Williams 2509612 Gas Fired Top Vent Gravity Wall Furnace Instruction Manual
- June 16, 2024
- williams
Table of Contents
- Williams 2509612 Gas Fired Top Vent Gravity Wall Furnace
- Product Information
- FAQs
- Basic Description
- Unpack Your Furnace
- Installing Your Wall Furnace
- Combustion & Ventilation Air
- Recessed Mount Installation
- Vent Installation
- Gas Supply and Piping
- Thermostat Installation
- Operating Your Furnace
- OPERATING INSTRUCTIONS
- FURNACE CONTROLS
- 43
- 54
- 38
- 52
- 43
- 54
- TROUBLE SHOOTING
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Williams 2509612 Gas Fired Top Vent Gravity Wall Furnace
Product Information
Specifications
- Model Numbers: 2509612, 2509622
- Type: Gas-fired top vent gravity wall furnace
- For Use with: Liquefied Petroleum (L.P.) Gas only
- Altitude Options: Basic Altitude (0-2000 ft) or High Altitude (2000-4000 ft)
- Manufacturer: Williams Furnace Co.
- Address: 225 Acacia St., Colton, CA 92324 U.S.A
Installation & Operating Instructions
Surface Mount Installation
To install the furnace on a surface, follow these steps:
- Choose a suitable location for the furnace.
- Ensure the surface is level and can support the weight of the furnace.
- Securely attach the furnace to the surface using appropriate mounting brackets or screws.
Vent Installation
To install the vent for the furnace, follow these steps:
- Choose an appropriate location for the vent.
- Ensure proper clearance from combustible materials.
- Install the vent pipe according to local building codes and regulations.
- Securely connect the vent pipe to the furnace using appropriate connectors.
Mount The Furnace
To mount the furnace, follow these steps:
- Select a suitable location for the furnace.
- Ensure proper clearance from combustible materials.
- Securely attach the furnace to the wall using appropriate mounting brackets.
Gas Supply and Piping
Proper gas supply and piping are crucial for the safe operation of the furnace. Follow these guidelines:
- Only use Liquefied Petroleum (L.P.) Gas as the fuel source.
- Ensure the gas supply is turned off before connecting the furnace.
- Use appropriate gas piping materials and connectors.
- Follow local building codes and regulations for gas installation.
Thermostat Installation
To install a thermostat for controlling the furnace, follow these steps:
- Select a suitable location for the thermostat.
- Mount the thermostat on the wall according to the manufacturer’s instructions.
- Connect the thermostat wiring to the furnace following the provided wiring diagram.
Start Up Procedure
To start up the furnace, follow these steps:
- Ensure the gas supply is turned on.
- Set the thermostat to the desired temperature.
- Wait for the furnace to ignite and start producing heat.
Operating Your Furnace
To operate the furnace, follow these guidelines:
- Regularly check and clean the air filters to ensure proper airflow.
- Maintain a clear area around the furnace for safety and accessibility.
- Monitor the furnace for any unusual noises or odors.
- Follow the manufacturer’s instructions for adjusting heat output and fan speed.
How To Care For Your Furnace
To care for your furnace and ensure its longevity, follow these tips:
- Regularly clean the exterior of the furnace using a soft cloth and mild detergent.
- Inspect the furnace for any signs of damage or wear.
- Keep the furnace area free from dust and debris.
- Schedule regular maintenance checks by a qualified technician.
Furnace Technical Information
For detailed technical information about the furnace, refer to the product manual or contact a qualified installer, service agency, or the gas supplier.
Troubleshooting Chart
If you encounter any issues with the furnace, refer to the troubleshooting chart in the product manual. It provides solutions to common problems and recommended actions.
Replacement Parts
If any parts of the furnace need replacement, refer to the product manual for a list of available replacement parts. Contact the manufacturer or an authorized dealer to order the required parts.
Blower Accessory (2901)
If you have a blower accessory (2901) for your furnace, refer to the product manual for installation instructions and usage guidelines. The blower accessory helps distribute heat more effectively.
Service Hints
If you require service or additional assistance with your furnace, follow these hints:
- Contact a qualified installer, service agency, or the gas supplier for professional help.
- Provide detailed information about the issue, including model numbers and any error codes displayed.
- Follow any specific instructions provided by the service technician.
How To Order Repair Parts
To order repair parts for your furnace, follow these steps:
- Identify the specific parts needed using the product manual or guidance from a qualified technician.
- Contact the manufacturer or an authorized dealer to place an order.
- Provide the necessary details, such as model numbers and part descriptions, to ensure accurate ordering.
FAQs
- Q: Can I use natural gas with this furnace?
- A: No, this furnace is designed for use with Liquefied Petroleum (L.P.) Gas only. Do not attempt to use natural gas.
- Q: Can I install this furnace in a mobile home or recreational vehicle?
- A: No, these furnaces are not suitable for installation in mobile homes, trailers, or recreational vehicles.
- Q: What should I do if I smell gas?
- A: If you smell gas, follow these steps immediately:
- Do not operate any electrical switches or appliances.
- Extinguish any open flames or sources of ignition.
- Evacuate the premises and call a qualified installer, service agency, or the gas supplier.
- Q: What is the warranty for this furnace?
- A: The furnace comes with a limited one-year warranty on all parts and labor. Additionally, there is a limited extended warranty of nine years for the heat exchanger. Refer to the warranty section in the product manual for more details.
owners manual
MODEL NOS. 2509612 2509622
INSTALLATION & OPERATING
INSTRUCTION MANUAL
GAS-FIRED TOP VENT GRAVITY WALL FURNACE
READ THIS OWNERS MANUAL CAREFULLY BEFORE YOU INSTALL YOUR NEW IMPROVED
EFFICIENCY
WILLIAMS WALL FURNACE
!iiI MODEL NO:!_i 2509611 2509621 3509611 3509621 5009611 5009621
FOR USE WITH LIQUEFIED
PETROLEUM (L.P.) GAS ONLY
Save This Manual For Future Reference.
NOTE: CANADIAN MODEL NUMBERS DIGIT FROM LEFT TO BE: 1 FOR BASIC ALTITUDES 2 FOR HIGH ALTITUDES EXAMPLE: MODEL: 3509612 BECOMES 3519612
THIRD
(0-2000 FT, BASIC ALTITUDE) OR BECOMES 3529612
(2000-4000 FT. HIGH ALTITUDE)
1 WARNING: If the information in this|
manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
· Open all windows. · Do not try to light any appliance. · Do not touch any
electrical switch; do
not use any phone in your building. · Extinguish any open flame. · Immediately
call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instruction. · If you
cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
WARNING: Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Refer to this manual. For assistance or
additional information consult a qualified installer, service agency or the
gas supplier.
WARNING: Do not install any of these furnaces (Natural or L.R Gas) in mobile
homes, trailers, or recreational vehicles.
Williams Furnace Co., 225 Acacia St., Colton, CA 92324 U.S.A
PRINTED IN US,A. 5/97
12 12 13
14-15 15-16 17-18 18-23 24-25
25 26-27 28-35 36-37 Back Cover Back Cover
Your Warranty
The Manufacturer, Williams Furnace Co.. warrants this wall furnace or heater
to the original purchaser under the following conditions: LIMITED ONE-YEAR
WARRANTY
1. Any part thereof which proves to be defective in material or workmanship
within one year from date of original purchase for use will be repaired or
replaced at the Manufacturer’s option, FOB its factory.
2. No liability is assumed by the Manufacturer for removal or installation
labor costs, nor for freight or delivery charges,
LIMITED EXTENDED WARRANTY
1. In addition to the above limited one-year warranty on the complete unit,
any heat exchanger which burns out or rusts under normal installation, use and
service conditions during a period of nine years following expiration of the
one-year warranty period will be exchanged for a like of functionaJly similar
part, FOB Manufacturer’s factory.
2. No liability is assumed by the Manufacturer for removal or installation
labor costs, nor for freight or delivery charges.
LIMITATIONS
1. THIS LIMITED WARRANTY IS THE ONLY WARRANTY MADE BY THE MANUFACTURER.
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE
ARE LIMITED TO THE SAME ONE YEAR TERM AS THIS EXPRESS WARRANTY. UNDER NO
CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL,
SPECIAL OR CONTINGENT DAMAGES OR EXPENSES ARISING DIRECTLY OR INDIRECTLY FROM
ANY DEFECT IN THE PRODUCT OR ANY COMPONENT OR FROM THE USE THEREOF THE
REMEDIES SET FORTH HEREIN ARE THE EXCLUSIVE REMEDIES AVAILABLE TO THE USER AND
ARE IN LIEU OF ALL OTHER REMEDIES.
Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation or consequential damages, so the above limitations or exclusions may not apply to you. 2. This warranty does not include any charge for labor or installation.
of incidental
3. This warranty does not extend to painted surfaces nor to damage or defects resulting from accident, alteration, misuse or abuse, or improper installation. 4. This warranty does not cover claims which do not involve defective workmanship or materials.
DUTIES OF THE CONSUMER
1. The heating equipment must be installed by a qualified installer and operated in accordance with the installation and homeowner’s instructions furnished with the equipment
2. Any travel, diagnostic costs, service labor, and labor to repair the defective unit will be the responsibility of the owner.
3. A bill of sale, cancelled check, payment record or permit should be kept to verify purchase date to establish the warranty period 4. Have the instafler enter the requested information in the space below.
GENERAL
1. The Manufacturer neither assumes nor authorizes any person to assume for
it any other obligation or liability in connection with said equipment.
2. Service under this warranty should be obtained by contacting your dealer.
Provide the dealer with the model number, serial number and purchase date
verification.
3. If. within a reasonable time after contacting your dealer, satisfactory
service has not been received, contact: Customer Service Department, 225
Acacia St.. Colton. CA 92324, for assistance,
4. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. AND YOU MAY ALSO HAVE OTHER
RIGHTS WHICH VARY FROM STATE TO STATE.
INSTALLATION
Model No,
INFORMATION
Serial No.
Orig. Purchaser
Address.
City and State
Zip
Dealer
Address
City and State.
Zip
Installation date authorized representative
local codes.)
Signed by_ who certifies that this appliance has been installed in accordance
with Manufacturer’s
–2–
.(Dealer or instructions and
A Word From The Manufacturer
Dear Customer, To set up our furnace assembly procedures, several hundred
quafity assurance, safety audit and design performance tests have been
conducted according to the standards provided by the American National
Standards Institute, the Department of Energy and our certification agency —
the American Gas Association Laboratories. This was done to assure you of
receiving the best value and most reliable appliance of its type available
today. We are confident that your Williams furnace can provide you years of
low cost, efficient, heating comfort. Thank you for purchasing a Williams
furnace.
Sincerely. Employees of Williams Furnace Company
Introduction
Please read our instructions before you install and use your furnace. This
will help you obtain the full value from this furnace. It could help you avoid
needless service costs, if the answer to the problem is found within this
instruction manual.
Basic Description
Vented wall furnaces are shipped ready to install in a 2 x 4 stud wall, with
studs 16 inches center to center.
Always consult your local heating or plumbing inspector, building department
or gas utility company regarding regulations, codes or ordinaces which apply
to the installation of a vented wall furnace.
No electric power is required unless furnace is equipped with an optional
blower accessory.
The efficiency rating of this appliance is a product thermal efficiency rating
determined under continuous operating conditions and was determined
independent of any installed system.
Single wall models described in this manual, are installed in a 2 x 4 stud
wall between studs spaced 16 inches center to center, or may be surface
mounted to a wall using free standing kit 4901.
Warmed air is discharged into the room in which the furnace is located.
The furnace contains a single multi-slot gas burner.
Combustion air is drawn in from the room where the fur-
nace is located and is vented out of the top of the furnace vertically through
vent piping in the stud space to a roof vent top. (Vent equipment is not
supplied with furnace, but may be obtained from WILLIAMS.)
Convection causes room air to circulate from the floor upward along the front,
back, and side of the heat exchanger, and then back to the room.
The furnace heat exchanger is built of heavy gauge steel treated for corrosion
resistance. The furnace cabinet is also constructed of heavy gauge steel and
has a neutral beige color enamel paint finish. The front of the cabinet is
fully Iouvered.
The furnace controls are located behind an access door on the lower front of
the furnace. All models are equipped with AGA/CGA listed gas valves and
pilots.
Models: 2509611, 2509612, 3509611, 3509612, 5009611, 5009612 are equipped with
a built-in thermostat control.
Models: 2509621, 2509622, 3509621, 3509622, 5009621, 5009622 are supplied with
a wall thermostat.
NOTE, ALL MODELS: This appliance is equipped with a vent safety shutoff
system, designed to protect against improper venting of combustion products.
Operation of this wall furnace when not connected to a properly installed and
maintained venting system or tampering with the vent safety shutoff system can
result in carbon monoxide (CO) poisoning and possible death.
Helpful Installation Information
The following booklets will help you in making the installation:
ANSI/NFPA 70, or current edition “National Electrical Code.” In Canada: CSA
C22.1 Canadian Electrical Code.
American National Standard Z223.1 or current edition “National Fuel Gas Code.”
Obtain from–American National Standards Institute, Inc., 1430 Broadway, New
York, N.Y. 10018. In Canada: CAN/CGA B149.
