WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat Instruction Manual
- June 16, 2024
- WHITE RODGERS
Table of Contents
- WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat
- Product Information
- Usage Instructions
- APPLICATIONS
- SPECIFICATIONS
- INSTALLATION
- WIRING CONNECTIONS
- THERMOSTAT QUICK REFERENCE
- INSTALLER/CONFIGURATION MENU
- OPERATING YOUR THERMOSTAT
- PROGRAMMING
- TROUBLESHOOTING
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat
Product Information
Specifications
- Model: Blue Single 1/1 Stage Thermostat
- Programming Choices: 5/2 Day, 5/1/1 Day, Non-Programmable
- Thermostat Application Guide:
- Gas or Oil Heat: Yes
- Electric Furnace: Yes
- Heat Pump (No Aux. or Emergency Heat): Yes
- Heat Pump (with Aux. or Emergency Heat): No
- Systems with up to 3 Stages Heat, 2 Stages Cool: No
- Heat Only Systems: Yes
- Cool Only Systems: Yes
- Electrical Rating: Battery Power, Input-Hardwire
Installation
WARNING:
Thermostat installation and all components of the control system shall conform
to Class II circuits per the NEC code.
Remove Old Thermostat
A standard heat/cool thermostat consists of three basic parts:
- The cover may be either a snap-on or hinge type.
- The base, which is removed by loosening all captive screws.
- The switching subbase, which is removed by unscrewing the mounting screws that hold it on the wall or adapter plate.
Before removing wires from the old thermostat, label each wire with the terminal designation from which it was attached. Disconnect the wires from the old thermostat one at a time. Do not let wires fall back into the wall.
Batteries
2 AA alkaline batteries are included in the thermostat. To install the
batteries:
- Pull the battery door as shown by the arrow and lift it open.
- Using the polarity indicated inside the battery door, insert the batteries.
- To close the battery door, swing the door down while pulling in the direction of the arrow.
- Once fully down, snap the door back into position.
To replace the batteries, set the system to OFF, following the instructions above.
Installing New Thermostat
Pull the thermostat body off the thermostat base. Forcing or prying on the
thermostat will cause damage to the unit.
Usage Instructions
Thermostat Quick Reference
Refer to the quick reference guide provided with your thermostat for easy
access to common functions and settings.
Installer Configuration Menu
The installer configuration menu allows you to customize various settings
and options for your thermostat. Refer to the user manual for detailed
instructions on accessing and using the installer configuration menu.
Operating Your Thermostat
Once installed, follow these steps to operate your thermostat:
- Set the mode to either heat or cool using the mode button.
- Adjust the desired temperature using the up and down arrows.
- Press the hold button to maintain the current temperature indefinitely.
- Use the program button to access and modify programmable settings, if applicable.
Programming
If your thermostat supports programmable settings, follow these steps to
program it:
- Access the programming menu by pressing the program button.
- Set the desired temperature for each period (eg, morning, afternoon, evening).
- Save your programming settings to activate the program.
Troubleshooting
If you encounter any issues with your thermostat, refer to the
troubleshooting section of the user manual for common problems and solutions.
FAQ
-
Does this thermostat support systems with multiple stages of heat and cooling?
No, this thermostat does not support systems with up to 3 stages of heat and 2 stages of cooling. -
Can I use this thermostat with a heat pump system that has auxiliary or emergency heat?
No, this thermostat is not compatible with heat pump systems that have auxiliary or emergency heat. -
What type of batteries does this thermostat use?
This thermostat uses 2 AA alkaline batteries. -
How do I access the installer configuration menu?
Refer to the user manual for detailed instructions on accessing and using the installer configuration menu.
