON
| ****
3,5 mA /
0 V
| ****
20,5 mA /
10 V
| ****
UL
[FAr]
| object to be measured outside the measuring range > 3 5 m| ****
OFF
| ****
ON
| ****
OFF
| ****
ON
| ****
20,5 mA / 10 V
| ****
3,5 mA /
0 V
| ****
OL
[Errp]
| plausibility (e gobject too fast)| ****
X1)
| ****
X1)
| ****
X1)
| ****
X1)
| ****
X1)
| ****
X1)
| ****
X1)
[LoFF]| laser switched
off
| OFF| ON| OFF| ON| 20,5 mA / 10 V| 3,5 mA /
0 V
| NoData
[SC1]| short circuit in switching output 1| 2)| 2)| n a
[SC2]| short circuit in switching output 2| 2)| 2)| X1)
[SC]| short circuit in all switching outputs| | | n.a
- unchanged
- [SC1] or [SC] only active, if output 2 is configured as switching output.
- See IODD of the device 26
Maintenance, repair and disposal
Faulty sensors must only be repaired by the manufacturer.
- Keep the front lens of the sensor free from soiling.
- After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations.
Factory setting
- Technical data and further information at www.ifm.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>