Safety Rules
WARNING
READ THESE RULES AND THE INSTRUCTIONS CAREFULLY. FAILURE TO FOLLOW THESE RULES
AND INSTRUCTIONS COULD CAUSE A MALFUNCTION OF THE FURNACE. THIS COULD RESULT
IN DEATH, SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE.
umn. The maximum inlet gas supply pressure is 13″ water column.
7. ANY SAFETY SCREEN, GUARD OR PARTS RE-
MOVED FOR SERVICING AN APPLIANCE MUST BE REPLACED PRIOR TO OPERATING THE AP-
PLIANCE TO AVOID PROPERTY DAMAGE, BODILY INJURY OR DEATH.
INSTALLATION MUST CONFORM TO LOCAL CODES. IN
THE ABSENCE OF LOCAL CODES, INSTALLATIONMUST CONFORM WITH THE NATIONAL FUEL
GAS CODE, ANSI Z223.1. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY
CONNECTED AND GROUNDED IN
ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE
CURRENT NATIONAL ELECTRICAL CODE ANSI/NFPA NO. 70.
, INSTALL the furnace vent directly to the outdoors, so that harmful gasses
will not collect inside the building. Follow the venting instructions for your
type installation exactly. Use only the type and size of vent pipe and
fittings specified.
9. BE SURE to provide for adequate combustion and ventilation air. See page
7. The flow of this air to the furnace must not be blocked.
IN CANADA
1. INSTALLATION MUST CONFORM TO LOCAL
CODES OR, IN THE ABSENCE OF LOCAL CODES, THE CURRENT CAN/CGA B149 INSTALLATION
CODE.
2. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY CONNECTED AND GROUND-
ED IN ACCORDANCE WITH LOCAL CODES OR,
IN THE ABSENCE OF LOCAL CODES, WITH THE CURRENT CSA C22.1 CANADIAN ELECTRICAL
CODE.
3. FIELD CONVERSIONS FOR HIGH ALTITUDE ARE NOT PERMITTED IN CANADA.
4. REFERENCE IS MADE IN THIS MANUAL REGARDING GAS TYPE AS L.RG. BE ADVISED
THAT L.P.G. IS NOT AVAILABLE IN CANADA, REFER TO PROPANE/L.R GAS.
10. NEVER vent flue gases intoanother room, a fireplace or any space inside a
building. This could cause property damage, bodily injury or death.
11. NEVER test for gas leaks with an open flame. Use soap suds to check all
gas connections. This will avoid the possibility of fire or explosion.
12. ALLOW furnace to cool before servicing. Always shut off electricity and
gas to furnace when working on it. This will prevent any electrical shocks or
burns.
13. DUE TO HIGH TEMPERATURES, locate the furnace out of traffic and away from
furniture and draperies.
14. ALERT children and adults to the hazards of high surface temperature and
to keep away to avoid burns or clothing ignition.
15. CAREFULLY supervise young children when they are in the same room with
the furnace.
1. USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD
CAUSE INJURY OR DEATH.
2. DO NOT install this furnace in an alcove.
3. DO NOT install these furnaces in a travel trailer, recreational vehicle or
mobile home.
4. MAINTAIN all clearances specified in section “Locating Wail Furnace and
Thermostat” and “Vent Installation.”
5. BE SURE furnace is for type of gas to be used. Check the rating plate by
the gas valve in the lower cabinet. Do not change it to use other gases.
Unsafe operation could result and could cause bodily injury and death.
6. For Natural gas, the minimum inlet gas supply pressure for the purpose of
input adjustment is 5″ column. The maximum inlet gas supply pressure is 7″
water column.
For L.F_gas, the minimum inlet gas supply pressure for the purpose of input
adjustment is 11″ water col-
16. DO NOT place clothing or other flammable material on or near furnace.
17. INSTALLATION and REPAIR must be done by a qualified service person. The
appliance should be inspected before use and at least annually by a
professional service person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It is imperative that
control compartments, burners and circulating air passages be kept clean.
18. BEFORE INSTALLING: To avoid electrical shock, turn off electrical
circuits that pass through the wall where you are going to install the
furnace.
19. BE AWARE of good safety practices by wearing personal protective
equipment such as gloves and safety glasses to avoid being injured by sharp
metal edges in or around furnace and while cutting or drilling holes in wood
and or sheet metal.
20. CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation. Verify proper
operation after servicing.
WARNING
DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE HEATER AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.
Unpack Your Furnace
The shipping carton contains the furnace and the items needed to install it:
The furnace is shipped assembled. The cabinet must be removed for the furnace
installation.
1. Open carton and carefully lift off cabinet face panel. 2. Remove small
parts bag and header plate from lower
portion of furnace.
3. Remove thermostat (wall thermostat models).
4. Stand Furnace upright.
5. Properly dispose of shipping material.
NOTE
Check the burner rating plate, located in burner compartment, to make sure
your furnace is equipped to operate on the type of gas available (either
Natural or L.P. Gas). DO NOT convert unit from Natural Gas to L.R Gas or from
L.R Gas to Natural Gas.
Basic Tools Needed
Hand drill or properly grounded electric drill. Expansion bit 1/2 inch to
1-5/8 inch or 1/2 inch and
1-1/2 inch blade bits
118 inch drill bit (metal) 6 foot folding rule or tape measure Screwdriver
(medium blade)
Pliers (wire cutting) Hammer Hole saw – 2 inches
Screwdriver (phillips head) Stud Locator or small finish nails
Tin Snips 8 inch adjustable wrench
12 inch adjustable wrench Key hole saw or sabre saw 2 – 10 inch or 12 inch
pipe wrenches Gloves and safety glasses
Basic Materials
Pipe and fittings to make connections to furnace. Pipe Joint Compound
resistant to L.R gases. Electrical wiring supplies as needed. Minimum wire
size is #14 gauge copper.
*Electrical supplies only required if accessory blower is being installed.
A type “BW” gas vent kit for vertical venting such as a WILLIAMS Oval Vent Kit
9901.
Extra lengths of double-wall vent pipe may be needed, depending on height or
length of run.
Optional Accessories
Free Standing Kit 4901 may be used with all single models. This kit allows the
furnace to be mounted on the surface of a wall.
Rear Outlet Register 6901 may be used with all single models when recessed
into a standard 2 inch x 4 inch interior stud partition. This kit directs some
of the heated air into the room opposite the one in which the furnace is
installed.
Blower Accessory 2901 may be used on all models and mounts on top of the
furnace. This blower increases circulation of warm air through the heated
space. A 115V outlet adjacent to the furnace is required. Oval B/W Vent Kit
9901
vent kit contains 4 feet of oval doublewalled vent pipe, plate spacers and
base plate or hold-
down plate that starts the venting from the top of furnace. See Page 12 for
some additional items you may need.
ALL MODELS: Decorator Face Panel Colors
Various Face Panel colors may be used on all models. All are constructed of
heavy gauge steel with your choice of colored enamel paint finish.
4915 (Almond) 4916 (Black) 4917 (Red) 4918 (white)
NOTE
Kits are identified on their carton by the manufacturing number 4901, 6901 and
2901 respectively.
–5–
Installing Your Wall Furnace
The following steps are all needed for proper installation and safe operation
of your furnace. If you have any doubts
as to any requirements, check with local authorities. Obtain professional help
where needed.
All of CHECKS AND ADJUSTMENTS in the Start-Up Procedure on page 17 are vital
to the proper and safe
operation of the furnace. Be sure they are done.
Locating Wall Furnace & Thermostat
The furnace is installed between 2 x 4 inch wall studs spaced on 16 inch
centers or stud space can be framed in to 16 inches. See page ft (Fig. 9).
Consider the following points before attempting to install the furnace.
CAUTION Do not make cut-outs in wall or ceiling before checking in the attic
for ceilingjoist locations and proposed venting.
1. Place the furnace near the center of the space to be heated for good air
circulation. Do not put it behind a door or draperies. Do not install it in a
closet, alcove, hallway or other confined space where the furnace could be
isolated by closing doors to the heated space. Do not locate the furnace where
a door could swing over the front panel, or where circulation could be
retarded by furniture or cabinets.
For large homes or homes with spread-out floor plans, two or more furnaces are
recommended.
CEILING
MINIMUM SPACE T MIN.
16″ MIN,
4. When furnace is properly installed with legs resting on floor plate, it
sets the dimension from the face panel to the bare floor. (21/2inches
approximately depending on the thickness of floor plate).
A protective barrier (metal or wood), cut to match width and depth of furnace,
should be used to cover over any floor coverings such as carpet or sheet vinyl
that might be finished off under the furnace.
NOTE At no time should the dimension from the bottom of the face panel to the
protective barrier be less than 11/2 inches.
5. The side of the furnace may be as close as 4 inches to a wall. The
recessed portion may have 0 inch clearance to combustible material.
. To provide adequate clearance and service access, the front of the furnace
must face the open room. Do not place obstructive furniture closer than four
feet to front of cabinet.
, After picking a location, inspect the wall, floor, attic and roof areas.
Make sure there are no pipes, wiring, bracing, etc., that would interfere with
furnace or vent installation.If required move them or pick a new location.
, Be sure that gas piping and electrical wiring can be brought to the
location. See sections covering piping and electrical wiring for your type of
furnace mounting. (Electrical wiring only required for optional blower
accessory.)
:URNACE WALL
4″ MIN. TO CLOSEST SIDE WALL
NOTE: MAXIMUM RECESS DEPTH OF SINGLE MODELS IS 41/£’
I1
2-1/2 “_
APPROX. L__ BARE FLOOR
If your furnace is a wall thermostat model, locate the thermostat about 5 feet
above the floor on an inside wall
where it will sense the average room temperature.
Avoid the following:
HOT SPOTS:
Concealed pipes or ducts
Fireplaces Registers TV sets Radios
Lamps Direct sunlight Kitchen
COLD SPOTS:
Concealed pipes or ducts
Stairwells-drafts Doors-drafts Unheated rooms on
other side of wall DEAD SPOTS: Behind doors Corners and alcoves
2. Check the minimum spacing needs as shown in Fig. 1.
3. The top of the furnace must be at least 16 inches from the ceiling.
After picking a location that meets the requirements make sure there are no pipes, wiring, or anything else that would interfere with thermostat installation. If required, move them or pick a new location.
I
I WARNING: DANGER OF PROPERTY DAMAGE, BODILY INJURY OR LOSS OF LIFE. DO NOT
INSTALL FURNACE I
IN ANY AREA WHERE OXYGEN IS IN USE.
–6–
Combustion & Ventilation Air
WARNING
DANGER OF ILLNESS BODILY INJURY OR DEATH THE FURNACE AND ANY OTHER FUEL
BURNING APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION
AND VENTILATION OF FLUE GASES. MOST HOMES WILL REQUIRE THAT OUTSIDE AIR BE
SUPPLIED INTO THE FURNACE AREA.
WARNING
DANGER OF PROPERTY DAMAGE, BODILY INJURY OR DEATH
EVEN WHEN HOUSE MEETS REQUIREMENTS FOR UNCONFINED SPACE WITH ADEQUATE AIR
INFILTRATION IT IS RECOMMENDED THAT A FRESH AIR INTAKE BE INSTALLED TO LESSEN
THE POSSIBLE DANGERS FROM ANY FUTURE CHANGES ON THE HOME,
The high cost of energy for home heating has brought about new materials and
methods used to construct or remodel most current homes. The improved
construction and additional insulation has reduced the heat loss and
made these homes much tighter around windows and doors so that infiltrated air
is minimal. This creates a problem to supply combustion and ventilation air
for gas-fired or other fuel burning appliances. Any use of appliances that
pull air out of the house (clothes dryers, exhaust fans, fireplaces, etc.)
increases this problem and appliances could be starving for air.
The combination of a tight energy efficient home with the use of exhaust fans,
fireplaces, clothes dryers, and gas appliances results in more and more air
being drawn from the house until fresh air may be sucked into the house down
the furnace flue or fireplace chimney. Carbon monoxide can be the result.
Carbon monoxide or “CO” is a colorless, odorless gas produced when fuel is not
burned completely or when the flame does not receive sufficient oxygen.
Automobiles, charcoal, wood fires and improperly vented or air-starved coal,
oil and gas furnaces or other appliances can produce carbon monoxide.
Be aware of these air starvation signals:
1. Headaches, nausea, dizziness 2. Excessive humidity — heavily frosted
windows, moist
“clammy” sensation. 3. Fireplace smokes, won’t draw 4. Furnace flue backs up
AIR REQUIREMENTS
The requirements for providing air for combustion and ventilation are listed
in the National Fuel Gas Code NFPA
54/ANSI Z223.1 (in Canada: CAN/CGA B149). Most homes will require that outside
air be supplied to the furnace area by means of ventilation grilles or ducts
connecting directly to the outside or spaces open to the outdoors such as
attic or crawl space. The only exception is when the furnace area meets the
requirements and definitions for an unconfined space with adequate air
filtration.
All air openings and connecting ducts must comply with the following:
IF THE FURNACE IS INSTALLED IN AN AREA WITH ANOTHER GAS APPLIANCE(S), THE
TOTAL INPUT RATING OF ALL APPLIANCES MUST BE CONSIDERED WHEN DETERMINING THE
FREE AREA REQUIREMENTS FOR COMBUSTION AND VENTILATION AIR OPENINGS.
Ducts must have the same cross-sectionalarea as the free area of the openings
to which they connect.