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR
OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Blue Single 1/1 Stage Thermostat with Automatic Heat/Cool Changeover Option
Single Stage or Heat Pump
Installation and Operating Instructions for Model:
Model | Programming Choices |
---|---|
1F80-0471 | 5/2 Day |
1F86-0471 | Non-Programmable |
APPLICATIONS
THERMOSTAT APPLICATION GUIDE
Description
Gas or Oil Heat| Yes
Electric Furnace| Yes
Heat Pump (No Aux. or Emergency Heat)| Yes
Heat Pump (with Aux. or Emergency Heat)| No
Systems with up to 3 Stages Heat, 2 Stages Cool| No
Heat Only Systems| Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces| Yes
Cool Only Systems| Yes
Hydronic (Hot Water) Zone Heat – 2 Wires| Yes
Hydronic (Hot Water) Zone Heat – 3 Wires| Yes
SPECIFICATIONS
- Electrical Rating:
- Battery Power. . . . . . . . . . . . . . . . . . . . . . . . . . mV to 30 VAC, NEC Class II, 50/60 Hz or DC
- Input-Hardwire . . . . . . . . . . . . . . . . . . . . . . . . . 20 to 30 VAC
- Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0 A per terminal, 1.5A maximum all terminals combined
- Setpoint Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45° to 90°F (7° to 32°C)
- Differential (Single Stage) . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F (adjustable)
- Differential (Heat Pump) . . . . . . . . . . . . . . . . . . . . . Heat 1.2°F; Cool 1.2°F (adjustable)
- Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . . 32° to +105°F (0° to +41°C)
- Operating Humidity . . . . . . . . . . . . . . . . . . . . . . . . . 90% non-condensing max.
- Shipping Temperature Range . . . . . . . . . . . . . . . . . -4° to +150°F (-20° to +65°C)
- Dimensions Thermostat. . . . . . . . . . . . . . . . . . . . . . 3.4″H x 4.4″W x 1.3″D
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power
to the system at the main fuse or circuit breaker box until installation is
complete.
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this product may replace a
product that contains mercury.
Mercury and products containing mercury must not be discarded in household trash. Do not touch any spilled mercury. Wearing non-absorbent gloves, clean up any spilled mercury and place it in a sealed container. For proper disposal of a product containing mercury or a sealed container of spilled mercury, place it in a suitable shipping container. Refer to www.white- rodgers.com for a location to send products containing mercury.
INSTALLATION
WARNING
Thermostat installation and all components of the control system shall conform
to Class II circuits per the NEC code.
Remove Old Thermostat
A standard heat/cool thermostat consists of three basic parts:
- The cover may be either a snap-on or hinge type.
- The base, which is removed by loosening all captive screws.
- The switching subbase, which is removed by unscrewing the mounting screws that hold it on the wall or adapter plate. Before removing wires from the old thermostat, label each wire with the terminal designation from which it was attached. Disconnect the wires from the old thermostat one at a time. Do not let wires fall back into the wall.
Installing New Thermostat
- Pull the thermostat body off the thermostat base. Forcing or prying on the thermostat will cause damage to the unit.
- Place the base over the hole in the wall and mark mounting hole locations on the wall using the base as a template.
- Move the base out of the way. Drill mounting holes. If you are using existing mounting holes and the holes drilled are too large and do not allow you to tighten the base snugly, use plastic screw anchors to secure the base.
- Fasten the base snugly to the wall using the mounting holes shown in Figure 2 and two mounting screws. Levelling is for appearance only and will not affect thermostat operation.
- Connect wires to the terminal block on the base.
- Push excess wire into the wall and plug the hole with a fire-resistant material (such as fibreglass insulation) to prevent drafts from affecting thermostat operation.
- Carefully line the thermostat up with the base and snap into place.
SS/HP Switch (Conventional or Heat Pump Selection)
The SS/HP switch is factory set to the SS position. In this posi-tion, the
thermostat is confi gured as a conventional single stage. If you have a single-
stage heat pump system, switch SS/HP to the HP position (see figure 2).
Gas/Elec Switch (Fan Option)
The GAS/ELEC switch is factory set to the GAS position. In this position, the
thermostat will not power the circulator fan on a call for heat but will power
the circulator on a call for cool. If your system requires that the thermostat
power the circulator fan on a call for heat, this switch should be set to the
ELEC position. Typically, gas and oil heating systems do not require the
thermostat to power the circulator fan during a call for heat. If your heat is
gas or oil, the switch should be set to the GAS position.
