Honeywell W4267_I DHS Mini Detector Installation Guide
- June 16, 2024
- Honeywell
Table of Contents
LightSpot Luminaire Controllers
MSM2000D/DALI – Digital Control Module
DHW/DHS – Mini Detector Head
W4267_I DHS Mini Detector
Installation and Commissioning Instructions
Note: QuickSet Pro (or HP18*) required for commissioning
- Please note that the HP18 offers different/limited programming options
Electrical Connections
Mounting Details
The MSM2000 Control Module is designed to be mounted within the luminaire on
fixing centres of 135mm.
Connections to the control module as shown above should be made using solid
strand wire (0.5-1.5mm?).
The interconnect cable between the detector head and control module should be
routed away from other luminaire internal wiring and away from the lamp end-
caps.
The recommended position for the detector is in the middle of the luminaire.
Where this is not possible and the detector is fitted near on end of the
lamps, please ensure that the detector is at the ‘cold’ end of the lamps.
The DHW/S Mini Detector Head should be mounted such that only the raised front
section of the bezel protrudes through the cut outin the louvre or infill
panel, constructed in accordance with the dimensions above.
Installation Guidelines
- The Mini Detector Head must be mounted within the luminaire. Do not mount remotely.
- The connecting cable must not be extended.
- Artificial light illuminating the Mini Detector Head must only be reflected from the room – i.e. there must be no directillumination.
- In order to receive satisfactory light-level regulating operation, a detector must observe a substantially greater proportion of artificial light from the luminaire(s) under its control than from neighbouring luminaires not under its control. This is particularly important when planning the installed layout of linear luminaires that have an integral detector positioned at one end.
Commissioning
Detectors are supplied factory pre-set which ensures the lighting will switch on automatically as soon as power is applied. Final commissioning of the detectors requires the use of an infrared Programmer. The QuickSet Pro gives access to the full range of parameters and options but limited programming functions can also be carried outusinganHP18.
Commissioning Detectors using the QuickSet Pro Programmer
Itis important that the Programmer be held perpendicular between 0.5m and 2m
from the sensor.
- Switch on by pressing any button (and unlock with top left rectangular button).
- Point the programmer at detector and press the DOWNLOAD button. The programmer will confirm the product’s identity and call up the correct menu of parameters and their current settings.
- Use a combination of UP, DOWN, FORWARD and BACK buttons to navigate the parameter menu, selecting options for each shown.
- When options for all parameters have been selected, point the programmer at the detector and press the UPLOAD button. The luminaire(s) will switch off briefly during the programming process.
- After a short period of inactivity (default 5 minutes), the programmer hibernates retaining the most recent settings.
OneSwitch Dimming
OneSwitch dimming affords local control to the end-user whereby a simple, momentary, push-to-make wall switch can be used to raise or lower the lighting level or to toggle the output ON/OFF. A press of less than 1 second will toggle the output status while a longer press will raise or lower the output. Each time the switch is pressed, the direction of dimming reverses. If the switch has not been pressed for 5 seconds, the direction will be up (brighter) – unless the output is already above 90% (dc 8V) in which case the direction is down.
To Test with Hand-held Controller
Once the LightSpot Luminaire Controllers have been installed within the
luminaires, a Hand-held Controller or Programmer (HC5A or HP18) may be used to
dim and brighten luminaires and to switch them ON and OFF.
NB: See also ‘Important Additional Notes’ overleaf.
Technical Data
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m
RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x
mounting height OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
ta=0-50°C
CAPACITY: Max 4 x DSI or DALI ballasts
INTERCONNECT CABLE TEMPERATURE RATING: 60°C
COLOUR: White (RAL9010) or silver bezel (DHW = White, DHS = Silver)
MATERIAL: UV stabilised polycarbonate (DHW/DHS)
Flame retardant PC/ABS (MSM2000D/DALI)
IP RATING: 20
DIMENSIONS: 32 (1) x 21 (w) x 18.6 (h) mm (DHW/DHS)
147 (1) x 30 (W) x 21 (h) mm (MSM2000D/DALI)
WEIGHT: 32g incl. 0.8m cable (DHW/DHS)
48g (MSM2000D/DALI)
ImportantAdditional Notes
-
Ameans fordisconnectionmust be incorporatedin the fixed wiring in accordance with the current wiring regulations.
-
Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains with regard to wiring practice. The OV line of the dimming outputis almost at Neutral potential.
-
The dimming control output should be connected only to the control input of the ballasts – never to other detectors.
-
This equipmentshould be used to control only those ballasts powered from the same phase as the detector.
-
Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent.
Therefore, products of this type should be regarded as capable of maintainingan APPROXIMATE lightlevel only. -
This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of some particular lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in orderto achieve a predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controlsin this respect.
-
Some devices in this product range feature a silvered surface finish; this is intended for decorative purposes only Care should be taken to avoid accidental separation of the silvered coating from the product. If the unitis builtinto a luminaire that is subsequently wrapped in film having adhesive properties, it is recommended that a layer of suitable packaging material be used to protectthe silvered area.
Honeywell Ex-Or
St. Marks Court, North Street, Horsham, West Sussex, RH12 1BW, UK.
Tel: +44 (0)1942 719229
Email: ex-ortechnicalsales@honeywell.com
www.ex-0r.com
At the end of their useful life the packaging and product should be
disposed of via a suitable recycling centre.
Do not dispose of with normal household waste.
Do not burn.
W42671