The minimum dimension of rectangular air ducts must not be less than 3 inches
in length or 3 inches in height.
LOUVERS/GRILLES AND SCREENS COVERING FREE AREA OPENINGS
If screen is used to cover opening(s), it must not be smaller than 1/4inch
mesh. Use the free area of a louver or grille to determine the size opening
required to provide the free area specified. If the free area is not known,
assume a 20% free area for wood and a 60% free area for metal louvers or
grilles.
EXAMPLE 1. FURNACE LOCATED IN UNCONFINED SPACE,”
An unconfined space must have a volume of a minimum 50 cubic feet per 1000 Btuh of total of all appliances in area. Adjoining rooms may be included only if there are no doors between the rooms, or if special provisions are made such as ventilation grilles installed between connecting rooms.
Fig. 4, page 8 shows the minimum area in square feet, based on 8 foot ceiling
heights, required for different Btuh input ratings. A. INFILTRATION AIR
If your furnace is in an open area unconfined space) the air that leaks
through the cracks around doors and windows may be enough for combustion and
ventilation air. The doors should not fit tightly. The cracks around windows
should not be caulked or
weather stripped.
VENT PIPE
DRAFT HOOD
] TYPICAL WATER HEATER
!
__1 ,A,C.
DRAFT
WALL FURNAC E
HOOD OPENING
–7–
Combustion & Ventilation Air (Con’t)
To determine if infiltration air is adequate, perform the following checks:
1. Close all doors and windows. 11you have a fireplace, start a fire and wait
until flames are burning vigorously, (or flue damper can be closed),
2. Turn on all exhausting devices, such as: – kitchen and bathroom exhaust
fans. – water heaters (gas and electric).
3. Turn on all vented gas appliances, such as: – heating equipment (includes
any room heaters) – water heaters.
4. Wait ten (10) minutes for drafts to settle down.
5. Check for drafthood spillage at each appliance. (Hold a lighted match 2
inches from draft opening. See Fig. 2, page 7).
B. No Spillage Match flame pulls toward drafthood — this indicates sufficient
infiltration air. Return exhausting devices and appliances to the condition
you found them.
C. Drafthood Spills
If there is spillage at a drafthood (match goes out or flame wavers away from
drafthood): 1. Check for plugged flue connectors and chimneys.
Check and repair stoppage and test again.
2. If you have a fireplace, open a window or door near the fireplace and then
check for spillage.
a. If spillage stops, do not use the fireplace without a nearby window or door
open until you can supply fresh air by a permanent duct.
3. If you have kitchen and bathroom exhaust fans, turn them off and check for
spillage.
a. If spillage stops, do not use exhaust fans until you can supply fresh air
by a permanent duct. Circuit breakers for fans should be turned off if
possible.
WARNING
DANGER OF ILLNESS, BODILY INJURY OR DEATH DRAFTHOOD SPILLAGE WITH UNOBSTRUCTED
VENTS, INDICATES THAT ADDITIONAL AIR MUST BE BROUGHT INTO THE STRUCTURE FROM
THE OUTSIDE. KEEP A WINDOW OPEN (MINIMUM 2 INCHES) NEAR THE APPLIANCE UNTIL A
PERMANENT AIR DUCT IS INSTALLED.
4. Spillage means air starvation and a fresh air duct or air intakes must be
installed to provide air directly to the furnace or other gas appliance.
D. If spillage exists or when the furnace is in a building of tight
construction where the windows and doors are weatherstripped, air for
combustion and ventilation must be obtained from outdoors or space open to the
outdoors.
Provide an opening(s) having a total free area of 1 sq. inch per 4000 Btuh of
the total of all appliances. The required area is shown in Fig. 7, page 9.
FRESH AIR DUCT
HOLES FROM VENTILATED ATrJc INTO STUD SPACE SEE FrG. 8
AIR GRILLE TO STUD SPACE
I 12″ MAXFROM FLOOR
HOLE IN BOTTOM OR BACK OF FURNACE INTO OPEN STUD SPACE
HOLES FROM VENTILATED CRAWL SPACE INTO STUD SEE FIG 7
OR CRAWL SPACE
SPACE
1. Duct must terminate at a point not more than 1 foot above the floor.
2. Duct size must be at least I inch of free area for each 4000 Btuh of input
of all appliances in area.
MINIMUM AREA IN SQUARE FEET
4000 Btuh Per
Square Inch
Opening
Max. Btuh
Round Duct
Input Rectangular
Duct
4″DIA. 4″DIA. 4″DIA. 4″DIA. 4″DIA. 41!2″DIA.
3″X3″SQ. 3″X3″SQ. 3″X4″SQ. 3″X4″SQ. 3″X5″SQ. 3″X5″SQ.
30,000 35,000 40,000 45,000 50,000 60,000
*Unconfined Space Min. Area In Sq. Ft,
8′ Ceiling Height
188 219 250 281 312 375
*Can be two or more rooms joined by ventilation grilles.
EXAMPLE 2. FURNACE LOCATED IN CONFINED SPACE
If furnace is installed in a confined space, it must be provided with free air
for proper combustion and ventilation of flue gases by one of the following
methods:
–8–
Combustion & Ventilation Air (Con’t)
A. All Air From Inside Building:
If the confined space adjoins an unconfined space as defined in EXAMPLE 1,
provide two permanent openings, one within 12 inches of the top and one within
12 inches of the bottom of the room connecting directly to unconfined space.
Each opening must have a free area of at least 100 square inches or 1 square
inch per 1000 Btuh combined input of appliances in one room if combined input
exceeds 100,000 Btuh.
WARNING
DANGER OF PROPERTY DAMAGE, BODILY INJURY OR DEATH
THE ADJOINING UNCONFINED SPACE MUST HAVE ADEQUATE AIR INFILTRATION AS DEFINED
IN EXAMPLE 1.
FOR EXAMPLE: Your furnace is rated at 50,000 Btu per hour. The water heater is
rated at 30,000 Btu per hour.The total is 80,000 Btu per hour. You need two
grilles, each with 100 square inches of free opening. Metal grilles have about
60% free area, so you need two metal grilles each with 160 square inches of
Iouvered area.
Refer to Fig. 5, which shows grille installation.
Using the previous example, the two connecting rooms plus the closet must
equal at least 500 sq. feet to handle the combined input 50,000 plus 30,000.
outdoors or spaces open to outdoors such as attic or crawl spaces.
Provide two permanent openings, one within 12 inches of top, one within 12
inches of bottom of room connecting directly, or by using ducts, with the
outdoor or areas open to outdoors.
If opening connects directly to, or with vertical ducts, the free area of each
opening must be at least 1 square inch per 4000 Btuh combined input of
appliances in area.
If horizontal ducts are used, the free area of each opening must be at least 1
square inch per 2000 Btuh combined input of appliances in area.
FOR EXAMPLE: Your furnace is rated at 50,000 Btu per hour. The water heater is
rated at 30,000 Btu per hour. The total is 80,000 Btu per hour. You need two
grilles, each with 20 square inches of free opening, unless connected by
horizontal ducts which would require each grille or opening to have a free
area of 40 square inches.
CH_MN[ y OR GAS VENT
3 OR CRAWL SPACE
GRILLES CONNECTING ROOMS TO MAKE UNCONFINED SPACE
VENTILATION
TWO ROOMS $PAC_
GRILLES CONNECTING TO MEET UNCONFINED
II
so
I, I
_N
OUTLET AIR
o-=
200 SO IN MINIMUM BETWEEN LARGE ROOMS
PNLEI AIR
*Openings for inlet or outlet air should not be made into attic area if attic is equipped with a thermostat controlled power vent.
100 So IN
1<[ COMMENOt
O
FRESH AIR DUCT
rPilO CRAWL $PAC_
_ U_NACE AREA
OR IN CLOS[T W_IH
_N WAIER
HLA1FR
B. All Air From Outdoors:
If confined space doesn’t adjoin an unconfined space (defined in EXAMPLE 1)
then air must be provided from
Furnace
Btuh/Input
30,000 35,000 40,000 45,000 50,000 60,000
–9–FREE AREA IN SQ. INCHES
EACH OPENING (FURNACE ONLY) BASED ON ONE SQ. INCH PER 4000 BTUH
Sq. Inch
of Opening
7.5 8.75 10.0 11.25 12.5 15.0
Req’d Number of Holes Sill or Header Plates
1V=”
2″
3″
7
4
2
8
5
2
9
5
3
10
6
3
11
6
3
13
8
4
Recessed Mount Installation
NOTE: Model Series 25096 and 35096. The maximum recess depth, from rear of
furnace forward is 41/=”.
FIND THE STUDS AND CEILING JOISTS
Use a stud Iocator or small finishing nails. Repeatedly drive and remove a
nail into the wall in the area of the stud until it is located. Then find the
inside edge of the stud. Leave the nail at this location.
The other stud should be about 141/2inches from the one found. Drive finishing
nails on the inside of this stud. Drew wall cut out to required size as shown
in Fig. 8. If wall studs are not on 16 inch centers see “Close Off Stud
Space.”
CUT WALL OPENING (See Caution on page 6)
All models: Cut wall opening 14-3/8 inches wide and 66-1/8 inches high
measured from top of floor plate. See Fig. 8. All corners must be square.
INSTALLATION OF REAR OUTLET REGISTER (If Used)
The optional rear outlet register 6901 can be installed when furnace is
recessed. In new construction, install the
rear outlet plasterground at the same time you install the header plate. For
existing construction, make necessary cutout and install the plasterground
just before you install the furnace. See instructions packed with kit and Fig.
8.
Do not allow wall finish material to project into the furnace recess.
Do not install rear outlet register where grille may be blocked by door swing,
curtains or any other obstruction.
GAS SUPPLY OPENING
A hole must be drilled for the gas line. See Fig. 8 for alternate gas line
openings.
Decide whether the gas line witl come through the floor or wall.
Drill a 11/2 inch hole in wall or floor (Fig. 8) as needed.
CLOSE OFF STUD SPACE (If Required)
If studs are not on 16 inch centers, cut the hole for the furnace next to an
existing stud and frame in the other side using a 2×4 and spacer blocks as
required. See Fig. 9, page 11.
HEADER PLATE AND GAS SUPPLY OPENINGS
115V. OUTLET FOR
TOP
BOTTOM HEADER NAILING
FLANGE
MODELS
2509611 2509612 2509621 2509622
AND
3509611 3509612 3509621 3509622
62V4
ALTERNATE GAS
TO TOP OF HEADER PLASTERGROUND
OPTIONAL REAR REGISTER
PLASTERGROUND
NAIL FLANGE
LOCATION
PLATE
FINtSHEO FLOOR
–10–
Recessed Mount Installation (Con’t)
CLOSE OFF STUD SPACE
CEILING PLATE SPACERS RECESSED MOUNT
PLA’flE
I_- EXISllNG STUD
I]I
NEW STUD
III
_S_NG FLOOR
S’PJD -_
I
[
·.– 14–3/8″
A
[ I I BLOCKS
III
HI
III
CUT PLATE OPENING (RECESSED VENTING)
Cut away the ceiling plate between the studs where the furnace is to be
installed. Work from the top in the attic.
If there is no access to the top, remove the wall covering between the two
wall studs, all the way to the ceiling. Work through this opening.
Cut out the entire plate so the plate edges will be even with the inner face
of the 2×4 studs (Fig. 10).
INSTALL VENT BASE PLATE (HOLD-DOWN PLATE)
Position base plate on top of header plate and fasten with screws. Note: These
items are included in Vent Kit 9901.
HEADER PLATE (VENT SUPPORT) Measure up 621/4 inches from the top of floor
plate. Place a mark on each stud at this distance. See Fig. 8, page 10. Place
the header plate between the studs with the lower edges even with marks on the
studs. Make sure header plate is level.
All models: Locate rear edge of nailing tabs at back of 2×4 stud which will
center the vent collar in the wall. Nail header plate to studs. See Fig. 8,
page 10.
INSTALL CEILING PLATE SPACER (RECESSED MOUNT) Refer to Fig. 10.
Two ceiling plate spacers are in the B/W Vent Kit. They must be fastened along
each long edge of the ceiling hole to hold the oval vent pipe in the center of
the hole.
Nail the ceiling plate spacers either across or in between the cut out section
of ceiling plate. If nailed between, end must be bent at 90 degrees.
Ceiling plate spacers preserve structural strength and position oval vent pipe
in the center of the cut out opening.
No electric power is required unless furnace is equipped with an optional
blower. Do not connect 115V service line to the gas control valve or wall
thermostat.
ELECTRICAL OUTLET (Optional) If you are installing optional blower accessory
with the furnace, rough-in a 115V electrical outlet as shown in Fig. 11.
–11 m
14 3/8
CEILING PLATE SPACERS NAILED IN BE’nNEEN CEILING PLATES OR ACROSS FACE IF
ACCESSIBLE
OPTIONAL ELECTRICAL OUTLET
7
BLOWER AGCT
62V4
,
%
Surface Mount Installation
The use of optional Free Standing Kit No. 4901 allows furnace to be mounted on
the surface of a wall. See detailed instructions packed with kit.
Vent Installation
The vent installation must comply with all local codes and ordinances. If in
doubt, consult your local codes or inspector. The furnace vent must be
directed to the outdoors so that harmful combustion gasses will not collect
inside the building. This furnace must not be connected to a chimney flue
serving a separate solid-fuel burning appliance.