When the thermostat is configured for a Heat Pump, the thermostat will always power the circulator fan on a call for heat in the HEAT mode.
Batteries
2 “AA” alkaline batteries are included in the thermostat. To install the
batteries, pull the battery door as shown by the arrow and lift it open. Using
the polarity indicated inside the battery door, insert the batteries. To close
the battery door, swing the door down while pulling in the direction of the
arrow. Once fully down, snap the door back into position.
To replace the batteries, set the system to OFF, following the instructions above.
The thermostat can be powered by system AC power or a Battery. If is displayed, the thermostat is battery-powered. If is not displayed, the thermostat is system-powered with optional battery backup. When the battery power remaining is approximately half, they will be displayed. When “Change ” is displayed, install fresh “AA” alkaline batteries immediately. For best results, replace all batteries with a premium brand alkaline battery such as Duracell® or Energizer ®. We recommend replacing batteries every 2 years. If the home is going to be unoccupied for an extended period (over 3 months) and is displayed, the batteries should be replaced before leaving. When less than two months of battery life remain, the setpoint temperature will offset by 10 degrees (10 degrees cooler in Heat mode / 10 degrees warmer in Cool mode). If offset occurs, the normal setpoint can be manually reset with or . Another offset will occur within two days if batteries are not replaced.
WIRING CONNECTIONS
Refer to equipment manufacturers’ instructions for specifi c system wiring information. After wiring, see the CONFIGURATION section for proper thermostat confi duration. Refer to 37-6754 for 1F80-0471 wiring diagram specifi cations.
TERMINAL DESIGNATION DESCRIPTIONS
Terminal Designation Description
- O/B …………………… (SS) Power closed for 3 wire zone HP) Changeover valve for heat pump
- Y ………………………. Compressor Relay
- W ……………………… Heat Relay
- G ………………………. Fan Relay
Terminal Designation Description
- RH …………………… Power for Heating
- RC …………………… Power for Cooling
- C …………………….. Common wire from the secondary side of the cooling system transformer or heat-only system transformer
THERMOSTAT QUICK REFERENCE
Home Screen Description
Programming and Configuration Items
- Flame icon ( ) is displayed when the system is in HEAT mode. Snowflake icon ( ) is displayed when the system is in COOL mode.
- The word “Hold” is displayed when the thermostat is in the HOLD mode. “Temp Hold” is displayed when the thermostat is in a Temporary HOLD mode.
- Displays “Change Filter” when the system has run for the programmed filter time as a reminder to change or clean your filter.
- Displays “Set” for setpoint when in Run Program mode.
- Displays System Mode (Heat, Cool, Auto, Off) or “Time” in menu mode.
- Displays Fan Mode (On, Auto) or “Run” in Menu mode or “Saving” in Cool SavingsTM Mode.
- Displays “Run Schedule”, “Schedule”, or “Menu”.
- Displays “Save” when Cool SavingsTM is working.
- Displays “Heat Pump” when the system is configured as a Heat Pump thermostat.
- Displays “Hold” in programmable mode when in “Hold” mode. Displays Light Bulb in non-programmable mode.
INSTALLER/CONFIGURATION MENU
With thermostat in Heat, Cool or Auto, in normal operation, press the Menu button for at least 5 seconds. The display will show item #1 in the table below. Press Menu to advance to the next menu item. Press or to change an item option. Shaded items are not available on 1F86.
INSTALLER/CONFIGURATION MENU
MENU REF| HP| SS| PRESS BUTTON| DISPLAYED
(FACTORY DEFAULT)| Press or select from the listed
options| COMMENTS
1| 1| | MENU| On (Cool O)| Heat b On| Reversing Valve Output (SS/HP switch
must be in the Heat Pump HP position)
2| 2| 1| MENU| P (2)| P 3, P 0| Selectable Programs Per Week (For programmable
thermostat only)
3| 3| 2| MENU| Cool Saving CS (OFF)| Cool Saving CS On| Select Cool Savings on
or off
MENU| CS (3)| 6, 5, 4, 2, 1| Selects Cool Savings value 1 (low) to 6 (high)
4| 4| 3| MENU| E (On)| E OFF| Selects Energy Management Recovery (EMR) on or
off
5| | 4| MENU| CR Heat (ME)| FA, SL| Adjustable Anticipation (Heat) (only when
SS/HP switch is at the SS position)
6| | 5| MENU| CR Cool (FA)| SL| Adjustable Anticipation (Cool) (only when
SS/HP switch is at the SS position)
7| 5| | MENU| CR Heat Pump (FA)| SL| Adjustable Anticipation (Heat Pump)
(only when SS/HP switch is at the HP position)
8| 6| 6| MENU| CL (OFF)| CL On| Compressor Lockout Time
9| 7| 7| MENU| Auto Heat Cool-Off| Heat Cool Off, Heat Off with Fan icon, Heat
Off without Fan icon, Cool Off, Auto Off| System Mode Configuration with
Automatic Changeover
10| 8| 8| MENU| L (On)| L OFF| Select Display Light on or off
11| 9| 9| MENU| 0 HI| 1 HI, 2 HI, 3HI, 4 HI,
1 LO, 2 LO, 3 LO, 4 LO
| Adjustable Ambient Temperature Display
12| 10| 10| MENU| F| C| Select Fahrenheit/Celsius Temperature Display
13
|
11
|
11
| MENU| Change Filter (OFF)| Change Filter On| Selects Filter Change-out
Indicator
MENU| Change Filter 200 h| 25 h to 1975 h in a 25-hour increment| When on,
select time in 25-hour increments
25-hour increment
14| 12| 12| RUN| | | Returns to Normal Operation
-
Select Reversing Valve Output (SS/HP switch must be set at HP, omitted if SS/HP switch is SS Position) – The O/B option is factory set at “O” position. This will accommodate the majority of heat pump applications, which require the changeover relay to be energized in COOL. If the thermostat you are replacing or the heat pump being installed with this thermostat requires a “B” terminal, to energize the changeover relay in HEAT, the O/B option should be set at “B” position.
-
Program Options 1F80 only – This control can be confi gured for 5/2 day or 5/1/1 day programming or non-programming mode. The default setting is P2, indicating 5/2 day programming. The programs per week can be toggled to P3 or P0 by pressing the or keys. A selection of 0 Days for non-programmable will eliminate the need for EMR, and that step in the menu will be skipped.
-
Select Cool Savings™ and value – Select the Cool Savings feature On or OFF. If selected On, press MENU to select the amount of adjustment for the feature in Cool mode with 1 (1°) being the least amount of adjustment and 6 (6°) being the most amount of adjustment. The default value is 3 (3°). In normal operation “Saving” will appear under “Fan”.
Cool Saving is an optional energy-saving feature that can reduce your cooling costs. It is based on the principle that lower indoor humidity makes a slightly higher temperature feel more comfortable. Cool Savings operates during periods of high demand which normally occur on the hottest summer days when the cooling system may run for hours to reach the thermostat setting. Long cooling run times also lower the indoor humidity. Cool Savings very slowly adjusts the setpoint temperature to make the setpoint closer to the displayed temperature, to a maximum number of degrees selected. Adjusting the setpoint temperature over a long cooling run time allows the system to reach your set temperature and turn off. The room temperature will be higher than the thermostat displays, but the reduction in humidity will allow comfort at the slightly higher temperature. When Cool Savings is making adjustments, “Save” will show next to the setpoint temperature and the room temperature may vary within the adjustment range selected. If this feature is selected OFF, no change will occur when the cooling system is continually running during periods of high demand. -
Energy Management Recovery: (this step is skipped if confi gured to be non-programmable).
Energy Management Recovery (E) On enables the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint.