NOTE: U.L. listed B/W Vent Kit 9901, You must provide other items, not
contained in kit, necessary to complete your specific venting situation
through the roof. Refer to typical venting system shown in Fig. 12.
WARNING This product is design certified by A.G.A./C.G.A. to be installed with
a U.L. listed type “B” approved vent and type “B/W” approved vent. See Fig.
12. Older style terra-cotta, transite, clay, concrete or masonary type vent
pipe cannot be used with this appliance. This older type vent pipe will not
heat fast enough to establish a draft, which will result in improper venting
of combustion products. Consequently, this could cause the vent safety control
system to shut down the furnace.
IMPORTANT Area above header within the stud space MUST be kept clear of any
attic insulation to allow the free circulation of air around oval vent piping.
In some areas the building code requires the use of an attic shield.
NOTE The B/W vent must extend through the ceiling and roof terminating at
least 12 feet above the finished floor on which the furnace rests. First vent
pipe offset (if required) must not be any closer than 2′-0″ from header plate.
INSTALL FURNACE VENT (RECESSED MOUNT) Lower a 4 foot length of oval, double
wall vent pipe through the place spacers to the hold-down plate. Push the vent
pipe into the hold-down plate until it is completely seated. (Hold-down cleat
will engage the groove in the vent pipe.)
COMPLETE THE VENTING Refer to Fig. 12.
Vent Installation (Con’t)
Type B/W gas vent shall extend from the header plate of the vented wall
furnace to a point above the highest ceiling plate within a stud space through
which the vent passes, without any offsets or crossovers therein. After a type
B/W gas vent passes through the highest ceiling plate within a stud space
above the furnace which it serves, the vent system may be completed with a
type B gas vent, of the same manufacturer (do not mix brands of pipe), and
offsets or breakovers shall not be greater than 45 degrees from vertical.
Refer to (UNIFORM MECHANICAL CODE).
Install oval to round adapter. Complete the piping extending it through the
roof. Use a 4 inch round double wall (Type B) vent pipe, roof flashing, storm
collar,and vent top as shown. The vent cap must be at least 2 feet higher than
any point that is within 10 feet horizontally of the vent cap. There must be
at least 1 inch clearance between the vent pipe and any combustible material.
TYPICAL VENT INSTALLATION
“dYQtTCAP MUST BE MINIMUM 2 FEET HIGHER 1HAN ANY POINT WI1HIN 10 FEET
0F ‘4ENT CAP
HEIGHTFROMHEADER PLATETO VENTCAPTOP MUSTBE S F£ MINIMUM 1 INCHMIH.
CLEARANCTEO COMBUSllBLES ,= USTE_ 4.” ROUNDB VISIT $ OVALTO ROUNDADAPTER $
OVALB/_V VENT (DOIJBLE WALL) $ PLATESPACER-
(RECESSMEODUNT)
2 R£Q’D
- eASE PLATE (HOLD-DOWN) OR STARTERPLATE SCREWEDDOWN TO HEADER PLAIT-,,
CAP STORM ROOF
NOTE
HEADER PLATE AND GASKETS PRO_/1D£D WITH FURNACE
TAKE CARE NO’r TO DISllJRB
_
GLUED TO
OF HEADER. _
MA’r_41AL
MUST NOT BLOCK FLUE Ex’nsNsICH * CONTAINED IN OVAL B/W
(STARTER) VENT KIT NO. 9901
“° NOT PROVIDED WITH KITS AVAILABLE
50,000 BTUH FURNACE AND HEADER NOT SHOWN.
NOTE: FLUE COLLAR GASKET, NOT REQUIRED ON MODELS 5009611, 5009612, 5009621 & 5009622
–12–
Mount The Furnace
POSITION FURNACE f B/W VENT
BOTTOM OF FURNACE
URING FURNACE LEGS NEAR FLOOR PLATE
NAIL FURNACE LEG TO STUD OR
(SEE DETAIL BELOW)
LEG
_
FLOiR PLATE
MODELS 2509612 2509622 3509612 3509622
AND 2509611 2509621 3509611 3509621
Clear the recess of a!l debris, remove any wood
plastergrounds. Stand furnace in front of recess, holding the furnace body at
an angle. Insert flue collar into open-
ing in the header plate and raise furnace carefully. See Fig. 13. Swing bottom
of furnace into recess with front
edges of legs flush with 2×4 floor plate. Nail through legs into studs or
floor plate. See Fig. 14.
DO NOT DAMAGE GASKET GLUED TO UNDER-
SIDE OF HEADER PLATE WHEN PLACING
FURNACE IN WALILM.PORTANT
I
REMOVING KNOCK-OUT PLATES
ANGLE
_FLOOR
PLATE
IMPORTANT AVOID NAILING THE LEGS SO TIGHTLY THAT IT
DISTURBS THE INNER FURNACE CASINGS. DO NOT TRY TO FORCE THE FURNACE INTO A
SMALLER-THAN-SPECIFIED RECESS.
REAR OUTLET KIT INSTALLATION (If Used)
CAUTION: Do not install rear outlet kit where grille may be blocked by door
swing, curtains or any other obstruction.
If Rear Outlet Register 6901 is used, the following procedure must be complete
before placing furnace body into wall recess. See Fig. 15. Attach speed nuts
to outer shield, and remove knock-out plates as follows: 1. Punch in lower
corners with screwdriver blade.
2. Break knock-out side and bottom connecting tabs: hold screwdriver blade
sideways against tab and strike head of screwdriver lightly with a hammer.
3. Swing plate outward; bend it back and forth to break the top tabs.
After furnace is in position, install rear outlet as shown in Fig. 16. Have
damper in open position when inserting assembly. Secure register assembly to
speed nuts with machine screws furnished.
MOUNTING REAR OUTLET
INNER SHIELD OF FURNACE
_
10-24 SPEED
NUT
/
HOLD SCREWDRIVER SIDEWAYS AGAINST
TABS ANO STRIKE
LIGHTLY WITH HAMMER
MODELS 2509612 2509622 3509612 3509622
AND 2509611 2509621 3509611 3509621
SHIELDS PLASTERGROUNO-
ASSEMB_
–13 m
Gas Supply and Piping
Gas control valve, within the furnace, is shipped with a sealed cover gas
inlet tapping. Do not remove seal until ready to connect piping.
WARNING
DANGER OF PROPERTY DAMAGE, BODILY INJURY OR DEATH.
MAKE SURE THE FURNACE IS EQUIPPED TO OPERATE ON THE TYPE OF GAS AVAILABLE.
MODELS DESIGNATED AS NATURAL GAS ARE TO BE USED WITH NATURAL GAS ONLY. FURNACE
DESIGNATED FOR USE WITH LIQUEFIED PETROLEUM (L.P.) GAS HAVE ORIFICES SIZED FOR
COMMERCIALLY PURE PROPANE GAS. THEY CAN NOT BE USED WITH BUTANE OR A MIXTURE
OF BUTANE AND PROPANE.
GAS SUPPLY
MINIMUM gas supply pressure for NATURAL GAS to the furnace control valve is 5
inches water column. For natural gas, it must not be more than 7 inches.
Minimum gas supply pressure for L.P. Gas to the furnace control valve must be
at least 11 inches water column. It must not exceed 13 inches.
Gas pressures and input to the burners must not exceed the rated input and
pressure shown on the rating plate. On Natural Gas the manifold pressure
should be 4 inches water column. The manifold pressure should be 11 inches
water column for L.R Gas. See page 17 for operation above 2000 feet altitude.
Orifice change may be required to suit gas supplied. Check with your WILLIAMS
service department.
ORIFICE SIZES
Furnace Technical Information, Page 25, shows the correct orifice sizes for
the different input ratings when using Natural or L.P. Gas.
use compound resistantto action of liquefied petroleum gases. 3. Use ground
joint unions. 4. Install a drip leg (sediment trap) to trap dirt and moisture
before it can enter the gas valve. Nipple must be a minimum of 3 inches long.
See Fig. 17. 5. Install a manual shut-off valve. 6. Provide a 1/8 NPT test
gauge connection immediately before the gas supply connection to the furnace.
GAS CONNECTION
If installation is for L.P gas, installer use two-stage regulator and make all
connections from storage tank to furnace. Use two pipe wrenches when making
the connection to the valve to prevent turning of, or damage to gas valve.
Connection between shutoff valve and burner control assembly can be made with
an A.G.AJC.G.A. design certified flexible connector if allowed by local codes.
Tighten all joints securely.
HO_IZONTAL
DROP
II
PIPED
I11 o,, SUPPLY
TEE FITTING
3,n i76 2 mini mINIMUM
+-=NIPPLE
r_ANUAL SHUT OFF <— CAP VALVE
R_SER PIPED GAS
SUPPLY
i TEE _FITTING
GAS PIPING
The gas supply line must be of an adequate size to handle the BTU/HR
requirements and length of the run for the unit being installed.
Determine the minimum pipe size from Fig. 18, page 15, basing the length of
the run from the gas meter or source to the unit.
All piping must comply with local codes and ordinances or with the National
Fuel Gas Code (ANSI Z223.1 NFPA No. 54), whichever applies. (In Canada:
CAN/CGA B149.) Refer to Fig. 17 for the general layout at the unit. It shows
the basic fittings needed.
The following rules apply:
1. Use new, properly reamed pipe free from chips such as steel or black iron
pipe and fittings or other approved by local codes.
2. Do not thread pipe too far. Valve distortion or malfunction may result
from excess pipe within control. Apply moderate amount of good quality dope to
pipe only, leaving 2 end threads bare. If LP gas installation,
PROPER PIPING PRACTICE
2 IMPERFECT
CONTROL
USE MODiERATE
AMOUNT
OF DOPE
THREAO
PIPt. RIGHT LENGTH
LEAVE 2 EI_O YHREADS
BARE
–14–
Gas Supply and Piping (Con’t)
CHECKING THE GAS PIPING
Test all piping for leaks. When checking gas piping to the furnace with gas
pressure at less than 1/2 PSI, shut off manual gas valve for the furnace, if
gas piping is to be checked with the pressure at or above 1/2PSI, the furnace
and manual shut off valve must be disconnected during testing. (SEE WARNING
BELOW.) Apply soapsuds (or a liquid detergent) to each joint. Bubbles forming
indicates a leak. Correct even the slightest leak at once,
WARNING
DANGER OF PROPERTY DAMAGE, BODILY INJURY OR DEATH.
NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER EXCEED SPECIFIED
PRESSURES FOR TESTING. HIGHER PRESSURES MAY DAMAGE THE GAS VALVE AND CAUSE
OVERFIRING WHICH MAY RESULT iN HEAT EXCHANGER FAILURE. LIQUID PETROLEUM (L.P.)
GAS IS HEAVIER THAN AIR AND IT WILL SETTLE IN ANY LOW AREA, INCLUDING OPEN
DEPRESSIONS AND IT WILL REMAIN THERE UNLESS AREA IS VENTILATED.
NEVER ATTEMPT STARTUP OF UNIT BEFORE THOROUGHLY VENTILATING AREA AND SMELLING
NEAR THE FLOOR FOR GAS ODOR.
LENGTH OF
PIPE-FT. 20 40 60
LENGTH OF
PIPE-FT. 2O 4O 60
GAS PIPE SIZES
NATURAL GAS PiPE CAPACITY – BTU PER HOUR
(INCLUDES FITTINGS) PIPE SIZE.
I/2″ 92,000 63,000 50.000
314″ 190.000 130,000 105,000
I” 350,000 245,000 195.000
L.P. GAS
PIPE CAPACITY – BTU PER HOUR (INCLUDES FITTINGS)
3/4″ 189I/,20″00 j 393,000
129,000
267.000
103.000
217,000
I” 732,000 504,000 409,000
Thermostat Installation
Models 2509611, 2509612, 3509611, 3509612, 5009611 and 5009612 utilize a built-in thermostat control system operated by a heat sensing bulb located in the burner compartment.
I IMPORTANT Handle the bulb with care. Do not kink the connect-
I
ing tubing.
Models 2509621, 2509622, 3509621, 3509622, 5009621 and 5009622 are operated by a millivolt type thermostat. Current to the thermostat is supplied by the pilot generator. Anticipation settings are not required.
of the wall and ceiling above the thermostat location. Pull the nail out and
push a small stiff wire through the hole so it can be found in the attic.
Drill a 1/2-inch hole through the ceiling wall plate (see Fig. 19 page 16).
4, Probe for obstructions in the partition. Then drill a 1/2-inch hole through
wall at selected location for thermostat.
5, From the attic, feed the thermostat cable or a stiff wire through wall
until even with thermostat location.
6. Snag thermostat cable through hole and pull cable through hole in wall so
that 6 inches of cable protrudes.
7. Route cable to wall furnace.
1. If an old thermostat is being replaced and is in a satisfactory location
and the wiring appears to be in good condition, use existing wiring. If in
doubt, use new wire.
2. If a new location is chosen or if this is a new installation, thermostat
cable must first be run to the location selected. All wiring must agree with
local codes and ordinances. These instructions cover bringing the wire down
from the attic but it can be run from a basement or crawl space using similar
methods.