Example: If E On is selected have your heating pro-grammed to 65° at night and 70° at 7 AM. If the building temperature is 65°, the difference between 65° and 70° is 5°. Allowing 5 minutes per degree, the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows more time per degree because it takes longer to reach a set temperature. -
5, 6 & 7) Cycle Rate Selection – The factory default settings with SS/HP switch in SS position for Heat is a medium cycle (ME) and Cool is a fast cycle (FA). For Heat Pump (HP), the default setting is a fast cycle (FA).
To change the cycle rate, press the or key.
Cycle rate differentials for different settings are:- MODE
- Fast FA
- Medium ME
- Slow SL
- Heat (SS) 0.4°F 0.6°F 1.8°F
- Cool (SS) 1.2°F – 1.7°F
- Heat Pump (HP) 1.2°F – 1.7°F
-
Select Compressor Lockout CL OFF or ON – Selecting CL ON will cause the thermostat to wait 5 minutes between cooling cycles. This is intended to help protect the compressor from short cycling. Some newer compressors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs, it will fl ash the setpoint for up to fi ve minutes.
-
System Mode Confi guration – This thermostat is confi gured for Heat and Cool with Auto changeover (SYSTEM switch with Cool Off Heat Auto) default. It can also be confi guard for Heat and Cool (Cool Off Heat), Heat only with a fan (Off Heat), Heat only without a fan, Auto only (Auto-Off), and Cool only (Cool Off).
-
Select Backlight Display – The display backlight improves display contrast in low lighting conditions. When the “C” terminal is powered, selecting backlight CdL ON will keep the light on continuously. Select backlight OFF will keep the light on momentarily after any key is pressed. When the “C” terminal is not powered, the light will be on momentarily after any key is pressed no matter whether the backlight is selected ON or OFF.
-
Select Temperature Display Adjustment 4 LO to 4 HI. Allows you to adjust the room temperature display up to 4°higher or lower. Your thermostat was accurately calibrated at the factory, but you have the option to change the display temperature to match your previous thermostat. The current or adjusted room temperature will be displayed on the left side of the display.
-
Select F° or C° Readout – Change the display readout to Centigrade or Fahrenheit as required.
-
Select Filter Replacement Reminder and Set Run Time. Select the “Change Filter” reminder On or OFF. If selected On, press MENU to select the time from 25 to 1975 hours in 25-hour increments. In a typical system, 200 hours (default) of run time is approximately 30 days. After the se-lected time of blower operation, the thermostat will display “Change Filter” as a reminder to change or clean your air filter. When “Change Filter” is displayed, press the MENU button to clear the display and restart the time to the next filter change.
OPERATING YOUR THERMOSTAT
Choose the Fan Setting (Auto or On)
- Set the FAN Switch to Auto or On.
- Fan Auto is the most commonly selected setting and runs the fan only when the heating or cooling system is on.
- Fan On runs the fan continuously for increased air circulation or to allow additional air cleaning.
Choose the System Setting (Heat, Off, Cool, Auto)
Press the SYSTEM button to select:
- Heat: The thermostat controls only the heating system.
- Off: Heating and Cooling systems are off.
- Cool: The thermostat controls only the cooling system.
- Auto: Auto Changeover is used in areas where both heating and cooling may be required on the same day. AUTO allows the thermostat to automatically select heating or cooling depending on the indoor temperature and the selected heat and cool temperatures. When using AUTO, be sure to set the Cooling temperatures more than 1° Fahrenheit higher than the heating temperature.
Manual Operation for Non-Programmable Thermostats Mode
Press the SYSTEM button to select Heat or Cool and use the or buttons to
adjust the temperature to your desired setting. After selecting your desired
settings you can also press the SYSTEM button to select AUTO to allow
the thermostat to automatically change between Heat and Cool.
IMPORTANT!