3. Before drilling hole in wall at selected location, drive a small finishing
nail through the ceiling in the corner
CAUTION Do not run wire behind flanges of Header Plate or in any location
where it might be damaged. Avoid splicing thermostat wire unless the spliced
wires are properly cleaned, soldered and taped.
NOTE
Use #18 Ga. wire as supplied for maximum length of 20 feet. If longer length
is needed, use #16 Ga. for maximum length of 25 feet.
m15m
Thermostat Installation (Con’t)
MOUNTING THE THERMOSTAT
1. To remove thermostat cover, squeeze both sides and lift. Carefully remove
and discard the packing tab protecting the switch contacts.
2. Connect thermostat wires to the terminal screws on the back of thermostat
base.
3. Push any excess wire back through hole in wall and plug hole with
insulation to prevent drafts from affecting thermostat operation.
4. Be sure to level thermostat for best appearance, fasten thermostat base to
wall through mounting holes with screws provided.
5. Replace the thermostat cover.
NOTE
Refer to installation instructions packed in the thermostat carton if you have
any doubt about the above procedures.
Connect thermostat wire, previously run to burner compartment from thermostat,
to control valve as shown in Fig. 20.
ROUTE THERMOSTAT CABLE
SMALL FINISH NAIL TO EOCATE HEADER 1HERMOSTAT CABt_
THERMOSTAT
GENERATOR
RED-_,
_–WHITE
BLUE KNOB
GENERATOR THERMOSTAT
LIMIT SWITCH
LIMIT SWITCH
“_ WILLIAMS P172100A (OR) P172200A
WILLIAMS
P295000A (OR) P295001A
GREEN KNOB
–16–
B*’WVENT_
Cabinet installation
PANEL ATTACHING SCREW
B/W !
IG SCREW EA SIDE
MODELS
2509611 2509612 2509621 2509622
AND
3509611 3509612 3509621 3509622
MODELS
5009611 5009612 5009621 5009622
BOTTOM PANEL
MENT (2} SCREWS EACH SIDE
CASING/ LEGS
(CONTROL) FLOOR PLAlr E
Place panel top over channel on header plate, as shown in Fig. 21. Press panel
tight against wall, and secure it to header with screw provided in final
assembly package. Open control door at bottom of panel and fasten panel at
each side through slots in flanges with screws provided.
Attach handle to panel door with screws provided.
Models 5009611, 5009612, 5009621 and 5009622: Install second face panel in
same manner.
LEGS
PANEL DOOR (CONTROL)
FLOOR PLATE
NOTICE
DURING THE FIRST FIRING OF THIS UNIT SOME SMOKE AND ODOR MAY OCCUR. WE
RECOMMEND VENTILATING THE AREA DURING THIS “BREAK IN” PERIOD. LET FURNACE
REACH FULL OPERATING TEMPERATURE.
Start-Up Procedure
Start the furnace using the procedures in section OPERATING YOUR FURNACE.
exceed the input of the rating plate reduced by 4 percent for each 1000 feet that the furnace is above sea level.
WARNING
DANGER OF PROPERTY DAMAGE, BODILY INJURY OR DEATH.
Gas supply pressure and manifold pressure with the
burners operating must also be as specified on the rating plate.
LIQUEFIED PETROLEUM L.P. GAS IS HEAVIER THAN AIR AND IT WILL SETTLE IN ANY LOW
Type of Gas ] Manifold Pressure, In. W.C.
AREA, INCLUDING OPEN DEPRESSIONS AND IT
WILL REMAIN THERE UNLESS AREA IS VENTILATED.
NEVER ATTEMPT STARTUP OF UNIT BEFORE THOROUGHLY VENTILATING AREA.
NaLtu.Rral
I
141
Rated input will be obtained on 2500 Btu propane at 11 inch manifold pressure and factory-sized orifices. If LP gas having a different heating value is supplied, orifices must
Check the furnace operation as outlined in the following instructions. If any sparking, odors or unusual noises are
be changed by a qualified service technician before the furnace is operated.
encountered, shut off electric power immediately. Recheck
CHECK THE MANIFOLD GAS PRESSURE
for wiring errors, or obstructions in or near fan motor (if equipped).
A tapped opening is provided in the gas valve to facilitate measuring the manifold gas pressure. A “U Tube”
CHECK GAS INPUT AND PRESSURES
manometer having a scale range from 0 to 12 inches of water should be used for this measurement. The manifold
For furnace located at elevations between sea level and
pressure must be measured with the burner and pilot
2000 feet, the measured input must not be greater than
operating. Any major changes in the flow must be made
the input shown on the rating plate of the furnace. For
by changing the size of the burner orifice. Check with your
elevations above 2000 feet, the measured input must not
WILLIAMS service department for proper orifice sizing.
n17–
Start.Up Procedure (Con’t)
CHECK THE GAS INPUT (NATURAL GAS ONLY)
-WARNING
NATURAL GAS HEATING VALUE (BTU PER CUBIC FOOT) CAN VARY SIGNIFICANTLY,
THEREFORE, IT IS THE INSTALLERS’ RESPONSIBILITY TO SEE THAT BTU INPUT TO THE
FURNACE IS ADJUSTED PROPERLY. FAILURE TO DO SO COULD CAUSE HEAT EXCHANGER
FAILURE, ASPHYXIATION, FIRE OR EXPLOSION, RESULTING IN DAMAGE, BODILY INJURY
OR DEATH. REFER TO THE NA-
TIONAL FUEL GAS CODE (NFPA-54) TO BE SURE THE FURNACE IS BURNING FUEL AT THE
PROPER RATE.
SLOTTING
IN EIURNI_ BOOY
TOP V1EW
Underfiring could cause inadequate heat, excessive condensation or ignition
problems. Overfiring could cause sooting flame impingement or overheating of
heat exchanger.
Before starting natural gas input check, obtain heating value of gas (BTU per
cubic foot) at standard conditions from your local supplier. This factor is
used in “Check the Gas Input” section and procedure.
To measure the input using the gas meter, proceed as follows:
Step 1: Turn off gas supply to all other appliances except the furnace.
Step 2: With the furnace operating, time the smallest dial on the meter for
one complete revolution. If this is a 2 cubic foot dial, divide the seconds by
2; if it is a 1 cubic foot dial, use the time in seconds as is. (3,600 = Sac.
Per Hr.) This gives the seconds per cubic foot of gas being delivered to the
furnace.
Step 3: Assuming natural gas with a heating value of 1000 Btu per cubic foot
and 34 seconds per cubic foot as determined by step (2), then: Input: 1,000 X
3,600 + 34 = 106,000 Btu Per Hour
GENERATOR “IHERMOCOUPLE
FRONT _EW
This measured input must not be greater than the input indicated on the rating
plate of the furnace.
Step 4: Relight all other appliances turned off in step 1 above. Be sure all
pilot burners are operating.
CHECK PILOT BURNER
The pilot flame must envelop 1/2 to 5/8 inch of thermocouple or generator. See
Fig. 22. Pilot flame is preset at the factory, so ordinarily does not require
field adjustment. If adjustment is needed, see page 24.
CHECK THERMOSTAT
Check thermostat operation. When set above temperature shown on the
thermostat, the main burner should light. Make certain the thermostat turns
off the furnace when room temperature reaches the selected setting and starts
the furnace when room temperature falls a few degrees.
Operating Your Furnace
MODELS 2509611 ; 3509611 ; 5009611
The furnace operates like this:
2509612; 3509612; 5009612 NOTE: SEE PAGE 21 FOR MODEL INFORMATION NOTE.
1. Cool air around built-in sensing bulb automatically turns on the burner.
SAFETY, OPERATING AND SHUTDOWN All models listed above are equipped with a Williams gas
2. Heat builds up in the furnace and starts the fan (if equipped). The heated air comes out the front panel louvers.
control valve part number P322051; P322052 (see page
3. When the built-in sensing bulb is sufficiently heated
- or part number P295100A; P295101A (see page 20).
WARNING
/
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS NEAR THE FURNACE.
J|
by the warmer room air it automatically turns off the main burner. 4. The fan runs until the heat is removed from furnace, then it will turn off (if equipped). NOTE: On new installation the gas lines will be filled with
WARNING’
air and may take several minutes to establish the pilot flame.
DANGER OF PROPERTY DAMAGE,
–MANUAL
SPARK IGNITER USAGE:–
BODILY INJURY OR DEATH
If furnace is equipped with a manual spark ignitor,
IF THE FURNACE OVERHEATS OR FAILS TO SHUT OFF, CLOSE MANUAL GAS VALVE FOR THE FURNACE BEFORE TURNING OFF ELECTRIC POWER FOR THE FAN.
follow these next steps:
1. Review the operating instructions on preceding
pages. 2. When instructed to “light the pilot” depress red
button located on the burner pan for pilot ignition.
Your furnace is equipped with a 100% safety pilot which
will shut off the gas supply in case the pilot is not burning or functioning
properly. Make sure the pilot is adjusted properly and that the thermocouple
connection at the control valve is tight. If furnace will not stay lit, call
your local
If necessary, depress red button several times for pilot ignition.
3. If pilot fails to ignite or a spark is not present while actuating red
button, follow steps 5 through 10 listed in operating instructions.
clas utility or qas sul_plier.
–18–
FOR YOUR SAFETY, READ BEFORE LIGHTING
WILLIAMS GAS CONTROL VALVE P322051 & P322052
I I WARNmINaGy: resIfulytoucaduosinngot pfroolploewrty thedsaemaIgnes,trucpteiorsnosnal exiancjutlryy, oar filrosssorofexlipfelo.sion I
A. This appliance has a pilot which must be Ilghfed by hand. When lighting the
pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell around the appliance area for gas. Be sure to smell
next to the floor because some gas is heavier than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch any electric switch; do not use any
phone in your building. · Immediately call your gas supplier from a neighbor’s
phone. Follow the gas aupplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.
C, Use only your hand to push In or turn the gas control knob. Never use
tools. If the knob will not push in or turn by hand, don’t try to repair It,
call a qualified servIce technician. Force or attempted repair may result In ·
fire or explosion.
D, Do not use this appliance if any part has been under water. Immediately
call · qualified service technician to inspect the appliance and to replace
any pert of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above. 2. Turn off all electric power to
the appliance (if applicable). 3, Open control access panel. 4. Turn
temperature dial clockwise F’ to “LO”.
5, Push in gas control knob slightly and turn clockwise f- to “OFF.”
TEMPERATURE
DIAL_
[@ ._ “L
t’J(‘
@l
@l / GAS CONTROL
, I .
J/” KNOB SHOWN
...J /’1’_[
IN “OFF”
NOTE: Knob cannot be turned from “PILOT” to “OFF” unless knob is pushed in
slightly. Do not force,
6. Wait five (5) minutes to clear out any gas then smell for gas, including
near the floor. If you then smell gas, stopl Follow “B” in the safety
information above. If you don’t smell gas, go to next step.
7. Loosen wingnut and open the pilot observation door (if equipped).
8. Find pilot–follow metal tube from gas control. The pilot is mounted on
side of burner.
9. Push in gee control knob slightly and turn
counterclockwise _ to “PILOT.”
10. Push in control knob all the
way end hold in. Immediately light the pilot.
THERMO- PILOT COUPLE BURNER
Continue to hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 10.
· If knob does not pop up when released,
immediately call your service technician supplier.
stop and or gas
· If the pilot will not stay lit after several tries, turn
the gas control knob to “OFF” and call your service
technician or gas supplier.
11. Close pilot observation door, tighten wingnut
(if equipped). 12. Turn gas control knob counterclockwise
’ to “ON”.
Sensing bulb is now activated. Set temperature desired temperature (1 – 5).
13. Close control access panel.
14. Turn on all electric power to the appliance
(if applicable).
dial to
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance if service is to be performed
(if applicable).
2. Open control access panel.
3. Push in gas control knob slightly and turn clockwise _ to “OFF.” Do not
force.
4. Close control access panel.
WARNING: DUE TO HIGH SURFACE TEMPERATURES — KEEP CHILDREN, CLOTHING, FURNITURE
OR ANY COMBUSTIBLE MATERIAL AWAY FROM FURNACE.
IMPORTANT: KEEP BURNER AND CONTROL COMPARTMENT CLEAN, SEE PAGE 24.
CONNECTION
[
BLACK
WIRING DIAGRAM FOR BUILT-IN
MOOOUP ,
GAS VALVE
I
REMOTE BULB
THERMOSTAT MODELS
LEGEND
—
FACTORY WIRED LOW VOLTAGE
NOTE:
IF ANY OF THE ORIGINAL WIRE AS SUP-
PLIED WITH THE APPLIANCE HAS TO BE
REPLACED, USE ONLY 18 GA. 4/64 IN-
SULATION, 105° C. AWM COPPER WIRE OR
ITS EQUIVALENT
FOR YOUR SAFETY, READ BEFORE LIGHTING
WILLIAMS GAS CONTROL VALVE P295100A & P295101A
I WARNmINaGy: resIfulyt oucaduosinngot pfroollpoewrty thedsaemaignes,trupcetirosnosnal exiancjutlryy, oar filroessorofexlipfelo.sion
A. This appliance has a pilot which must be lighted by hand. When lighting the
pilot, follow these Instructions exactly.
B. BEFORE LIGHTING smell around the appliance area for gas. Be sure to smell
next to the floor because some gas is heavier than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch any electric switch; do not use any
phone In your building. · Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push In or turn the gas control knob. Never use
tools. If the knob will not push In or turn by hand, don’t try to repair It,
call e qua,fled sentice technician. Force or attempted repair may result In a
fire or explosion.
B. Do not use this appliance If any part has been under water. Immediately
call a qualified service fechnlclan to inspect the appliance and to replace
any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOPI Read the safety information above. 2. Turn off all electric power to
the appliance (if applicable). 3. Open control access panel. 4. Push in gas
control knob slightly and turn
clockwise F’_ to “OFF.”
TEMPERATURE DIAL
KNOB SHOWN IN “OFF”
8. Turn knob on gas control
1
counterclockwise to “PILOT.”
9. Push in control knob all the way and hold in. Immediately light the pilot.
THERMO- PILOT COUPLE BURNER
Continue to hold the control knob in for about one (I) minute after the pilot is lit. Release knob and It wnl
pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 10.
POSITION
· If knob does not pop up when released, stop and immediately call your service technician or gas supplier.
NOTE: Knob cannot be turned from “PILOT” to “OFF” lo. unless knob is pushed in slightly. Do not force.
· If the pilot will not stay lit after several tries, turn the gas control
knob to “OFF” and call your service technician or gas supplier.
Close pilot observation door, tighten wJngnut (if equipped).
5. Wait five (5) minutes to clear out any gas then smell for
gas, including near the floor. If you then smell gas, stopl Follow “B” in the
safety information above. If you don’t smell gas, go to next step. 6. Loosen
wingnut and open the pilot observation door (if equipped).
11. Turn gas control know counterclockwise I_ to “ON”. Burner is now under control of the thermostatic sens-
ing element. Turn temperature dial (numbered 1 thru 8)
counterclockwtae_toward
8 to obtain desired
temperature.
12. Close control access door
7. Find pilot–follow metal tube from gas control. The pilot is mounted on side of burner,
13. Turn on all electric power to the appliance (if applicable)
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance if service is to be performed
(if applicable),
2. Open control access panel,
3. Push in gas control knob slightly and turn clockwise f_, to “OFF.” Do not
force.
4. Close control access panel.
WARNING: DUE TO HIGH SURFACE TEMPERATURES — KEEP CHILDREN, CLOTHING, FURNITURE
OR ANY COMBUSTIBLE MATERIAL AWAY FROM FURNACE.
IMPORTANT: KEEP BURNER AND CONTROL COMPARTMENT CLEAN, SEE PAGE 24.
CONNECTION WIRING DIAGRAM FOR BUILT-IN
VENT SAFETY SHUT OFF DE’VICE
_ ‘I’HERMOCOUPLE
II
I
GAS VALVE
BLACK
RE),IOTE BULB
–20–
THERMOSTAT MODELS
LEGEND
—
FACTORY WIRED LOW VOLTAGE
NOTE:
IF ANY OF THE ORIGINAL WIRE AS SUP-
PLIED WITH THE APPLIANCE HAS TO BE
REPLACED, USE ONLY 18 GA., 4/64 IN-
SULATION, 105e C. AWM COPPER WIRE OR ITS EQUIVALENT
Operating Your Furnace (Con’t)
MODELS 2509621; 3509621; 5009621 2509622; 3509622; 5009622
SAFETY, OPERATING AND SHUTDOWN All models listed above are equipped with a
Williams gas control valve part number P172100A; P172200A (see page 22) or
part number P295000A; P295001A (see page 23).
WARNING
FLAMMABLE LIQUIDS OR VAPORS NEAR THE I DFUORNNAOCTES. TORE OR USE GASOLINE OR
OTHER
WARNING
DANGER OF PROPERTY DAMAGE, BODILY INJURY OR DEATH
IF THE FURNACE OVERHEATS OR FAILS TO SHUT OFF, CLOSE MANUAL GAS VALVE FOR THE
FURNACE BEFORE TURNING OFF ELECTRIC POWER FOR THE FAN.
Your furnace is equipped with a 100% safety pilot which will shut off the gas
supply in case the pilot is not burning or functioning properly. Make sure the
pilot is adjusted properly and that the pilot generator connection at the
control valve is tight. If furnace will not stay lit, call your local gas
utility or gas supplier.
The furnace operates like this: 1. Thermostat turns on the main burner.
2. Heat builds up in the furnace and starts the fan (if equipped). The heated
air comes out the front panel louvers.
3. When the thermostat setting is reached, it shuts off the main burner.
4. The fan runs until the heat is removed from furnace, then it turns off.
NOTE
On new installation the gas lines will be filled with air and may take several
minutes to establish the pilot flame.
–MANUAL
SPARK IGNITER USAGE:-
If furnace is equipped with a manual spark ignitor, follow these next steps:
1. Review the operating instructions on preceding
pages. 2. When instructed to “light the pilot” depress red
button located on the burner pan for pilot ignition. If necessary, depress red
button several times for pilot ignition. 3. If pilot fails to ignite or a
spark is not present while actuating red button, repeat steps 5 through 10
listed in operating instructions.
–MODEL
NUMBER INFORMATION–
NOTE: CANADIAN MODEL NUMBERS THIRD DIGIT FROM LEFT TO BE: 1 FOR BASIC
ALTITUDES 2 FOR HIGH ALTITUDES EXAMPLE: MODEL: 3509612 BECOMES 3519612
(0-2000 FT. BASIC ALTITUDE) OR BECOMES 3529612
(2000-4000 FT. HIGH ALTITUDE)
D21–
FOR YOUR SAFETY, READ BEFORE LIGHTING
WILLIAMS GAS CONTROL VALVE P172100A & P172200A
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal Injury or loss of life.
I
A. This appliance has a pilot which must be lighted by hand. When lighting the
pilot, follow these Instructions exactly.
B. BEFORE LIGHTING smell around the appliance area for gas. Be sure to smell
next to the floor because some gas Is heevler than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch any electric switch; do not use any
phone in your building. · Immediately call your gas supplier from s neighbor’s
phone. Follow the gas suppller’s Instructions.
· If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push In or turn the gas control knob. Never use
tools. If the knob will not push In or turn by hand, don’t try to repair it,
call a qualified servIce technician. Force or attempted repair may result In a
fire or explosion.
D. Do not use this appliance If any part has been under water. Immediately
call a qualified service technician to inspect the appUance and to replace any
part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above. 2. Turn off all electric power to
the appliance (if applicable). 3, Set the thermostat to lowest setting. 4.
Open control access panel. 5, Push in gas control knob slightly and turn
clockwise _ to “OFF.”
_’
@!
CONTROL
KNOB SHOWN IN”OFF’POSiTION
NOTE: Knob cannot be turned from “PILOT” to “OFF”
unless knob is pushed in slightly. Do not force.
6. Wait five (5) minutes to clear out any gas then smell for gas, including
near the floor. If you then smell gas, stop! Follow “B” in the safety
information above. If you don’t smell gas, go to next step.
7. Loosen wingnut and open the pilot observation door (if equipped).
8. Frnd pilot–follow metal tube from gas control. The pilot is mounted on
side of burner.
GENERATOR
n
9. kPnuosbh sinlighgtalys coanntdrolturn
….._ J__
counterclockwise _ to “PILOT.”
PILOT
10. Push in control knob all the way and hold in. Immediately light the pilot.
BURNER
Continue to hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will
pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 10.
· If knob does not pop up when released, stop and immediately call your service tachnlclan or gas supplier.
· If the pilot will not stay lit after several tries, turn
the gas control knob to “OFF” and call your service technician or gas
supplier.
11. Close pilot observation door, tighten wingnut (it equipped).
12. Turn gas control knob counterclockwise_to
“ON”.
13. Close control access panel. 14. Turn on all electric power to the
appliance
(if applicable).
15. Set thermostat to desired setting.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Open control access panel.
4. From “ON” position, depress and turn gas control knob clockwise _ 5. Close control access panel.
to “OFF”
position. Do not force.
WARNING: DUE TO HIGH SURFACE TEMPERATURES — KEEP CHILDREN, CLOTHING, FURNITURE
OR ANY COMBUSTIBLE MATERIAL AWAY FROM FURNACE.
IMPORTANT: KEEP BURNER AND CONTROL COMPARTMENT CLEAN, SEE PAGE 24.
CONNECT;ON WIRING DIAGRAM FOR WALL THERMOSTAT MODELS
T:’_E’M= ©STAT
GENE,ATOR -_
OEVIC_
BLACK _
3 L_,C:<
LEGEND
—
FACTORY WIRED LOW VOLTAGE
NOTE:
IF ANY OF THE ORIGINAL WIRE AS SUP-
PLIED WITH THE APPLIANCE HAS TO BE
REPLACED, USE ONLY 18 GA., 4/64 IN-
SULATION, 105″ C. AWM COPPER WIRE OR ITS EQUIVALENT
/)LACK
I
J
m22–
FOR YOUR SAFETY, READ BEFORE LIGHTING
WILLIAMS GAS CONTROL VALVE P295000A & P295001A
I WARNmINaGy: resIfulytoucaudsoinngot pfroollpoewrty thedsaemaignes,trucpteiorsnosnal exiancjutlryy, oar filroessorofexlipfelo.sion
A. This appliance has a pilot which must be lighted by hand. When lighting the
pilot, follow these Instructions exactly.
S. BEFORE LIGHTING smell around the appliance area for gas. Be sure to smell
next to the floor because some gas is heavier than sir and will settle onthe
floor.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch sny electric switch; do not usa any
phone in your building. · Immediately call your gas supplier from a neighbor’s
phone. Follow the gas suppiler’s instructions.
· If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use
tools. If the knob will not push In or turn by hand, don’t try to repair it,
call a qualified service technician. Force or attempted repair may result In s
fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to Inspect the appliance and to replace
any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOPi Read the safety Information above. 2. Set the thermostat to lowest
satting. 3. Turn off sU electric power to the appliance (if applicable). 4.
Open control access panel. 5. Push in gas control knob slightly and turn
clockwise _ to “OFF.”
9. Push in gas control
GENERATOR _
knob slightly and turn
counterclOCkwise to “PILOT.”
10. Push in control knob all the way and hold in. Immediately light the pilot.
PILOT BURNER
GAS CONTROL KNOB SHOWN IN “OFF” POSITION
Continue to hold the control knob in for about one (1) minute after the pilot
is lit. Release knob and it will
pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through
10.
· if knob does not pop up when released,
immediately call your sa_ice technician supplier.
stop and or gas
NOTE: Knob cannot be turned from “PILOT” to “OFF”
unless knob is pushed in slightly, Do not force.
6. Wait five (5) minutes to clear out any gas then smell for gas, including
near the floor, if you then smell gas, stop! Follow “B” in the safety
information above. If you don’t smell gas, go to next step.
7. Loosen wlngnut and open the pilot observation door (if
equipped). 8. Fiend pilot–follow metal tube from gas control. The pilot is
mounted on side of burner.
· If the pilot will not stay lit after several tries, turn
the gas control knob to “OFF” and call your service technician or gas
supplier.
11. Close pilot observation door, tighten wingnut (if equipped).
12. Turn gas control knob counterclockwise _
13. Close control access panel.
to “ON”.
14. Turn on sli electric power to the appliance (if applicable).
15. Set thermostat to desired setting.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting. 2. Turn off all electric power to
the appliance if service is to be performed.
3. Open control access panel. 4. Push in gas control knob slightly and turn
clockwise _ to “OFF”. Do not force.
5. Close control access panel.
WARNING: DUE TO HIGH SURFACE TEMPERATURES — KEEP CHILDREN, CLOTHING, FURNITURE
OR ANY COMBUSTIBLE MATERIAL AWAY FROM FURNACE.
IMPORTANT: KEEP BURNER AND CONTROL COMPARTMENT CLEAN, SEE PAGE 24.
CONNECTION WIRING DIAGRAM
VENT SAFETTHE. SHUT OFF DEVICEI_
TAT -I
r-] GENERATOR
II
r—–1
i
BLACK
FOR WALL THERMOSTAT MODELS
GAS VALVE
LEGEND
—
FACTORY WIRED LOW VOLTAGE
NOTE:
IF ANY OF THE ORIGINAL WIRE AS SUP-
PLIED WITH THE APPLIANCE HAS TO BE
REPLACED, USE ONLY 18 CA., 4/64 IN-
SU LATION, 105° C. AWM COPPER WIRE OR
ITS EQUIVALENT
–23–
How To Care For Your Furnace
WARNING DANGER OF BODILY INJURY OR DEATH TURN OFF ELECTRIC POWER SUPPLY AT
DISCONNECT SWITCH, FUSE BOX OR SERVICE PANEL BEFORE REMOVING ANY DOORS OR
ACCESS OR SERVICE PANELS FROM UNIT.
CABINET FINISH
Clean cabinet with damp rag. Never use abrasive cleaners. Cabinets are
finished in heat resistant baked enamel -DO NOT refinish with wall paint.
FURNACE AREA
Keep the area near the furnace clear and free from combustible materials,
gasoline, and other flammable liquids and vapors.
COMBUSTION AND VENTILATION AIR
The combustion and ventilation air supply must not be blocked.
Do not put anything in or on the furnace cabinet. For better circulation and
more effective heating, do not place obstructive furniture closer than four
feet to the front of the cabinet or two feet to the side of the cabinet.