Manual Operation (Bypassing the Program) Programmable Thermostats
Press or the HOLD button and adjust the tem-perature wherever you like. This
will override the program. The HOLD feature bypasses the program and allows
you to adjust the temperature manually, as needed. Whatever temperature you
set in HOLD will be maintained 24 hours a day, until you manually change the
temperature or press Run Schedule to cancel HOLD and resume the programmed
schedule.
Program Override (Temporary Override)
Press or buttons to adjust the temperature. This will override the temperature
setting until the next programmed time. To cancel the temporary setting at any
time and return to the program, press Run Schedule. If the SYSTEM button is
pressed to select AUTO the thermostat will change to Heat or Cool, whichever
ran last. If it switches to heat but you want cool, or it changes to cool but
you want heat, press both and buttons simultaneously to change to the other
mode.
PROGRAMMING
PROGRAMMING (For Programmable Model Only)
Set Current Time and Day
- Press the Menu and then the Time button once. The display will show the hour only.
- Press and hold either the or button until you reach the correct hour and AM/PM designation (AM begins at midnight, PM begins at noon).
- Press Time once again. The display window will show the minutes only.
- Press and hold either the or button until you reach the correct minutes.
- Press Time once again. The display will show the day of the week.
- Press the or button until you reach the current day of the week.
- Press Run to exit the Time mode.
Enter the Heating Program
- Press the SYSTEM button to select “Heat” in the system switch area indicating the active mode being programmed.
- Press the Menu button and then press Schedule.
- The top of the display will show the day(s) being programmed. The time and temperature (flashing) are also displayed. “1” will also be displayed to indicate the period.
- Press or button to change the temperature to your selected temperature for the 1st heating period.
- Press the Time button, and time will flash.
- Press or button to adjust the start time for the 1st period.
- The time will change in 15-minute increments.
- After you have set the time and the temperature for the period to begin, press Schedule to advance to the next program period.
- Repeat steps 2 through 8 until all of the program times and temperatures are set for all program periods on that day.
- Press Schedule to the next day and repeat steps 2 through 9.
- When programming is complete and all of the times and temperatures match your desired heating schedule, press Run Schedule. The thermostat will now run your program.
Enter the Cooling Program
- Press the SYSTEM button to select “Cool” in the system switch area indicating the active mode being programmed.
- Follow the Enter Heating Program instructions for entering cooling times and temperatures.
Energy Saving Factory Pre-Program
The 1F80-0471 thermostats are programmed with the energy-saving settings shown
in the table below for all days of the week. If this program suits your needs,
simply set the thermostat clock and press the RUN button. The table below
shows the factory-set heating and cooling schedule for all days of the week.
| Wake Up (Period 1)| Leave For Work (Period 2)| Return Home
(Period 3)| Go To Bed (Period 4)
---|---|---|---|---
Heating Program| 6:00 AM| 70°F| 8:00 AM| 62°F| 5:00 PM| 70°F| 10:00 PM|
62°F
Cooling Program| 6:00 AM| 75°F| 8:00 AM| 83°F| 5:00 PM| 75°F| 10:00 PM|
78°F
Planning Your Program – Important
- The Heating and Cooling Program schedules below allow you to pencil in your program times and temperatures.
- The 1F80-0471 comes configured for 5/2 day programming and can also be configured for 5+1+1 programming (see configuration section).
- Factory settings are listed on Monday through Friday, Saturday and Sunday. If you are re-programming a 5/2 day schedule, pencil in your times and temperatures directly below the factory times and temperatures.
- If you are re-programming a 5+1+1 fill in all lines with the times and temperatures you want.
Keep the following guidelines in mind when planning your program.
- In Heating, lower temperatures will save energy.
- In Cooling, higher temperatures will save energy.
- If you plan on using Auto Changeover, do not program the heating higher than the cooling.