ANNUAL UPKEEP NEEDED
It is recommended that a qualified service technician perform these checks at
the beginning of each heating season.
CLEANING OPTIONAL FAN (If Equipped) Shut off electricity, then remove screws
and face panel. Clean any lint or dirt from fan blades, fan motor, and exposed
air passages. Use a brush. See page 33.
PILOT BURNER
Light pilot using instructions in OPERATING YOUR FURNACE on pages 18 through
23. Leave thermostat at lowest setting. Pilot flame should surround 1/2 to 5/8
inch of the generator or thermocouple tip. Refer to Fig. 22, page 18. If flame
needs adjusting, do so as follows:
ADJUST PILOT BURNER
See Fig. 22, page 18 and Fig. 23. 1. Remove screw cover over pilot adjusting
screw. 2. Insert small screwdriver. Adjust flame as needed. Turn
screw counterclockwise (=-‘–,)to increase flame, clockwise (,–_) to decrease.
3. Turn thermostat to highest setting. Main burners should light quickly and
smoothly. Turn thermostat to lowest setting. Main burners should go out. Pilot
should remain lit.
4. Replace screw cover with gasket over pilot adjusting screw.
BURNER FLAME
Start the furnace and let it operate about 10 minutes then look at the burner
flame. Flames should be soft and blue, see Fig. 23. If flames appear abnormal,
contact the gas company or a qualified service technician immediately.
NOTE
No adjustment is provided, or is necessary, for models equipped with welded
formed steel burners.
MAIN BURNER FLAME PATTERN
Jl II It li
llBII
CORRECT
INSUFFICIENT AIR · LONG OPEN END CONES¸ YELLOW IN COLOR
INNER CONES lIGHT BLUE POINTED TOI
OUTER MANTLE LIGHT BLUE PROPER FLAME I/2 ‘r Io 3/4 ¸. H_GH
ADJUST MAIN BURNER FLAME PATTERN
Top vented wall furnaces equipped with cast iron burners have an interrupter
screw located under the burner body and extends into the burner neck
(venturi). This screw is used to adjust the primary air to fuel mixture for
proper burner flame. Allow furnace to operate about 10 minutes before making
adjustments.
Burner flames should be a series of blue cones slightly orange at the tips.
When flames are sharp and blue with no orange visible, turn air adjusting
screw in burner venturi clockwise until very short orange tips are visible. If
flames are lazy and yellow, turn air screw counterclockwise to eliminate
yellow. See Fig. 23.
VENT SYSTEM
Make sure that no parts of the venting system are blocked or rusted. Clean or
replace before using furnace.
–24–
How To Care For Your Furnace (ton’t)
WARNING MAKE SURE GAS SUPPLY IS OFF BEFORE I REMDOAVNINGGER POAFNEBLOSDIOLRY DINOJOURRSY, OERTCD. EATH
FURNACE CONTROLS
ELEMENT
THERMOCOUpIF
RATING PI..AT_
INN_ BOOY
I_MP.
GAS
GAS INPUT
FURNACE:
CAL’_ KNOB
MANUAL SHUT-O_”
OUN11NG
LEG REMOTE
VALVE _’-DRIP LEG
“_IERMO BULB
GROUND
(ATTACHED UNDERSIDE OF VALVE) JOINT UNION
RTIING
CLEANING BURNER COMPARTMENT
Because cold air is attracted to the flame during furnace operation, a build
up of lint from bedding and dust (etc.)
in the burRer area will occur each heating season. It is necessary to clean
this area regularly. Use a vacuum cleaner with a narrow attachment to reach
small areas. Be careful in and around the pilot. A change in its adjustment
could be made if struck during cleaning.
BURNER CLEANING
Check burner. If cleaning is required, contact a qualified service technician
to clean and service burner.
TO REMOVE BURNER(S)
Clean all foreign materials from top of burner. For access to burner of all
models:
1. Open burner compartment door.
2. Shut off gas supply to furnace (Manual Shut-Off Valve).
3. Disconnect gas line inside cabinet at ground joint union fitting. See Fig.
24.
4. Remove (2) screws securing burner pan assembly to inner liner.
NOTE
If furnace is equipped with a welded formed steel burner, remove additional
(2) screws securing burner to heating element.
5. Pull burner pan assembly forward approximately 1/2 inch and drop down to
expose top of burner.
6. After cleaning, replace burner pan assembly by reversing above procedure.
Furnace Technical Information
MODEL NUMBER
2509612 2509622
2509611 2509621
3509612 3509622
3509611 3509621 5009612 5009622
5009611 5009621
TYPE GAS NAT. L.P. NAT. L.P. NAT. L.R
INPUT RATING BTU/HR**
25,000
HTG. CAPAC. MAIN BURNER ORIFICE
RATING
BTU/HR**
DRILL DEC. QTY.
19,350
43
.089
1
25,000
19,350
54
.055
1
35,000
25,930
38
.101
1
35,000
25,930
52
.063
1
50,000
38,000
43
.089
2
50,000
38,000
54
.055
2
**For elevations above 2000 feet reduce ratings 4% for each 1000 feet above sea level. ***Btuh = British Thermal Units per hour. The efficiency rating of these appliances is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system.
–25–
WILLIAMS
TROUBLE SHOOTING GAS-FIRED TOP VENT GRAVITY
WALL FURNACE
SYMPTOM 1. Pilot will not stay lit after
carefully following lighting instructions.
2. Pilot burning – no gas to main burner.
3. Furnace operates but turns “Off” before room temperature is attained.
POSSIBLE CAUSES A. Thermocouple or
generator producing insufficient millivoltage. B. Loose or dirty thermocouple
or generator connections at gas valve. C. Thermocouple or generator defective.
D. Grounded thermostat lead wire. (Wall thermo* stat model.)
E. Thermomagnetic pilot safety defective.
F. Vent Safety Shutoff System.
A. Manual valve not turned to “On” position after lighting pilot.
B. Temperature dial or thermostat not turned to a position calling for heat.
C. Plugged burner orifice. D. Temperature dial out of
calibration. (Bulb control model.) E. Mis-wired or broken thermostat wires.
Defective thermostat. (Wall thermostat model.) F. Pilot generator may not be
generating sufficient millivoltage to open valve. G. Defective valve.
A. Sensing bulb not located properly. (Bulb control model.)
B. Temperature dial out of calibration. (Bulb control model.)
CORRECTIVE ACTION Check pilot flame – must impinge on thermocouple or
generator. Be sure thermocouple or generator is fully inserted in bracket.
Clean and/or tighten thermocouple or generator connections at valve.
Check thermocouple with millivolt meter. Should generate approximately 30
millivolts when not connected to load. When connected to load, should generate
approximately 14 millivolts; if below 7 millivolts, replace. Check generator
with millivolt meter. Take reading at generator terminals of valve with pilot
burning and thermostat contacts closed. Should be 140 millivolts or more.
Remove thermostat lead wires from valve terminals. If pilot now stays lit,
trace thermostat wiring circuit for a ground. May be grounded to furnace or
gas supply. Replace gas valve after above is checked out.
Check wiring connections from valve to vent safety shutoff device. Be sure all
connections are tight. Check for blocked vent or disconnected vent. Turn gas
valve knob to “On” position.
Set temperature dial or thermostat to a position calling for heat.
Check – clean or replace. See valve instruction sheet.
Check connections at valve terminals. If valve operates check thermostat
wires.
Sea 1A above.
Replace. Check location of sensing bulb – see Fig. 24, page 25.
See valve instruction sheet.
(Continued next page
–26–
WILLIAMS
TROUBLE SHOOTING
GAS-FIRED TOP VENT GRAVITY
WALL FURNACE
SYMPTOM
3. Furnace operates but turns “Off” before room temperature is attained.
(continued)
4. Furnace not producing sufficient heat.
POSSIBLE CAUSES
C. Thermostat location. (Wall thermostat model.)
D. Defective thermostat. (Wall thermostat model.)
A. Furnace may be too small for space being heated.
B. Furnace not burning at full rate.
5. Furnace operates but will not shut “Off” when
room temperature is attained.
A. Sensing bulb not located properly. (Bulb control model.)
B. Temperature dial out of calibration. (Bulb control model.)
C. Bulb or capillary broken. (Bulb control model.)
D. Thermostat wiring defective. (Wall thermostat model.)
E. Thermostat location. (Wall thermostat model.)
6. Pilot outage problem. 7. Abnormal operation.
F. Defective thermostat. (Wall thermostat model.)
G. Dirt under valve seat or valve stuck open.
A. Pilot flame may be low or blowing (high) causing safety to drop out.
A. Delayed ignition – pilot flame may be too low.
B. Expansion noise ticking.
C. Spillage
D. Excessive flame roll-out.
CORRECTIVE ACTION Check thermostat location – should not be in the path of
warm air discharge from furnace, near a lamp, or above a TM. or stereo set.
Check thermostat calibration or replace.
Check heat loss calculations.
Check for low gas pressure at gas valve – should be 4″ W.C. for natural gas;
11″ W.C. for L.RG. Check burner orifice.
Check location of sensing bulb – see Fig. 24, page 25.
See valve instruction sheet.
Replace valve.
Thermostat lead wires may be shorted together caused by a nail or staple –
check by removing thermostat leads from valve terminals. Check thermostat
location – if on an outside wall or a hole in wall behind thermostat causing
cold air to contact thermostat – relocate. Check thermostat calibration or
replace.
Replace valve.
Adjust pilot flame. Pilot orifice or aerating hole may be plugged (check for
spider webs or other organic material). Adjust pilot flame.
Check installation – casing may be distorted by being fastened to an uneven
opening or jammed under header.
Check vent system – may be blocked flue, excessive down draft (wind) or
negative pressure in room caused by ventilating fan or a fire in a fireplace,
Correct as necessary. Furnace possibly over rate – check for high gas pressure
at gas valve (see 4B above).
m27m
WILLIAMS GAS-FIRED TOP VENT GRAVITY WALL FURNACE
REPLACEMENT PARTS LIST FOR MODELS 2509611; 2509612; 2509621; 2509622 3509611;
3509612; 3509621; 3509622
REF. PART NO. NO.
DESCRIPTION
1
4915
FACE PANEL
2
9C155
FRONT HEAT SHIELD
3
9D52
3
9D54
4
9B199
COMBUSTION CHAMBER COMBUSTION CHAMBER DEFLECTOR
ASSY.ASSY. –
2509611; 3509611;
2509612; 3509612;
2509621; 3509621;
2509622 .3509622
5
9C153
INNER SHIELD TOP
6
9C166
DRAFTHOOD ASSEMBLY- 2509611; 2509612; 2509621; 2509622
6
9C165
DRAFTHOOD ASSEMBLY- 3509611; 3509612; 3509621; .:3509622
7
P321826 LIMIT SWITCH- 2509611; 2509612; 2509621; 2509622
7
P322055 LIMIT SWITCH – ,3509611; 3509612; 3509621; .3509622
8
9C172-1 SHIELD ASSEMBLY
9
5902
HEADER ASSEMBLY (REF. 9B56-1)
10 6901
11
“_ REAR OUTLET
/
REAR PLASTERGROUND _–‘—REAR
OUTLET REGISTER
9901
OVAL B//W VENT KIT
“A- P320994
DOOR HANDLE
‘A- P322085
OWNERS MANUAL
,A-NOT SHOWN “_ NOT AVAILABLE SEPARATELY
(KIT FORM ONLY)
NOTE: SCREWS AND BOLTS ARE STANDARD HARDWARE ITEMS, AVAILABLE LOCALLY.
FOR PARTS ILLUSTRA]3ONS, SEE BELOW AND PAGE 29
REAR OUTLET REGISTER 6901
m28–
WILLIAMS GAS-FIRED TOP VENT GRAVITY WALL FURNACE
REPLACEMENT PARTS FOR MODELS
2509611;
2509612;
2509621;
2509622
3509611;
3509612;
3509621;
3509622
I
I
–29–
USE ONLY MANUFACTURER’S AUTHORIZED PARTS
=,,_
ip,lo.,,e3
WILLIAMS GAS-FIRED TOP VENT GRAVITY WALL FURNACE
CONTROL ASSEMBLY REPLACEMENT PARTS LIST FOR MODELS –
2509611; 2509612; 2509621; 2509622 3509611; 3509612; 3509621; 3509622
REF. PART NO. NO.
1
9Ct05
1
P025600
2
P043800
3
P321837
3
P179800
3
P322274
3
P322275
4
9C104
4
9B59
5
P321828
6
P322051
6
P522052
6
P172100A
6
P172200A
7
P328500
8
P090500
9
P026200
10
9A106
11
12A01
12 P321856
13 P522016
DESCRIPTION
T-BURNER (FORMED STEEL, NAT. GAS ONLY) BURNER (CAST IRON) GENERATOR PILOT
BURNER PILOT BURNER PILOT BURNER PILOT BURNER BURNER PAN ASSEMBLY (T-BURNER)
BURNER PAN ASSEMBLY (CAST IRON) TERMINAL BLOCK THERMOCOUPLE CONTROL GAS VALVE
CONTROL GAS VALVE CONTROL GAS VALVE CONTROL GAS VALVE ORIFICE ADAPTER ORIFICE
(SPECIFY GAS TYPE & INPUT) LOCKNUT MANIFOLD RETAINER (CAST IRON BURNER)
MANIFOLD ASSEMBLY (CAST IRON BURNER) WIRE ASSEMBLY (2 REQUIRED) THERMOSTAT
; 00000000
XX X
XX X
XX X
X XX XX
X
XX X XX X×X
X X X XX
_LO u3 LO
Cxl r,o OJ
XX
X
XX
:X X X X
X XX
XX
XX
X
XX
X
X
XX
XX
XX
X ‘X X X X
XX X X X
X
XX
X
XX
X XX X X
;X X X X
FOR PARTS ILLUSTRATIONS, SEE PAGE 31
“X” DENOTES USAGE
NOTE: SCREWS AND BOLTS ARE STANDARD HARDWARE ITEMS, AVAILABLE LOCALLY.
m30–
WILLIAMS
2509611;
GAS-FIRED TOP VENT GRAVITY WALL FURNACE
REPLACEMENT PARTS FOR MODELS -2509612: 2509621; 2509822; 3509811; 3509612;
3509621;
FOR REPLACEMENT PARTS LISTING SEE PAGE 50
3509622
NAT. GAS CONTROL ASSEMBLY
L.P. GAS CONTROL ASSEMBLY
I I
I
I I
I
I
WILLIAMS GAS – FIRED TOP VENT GRAVITY WALL FURNACE
REPLACEMENT PARTS LIST FOR MODELS 5009611; 5009612; 5009621 ; 5009622
REF. PART NO. NO.
DESCRIPTION
1
4.915
2
9C155
FACE PANEL (2 REQUIRED) FRONT HEAT SHIELD (2 REQUIRED)
3
9A277
CARRYOVER SHELL
4- 9D65
4A 9073
5
9C171
COMBUSTION CHAMBER ASSE]_BLY (FRONT) COMBUSTION CHAMBER ASSEMBLY (REAR) OUTER CASING ASSEMBLY
6
95199
DEFLECTOR
7
5901
HEADER (REF. – 9C30)
8
P321826 UMIT SWITCH
9
9C’170
I0
9C157
DRAF-IHOOD ASSEMBLY (2 REQUIRED) NON – VISION SHIELD
11
9C158
INNER SHIELD TOP (2 REQUIRED)
9901 P320994
OVAL B/W VENT KIT DOOR HANDLE
P322085
OWNERS MANUAL (REV. 11/95)
,# NOT SHOWN _” NOT AVAILABLE SEPARAltl.Y (KIT FORM ONLY)
NOTE: SORES’,/SAND BOLTS ARE STANDARD HARDWARE I'[_MS, AVAILABLE LOCALLY.
FOR PARTS ILLUS’i’RATIONS SEE PAGE 33
–32–
WILLIAMSGAS – FIRED TOP VENT GRAVITY WALL FURNACE
REPLACEMENT PARTS FOR MODELS 5009611; 5009612; 5009621; 500962?
\
©
USE ONLY MANUFACTURER’S
AUTHORIZED PARTS
,,._
IF.t{w-}
–33–
WILLIAMS GAS-FIRED TOP VENT GRAVITY WALL FURNACE
CONTROL ASSEMBLY REPLACEMENT PARTS LIST FOR MODELS –
5009611; 5009612; 5009621; 5009622
REF. PART NO. NO.
1
9C105
1
P025600
DESCRIPTION
T-BURNER (FORMED STEEL.NAT. GAS ONLY),2 REQUIRED.
BURNER (CAST IRON), 2 REQUIRED.
LO _O!LO tO
oOoo oO
u-)u-)u3 u-)
x
X
x
X
2
P043800
GENERATOR
3
P320758
CARRYOVER PILOT – NAT.
XX x
3
P320778
CARRYOVER PILOT – L.P.G.
X
3
P322396
CARRYOVER PILOT – NAT.
X
3
P322397
CARRYOVER PILOT – L.P.G.
X
4
9C95
BURNER PAN ASSEMBLY (T-BURNER)
X
X
4-
9C34
BURNER PAN ASSEMBLY (CAST IRON)
X
X
5
P321828
TERMINAL BLOCK ll4ERMOCOUPLE
XX
6
P322052
CONTROL GAS VALVE
X
6
P322051
CONTROL GAS VALVE
6
P1722OOA CONTROL GAS VALVE
X X
6
P17210OA CONTROL GAS VALVE
X
7
9A174
SHIELD-BRNR. PAN (FORMED STL. BRNR., NAT. GAS ONLY).
X
X
8
P090500
ORIFICE (2 REQ. SPECIFY GAS TYPE & INPUT)
X X XX
9
P026200
LOCKNUT, 2 REQUIRED.
X XX X
10
9A298
11
9A108
11
9A200
12
7A189
13
9B124
1,3 9C96
14
P322016
MANUAL SPARK IGNITOR (PIEZO) MANIFOLD ASSEMBLY (CAST IRON BURNER) MANIFOLD ASSEMBLY (FORMED STEEL BURNER) PIEZO BRACKET (SPARK IGNITOR) CARRYOVER BRACKET (CAST IRON BURNER) CARRYOVER BRACKET (FORMED STL. BRNR. NAT THERMOSTAT
GAS ONLY)
X XX X
X
X
X
X
X XX X
X
X
X
X
XX
15
P321836
WIRE ASSEMBLY (2 REQUIRED)
X×XX
FOR PARTS ILLUSTRATIONS, SEE PAGE 35
“X” DENOTES USAGE
NOTE: SCREWS AND BOLTS ARE STANDARD HARDWARE ITEMS, AVAILABLE LOCALLY
m34–
WILLIAMS
GAS-FIRED TOP VENT GRAVITY
REPLACEMENT PARTS FOR MODELS 5009611; 5009612: 5009621; 5009622
WALL FURNACE
FOR PARTS LISTING, SEE PAGE 54
NAT. GAS CONTROL ASSEMBLY
I
L.P. GAS CONTROL ASSEMBLY
135–
USE ONLY MANUI:’ACTURER*S
AUTHORIZED PART5
LIr/oo-ol
INSTALLATION INSTRUCTIONS
2901 BLOWER ACCESSORY KIT
NOTE: All electrical work must conform to your local codes and ordinances or
in their absence, with currant National Electrical Code, ANSI/NFPA 70. If you
are not familiar with wiring codes in general, have a competent electrician do
this job.
WARNING. DANGER OF PROPERTY DAMAGE,
BODILY INJURY OR DEATH TURN OFF ELECTRIC POWER SUPPLY AT DISCONNECT SWITCH,
FUSE BOX OR SERVICE PANEL BEFORE REMOVING OR WORKING ON FAN CABINET.
BLOWER ACCESSORY KIT
This accessory is installed on furnace top and increases circulation of warm air through heated space. A 115V outlet adjacent to the furnace is required.
For Automatic SettingYou must select “HI” or “LOW” position. When furnace heats up the temperature sensing device will be activated and the fan will operate.
Blower accessory will not operate if toggle switch is set in off (center) position.
Install as follows:
STEP 1. Install 115V electrical outlet where shown in your owners manual; see
rough-in illustration
STEP 2. Remove (2) screws securing blower grille assembly, and remove blower grille (See Fig. A.)
STEP 3. Remove (2) screws securing junction box cover (See Fig. C). Then remove cover to gain access to knockout hole located in junction box (See Fig. C)
STEP 4. Locate knockout hole and remove knockout using a hammer and screwdriver.
STEP 5. Place blower cabinet on furnace top (See Fig. A).
STEP 6. Route 115V field wiring into junction box through knockout hole.
STEP
Make field wiring connection inside junction box (See Fig. B). Follow applicable local and national electrical codes.
STEP 8.
Drill 1/8 inch diameter hole in each side of the furnace face panel through the holes on the sides of the fan cabinet, and secure the cabinet to the furnace with the two sheet metal screws provided.
NOTE: Set blower cabinet against _all surface (required on deeper face panels).
STEP 9. Replace junction box cover, securing with screws previously removed.
STEP 10. Replace blower grille, securing with screws previously removed.
STEP 11. Set switch to desired position. If left in “HI” or “LOW” position during summer months blower accessory could be activated by sunlight striking furnace face panel through unshaded windows. If this is undesirable set switch to “OFF” position.
FIG. A
OP_ONAL FAN ACCESSORY
SEE PAGE 37 FOR ADDITIONAL ILLUSTRATIONS
–36–
INSTALLATION INSTRUCTIONS
REF. ;’ART NO. NO.
DESCRIPTION
1 P013200 Screw-#8×3/8SheetMetal(8) Required
2
BlowerGrille
3 P093200 Screw-#Bx3/S8heetMetal(2)Required 4 P1410C0 Screw-#10xl/2SheetMetal(1)Required 5 P320911A FanSwitch-2 Speed 6 P3,?.G912 WireBridle 7 P127300 Washer-fla#t-10-32(2) Required 8 P04110 NutMach.-#8-32WlStarWasher(2) Required 9 9C102 BlowerBody 10 P321078 Grommet- motmorount(2) Required 11 P012900 Bushing-StraRinelief 12 P322395 AutomatiFcanSwitch
13 P029200 Borew-Machin-e#6-32×15/1(62) Required 14 P320905 Motor-2 Speed 15 P320907 FanBiede
16 9D12-1 OrificePlate 17 68161 JunctionBoxPlate
FIG. B.
BLOWER ACCESSORY KIT NO. 2901
NOT
FAN 5″t_TCH
BK
I_ 51.
FAN },ITR
W
I” I HOT I
F_I _TCH
1r5v 6_,4z I I GNO
TCGG-E ST:H
_eL
“q” t NEUT I
I
—- — HI_ vo_toge d, Hl<jt “*_dtoe roctoPf.
O w connector for” ltho to
LEGEND
– factory _g
[_1/4 k< coect t,=,-mln=for
focto,”y wk-th<j con_ectnL
ELK- BLACX BL ” BLUE W = Y’_ITE
NOTES:
R – R_ G –
1 Motor is therrly prolected
2 If any o the origiP_d wire as supple3 with the apiarme has to be replaced,
u, c_ty 18 Ga, 4/64 ir_Jiabon, 105o C. AWM cop –
er wire or ds equivalent HSV 6OHz. – less than 3 _ps.
FROt*4 SUPPLY C_RC_IT, BE;”OR£ SVtC
[OWRA.RC.NLINEGA:NINOGlS,_CNNECT APPLIANC
]
Tot
load I_ than 3 AMPS* | P320904
6_
JUNC_ON
3 1 9
,
12 14 15
FIG. C
–37–
DATE
Service Record MAINTENANCE PERFORMED
COMPONENTS REQUIRED
–38 D
— Notes —
–39–
.0TE:”
DIAN_ MODEL NUMBERS THIRD
DIGIT FROM LEFT ,T_ BE:
1_FOR8ASIC_LTRUDES
2_EORHIGH,ALTITUDES
.
EXAMPLE ‘ ..”
MODEL; 350961_BECOMES 3519612
_- (0-2000FT. BASICAL1TrUOE)
OR BECOMES 3529612
:
(2000-4000FT. HIGHALTITUDE)
Service Hints
If your furnace fails to work right, you may avoid inconvenience and the cost
of a service call by checking the following points before you call for
service.
FOR YOUR SAFETY
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
If you smell gas: 1. Open windows. 2. Don’t touch electrical. 3. Extinguish
any open flame. 4. Immediately call your gas
supplier.
POSSIBLE CAUSE
WHAT TO DO
If your furnace Is not heating or not giving enough heat —
Thermostat is not set correctly.
Reset thermostat to desired setting.
Pilot is out.
Check pilot. Relight if necessary
following instructions for “Operating
Your Furnace:’
Pilot is on but burner won’t
If gas valve is set at other than “On”
come on,
furnace will not operate. Shut furnace down and follow instructions for
relighting in “Operating Your Furnace” section.
Burner is not operating properly.
Air flow restricted.
Check flame, If it is yellow the burner is not getting enough air. Or if flame is blue and noisy and seems to lift off the burner, the burner is getting too much air. See “Checks and Adjustments:’ page 24, Check that doors, drapes or furniture are not blocking furnace louvers.
Pilot goes out time after time -Furnace flue blocked.
Pilot and burner access door
Locate vent outlet blockage and clean.
Check the door. See section on
not closed properly.
“Operating Your Furnace” beginning on page 18.
If burner is noisy -Gas input amount is incorrect. Too much primary air.
Contact Williams Service Department. Contact Williams Service Department.
If blower does not run -Fan switch not set. Blower not connected to
electric power.
Select fan speed. Connect to electric power.
if blower motor is noisy -Housing rattling. Blower dirty. Blower wheel bent.
Tighten screws. Clean blower wheel.
Straighten or replace.
See troubleshooting section for more detailed information.
How to Order Repair Parts
When ordering repair information:
1. MODEL NUMBER 2. MFG. DATE CODE 3. PART NUMBER 4. PART DESCRIPTION
parts, always give the following
All parts listed herein may be ordered from your equipment supplier.
The Model Number of your Williams wall furnace will be found on the rating
plate near gaB valve, inside control compartment.
WILLIAMS FURNACE COMPANY 225 Acacia Street
Colton, CA 92324 USA
909-825-0993
MANUFACTURED IN THE U.S.A.
Established 1916
FAX: 909-824-8009
© 1997 The Williams Furnace Company
Printed in U.S.A.
REV. 5/97
P322085
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>