Worksheet for Re-Programming 5/2 Day and 5+1+1 Day Program
Heating Program| Wake Up (Period 1)| Leave For Work (Period 2)|
Return Home (Period 3)| Go To Bed (Period 4)
---|---|---|---|---
Mo-Fr| 6:00 AM| 70°F| 8:00 AM| 62°F| 5:00 PM| 70°F| 10:00 PM| 62°F
| | | | | | |
Sat-Sun or Sat| 6:00 AM| 70°F| 8:00 AM| 62°F| 5:00 PM| 70°F| 10:00
PM| 62°F
| | | | | | |
Sun 5+1+1 only| 6:00 AM| 70°F| 8:00 AM| 62°F| 5:00 PM| 70°F|
10:00 PM| 62°F
| | | | | | |
Cooling Program| Wake Up (Period 1)| Leave For Work (Period 2)|
Return Home (Period 3)| Go To Bed (Period 4)
---|---|---|---|---
Mo-Fr| 6:00 AM| 75°F| 8:00 AM| 83°F| 5:00 PM| 75°F| 10:00 PM| 78°F
| | | | | | |
Sat-Sun or Sat| 6:00 AM| 75°F| 8:00 AM| 83°F| 5:00 PM| 75°F| 10:00
PM| 78°F
| | | | | | |
Sun 5+1+1 only| 6:00 AM| 75°F| 8:00 AM| 83°F| 5:00 PM| 75°F|
10:00 PM| 78°F
| | | | | | |
TROUBLESHOOTING
Reset Operation
Note: When the thermostat is reset, the installer configuration menu settings and programming will reset to factory settings. If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals R and C (do not short them together) and removing batteries for 2 minutes. After resetting the thermostat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.
Note: Be sure to review the installer confi duration menu settings.
To reset the programming, clock and confi duration settings, press the FAN button simultaneously. The thermostat should go blank and then all segments will be displayed momentarily.
Symptom | Possible Cause | Corrective Action |
---|---|---|
No Heat/No Cool/No Fan (common problems) | 1. Blown fuse or tripped |
circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or panel loose or not properly installed.
4. Loose connection to thermostat or system.
| Replace the fuse or reset the breaker. Turn the switch to ON.
Replace the door panel in the proper position to engage the safety interlock or door switch.
Tighten connections.
No Heat| 1. Pilot light not lit.
2. Furnace Lock-Out Condition. Heat may also be intermittent.
3. The heating system requires service or the thermostat requires replacement.
| Re-light pilot.
Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local HVAC service person for assistance.
Diagnostic: Set the SYSTEM Switch to HEAT and raise the setpoint above room temperature. Within a few seconds, the thermostat should make a soft-click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or an HVAC service person to verify the heating is operating correctly.
No Cool| 1. The cooling system requires service or the thermostat
requires replacement.| Same as diagnostic for No Heat condition except setting
the thermostat to COOL and lowering the setpoint below the room
temperature. There may be up to a five-minute delay before the thermostat
clicks in Cooling.
Heat, Cool or Fan Runs Constantly| 1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. FAN Switch set to Fan ON.
| Check each wire connection to verify they are not shorted or touching
together. No bare wire should stick out from under the terminal block. Try
resetting the thermostat as described above. If the condition persists the
manufacturer of your system or service person can instruct you on how to test
the Heat/Cool system for correct operation. If the system operates correctly,
replace the thermostat.
Thermostat Setting & Thermostat Thermometer Disagree| 1. The thermostat
thermometer setting requires adjustment.| The thermometer can be adjusted +/-
4 degrees. See Temperature Display Adjustment in the Configuration Menu
section.
The furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide
temperature swing)| 1. The location of the thermostat and/or the size of
the Heating System may be influencing the cycle rate.| Digital thermostats
provide precise control and cycle faster than older mechanical models. The
system turns on and off more frequently but runs for a shorter time so there
is no increase in energy use. If you would like an increased cycle time,
choose SL for the slow cycle in the Configuration menu, steps 6 (heat), 7
(cool) or 8 (heat pump). If an acceptable cycle rate is not achieved, contact
a local HVAC service person for additional suggestions.
HOMEOWNER HELPLINE: 1-800-284-2925
White-Rodgers is a division of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. www.white- rodgers.com.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>